Next Article in Journal
Improving Sentence Representations via Component Focusing
Next Article in Special Issue
Regulation Principles of Power Flow Gradients to Multiple Characteristic Independent Variables in UPFC Embedded Power System
Previous Article in Journal
Dependence Representation Learning with Convolutional Neural Networks and 2D Histograms
Previous Article in Special Issue
Flexibility of Wireless Power Transfer Charging Station Using Dynamic Matching and Power Supply with Energy Dosing
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Performance Tuning for Power Electronic Interfaces Under VSG Control

1
Key Laboratory of Distributed Energy Storage and Micro-Grid of Hebei Province, North China Electric Power University, Baoding 071000, China
2
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 100000, China
*
Authors to whom correspondence should be addressed.
Appl. Sci. 2020, 10(3), 953; https://doi.org/10.3390/app10030953
Submission received: 29 December 2019 / Revised: 24 January 2020 / Accepted: 25 January 2020 / Published: 2 February 2020
(This article belongs to the Special Issue Power Electronic Applications in Power and Energy Systems)

Abstract

:
Renewable generation, such as solar PV and wind power, is commonly integrated into the power grid through inertialess power electronic interfaces (PEIs). Due to the increasing penetration of renewable generation, the frequency stability of the current power system deteriorates. In order to sustain the desired level of the overall inertia, the virtual synchronous generator (VSG) algorithm has been proposed. The concept of VSG is to enable the PEIs to emulate the external properties of traditional synchronous generators (SGs), such as inertia and primary frequency responses. By exploitation of the well-established knowledge system of conventional SG-based power grids, the VSG can also be implemented with the capabilities of primary, secondary, and tertiary frequency control in multiple temporal stages. This paper focuses on parameter tuning for VSG-PEIs by performance indices. The emulation strategies are completed with the capability of secondary and tertiary frequency regulation. The transfer functions of the dynamic systems of PEIs are simplified and referred to the control theory. The composite influences of different parameters on performance indices are analyzed. The methods of the parameter tuning are proposed according to the temporal sequences of the control stages. By typical performance standards, the proposed method is verified through simulation.

1. Introduction

With the deficit of fossil fuels and environmental concerns, renewable power has been widely researched and utilized in recent decades [1,2,3]. Iceland and Norway obtain essentially all electricity from renewable sources, and other nations and regions are evolving towards 100% renewables [4]. However, renewable generation also brings great challenges. On the one hand, renewable generation is stochastic and fluctuant with meteorological conditions. The system power balance is persistently disturbed by renewable generation fluctuations. On the other hand, renewable generation (such as solar photovoltaic and wind power) is commonly integrated through power electronic interfaces (PEIs), which are with almost no inertia because of its fast and accurate switches [5]. By the increasing penetration of renewable generation, the frequency stability of the current power system deteriorates.
The current power system has been through transitions in intrinsic properties, one of which is represented by the decreasing of the overall inertia. The inertia is an important indicator to evaluate the strength of the power systems because inertial response (IR) can slow down the rate of change of frequency (ROCOF) and buy time for the activation of primary frequency response (PFR) to reduce nadir/peak frequency (maximum frequency deviation) [6]. In order to tackle the loss of inertia in the inverter-based generation (IBG), the concept of the virtual synchronous generator (VSG) has been proposed [7,8,9,10,11,12,13]. As the control strategies of the voltage-sourced inverters (VSIs) are commonly composed of a highly programmable supplementary controller and a double-loop controller in a cascade structure, by the implementation of the VSG algorithm, the PEI external characteristics can mimic those of synchronous generators (SGs) closely [9]. Therefore, the well-developed theory for the operation of the SG-based power system can still be exploited for the evolving power grids [7]. Two classical models, the ‘synchronverter’ and Ise’s, focus on the loss of inertia in conventional VSI droop control, and the emulation of the properties of the inertia and the speed-governor is implemented [9,11,13]. Experiment-based studies can be found in [14,15] for stand-alone applications. In [12], the equivalence between the VSG and the frequency-droop algorithms are demonstrated. It is accurate for an individual unit, but when the VSG algorithm is implemented in the power systems, the damping coefficient of loads (which is typically 1-1.5) should be considered because it is much larger than that of the damper windings (such as 0.1) [16]. However, the above studies are all restrained in the stages of the short-term frequency response. The frequency control of the conventional power systems includes a hierarchical structure because the system operation requires the ability to respond to change in demand and supply in multiple temporal stages [17]. With higher penetration of renewable generation, the IBG units would eventually and inevitably take the responsibility of regulating the overall energy balance because of the consequent displacement of traditional SGs. Therefore, the flexibility of the power system operation requires the VSG algorithm to extend its application scope.
As the parameters of PEIs are tunable rather than restrained by physical equipment, VSG algorithms can modify the inertia properties of the renewable units in real-time. General analysis for dynamic performance can also be found in [18,19], in which the influence of inertia and droop properties are analyzed based on transfer functions. Continuous change and step change of virtual inertia parameters are designed to minimize frequency deviation and energy support [20,21,22]. The change of inertia is straightforward but arbitrary. In [10], the requirements for dynamic support are illustrated based on system operation, including the standards of the frequency nadir, the maximum ROCOF, and the duration of delivery. However, it lacks the discussion on how to quantitatively tune the parameters to satisfy these standards. In [12], a step-by-step parameter design for virtual synchronous generators is conducted based on small-signal modeling, which focuses on independent decoupling and tuning of active and reactive power loops of a single grid-connected inverter. However, this approach is oriented for coping with unbalanced grid voltages, but not for quantitative performance indices. Also, the decoupling condition includes that the short-circuit ratio is no less than 10, which is typically not satisfied in power systems [23]. In [24], quantitative performance analysis is completed for the inertial response provided by the capacitor in the DC link. However, the capacitor can only provide frequency support as an energy buffer, and the response ability is restrained by the predesigned capacitance. Again, from the view of the operation flexibility, the quantitative performance analysis for the overall power systems should be considered for the generation mix (SGs and IBG units).
Within a microgrid, based on the information technology and communication network, secondary frequency regulation (SFR) and tertiary frequency regulation (TFR) could also be implemented on VSIs [25,26,27,28,29]. In recent research, the VSG-based IBG can also participate in system frequency regulation when active power reserves (APRs) are implemented. Instead of the traditional maximum power point (MPP) tracking, the APR strategy controls the IBG units to operate at a sub-optimal point [30]. Therefore, generation availability is reserved to tackle the power imbalance caused by the uncertain nature of renewables [31]. Active power reserves by RG units can be realized by two types of control strategies: (1) the delta control, which deloads RG units by constant percentages or values, or both according to the meteorological conditions [32]; and (2) the balance control, which controls the RG output by upper limit when the surplus power acts as reserves [33]. The APR control strategy enables the IBG units with persistent generation availability to participate not only short-term frequency response stages (IR and PFR) but also long-term frequency regulation stages (SFR and TFR). Therefore, a complete hierarchical structure of multiple temporal frequency control stages could be emulated on the VSG-based IBG units.
In order to enhance the VSG algorithm to sustain the flexibility level of power systems containing a mixed generation at all times, in this paper, a quantitative approach of performance tuning for VSG-PEIs participating in multiple temporal stages of frequency control is presented. The contributions of this work could be summarized as follows:
(1) Besides the capabilities of IR and PFR, by referring to the knowledge of conventional generation and operation, an enhanced control strategy for the capabilities of SFR and TFR are designed to complement the VSG algorithm. Therefore, VSG-based PEIs could perform multiple temporal frequency control.
(2) The analysis of frequency response dynamics, based on the simplification of the transfer function down to the second-order form, is conducted for both the stages of (1) IR and PFR, and (2) SFR. Six performance indices are proposed, and the frequency responses influenced by different parameters are analyzed.
(3) It is noted that the performance indices are influenced by composite parameters, but the hierarchical stages of IR, PFR, and SFR operate in chronological order. Therefore, a parameter tuning algorithm is designed in which the parameters are also determined following a chronological sequence.
(4) The proposed parameter tuning approach could either be used to analyze dynamic performance and tune parameters for either the bulk system performance after the power unbalance disturbances or the dominant generation units in a stand-alone scenario.
The rest of the paper is organized as follows: Section 2 presents the complete emulation control strategies for PEIs with multiple temporal frequency control. Section 3 analyzes the parameter influence on the IR and PFR stages. Section 4 analyzes the parameter influence on the SFR stage. Through analyzing the composite influence on system performances by different parameters, Section 5 proposes a parameter tuning algorithm by consideration of the time sequence of performance indices in the multiple frequency control stages. Section 6 verifies the proposed algorithm by simulation.

2. VSG Emulation Control Strategies for VSIs with Frequency Control

For the IBG, the external characteristics are largely determined by the supplementary controller in the control structure. In inchoate studies, among the VSG implementations in different orders, the simplest second-order model is with better stability in transients [34] and can be combined with virtually any VSI control strategies involving a cascade structure [35]. By the implementation of the VSG algorithm, the IBG is capable of performing IR and PFR in the same way as the SGs.
The equations of motion, describing the effect of unbalance between the mechanical torque and the electromagnetic torque on rotation, could be found in many classical textbooks (such as [16]). The inertial response of the SGs is instantaneous without prerequisite measurements. For traditional SGs, the inertia is provided by the kinetic energy stored in the rotation equipment. The inertia constant HSG indicates the inertia property, which can be expressed as
H S G = J S G ω r 2 2 V A b a s e
where J is the moment of inertia, ω r is the angular speed of the rotor, VAbase is the rated power. Similar to HSG, the virtual inertia constant Hvir of PEIs can be analogically expressed as the ratio of the provided energy to its rated power
H v i r = J v i r ω m 2 2 V A b a s e
where Jvir is the virtual moment of inertia, ω m is the virtual angular speed. The inertial response follows Newton’s law of motion which can be expressed as the swing equation,
P m P e = d Δ ω r / d t 2 H S G + D Δ ω r
where D is the damping coefficient of frequency sensitive load, Pm and Pe are the virtual mechanical and electrical power (when the initial status is assumed as 0, and the second-order terms are neglected), ω r is virtual angular speed. When the swing equation is represented by inertia constant, all the parameters are per-unit values.
The PFR of SGs is provided by the turbine-governor system [16]. In per unit value, for a typical SG with a reheat steam turbine, the droop property is
Δ Y = 1 R × 1 1 + s T G × 1 + s F H P T R H ( 1 + s T C H ) ( 1 + s T R H ) Δ ω r
where R is the speed droop, Y is the valve position, TG is the time constant of speed governor, and FHP, TRH, TCH are typical parameters for a reheat steam turbine. The emulation for the properties of turbine-speed governor systems of SGs is necessary when the VSG-based PEIs are operated in parallel with traditional power plants.
By the exploitation of conventional theories of the SG-based power system, the VSG algorithm also enables the PEIs to perform SFR and TFR. The SFR kicks in when the frequency deviation lasts for a preset time period after the frequency is stabilized by the IR and PFR. The TFR is activated by the system operator (SO) to set the load reference for each generation unit. For traditional SGs, the SFR and TFR are executed by the regulation of load reference settings, which is shown in Figure 1a. The variables of load references also pass through the blocks of the turbine-governor system. However, because only specific units in the power system are selected to perform automatic generation control (AGC) regulation, when the emulation of AGC is implemented on VSG-PEIs, the load reference can be directly fed into the block of the virtual swing equation, as shown in Figure 1b. In Figure 1b, τ is the time delay of SFR, KI is the coefficients of the integral controller.
The system frequency indicates the overall power balance between the generation and the demand at any instantaneous time. In the traditional SG-dominated power system, active power-frequency control is a series of multiple temporal processes that can be divided into four stages [16]. As the VSG algorithm can fully emulate the frequency control performance of the SGs, the multiple temporal frequency control is also provided by the VSG-PEIs. For quantitative analysis, the performance indices mainly include the maximum ROCOF, the frequency nadir, the settling frequency, and the settling time, which are shown in Figure 2.
Furthermore, in a small synchronous area, the equivalent inertia constant H s y s of different VSG-based PEIs and SGs can be expressed as
H s y s = i = 1 n ( H i S i S s y s )
where n is the total number of generation units with inertia properties, H i and S i are the inertia constant and power rating of the i-th unit, respectively, S s y s is the power base of the system [32,36]. Also, the equivalent speed droop R e q can be expressed as
R e q = 1 i = 1 n 1 R i
where R i is the speed droop property of the i-th generation unit [16].
Consequently, for a local synchronous system, the generation units can be simplified and equivalent to a single unit. The emulation strategy mentioned before could be considered as the overall characteristics of the entire local synchronous area. Then once the parameters are tuned, it could either be used to control the dominated PEI in a stand-alone system or calculate the parameters reversely for individual units with inertia properties.

3. Simplification of the Dynamic System in IR and PFR Stages

The emulation of IR and PFR is derived from the mechanism imitation of the swing equation and the turbine-speed governor system. The effect of the closed-loop transfer function of the VSI based on the cascade control structure is assumed to be fast and accurate. Then the high-order system involving virtual IR and PFR can be simplified into a second-order dynamic system by the dominant poles and zeros without too much error. The performance indices can be deduced from the simplified transfer function. Take a stand-alone VSG-PEI supplying isolated load for example, the block diagram involving IR and PFR is shown in Figure 3.
For a step change of demand Δ P L , the transfer function from Δ P L to the virtual angular speed of rotor Δ ω r is
G ( s ) = Δ ω r Δ P L = R ( 1 + s T G ) ( 1 + s T C H ) ( 1 + s T R H ) ( 2 H s + D ) ( 1 + s T G ) ( 1 + s T C H ) ( 1 + s T R H ) R + s F H P T R H + 1
For SGs with reheat steam turbines, typical parameters are shown in Table 1.
The pole-zero map of the transfer function is shown in Figure 4. From the transfer function G(s), the zeros are fixed on the real axis. With the increasing of H, the poles P3 and P4 tend to approach the zeros Z2 and Z3. As P3 and P4 are fast poles and very close to Z2 and Z3, the dynamic responses are mainly determined by the dominant zeros Z1 and the slow poles P1 and P2 [37]. It is noted that the inertia constants of different SGs, which are shown in Table 2, are in a small range rather than accurately the same [16]. The concept of VSG is to enable the PEIs to provide approximately synchronous responses like traditional SGs. Moreover, fast poles influence the early part of the time history [37]. The frequency responses based on the transfer function of the original and simplified systems are shown in Figure 5, which shows the maximum error between the two dynamic systems is less than 10% frequency deviation. Therefore, the estimation by the dominant zeros and poles are practically acceptable.
According to the dominant zeros and poles (Z1, P1, and P2), the simplified transfer function of the dynamic system is derived from Equation (7), which can be expressed as
G ( s ) = R ( 1 + s T R H ) ( 2 H s + D ) ( 1 + s T R H ) R + s F H P T R H + 1 = K s + z 1 s 2 + 2 ζ ω n s + ω n 2
where ω n and ζ are the undamped natural frequency and damping ratio [37],
K = 1 2 H ,   z 1 = 1 T R H ,   ω n = 1 + R D 2 H R T R H ζ = 2 H R + T R H D R + F H P T R H 4 H R T R H × 2 H R T R H 1 + R D
When the system is subjected to a step increase in demand
Δ P L = Δ p s
By multiplying (8) and (10) and taking the inverse Laplace transformation, the dynamic response of frequency deviation in time-domain can be expressed as
Δ f ( t ) = K Δ p × [ z 1 ω n 2 + A e ζ ω n t sin ( ω d t + β ) ]
where
ω d = ω n 1 ζ 2 A = ( z 1 ζ ω n ω d ω n ) 2 + ( z 1 ω n 2 ) 2 β = arctan [ z 1 ω d ω n ( z 1 ζ ω n ) ] + π
Assuming the original state of the frequency is 1.0 pu, the frequency response is
f ( t ) = 1 + K Δ p × [ z 1 ω n 2 + A e ζ ω n t sin ( ω d t + β ) ]
From Equation (11), performance indices during IR and PFR can be derived. First, the rate of change of frequency (ROCOF) is
R O C O F = d Δ f d t K Δ p × [ A ζ ω n e ζ ω n t sin ( ω d t + β ) A ω d e ζ ω n t cos ( ω d t + β ) ]
It is noted that, when t = 0, ROCOF reaches maximum magnitude, which can be expressed as
R O C O F max = K Δ p × ( A ζ ω n sin β A ω d cos β )
From Equation (11), when ROCOF = 0, the peak time t p e a k (the time when the frequency reaches a nadir or a peak) can be expressed as
t p e a k = 1 ω d ( arctan 1 ζ 2 ζ β )
Substitute (16) to (13), then the peak frequency fpeak (or nadir) is
f p e a k = 1 + K Δ p × z 1 ω n 2 + K Δ p A e ζ ω n t p e a k 1 ζ 2
When the third item in the Equation (17) decays approximately to zero, the quasi-steady-state frequency fss is achieved, which can be expressed as
f s s = 1 + K Δ p × z 1 ω n 2 = 1 R D R + 1 Δ p
The frequency deviation can also be evaluated by the frequency overshoot σ , which can be expressed as
σ = | f s s f p e a k f s s | × 100 % = | A ω n 2 1 ζ 2 e ζ ω n t p e a k z 1 + ω n 2 / K Δ p |
The settling time ts can be defined as the dynamic response enters the 2% quasi-steady-state error band [17],
| f ( t s ) f s s 1 f s s | = 2 %
and by submitting Equations (11) and (12) into Equation (20), the settling time can be deduced as
t s = 1 ζ ω n ln z 1 50 A ω n 2
From the performance indices, the effect of separate parameters on system performance can be derived. When subjected to a step increase of load by 0.03 pu, the trends of the above performance indices corresponding to different H and R are shown in Figure 6 and Figure 7. In Figure 6, R is set as a constant, and in Figure 7, H is set as a constant.
From Figure 6a,b,e, the increasing of inertia constant H leads to the decreasing of the magnitude of ROCOF, frequency nadir, and the overshoot. Therefore, it proves that inertia property could suppress the ROCOF and improve frequency nadir. From (c), the increasing of H also delays the peak time. However, the increasing H would slow down the dynamic responses, which is shown in (d). Therefore, there is a trade-off between the nadir improvement and the delivery time. From (f), the settling frequency is irrelative to H.
From Figure 7a, percentage R does not influence the ROCOF. From (b) and (e), the nadir gets worse, and the overshoot increases as the percentage R increases. From (c) and (d), the changes in percentage R do not alter the peak time and settling time very much. From (f), the increase of R would decrease the settling frequency. Consequently, the speed droop coefficient R indicates the proportional relationship between the amount of support power and the counteracted frequency deviation. The lower R represents a larger amount of active power supported, which results in a better nadir.

4. Simplification of the Dynamic System in SFR Stages

The secondary control regulates the reference generation output and restores the system frequency to the nominal. The SFR is activated after the PFR has stabilized the system frequency. In VSG-PEI, the virtual SFR is executed by adding an integrator, shown in Figure 1b. After the frequency is stabilized, when the SFR kicks in, the transfer function of the dynamic system in the new stage is
G ( s ) = ( R ( 1 + s T G ) ( 1 + s T C H ) ( 1 + s T R H ) s ) / ( s ( 1 + s F H P T R H ) + K I R ( 1 + s T G ) ( 1 + s T C H ) ( 1 + s T R H ) + ( 2 H s + D ) ( 1 + s T G ) ( 1 + s T C H ) ( 1 + s T R H ) R s )
The pole-zero map of the transfer function is shown in Figure 8.
From the pole-zero map, the zeros are fixed on the real axis. With the increasing of KI, P1 tends to approach to Z2, which results in the mutual cancelation of effects. The effect of poles P4 and P5, and the zeros Z3 and Z4, which are far away from the imaginary axis, would be neglected for simplifications. Therefore, the poles P2 and P3, and the zero Z1 are dominant in the dynamic processes.
From the slow zeros and poles (Z1, P1, and P2), the system transfer function (Equation (22)) is simplified into the second-order, which can be expressed as
G ( s ) = R s s ( 1 + s F H P T R H ) + K I R + R ( M s + D ) s = K s + z 1 s 2 + 2 ζ ω n s + ω n 2
where ω n and ζ are the undamped natural frequency and damping ratio,
K = R F H P T R H + M R ,   z 1 = 0 ,   ω n = K I R F H P T R H + M R ζ = D R + 1 2 ( F H P T R H + M R ) × F H P T R H + M R K I R
It is noted that the initial status in the dynamic system is inherited from the IR and PFR stages. By taking the inverse Laplace transformation, the dynamic response of system frequency in time-domain is derived, which can be expressed as
f ( t ) = 1 K ω d e ζ ω n t sin ω d t
where
ω d = ω n 1 ζ 2
From Equation (25), system performance indices during SFR can be derived. First, the rate of change of frequency (ROCOF) can be expressed as
R O C O F = d f d t = K ω d × ( ζ ω n e ζ ω n t sin ω d t + ω d e ζ ω n t cos ω d t )
In Equation (27), when t = 0, ROCOF reaches the maximum value, which can be expressed as
R O C O F max = K
The peak time t p e a k is achieved when ROCOF = 0, then from Equation (27), the peak time can be expressed as
t p e a k = 1 ω d arctan 1 ζ 2 ζ
By substituting (29) into (25), the peak frequency fpeak can be expressed as
f p e a k = 1 K ω d e ζ ω n t p e a k 1 ζ 2
From Equation (25), the quasi-steady-state frequency fss is
f s s = 1
For floating control, the frequency deviation can be evaluated by the frequency overshoot σ , which can be derived as
σ = | f s s f p e a k f s s | × 100 % = | K ω d 1 ζ 2 e ζ ω n t p e a k | × 100 %
The settling time ts can be defined when the decaying exponential e ζ ω n t reaches 1% [37].
e ζ ω n t s = 0.01
then from Equation (33), the settling time can be derived as
t s = 4.6 ζ ω n
From the performance indices, the effect of separate parameters on system performance in the SFR stage can be derived. When SFR kicks in, the trends of the above performance indices corresponding to different KI, H, and R are shown in Figure 9, Figure 10, and Figure 11, respectively.
From Figure 9a,d,f, the coefficient of the integrator is irrelative to the magnitude of the ROCOF, the settling time, and the settling frequency. From (b), (c), (e), the increase of the integral effect would decrease the peak frequency, the peak time, and the overshoot.
From Figure 10a,b,e, the increasing of inertia constant would decrease the magnitude of the ROCOF, the peak frequency, and the overshoot. However, from (c) and (d), the increase of inertia property would also increase the peak time and the settling time. From (f), the inertia constant is irrelative to the settling frequency.
From Figure 11a,b,d,e, the increase of speed droop R would also increase the magnitude of ROCOF, the peak frequency, the settling time and the overshoot. However, from (c), the increase in speed droop would decrease the peak time. From (f), the speed droop is irrelative to the settling frequency.

5. Parameter Tuning for Frequency Response and Regulation

From the derived expressions before, the performance indices are influenced by multiple parameters. In the process of IR and PFR, the performances are determined by the composite effects of the inertia constant H and the speed droop R. In the following process of SFR, the performances are determined by the integral coefficient KI, as well as the inherited or readjusted H and R.

5.1. Composite Parameter Analysis for IR and PFR

During the processes of IR and PFR, four key performance indices (the maximum magnitude of ROCOF, the frequency nadir, the settling frequency, and the settling time) are influenced by the composite effects of the coefficients H and R, which are shown in Figure 12. In Figure 12, H varies from 3 to 10, R varies from 0.04 to 0.08, and the step increase of load is constant.
From Figure 12, the magnitude of ROCOF decreases as H increases, but does not relate to R. The frequency nadir improves with the increase of H and the decrease of R. The settling frequency increases with the decrease of R but does not relate to H. The settling time is influenced by both H and R.

5.2. Composite Parameter Analysis for SFR

During the process of SFR, as the effect of the integration is gradual and small, two key indices, the settling time and the overshoot, are selected. The parameters in the SFR stage involve H, R, and the integral coefficient KI. From previous results, the settling time in the SFR stage is irrelative to KI. The overshoot is relative to all three parameters. The composite parameter influences are shown in Figure 13.

5.3. Parameter Tuning for Performance Indices

In some countries (such as Germany, the USA, and the UK), the system operators have developed a time frame for renewable penetrated grids. For example, the prescribed limit for ROCOF is 0.125 Hz/s [38]. Also, in this material, the maximum ROCOF and PFR delivery time in its case study are set to be 0.5 Hz/s and 10s, respectively. In another research, the maximum frequency deviation Δ f m a x is set as 0.2 Hz [24]. It is noted that if the ROCOF exceeds 1 Hz/s, the frequency relay would be tripped and incur a large disturbance to a power system [39]. Generally, the delivery of PFR is required to be within 10–30s, and the time for SFR delivery is from 30 s to several minutes. The PFR capacity should always limit the frequency between 49.5–50.5Hz. The typical standards (nominal frequency is 50 Hz) are summarized in Table 3.
It is noted that the stages of IR, PFR, and SFR activate in chronological order. Therefore, based on the composite effects and the standards, a flowchart of parameter design for VSG-PEIs is shown in Figure 14. In step A, the standards for ROCOF and frequency nadir are input. The maximum ROCOF only relates to inertia constant, so the range of H could be determined according to the ROCOF standard. The frequency nadir relates to both H and R, then according to the H range and the nadir requirement, the range of R could be determined. Therefore, in step B, the satisfying ranges of H and R are obtained. In step C, the desired H and R are determined by checking the settling frequency and the settling time. If the VSG-PEI does not participate in the following SFR, the design comes to an end. Otherwise, the parameter design goes on for the SFR stage. If the parameters of H and R are inherited from the previous, it jumps to step F. If not, in step D and E, the standard of settling time is input, and the satisfying ranges of H and R are obtained. In step F, KI, and H, R are determined by checking the overshoot.

6. Case Study and Simulation

In this section, the proposed VSG emulation strategies and the parameter tuning approach are verified in simulation through MATLAB/Simulink. Based on the predetermined standards of the performance indices shown in Table 4, the parameters in the simulation are shown in Table 5.

6.1. Frequency Response in the Initial Systems and Previous Approaches

From 1996–2016, the equivalent inertia constants Heq in many European countries and districts have decreased larger than 15%, which are shown in Figure 15 [40]. Considering the worst case in which the inertia constant Heq = 3.0, the frequency response of the system without renewable participation is shown in Figure 16. The percentage droop is set as 5.
In the previous research, renewable penetration is typically set varying from 10% to 30% [38], and the inertia constant for VSG-IBG is usually set as 5.0 s. According to Equation (5), under the worst case (the initial Heq = 3.0), the equivalence inertia constant is no more than 3.6 (when renewable penetration is 30%). The frequency response with renewable participation but without parameter tuning is shown in Figure 17. The percentage droop is set as 5.

6.2. Frequency Response with Renewable Participation and Parameter Tuning

In order to satisfy the performance standards, the equivalent inertia constant Heq is set as 5 by the parameter tuning. The generation units in a power system can be divided into two parts: (1) synchronous generators coupled to the power system, and (2) renewable generation units with virtual inertia. From Equation (5), Heq obeys
H e q = i = 1 S G ( H i S rated ,   i ) + j = 1 R G ( H v i r ,   j S R T ,   j ) S s y s
where Hi is the inertia constant of synchronous generators i, and Srate, i is the rated power of a single unit. Hvir, j is the virtual inertia constant emulated by renewable generation units, and SRT, j is the output power of the j-th unit in real-time. Ssys is the rated power of the mix power system. Then, from Equation (35), the equivalent inertia property emulated by the RG units can be derived.
When subjected to a step increment of demand by 0.03 pu, the frequency response is shown in Figure 18. By the predetermined settings, the proposed parameter tuning method satisfies the standards of performance indices. From Figure 18a, the maximum frequency deviation is 0.1799 Hz, and the PFR settling frequency is 49.9237 Hz. From (b), the maximum ROCOF is 0.1602 Hz/s. From (c), the output power of the converter interface increases to suppress the ROCOF. The final value of the power in the PFR loop is a little higher than the actual load increment because of the power loss in the switches and the filter.
The comparison of the simulation results between the frequency response with or without the participation of renewable generation is listed in Table 6.
From Table 6, it can be concluded that:
(1) Due to the growing penetration of renewable generation and the consequent loss of inertia, the overall inertia property decreases, and the system performance could not satisfy the standard of the nadir index.
(2) Previous research on VSG focuses on the validity of control strategies but lacks the parameter analysis of the equivalent inertia based on conditions in actual power systems. Therefore, the emulation approaches based on typical inertia constants could not satisfy the standard of the nadir index as well.
(3) By parameter tuning, all the standards are satisfied. It is also noted that the settling frequency stabilized by the PFR is also improved, which is advantageous to cope with another possible disturbance before the frequency is restored by the SFR.

6.3. Frequency Regulation

Following the IR and PFR, the SFR kicks in after the frequency is stabilized at the 20th second. By the calculated parameter KI, the proposed parameter tuning method satisfies the standard of the SFR delivery time. From Figure 19a, the SFR restores the frequency to the nominal. The settling time is within 40 s. From (b), the ROCOF is stabilized when the SFR ends. From (c) and (d), the power in the SFR loop gradually overrides the power from the PFR loop.

7. Conclusion

Based on the quantitative analysis of performance indices, this paper proposes a parameter tuning method for VSG-PEIs performing frequency control. From the above analysis, the following conclusions are made:
(1) From the perspective of the time scale and the activation, the frequency control is divided into two parts: the frequency response including IR and PFR, and the frequency regulation including SFR. Two dynamic systems are formed in different parts.
(2) By the effects of the dominant poles and zeros, the dynamic systems of the VSG-based PEIs in both parts are simplified into approximation models with second-order transfer functions. The performance indices are deduced from the reduced-order models.
(3) Different stages of frequency control kick in chronological order. In the proposed algorithm, the inertia constant is considered first for the ROCOF standard in the inertial response stage. Then the inertia constant and the speed droop are designed by checking the requirements of the nadir, the settling time, and settling frequency.
(4) In frequency regulation, the parameter of inertia and speed droop are inherited or readjusted from the previous part. The integral coefficient is determined according to the standard of SFR delivery time.
(5) The proposed algorithm can be utilized in two scenarios: (1) the parameter determination for the dominated PEIs in a stand-alone system, and (2) the equivalent parameter determination for a synchronous area with different units with inertia properties.
By the simulation results, the proposed method can fully satisfy typical performance standards.

Author Contributions

This study was carried out by W.Z. under the supervision of X.Y. The editing was mostly done by H.H. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by National Natural Science Foundation of China-Hebei on the project of “Research on inertia characteristics and control strategy for primary frequency and voltage regulation of DFIG” (no. E201802134).

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

1. Acronyms
AGCAutomatic generation control
APRActive power reserve
IBGInverter-based generation
IRInertial response
MPPMaximum power point
PEIPower electronic interfaces
PFRPrimary frequency response
RGRenewable generation unit
ROCOFRate of change of frequency
SFRSecondary frequency response
SGSynchronous generator
SOSystem operator
TFRTertiary frequency response
VSGVirtual synchronous generator
VSIVoltage-sourced inverter
2. Sets and indices
ROCOFRate of change of frequency
t p e a k Peak time
f p e a k Peak frequency
f s s Steady-state frequency
σ Overshoot
t s Settling time
SGSet of synchronous generators
RGSet of renewable generation
3. Variables
ω r Angular speed of rotor
H v i r Virtual inertia constant
J v i r Virtual moment of inertia
ω m Virtual angular speed
P m Virtual mechanical power
P e Electrical power
Y Valve position
4. Parameters
H S G Inertia constant of synchronous generator
J S G Moment of inertia of synchronous generator
V A b a s e Rated power
D Load damping
R Speed droop
T G Time constant of speed governor
F H P ,   T R H ,   T C H Typical parameters for a reheat steam turbine
H s y s Equivalent inertia constant of the system
S s y s Rated power of the system
H i Inertia constant of the i-th synchronous generator
S i Rated power of the i-th synchronous generator
H j Inertia constant of the j-th reneable generation unit
S j Rated power of the j-th reneable generation unit
R e q Equivalent speed droop of the system
R i Speed droop of the i-th unit
Δ P L Step increase of load
ω n Undamped natural frequency
ζ Damping ratio
H Inertia constant
K I Integral coefficient
V d c DC voltage at the DC side of the inverter
V a c AC voltage at the AC side of the inverter
L Inductance of the LC filter
C Capacitance of the LC filter
f AC system frequency
f p w m Frequency of the modulation wave
τ Time delay of the SFR
i Synchronous generator i
j Renewable generation unit j
H e q Equivalent inertia constant of the system
S r a t e d Rated power of synchronous generators
S R T Power of renewable generation units in real-time
5. Prefix and footnote
Δ deviation

References

  1. Yan, X.; Zhang, W. Review of VSG Control-Enabled Universal Compatibility Architecture for Future Power Systems with High-Penetration Renewable Generation. Appl. Sci. 2019, 9, 1484. [Google Scholar] [CrossRef] [Green Version]
  2. Lopes, J.P.; Hatziargyriou, N.; Mutale, J.; Djapic, P.; Jenkins, N. Integrating distributed generation into electric power systems: A review of drivers, challenges and opportunities. Electr. Power Syst. Res. 2007, 77, 1189–1203. [Google Scholar] [CrossRef] [Green Version]
  3. Piano, S.L.; Mayumi, K. Toward an integrated assessment of the performance of photovoltaic power stations for electricity generation. Appl. Energy 2017, 186, 167–174. [Google Scholar] [CrossRef] [Green Version]
  4. U.S. Energy Information Administration. Annual Energy Outlook 2019. Available online: https://www.eia.gov/outlooks/aeo/pdf/aeo2019.pdf (accessed on 29 December 2019).
  5. Blaabjerg, F.; Teodorescu, R.; Liserre, M.; Timbus, A. Overview of Control and Grid Synchronization for Distributed Power Generation Systems. IEEE Trans. Ind. Electron. 2006, 53, 1398–1409. [Google Scholar] [CrossRef] [Green Version]
  6. Delille, G.; Francois, B.; Malarange, G. Dynamic frequency control support by energy storage to reduce the impact of wind and solar generation on isolated power system’s inertia. IEEE Trans. Sustain. Energy 2012, 3, 931–939. [Google Scholar] [CrossRef]
  7. Beck, H.-P.; Hesse, R. Virtual synchronous machine. In Proceedings of the 9th International Conference on Electrical Power Quality and Utilisation, Barcelona, Spain, 9–10 October 2007. [Google Scholar]
  8. Driesen, J.; Visscher, K. Virtual synchronous generators. In Proceedings of the IEEE Power and Energy Society General Meeting—Conversion and Delivery of Electrical Energy in the 21st Century, Pittsburgh, PA, USA, 20–24 July 2008. [Google Scholar]
  9. Zhong, Q.; Weiss, G. Synchronverters: Inverters that mimic synchronous generators. IEEE Trans. Ind. Electron. 2011, 58, 1259–1267. [Google Scholar] [CrossRef]
  10. Wu, H.; Ruan, X.; Yang, D.; Chen, X.; Zhao, W.; Lv, Z.; Zhong, Q.-C. Small-Signal Modeling and Parameters Design for Virtual Synchronous Generators. IEEE Trans. Ind. Electron. 2016, 63, 4292–4303. [Google Scholar] [CrossRef]
  11. Liu, J.; Miura, Y.; Ise, T. Comparison of dynamic characteristics between virtual synchronous generator and droop control in inverter-based distributed generators. IEEE Trans. Power Electron. 2016, 31, 3600–3611. [Google Scholar] [CrossRef]
  12. D’Arco, S.; Suul, J.A. Equivalence of virtual synchronous machines and frequency-droops for converter-based microgrids. IEEE Trans. Smart Grid 2014, 5, 394–395. [Google Scholar] [CrossRef]
  13. Hirase, Y.; Sugimoto, K.; Sakimoto, K.; Ise, T. Analysis of Resonance in Microgrids and Effects of System Frequency Stabilization Using a Virtual Synchronous Generator. IEEE J. Emerg. Sel. Top. Power Electron. 2016, 4, 1287–1298. [Google Scholar] [CrossRef]
  14. Belila, A.; Tabbache, B.; Berkouk, E.; Benbouzid, M. Integration of a storage system in a hybrid system “diesel-photovoltaic” for stand-alone applications. In Proceedings of the IEEE International Conference on Environment and Electrical Engineering and IEEE Industrial and Commercial Power Systems Europe (EEEIC/I&CPS Europe), Milan, Italy, 6–9 June 2017. [Google Scholar]
  15. Belila, A.; Tabbache, B. A control strategy of hybrid system“diesel-photovoltaic-battery” for stand-alone applications. In Proceedings of the IEEE 15th International Conference on Environment and Electrical Engineering (EEEIC), Rome, Italy, 10–13 June 2015. [Google Scholar]
  16. Kundur, P. Power System Stability and Control; McGrawHill: NewYork, NY, USA, 1993. [Google Scholar]
  17. NREL. Flexibility in 21st Century Power Systems. Available online: https://www.nrel.gov/docs/fy14osti/61721.pdf (accessed on 29 December 2019).
  18. Wang, Z.; Yi, H.; Wu, J.; Zhuo, F.; Wang, F.; Zeng, Z. Dynamic performance analysis of paralleled virtual synchronous generators under grid connected and islanded mode. In Proceedings of the IEEE Applied Power Electronics Conference and Exposition (APEC), Tampa, FL, USA, 26–30 March 2017. [Google Scholar]
  19. Chen, J.; O’Donnell, T. Analysis of virtual synchronous generator control and its response based on transfer functions. IET Power Electron. 2019, 12, 2965–2977. [Google Scholar] [CrossRef]
  20. Torres, M.A.L.; Lopes, L.A.C.; Moran, L.A.T.; Espinoza, J.R.C. Self-Tuning Virtual Synchronous Machine: A Control Strategy for Energy Storage Systems to Support Dynamic Frequency Control. IEEE Trans. Energy Convers. 2014, 29, 833–840. [Google Scholar] [CrossRef]
  21. Li, D.; Zhu, Q.; Lin, S.; Bian, X.Y. A self-adaptive inertia and damping combination control of VSG to support frequency stability. IEEE Trans. Energy Conv. 2017, 32, 397–398. [Google Scholar] [CrossRef]
  22. Alipoor, J.; Miura, Y.; Ise, T. Power system stabilization using virtual synchronous generator with alternating moment of inertia. IEEE J. Emerg. Sel. Top. Power Electron. 2015, 3, 451–458. [Google Scholar] [CrossRef]
  23. Fouad, A.A.; Anderson, P.M. Power System Control and Stability; Wiley-IEEE Press: New York, NY, USA, 2003. [Google Scholar]
  24. Fang, J.; Li, H.; Tang, Y.; Blaabjerg, F. Distributed Power System Virtual Inertia Implemented by Grid-Connected Power Converters. IEEE Trans. Power Electron. 2018, 33, 8488–8499. [Google Scholar] [CrossRef] [Green Version]
  25. Peng, F.Z.; Li, Y.W.; Tolbert, L.M. Control and protection of power electronics interfaced distributed generation systems in a customer-driven microgrid. In Proceedings of the IEEE Power & Energy Society General Meeting, Calgary, AB, Canada, 26–30 July 2009. [Google Scholar]
  26. Chiang, S.J.; Yen, C.Y.; Chang, K.T. A multimodule parallelable series-connected PWM voltage regulator. IEEE Trans. Ind. Electron. 2001, 48, 506–516. [Google Scholar] [CrossRef]
  27. Yu, X.; Khambadkone, A.M.; Wang, H.; Terence, S.T.S. Control of Parallel-Connected Power Converters for Low-Voltage Microgrid—Part I: A Hybrid Control Architecture. IEEE Trans. Power Electron. 2010, 25, 2962–2970. [Google Scholar] [CrossRef]
  28. Vilathgamuwa, D.M.; Loh, P.; Li, Y. Protection of Microgrids During Utility Voltage Sags. IEEE Trans. Ind. Electron. 2006, 53, 1427–1436. [Google Scholar] [CrossRef]
  29. Chowdhury, S.; Chowdhury, S.P.; Crossley, P. Microgrids and Active Distribution Networks; Inst. Eng. Technol.: London, UK, 2009. [Google Scholar]
  30. Craciun, B.-I.; Kerekes, T.; Sera, D.; Teodorescu, R. Frequency Support Functions in Large PV Power Plants with Active Power Reserves. IEEE J. Emerg. Sel. Top. Power Electron. 2014, 2, 849–858. [Google Scholar] [CrossRef]
  31. Doherty, R.; O’Malley, M. A New Approach to Quantify Reserve Demand in Systems with Significant Installed Wind Capacity. IEEE Trans. Power Syst. 2005, 20, 587–595. [Google Scholar] [CrossRef]
  32. Tan, Y.; Meegahapola, L.; Muttaqi, K.M. A suboptimal power-point-tracking-based primary frequency response strategy for DFIGs in hybrid remote area power supply systems. IEEE Trans. Energy Convers. 2016, 31, 93–105. [Google Scholar] [CrossRef]
  33. Margaris, I.D.; Papathanassiou, S.A.; Hansen, A.D.; Sørensen, P.E.; Hatziargyriou, N.D. Frequency Control in Autonomous Power Systems with High Wind Power Penetration. IEEE Trans. Sustain. Energy 2012, 3, 189–199. [Google Scholar] [CrossRef]
  34. Alsiraji, H.A.; El-Shatshat, R. Comprehensive assessment of virtual synchronous machine based voltage source converter controllers. IET Gener. Transm. Distrib. 2017, 11, 1762–1769. [Google Scholar] [CrossRef]
  35. D’Arco, S.; Suul, J.A. Virtual synchronous machines—Classification of implementations and analysis of equivalence to droop controllers for microgrid. In Proceedings of the IEEE Powertech Grenoble Conference, Grenoble, France, 16–20 June 2013. [Google Scholar]
  36. Ekanayake, J.; Jenkins, N.; Strbac, G. Frequency Response from Wind Turbines. Wind Eng. 2008, 32, 573–586. [Google Scholar] [CrossRef]
  37. Franklin, G.F.; Powell, J.D.; Emami-Naeini, A. Feedback Control of Dynamic Systems; Pearson: New York, NY, USA, 2014. [Google Scholar]
  38. Prakash, V.; Bhakar, R.; Tiwari, H.; Sharma, K.C. Inertia and primary frequency response assessment under uncertain photovoltaic generation. In Proceedings of the 8th IEEE India International Conference on Power Electronics (IICPE), Jaipur, India, 13–15 December 2018. [Google Scholar]
  39. Frack, P.F.; Mercado, P.E.; Molina, M.G.; Watanabe, E.H.; De Doncker, R.W.; Stagge, H. Control-Strategy for Frequency Control in Autonomous Microgrids. IEEE J. Emerg. Sel. Top. Power Electron. 2015, 3, 1046–1055. [Google Scholar] [CrossRef]
  40. Fernández-Guillamón, A.; Gómez-Lázaro, E.; Muljadi, E.; Molina-García, Á. Power systems with high renewable energy sources: A review of inertia and frequency control strategies over time. Renew. Sustain. Energy Rev. 2019, 115, 109369. [Google Scholar]
Figure 1. Control structure of AGC: (a) AGC on synchronous generators and (b) virtual AGC on VSG-PEIs.
Figure 1. Control structure of AGC: (a) AGC on synchronous generators and (b) virtual AGC on VSG-PEIs.
Applsci 10 00953 g001aApplsci 10 00953 g001b
Figure 2. Multiple temporal stages of frequency response after a step increase of load.
Figure 2. Multiple temporal stages of frequency response after a step increase of load.
Applsci 10 00953 g002
Figure 3. Block diagram of the emulation of IR and PFR.
Figure 3. Block diagram of the emulation of IR and PFR.
Applsci 10 00953 g003
Figure 4. Pole-zero map of the transfer function.
Figure 4. Pole-zero map of the transfer function.
Applsci 10 00953 g004
Figure 5. Frequency responses of dynamic systems based on original and simplified transfer functions (H = 5, 7, 10, 15 under a 3% step increase of the load).
Figure 5. Frequency responses of dynamic systems based on original and simplified transfer functions (H = 5, 7, 10, 15 under a 3% step increase of the load).
Applsci 10 00953 g005
Figure 6. Inertia influence on performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Figure 6. Inertia influence on performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Applsci 10 00953 g006
Figure 7. Speed droop influence on performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Figure 7. Speed droop influence on performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Applsci 10 00953 g007
Figure 8. Pole-zero map of the transfer function in the SFR stage.
Figure 8. Pole-zero map of the transfer function in the SFR stage.
Applsci 10 00953 g008
Figure 9. Integral effect on the performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Figure 9. Integral effect on the performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Applsci 10 00953 g009
Figure 10. Inertia effect on the performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Figure 10. Inertia effect on the performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Applsci 10 00953 g010
Figure 11. Speed droop effect on performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Figure 11. Speed droop effect on performance indices: (a) maximum ROCOF, (b) peak frequency, (c) tpeak, (d) ts, (e) overshot, and (f) setting frequency.
Applsci 10 00953 g011
Figure 12. Composite parameter influences on performance indices in the IR and PFR stages: (a) ROCOF versus H and R, (b) frequency nadir versus H and R, (c) PFR settling frequency versus H and R, and (d) PFR settling time versus H and R.
Figure 12. Composite parameter influences on performance indices in the IR and PFR stages: (a) ROCOF versus H and R, (b) frequency nadir versus H and R, (c) PFR settling frequency versus H and R, and (d) PFR settling time versus H and R.
Applsci 10 00953 g012aApplsci 10 00953 g012b
Figure 13. Composite parameter influences on performance indices in the SFR stages: (a) SFR settling time versus H and R, (b) SFR overshoot versus H and KI, and (c) overshoot versus R and KI.
Figure 13. Composite parameter influences on performance indices in the SFR stages: (a) SFR settling time versus H and R, (b) SFR overshoot versus H and KI, and (c) overshoot versus R and KI.
Applsci 10 00953 g013aApplsci 10 00953 g013b
Figure 14. Flowchart of parameter tuning for VSG-PEIs.
Figure 14. Flowchart of parameter tuning for VSG-PEIs.
Applsci 10 00953 g014
Figure 15. Estimated reduction of Heq in different European areas.
Figure 15. Estimated reduction of Heq in different European areas.
Applsci 10 00953 g015
Figure 16. Frequency response without renewable participation: (a) frequency, and (b) ROCOF.
Figure 16. Frequency response without renewable participation: (a) frequency, and (b) ROCOF.
Applsci 10 00953 g016aApplsci 10 00953 g016b
Figure 17. Frequency response with renewable participation without parameter tuning: (a) frequency and, (b) ROCOF.
Figure 17. Frequency response with renewable participation without parameter tuning: (a) frequency and, (b) ROCOF.
Applsci 10 00953 g017
Figure 18. Frequency response by the parameter tuning: (a) frequency, (b) ROCOF, and (c) power in PFR loop.
Figure 18. Frequency response by the parameter tuning: (a) frequency, (b) ROCOF, and (c) power in PFR loop.
Applsci 10 00953 g018aApplsci 10 00953 g018b
Figure 19. Secondary frequency regulation by the parameter tuning: (a) frequency, (b) ROCOF, (c) power in PFR loop, and (d) power in SFR loop.
Figure 19. Secondary frequency regulation by the parameter tuning: (a) frequency, (b) ROCOF, (c) power in PFR loop, and (d) power in SFR loop.
Applsci 10 00953 g019
Table 1. Typical parameters of an SG with a reheat steam turbine [16].
Table 1. Typical parameters of an SG with a reheat steam turbine [16].
ParameterValueUnitParameterValueUnit
R0.05puFHP0.3pu
H5puTRH7s
D1puTCH0.3s
TG0.2s
Table 2. Typical inertia constant of traditional synchronous machines [16].
Table 2. Typical inertia constant of traditional synchronous machines [16].
Type of Generation UnitInertia Constant
Thermal unit(1) 2 poles2.5–6.0
(2) 4 poles4.0–10.0
Hydraulic unit2.0–4.0
Table 3. Performance indices for IR and PFR.
Table 3. Performance indices for IR and PFR.
Performance IndicesStandard
Maximum ROCOF magnitude0.125–0.5 Hz/s
Frequency nadir/peak magnitude0.2–0.5 Hz
Settling frequency49.5–50.5 Hz
PFR delivery time10–30 s
SFR delivery time30 s–minutes
Table 4. Predetermined standards of performance indices.
Table 4. Predetermined standards of performance indices.
Performance IndicesStandard
Maximum ROCOF magnitude0.5 Hz/s
Frequency nadir/peak magnitude0.2 Hz
PFR Delivery timeWithin 20 s
SFR Delivery timeWithin 40 s
Table 5. Parameters in simulation.
Table 5. Parameters in simulation.
ParameterValueUnitParameterValueUnit
Vdc800VHeq5pu
Vac0.22kVD1pu
L10mHR0.05-
C350 μ F Voltage droop3%pu
f50HzLoad step0.03pu
fpwm5000HzStep time1s
VAbase15000WKI10-
τ 20s
Table 6. Comparison of system performance in different scenarios.
Table 6. Comparison of system performance in different scenarios.
Without Renewable ParticipationWith Renewable Participation without Parameter TuningWith Renewable Participation and Parameter Tuning
Heq (s)3.03.65
Nadir (Hz)49.689549.701449.8201
|ROCOF|max (Hz/s)0.44520.37070.1602
Settling frequency (Hz)49.833049.873049.9237

Share and Cite

MDPI and ACS Style

Zhang, W.; Yan, X.; Huang, H. Performance Tuning for Power Electronic Interfaces Under VSG Control. Appl. Sci. 2020, 10, 953. https://doi.org/10.3390/app10030953

AMA Style

Zhang W, Yan X, Huang H. Performance Tuning for Power Electronic Interfaces Under VSG Control. Applied Sciences. 2020; 10(3):953. https://doi.org/10.3390/app10030953

Chicago/Turabian Style

Zhang, Weichao, Xiangwu Yan, and Hanyan Huang. 2020. "Performance Tuning for Power Electronic Interfaces Under VSG Control" Applied Sciences 10, no. 3: 953. https://doi.org/10.3390/app10030953

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop