Enhancement of Power Quality Using Voltage and Hall Effect Current Sensors Applied on Controlled Single-Phase Active Power Filter †

Botucatu College (UNIBR), Botucatu 18611-020, Brazil
*
Author to whom correspondence should be addressed.
Presented at the 7th International Electronic Conference on Sensors and Applications, 15–30 November 2020; Available online: https://ecsa-7.sciforum.net/.
Eng. Proc. 2020, 2(1), 74; https://doi.org/10.3390/ecsa-7-08212
Published: 14 November 2020
(This article belongs to the Proceedings of 7th International Electronic Conference on Sensors and Applications)

Abstract

:
Switched-mode power supply and semiconductor devices have been gaining more and more applicability in the industrial scenario. With the massive use of these devices, several problems related to power quality and equipment degradation have been arising, caused mainly by the harmonic content present in current and voltage. Power quality problems have direct implications for business productivity, causing high economic losses. Therefore, it is mandatory to develop solutions that mitigate these problems. Active power filters (APF) are power electronic equipment capable of compensating power quality problems. Moreover, it presents the ability to dynamically adjust their modes of operation in response to changes in load or the power systems. Active power filters present the economical advantage of using the same current and voltage sensors already existing in a power system. Aiming to develop an APF for single-phase applications, this work proposes a shunt controlled active power filter using hall effect current and voltage sensor, aiming to compensate harmonic currents provided by nonlinear loads. It was proposed two proportional-integral compensators, where the external loop is responsible for link-CC control and the inner loop is responsible for current compensation. The results show the applicability of the proposed APF, since all harmonic content was filtered.

1. Introduction

The advent of power electronics allowed the improvement of semiconductor devices, generating a crucial change in the drive, control and power level of various types of loads. Therefore, power electronic systems are used increasingly in a wide range of application fields, such as variable-speed drives, switched sources, rectifiers, and others. Moreover, they are widely used for administrative equipment such as personal computers [1]. However, power semiconductor devices bring, as a disadvantage, the appearance of harmonics in the electrical grid [2]. These harmonics are originated by the non-linear conduction of the electronic switches, causing distortions in the voltage and current waveform. Due to this non-linear current, the system has to supply a large amount of reactive power [3].
In this context, grid harmonics cause problems, such as voltage regulation and stability, deterioration of power quality, and increasing system losses. Due to the enormous financial and operational impact caused by the presence of reactive energy in the grid, the correct control and mitigation of reactive power and harmonic are more than necessary topics nowadays [4,5].
To solve problems related to loads with high harmonic content, active power filters (APFs) [6] are used. APFs are used to compensate current distortions from non-linear loads. This is accomplished by injecting harmonic currents into the grid as phase opposition to the harmonic currents generated by the load [7]. In addition, active power filters present the economical advantage of using the same current and voltage sensors already existing in power systems [8].
In this context, this work proposes a shunt controlled active power filter using Hall effect current and voltage sensor aiming to mitigate harmonic current content from non-linear loads. To achieve this goal, a non-linear load (emulated through a rectifier) was powered by a single-phase voltage supply. At the common coupling point, a shunt active power filter, consisting of a DC bus and four semiconductor switches (IGBT) switches, was set in parallel with the load. The proposed control system for the switching of the electronic devices was achieved through the acquisition of the current and voltage signals from the grid by the hall effect sensors. Furthermore, two proportional-integral compensators were proposed, where the external loop is responsible for link-DC control, and the inner loop is responsible for current compensation. Harmonic mitigation was achieved by assessing these current and voltage signals from hall effect sensors in the proposed AFP. This control technique allows the compensation of currents generated by non-linear loads.
In conclusion, based on the relevance of the power electronics devices in the industrial scenario, it is crucial to develop systems capable to mitigate reactive power and harmonic content [9]. Furthermore, the control algorithm proposed in this work proved to be an efficient technique for the APF system. The hall effect sensors applied to signal acquisition are considerably useful, due to their applications in power systems, allowing the development of viable active power filters. Finally, the results showed the applicability of the proposed APF, since all harmonic content was filtered.
This paper is divided into six sections. Section 2 and Section 3 describe the hall effect sensors and the control algorithm, respectively. Section 4 describes the experimental setup that was carried out in this work. Section 5 contains the results, and Section 6 presents the conclusions.

2. Hall Effect Sensors

A Hall effect sensor is a transducer that, when under application of a magnetic field, responds with a variation in its output voltage [10].
The Hall effect is a property that manifests itself in a conductor when a magnetic field perpendicular to the current flow is applied on it. When this occurs, a voltage in the conductor is generated, called Hall voltage. This voltage has a perpendicular direction to the magnetic field and current, and is proportional to the magnetic flux density and current. The magnetic field applied causes a gradient of carrier concentration in the entire conductor. When the number of carriers on one side of the conductor is greater than the other, then this voltage will appear. Hall voltage amplitude varies with current and magnetic field [10].

3. Control Technique

The control algorithm developed in this article is based on the proportional-integral compensators. The following subsections will present the active power filter and the control algorithm.

3.1. Active Power Filter

The active power filter consists of injecting compensation currents into the electrical grid in order to cancel the harmonic and reactive power generated by the load. The main goal of the APF is that the currents of the load and the currents of the active power filter result in sinusoidal grid currents, i.e., no harmonic content [7]. A typical system setup is shown in Figure 1.
The structure chosen for the assembly of the active power filter was the full bridge voltage source inverter. This topology consists of four semiconductor switches (IGBT) and a DC bus.

3.2. Control Algorithm

The proposed control algorithm is based on two proportional-integral compensators, where the external loop is responsible for link-DC control and the inner loop is responsible for current compensation. The block diagram of the control system is shown in Figure 2.
The control system was designed according to the experimental assembly specifications shown in the following section. For the practical implementation of the proportional-integral controller, operational amplifiers were used. With this, the external loop has the function of controlling the DC bus voltage at a specific value and providing the current reference for the internal loop. This loop aims to generate the necessary pulses for switching IGBT devices, mitigating current harmonics. The structure of the proportional-integrated controllers, and its values are presented in Figure 3.

4. Experimental Setup

For the implementation of the active power filter, a highly non-linear load was used. The filter in operation should reduce the harmonic current distortions to values lower than 10 per cent. The load is defined by a rectifier with a capacitor and a resistor in parallel on the DC side of the rectifier. The capacitor used was 1 mF with a resistance of 200 ohms. Therefore, the load has an active power of 153.6 W; reactive power of 476 VAr and power factor of 0.302. The grid power supply is 127 Vrms with 60 Hz frequency. The DC bus voltage is 350 V and the switching frequency of IGBTs is 30 kHz. The structure of the APF used is shown in Figure 4. The experimental setup is shown in Figure 5.

5. Results

The load current waveform is shown in the Figure 6a. It is noted that its behavior is highly non-linear. The Figure 6b presents the content of the fast Fourier transform (FFT) of this waveform, in which it is possible to notice its high harmonic content. After the APF application, it is possible to observe that the load current was filtered, and all this harmonic content now flows through the filter. Therefore, the grid current presents a sinusoidal shape, as shown in Figure 7a. This sinusoidal behavior is evidenced by the FFT of this signal, presented in Figure 7b.

6. Conclusions

Due to the relevance of power electronics devices in production lines and industrial environment, active power filters are powerful tools to improve the power quality. Therefore, in this work, an active power filter was used, that uses a current hall effect sensor to provide the current signals for the control systems.
The application of the technique has stood out for providing precise and high accuracy results, as proven by FFT analysis of the grid and load current. It allowed one to mitigate the harmonic content present in the load. The compensation was correctly achieved, once the total harmonic distortion was lower than 10 per cent, as this work proposed.
In future works, a three-phase system can be assessed. Furthermore, the application of APF in renewable energy systems can be proposed as wind and photo-voltaic.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Falck, J.; Felgemacher, C.; Rojko, A.; Liserre, M.; Zacharias, P. Reliability of Power Electronic Systems: An Industry Perspective. IEEE Ind. Electron. Mag. 2018, 12, 24–35. [Google Scholar] [CrossRef]
  2. Bose, B.K. Power Electronics, Smart Grid, and Renewable Energy Systems. Proc. IEEE 2017, 105, 2011–2018. [Google Scholar] [CrossRef]
  3. Mishra, A.K.; Das, S.R.; Ray, P.K.; Mallick, R.K.; Mohanty, A.; Mishra, D.K. PSO-GWO Optimized Fractional Order PID Based Hybrid Shunt Active Power Filter for Power Quality Improvements. IEEE Access 2020, 8, 74497–74512. [Google Scholar] [CrossRef]
  4. Ferreira, S.C.; Gonzatti, R.B.; Pereira, R.R.; da Silva, C.H.; da Silva, L.E.B.; Lambert-Torres, G. Finite Control Set Model Predictive Control for Dynamic Reactive Power Compensation With Hybrid Active Power Filters. IEEE Trans. Ind. Electron. 2018, 65, 2608–2617. [Google Scholar] [CrossRef]
  5. Rocha, M.A.; de Souza, W.G.; Serni, P.J.A.; Andreoli, A.L.; Clerice, G.A.M.; da Silva, P.S. Control of three-phase PWM boost rectifiers using proportional-resonant controllers. In Proceedings of the 2018 Simposio Brasileiro de Sistemas Eletricos (SBSE), Niteroi, Brazil, 12–16 May 2018. [Google Scholar] [CrossRef]
  6. Hou, S.; Fei, J.; Chen, C.; Chu, Y. Finite-Time Adaptive Fuzzy-Neural-Network Control of Active Power Filter. IEEE Trans. Power Electron. 2019, 34, 10298–10313. [Google Scholar] [CrossRef]
  7. Bosch, S.; Staiger, J.; Steinhart, H. Predictive Current Control for an Active Power Filter With LCL-Filter. IEEE Trans. Ind. Electron. 2018, 65, 4943–4952. [Google Scholar] [CrossRef]
  8. Pandey, S.K.; Singh, B. Hybrid DSC with Compensation Capability Based Control for Grid Integrated SPV System. In Proceedings of the 2020 IEEE 9th Power India International Conference (PIICON), Sonepat, India, 28 February–1 March 2020. [Google Scholar] [CrossRef]
  9. Kashif, M.; Hossain, M.; Zhuo, F.; Gautam, S. Design and implementation of a three-level active power filter for harmonic and reactive power compensation. Electr. Power Syst. Res. 2018, 165, 144–156. [Google Scholar] [CrossRef]
  10. Ramsden, E. Hall-Effect Sensors: Theory and Applications; Elsevier: Amsterdam, The Netherlands; Newnes: Boston, MA, USA, 2006. [Google Scholar]
Figure 1. Active Power Filter.
Figure 1. Active Power Filter.
Engproc 02 00074 g001
Figure 2. Control Algorithm Block Diagram.
Figure 2. Control Algorithm Block Diagram.
Engproc 02 00074 g002
Figure 3. Proportional-Integral Design.
Figure 3. Proportional-Integral Design.
Engproc 02 00074 g003
Figure 4. Active power filters (APF) Proposed Topology.
Figure 4. Active power filters (APF) Proposed Topology.
Engproc 02 00074 g004
Figure 5. (a) control setup; (b) instrumentation and measure; (c) semiconductor switches (IGBT) devices.
Figure 5. (a) control setup; (b) instrumentation and measure; (c) semiconductor switches (IGBT) devices.
Engproc 02 00074 g005
Figure 6. (a) Load Current; (b) Load Current FFT.
Figure 6. (a) Load Current; (b) Load Current FFT.
Engproc 02 00074 g006
Figure 7. (a) Grid Current; (b) Grid Current fast Fourier transform (FFT).
Figure 7. (a) Grid Current; (b) Grid Current fast Fourier transform (FFT).
Engproc 02 00074 g007
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Barnabé, F.; Rocha, M.; Clerice, G. Enhancement of Power Quality Using Voltage and Hall Effect Current Sensors Applied on Controlled Single-Phase Active Power Filter. Eng. Proc. 2020, 2, 74. https://doi.org/10.3390/ecsa-7-08212

AMA Style

Barnabé F, Rocha M, Clerice G. Enhancement of Power Quality Using Voltage and Hall Effect Current Sensors Applied on Controlled Single-Phase Active Power Filter. Engineering Proceedings. 2020; 2(1):74. https://doi.org/10.3390/ecsa-7-08212

Chicago/Turabian Style

Barnabé, Felipe, Marco Rocha, and Guilherme Clerice. 2020. "Enhancement of Power Quality Using Voltage and Hall Effect Current Sensors Applied on Controlled Single-Phase Active Power Filter" Engineering Proceedings 2, no. 1: 74. https://doi.org/10.3390/ecsa-7-08212

Article Metrics

Back to TopTop