Next Article in Journal
Multi-Beam Luneburg Lens with Reduced Size Patch Antenna
Next Article in Special Issue
Coordinated Voltage-Power Control for DC Distribution Networks Based on an Uncertainty and Disturbance Estimator
Previous Article in Journal
Wavelet Threshold Ultrasound Echo Signal Denoising Algorithm Based on CEEMDAN
Previous Article in Special Issue
Adaptive Droop Control of VSC-MTDC System Based on Virtual Inertia
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Frequency Support Control of Multi-Terminal Direct Current System Integrated Offshore Wind Farms Considering Direct Current Side Stability

Electric Power Research Institute, State Grid Jiangsu Electric Power Co., Ltd., Nanjing 211103, China
*
Author to whom correspondence should be addressed.
Electronics 2023, 12(14), 3029; https://doi.org/10.3390/electronics12143029
Submission received: 1 June 2023 / Revised: 5 July 2023 / Accepted: 9 July 2023 / Published: 10 July 2023

Abstract

:
The frequency stability of modern power systems is challenged due to widespread application of large-scale renewable energy systems, of which the offshore wind farm (OWF) is one of the dominant resources. The OWFs are usually integrated into the grid by multi-terminal direct current (MTDC) transmission systems, which makes the energy flow complicated and the frequency control design challenging. A frequency support control method of MTDC system integrated OWFs (referred to as the OWF-MTDC system) is proposed in this paper. First, the wind turbine generation system (WTGS) is controlled to reserve a certain amount of available power according to the real-time wind speed for more comprehensive frequency regulation. Then, the frequency support control of OWFs is designed, and they can release the rotor kinetic energy and reserved power to support the onshore grid frequency. In addition, the virtual inertia control of a modular multi-level converter (MMC) is designed, which can also provide frequency support in an emergency by use of the DC capacitor. To ensure that the frequency control of the OWF-MTDC system does not degrade the stability of the system, a detailed DC impedance model of the MMC-based MTDC systems is developed, considering the constant power control and DC voltage control. Based on the impedance model, the impact of the frequency control coefficients on the DC side stability of the MTDC system is analyzed. Simulation results validate the stability analysis and verify the proposed frequency control method, which can effectively provide frequency support to the onshore power grid.

1. Introduction

Offshore wind farms (OWFs) are developing rapidly and have attracted considerable attention in the field of renewable energy grid integration research due to their remarkable advantages, such as small footprint and high annual operating hours [1]. Due to the large scale of OWFs and the long distance between OWFs and onshore grids, voltage source converter-based multi-terminal direct current (VSC-MTDC) transmission technology is considered to be the most suitable option to integrate OWFs into the grid [2,3], making the OWF-MTDC system widely applied. The increasing penetration of wind power and other renewable energy sources significantly reduces the grid inertia, but the OWFs do not respond to grid frequency fluctuation under the conventional control scheme, which threatens the grid frequency stability [4]. To ensure safe and stable operation of the power system, research on frequency support control of OWF-MTDC systems is necessary and urgent.
The research on frequency control usually focuses on microgrids at first. For instance, the authors of [5] proposed a distributed event-triggered secondary control for frequency/voltage restoration and power sharing in cyber-physical microgrids. However, this approach may result in zero internal execution time, which leads to an accumulation of event times, also known as the Zeno phenomenon. In [6], the grid situational awareness system is analyzed, and the smart grid situational awareness model and conceptual design is presented, based on which the event-triggered strategy naturally excludes the Zeno phenomenon. As for the frequency control of OWFs for large-scale grid support, some attempts have been made to explore the assistance from the energy storage system (ESS) with its flexible charge–discharge capability [7], but the ESS will bring in nonnegligible cost. Moreover, the MTDC system in charge of integrating OWFs into the grid can provide frequency support as well. In [8], a frequency support strategy was developed for AC grids connected by an MTDC system, where the frequency of the disturbed grid can be restored by dispersing the disturbance to all interconnected grids. However, this may lead to severe frequency drops in other AC grids, and the frequency regulation capabilities of MMCs have not been fully utilized. Although the above control methods achieve a certain frequency support performance, they barely explore the potential frequency regulation capability of OWFs.
The wind turbine generation system (WTGS) typically operates in maximum power point tracking (MPPT) mode, and its output power is decoupled from the grid frequency. To realize grid frequency support, the WTGSs can emulate the inertia or frequency damping characteristics of synchronous generators. To emulate the inertia characteristic, the rate of change of frequency (RoCoF) signal can be transferred to the rotor side converter (RSC) of an OWF to release rotor kinetic energy and output required power when frequency events occur [9,10,11]. Notably, the rotor kinetic energy that the WTGS can release for frequency support is determined by the real-time wind speed and rotor speed [12]. A low wind speed corresponds to a low rotor speed, indicating less kinetic energy stored in the rotor. In this case, if the WTGS overexploits the kinetic energy of the rotor, it may trigger low-speed disconnection of the WTGS [13], which would result in serious consequences. On the other hand, the virtual inertia provided by the rotor kinetic energy mainly supports the grid during a short period after a fault, while the WTGS may even absorb power from the grid during the rotor speed recovery period, which will threaten the long-term frequency stability. To address this issue, power reserve control (PRC) can be employed to operate the WTGS away from the maximum power point, i.e., to reserve a certain amount of available output power to provide stable active power support when the frequency drops [14]. Considering the difference in operating wind speeds among different OWFs, the reserve power of WTGSs should be reasonably set according to the real-time maximum available power, and the additional power required for frequency regulation should also be manipulated fairly based on the operating status of each WTGS. A distributed framework is proposed in [15] to issue uniform torque and pitch angle instructions of wind turbines for equal distribution of power reserve requirements. Moreover, a dynamic power reserve strategy is proposed in [16] to coordinate OWFs under different wind speed zones and analyze the feasibility of rotor overspeed control to achieve variable virtual inertia. Although the discussed research can realize frequency support from OWFs, the coordination with MMCs in the MTDC system has not been discussed.
Notably, the DC capacitors in the MMCs of MTDC systems can also be utilized to provide virtual inertia, which is realized by releasing electrostatic energy from the capacitor in emergencies [17]. A simplified approach is to convert frequency changes into a DC voltage reference value through droop control, thereby controlling the charging and discharging of the DC capacitor [18,19]. However, the frequency–voltage droop control alters the control framework of the MMC, which may threaten the stability of the MTDC system or lead to resonance instability due to the coupling effect between the capacitive MMC and inductive DC lines [20]. In the literature, the droop coefficient is usually set directly according to the frequency deviation and voltage deviation thresholds, without considering the impact of the droop coefficient on system stability. Therefore, to avoid large-scale stability issues, it is necessary to analyze the resonance stability of the MTDC system when providing frequency support.
In order to analyze the resonance stability of the MTDC system, the models of MMCs should first be developed. Among the existing techniques, the impedance analysis method has a clear physical meaning and relatively simple calculation, so it is widely used in the resonance analysis of high-voltage direct current (HVDC) systems [21]. The internal dynamic characteristics of the MMC are complex, and its impedance model is difficult to derive. References [22,23] obtain an accurate impedance model of MMCs based on the harmonic state space and harmonic linearization method, but the order of the model is high, which is not conducive to the analysis of multi-terminal system stability. References [24,25,26] proposed several different DC side impedance models for the flexible DC transmission system based on the two-level voltage source converter, and these models were used for DC side resonance analysis. However, although the literature has achieved results on the modeling of MMCs and OWFs when participating in frequency regulation, the impact of frequency control coefficients of MMCs on the stability of MTDC systems has not been measured with a detailed analysis, and the design of the frequency control of OWFs and MTDC systems lacks supportive instruction.
To address the above issues, this paper proposes the frequency support control of OWF-MTDC systems considering the coordination of OWFs and MMCs in frequency regulation. Then, this paper develops the impedance model of the OWF-MTDC system with frequency support control, based on which the impact of frequency control coefficients on the stability of the MTDC system is analyzed. It further supports the design of frequency control coefficients in the OWF-MTDC system. The rest of the paper is organized as follows. The power reserve control and additional power control for WTGSs as well as the virtual inertia control of DC capacitors in MMCs are designed in Section 2. Then, the equivalent impedance model of MMCs and further the model of the MTDC system are developed in Section 3, based on which the impact of frequency control on the stability of the MTDC system is analyzed, providing the design basis for the frequency control coefficient of MMCs proposed in Section 2. Section 4 describes the case study in PSCAD/EMTDC software, which validates the performance of the control method and the stability analysis results. Section 5 concludes this paper.

2. Frequency Support Control of OWF-MTDC Systems

2.1. Configuration of OWF-MTDC System

The typical configuration of an OWF-MTDC system is radial topology [27], as shown in Figure 1. The power generated by the OWFs is transferred to the wind farm voltage source converter (WFVSC), then transferred to the grid side voltage source converter (GSVSC) via DC cables, and finally integrated into the onshore power grid. The WFVSC usually adopts island control to regulate the (OWF side) grid frequency and AC voltage, forming the AC grid of OWFs. The GSVSC usually adopts DC voltage control and active power control to maintain the DC voltage and manipulate power supply.

2.2. Power Reserve Control of WTGS

WTGSs usually operate in MPPT mode to output the maximum available power under real-time wind speed. The maximum available power of a WTGS is given by [28]
P opt = k opt ω r 3
where Popt is the maximum available output power of the WTGS, wr is the rotor speed of the wind turbine, and kopt is the power tracking curve coefficient of the WTGS when operating in MPPT mode, which is given by
k opt = π ρ R 5 C p max 2 λ opt 3
where ρ is the air density, R is the radius of the blade, C p max is the maximum wind energy utilization coefficient, λopt is the optimal tip speed ratio.
In conventional control, the power reference obtained by the MPPT algorithm is transferred to the active power control of the RSC of WTGS. This allows the WTGS to adjust its rotor speed in time to capture the maximum available power, while the grid side converter (GSC) of the WTGS is responsible for maintaining DC voltage. Obviously, the WTGS operating in MPPT mode cannot supply excess power to the grid when the grid is experiencing power shortage, and the underfrequency event will then occur. Thus, for the WTGS to provide stable and continuous frequency support to the grid, it is necessary to reserve a certain amount of power in advance, i.e., to adopt PRC (also known as de-loading control). The PRC methods include overspeed control and pitch angle control. Both methods can cause the WTGS to deviate from its optimal operating point [29]. By setting a constant power reserve rate (d%) for all the WTGSs in an OWF, the WTGSs operating at high wind speeds will perform more power reserve and primary frequency regulation tasks. By inputting the power reference obtained from the reserved power curve into the RSC, the WTGS can operate at the power reserve point. The MPPT curve and d% reserved power curve of the WTGS at different wind speeds are shown in Figure 2, where va and vb are the cut-in wind speed the rated wind speed of the WTGS.

2.3. Frequency Support Control of WTGS

Since the rotor speed of the WTGS does not respond to the onshore grid frequency, it is necessary to introduce the frequency signal into the WTGS to artificially couple the rotor speed to the frequency. Considering that the grid frequency is mainly governed by the synchronous generator, the most effective frequency support method for the WTGS is to emulate inertia and frequency damping characteristics.
By introducing the RoCoF signal into the active power controller of the RSC as an additional droop loop, the rotor kinetic energy of the WTGS can be used to emulate the inertia response, which is called virtual inertia control. Alternatively, adding a frequency–power droop control to the active power controller of the RSC can emulate frequency damping characteristics for the WTGS. With the virtual inertia control and frequency droop control, the power reference of the RSC is given by
P ref = P de 2 H d f d t K P f f 0
where the second term represents the virtual inertia control and the third term represents the droop control.
Considering the variability of wind speed, the virtual inertia constant and frequency–power droop coefficient should be set according to the actual operating condition of the WTGS, which can be expressed as
H = ω 0 2 ω min 2 ω max 2 ω min 2 H 0
where H is the virtual inertia constant for the WTGS, ωmax and ωmin are the maximum and minimum speed of the WTGS for normal operation, respectively, ω0 is the rotor speed before disturbance, and H0 is the initial virtual inertia.
K P = P res P rated K P 0
where KP is the droop coefficient for the WTGS, Pres is the power reserve value, Prated is the rated power of the WTGS, and KP0 is the initial droop coefficient.
The active power control diagram of the RSC is shown in Figure 3, where Pref is the power reference with virtual inertia control and droop control, Pde is the power reference obtained from the reserved power tracking curve, H is the virtual inertia, KP is the frequency–power droop coefficient, f is the real-time frequency, f0 is the rated frequency.

2.4. Virtual Inertia Control of DC Capacitor in MMC

The virtual inertia can also be provided by the DC capacitors in the MMC of MTDC system. By regulating the charging or discharging of the DC capacitor, the frequency–power characteristic of the synchronous generator rotor can be emulated, and the virtual inertia can be provided, i.e.,
C dc v dc S base d v dc d t = 2 H dc f N d f d t
where Cdc is the DC capacitance, vdc is the DC voltage, Sbase is the rated capacity of the MTDC system, Hdc is the virtual inertia of the DC capacitor, and fN is the rated frequency.
Integrating both sides of (6) obtains
C dc 2 S base v dc 2 v dc 0 2 = 2 H dc f N f f 0
where vdc0 and f0 are the DC voltage and frequency before disturbance, respectively.
Expressing the voltage and frequency in per unit values, (7) can be written as
C 2 v dcpu 2 v dc 0 pu 2 = 2 H dc f pu f 0 pu
where
C = C dc v dc 0 2 S base
Since the DC voltage variation can be neglected with respect to the rated voltage, (8) can be linearized at vdc0pu as
C v dc 0 pu Δ v dcpu = 2 H dc Δ f pu
where Δvdc is the DC voltage deviation and Δf is the frequency deviation.
According to (10), the virtual inertia control of the MMC of the MTDC system can be represented as
v dcref = K DC Δ f + v dc 0
where vdcref is the DC voltage reference with virtual inertia control, KDC is the control parameter for virtual inertia control of the DC capacitor, also known as the frequency–voltage droop coefficient.
The diagram of the virtual inertia control of the MMC is shown in Figure 4. Note that only the MMC with DC voltage control can realize virtual inertia control in this way, where the output power of the DC capacitor can be manipulated.
For the MMC, the energy stored in the capacitors of all submodules is equivalent to the energy stored by an equivalent capacitor. Therefore, Cdc in (9) should be replaced by the equivalent capacitance of the MMC, i.e.,
C eq = 6 n C sub N MMC
where Ceq is the equivalent capacitance, n is the number of MMCs, and NMMC is the number of submodules in a single bridge arm.
The flow chart of the proposed frequency control of the OWF-MTDC system is shown in Figure 5, where the specific steps are demonstrated as follows.
Step 1: Define power reserve requirements for each wind turbine.
Step 2: The WTGS operates in PRC mode and reserve power according to requirements.
Step 3: Judge whether the frequency deviation exceeds the deadband. If so, go to the next step. If not, return to step 1, and the WTGS keeps the PRC mode.
Step 4: Trigger the virtual inertia control and frequency droop control of the WTGS, as well as virtual inertia control of the DC capacitor of the MMC.
Step 5: Judge whether the rotor kinetic energy of the WTGS or capacitive electrostatic energy of the MMC release exceeds the limit. If so, go to the next step. If not, return to step 4.
Step 6: The control process is finished.

3. DC Side Stability Analysis of MTDC System

3.1. MMC-MTDC System Structure

Figure 6 presents a typical four-terminal OWF-MTDC system. MMC1 and MMC2 are connected to the OWFs and are controlled by islanded control. MMC3 and MMC4 are connected to an AC system, which is a typical IEEE 3-machine and 9-bus system. As the focus of this section is the DC side stability of the MMC-MTDC system, the description of the AC grid will be given in a later section.
In the MMC-MTDC system, MMC3 adopts constant power control and MMC4 adopts DC voltage control with additional virtual inertia control of the DC capacitor. The impedance Z12 of the DC line between MMC1 and MMC2 consists of the equivalent resistance R12 and inductance L12. The impedance Z23 of the DC line between MMC2 and MMC3 consists of the equivalent resistance R23 and inductance L23. The impedance Z34 of the DC line between MMC3 and MMC4 consists of the equivalent resistance R34 and inductance L34. Llim is the current limiting reactor on the DC line.
In the following, the DC side impedance of each MMC will be modeled, and then the total DC side impedance of the MMC-MTDC system will be obtained. Based on the model, the DC side stability of the MTDC system can be analyzed.

3.2. DC Side Impedance of MMC

The internal dynamic characteristics of the MMC are complex. To accurately describe its internal dynamic characteristics, high-order differential equations are required, which greatly increase the difficulty of modeling. When it comes to the external output characteristics of the MMC, the average value model of the MMC can be applied. Then, the model can ignore the charging and discharging processes of submodule capacitors and the influence of circulating currents between bridge arms, so the strategies of capacitor voltage equalization control and phase current circulating current suppression control can be omitted. This method can effectively reduce the complexity of the model while ensuring a certain degree of accuracy. The average value model of the MMC is shown in Figure 7, where Larm and Rarm are the bridge arm inductance and bridge arm resistance, respectively, and Ce is the equivalent DC side capacitance, which can be expressed as
C e = 6 C sub / N
where N is the number of submodules and Csub is the capacitance of each submodule.
In Figure 7, ZP and ZV are parallel equivalent impedances of equivalent controlled current sources (ECCSs) of the MMC with constant power control and voltage control, respectively. In Figure 6, the ECCS output impedances of MMC1 and MMC2 are Z1 and Z2, vdc and idc are the voltage and current of the DC side of the ECCS, respectively, and idc,line is the DC output current of the MMC. The DC side impedance, which is obtained by taking the positive and negative terminals of a single converter station as ports, includes the ECCS output impedance, the DC equivalent capacitance, and the bridge arm impedance.
The ECCS output impedance of the MMC can be obtained from the relationship between DC voltage disturbance Δvdc and DC current response Δidc. Specifically, the output power of the ECCS on the DC side is given by
P dc = v dc i dc
where Pdc0 is the rated DC active power.
Linearizing (14) obtains
Δ i dc = Δ P dc v dc 0 P dc 0 v dc 0 2 Δ v dc
To obtain the ECCS output impedance, which is the relationship between Δvdc and Δidc, it is necessary to express ΔPdc in terms of Δvdc in (15). The power balance between the DC side and AC side of ECCS is given by
Δ P dc = Δ P ac
where Pac is the active power on the AC side of the MMC, and its expression is given by
P a c = 3 2 ( u c d i d + u c q i q )
After linearization near the steady-state operating point, the expression for the disturbance in Pac can be obtained as
Δ P ac = 3 2 u c d 0 u c q 0 Δ i d Δ i q + 3 2 i d 0 i q 0 Δ u c d Δ u c q
where ucd0, ucq0, id0, and iq0 are the steady-state values of ucd, ucq, id, and iq, respectively.
In summary, the key to establishing the ECCS output impedance is to obtain the relationship between Δvdc and ΔPac. Based on the ECCS output impedance, the DC side impedance of the MMC can be easily calculated according to the MMC model in Figure 7.

3.3. DC Side Impedance of MMC with Constant Power Control

The typical vector current control of the MMC is shown in Figure 8, where the DC voltage control and the constant power control are shown as the outer control loops. In Figure 8, ug, us, and uc are the voltage at the AC system bus, the point of common coupling (PCC), and the MMC AC output, respectively, P is the active power output of MMC, i is the AC current, Lg is the impedance of the AC system, LT and RT are the inductance and resistance of the transformer, respectively, θ is the phase of the PCC point voltage, ω0 is the base frequency of the AC system, and Kv(s) and Kp(s) are the transfer functions of the PI loop for voltage control and power control, respectively. Moreover, the subscripts d, q, and abc indicate the variables of the d-axis, q-axis, and abc-frame, respectively, and the subscripts “ref” and “0” indicate the reference value and rated value of the variable. Since this paper focuses on the impact of frequency support control on the DC side stability of the MTDC, which is realized on the DC voltage control loop, the reactive power control loop is not considered, and the reactive current reference value iref,q is set to 0.
By derivation as shown in Appendix A, ZP can be obtained as
Z P ,   de = Δ v dc Δ i dc = v dc 0 i dc 0 3 2 u c d 0 u c q 0 T G c 1 G LT + Z T + 3 2 K p ( s ) ( G u 0 G i 0 Z T ) 1 3 2 K p ( s ) G i 0 + i d 0 i q 0 T m d 0 m q 0 1
Based on the average value model of the MMC as shown in Figure 7, in the impedance model of the MMC on the DC side, the equivalent output impedance of the ECCS is first connected in parallel with the equivalent capacitance Ce on the DC side, and then connected in series with the equivalent impedance Larm and Rarm of the bridge arm. Based on the average value model of the MMC shown in Figure 7, the DC impedance Zdc_3 of the MMC station with constant active power control can be obtained as
Z dc _ 3 = Z P 1 + s C e Z P + 2 3 ( s L arm + R arm )
Considering that MMC1 and MMC2, which connect OWF1 and OWF2, adopt island control, the expressions of the ECCS output impedances Z1 and Z2 for MMC1 and MMC2 are given by
Z 1 = v dc 0 2 P 1 , Z 2 = v dc 0 2 P 2
where P1 and P2 are the rated power of MMC1 and MMC2, respectively.
Similar to the analysis of the average model for the MMC above, the expressions of the DC side impedances Zdc_1 and Zdc_2 for MMC1 and MMC2 can be obtained as
Z dc _ 1 = Z 1 1 + s C e Z 1 + 2 3 ( s L arm + R arm ) Z dc _ 2 = Z 2 1 + s C e Z 2 + 2 3 ( s L arm + R arm )

3.4. DC Side Impedance of MMC with DC Voltage Control and Virtual Inertia Control

As shown in Figure 8, the control structure of the MMC with DC voltage control is the same as that with constant power control, except for the difference in the outer loop structure. Kv(s) is the PI controller for the voltage outer loop, which can be expressed as
K v ( s ) = k vp + k vi / s
where kvp and kvi are the proportional and integral parameters of the PI controller.
Since only the outer loop structure is changed for the MMC with DC voltage control, the inner loop structure, PWM structure, and AC system structure of the MMC output impedance model derived previously in the constant power control mode can still be used in the MMC with DC voltage control.
Based on the relationship between DC voltage disturbance Δvdc, current disturbance Δidc, and power disturbance ΔPdc shown in (15), the DC side output impedance of the MMC station under DC voltage control can be derived. According to the outer loop structure shown in Figure 8, the expression of the current reference for the current inner loop can be obtained as
i d ref i q ref = K v ( s ) 0 ( v dcref v dc )
Linearizing (24) near the operating point obtains
Δ i d ref Δ i q ref = K v ( s ) 0 ( Δ v dcref Δ v dc )
In order to provide inertia support to the AC system, frequency–voltage droop control is introduced into the outer control loop of the MMC with DC voltage control. This allows the reference value of the DC voltage to change with the system frequency, the expression is
v dcref = ( f f ref ) K DC + v dc 0
where f is the real-time frequency of the system, fref is the reference frequency value, and KDC is the droop coefficient.
Linearizing (26) near the equilibrium point obtains
Δ v dcref = K DC Δ f
According to the characteristics of the AC system in Figure 6, the relationship between frequency and power can be obtained by a genetic algorithm [30], as shown in (28).
Δ f = G F ( s ) Δ P s = Δ P ( 0.1499 s 3 + 32.58 s 2 + 12.89 s + 1 ) s ( 270.3 s 3 + 209.2 s 2 + 96.34 s + 19.11 )
Introducing (28) into (27) obtains
Δ v dcref = K DC G F ( s ) Δ P s = G P ( s ) Δ P
where GP(s) is
G P ( s ) = K DC ( 0.1499 s 3 + 32.58 s 2 + 12.89 s + 1 ) s ( 270.3 s 3 + 209.2 s 2 + 96.34 s + 19.11 )
Substituting (29) into (25) obtains
Δ i d ref Δ i q ref = K v ( s ) 0 ( G P ( s ) Δ P Δ v dc )
By derivation as shown in Appendix B, ZV can be obtained as
Z V = Δ v dc Δ i dc = v dc 0 G V
where
G V = 3 2 u c d 0 u c q 0 G iv 1 G uv + i d 0 i q 0 m d 0 m q 0 + 3 2 u c d 0 u c q 0 G iv 1 G c K v ( s ) 0 i dc 0
Based on the MMC average value model shown in Figure 7, the DC side impedance Zdc_4 of the MMC with DC voltage control can be obtained as
Z dc _ 4 = Z V 1 + s C e Z V + 2 3 ( s L arm + R arm )

3.5. Impact of Frequency–Voltage Droop Coefficients on the Stability of MMC-MTDC System

The DC side impedance of each MMC in the MTDC system has been derived above. Taking the output of MMC2 as the port to evaluate the DC side stability of the MTDC system, after a simple series–parallel connection, the DC side impedance of the MMC-MTDC system is obtained as
Z sys = ( Z dc _ 1 + Z 12 ) / / Z dc _ 1 + ( Z dc _ 4 + Z 34 ) / / Z dc _ 2 + Z 23 + L lim
To quantitatively analyze the DC side impedance of the MMC-MTDC system, a set of reference system parameters is required. The parameters of the four-terminal MMC-MTDC system shown in Figure 6 are listed in Table 1 and Table 2.
The expression of the DC side impedance model of the MMC-MTDC system is given in (35). In order to verify the accuracy of Zsys, a frequency sweep is performed on the MMC-MTDC system in PSCAD/EMTDC. The comparison between Zsys and the simulation results of the frequency sweep in the simulation software is shown in Figure 9. As can be seen from Figure 9, Zsys conforms well to the simulation frequency sweep results, and further analysis of the system stability can be conducted based on this.
Based on the four-terminal MMC-MTDC system structure as shown in Figure 6, combined with the DC side impedance expressions (20), (22), (34) of each converter station, as well as the overall DC side impedance expression (35) of the MMC-MTDC system and the benchmark system parameters in Table 1 and Table 2, the eigenvalue trajectory of Zsys when the droop coefficient KDC changes is obtained, and thus the impact of KDC on the system stability can be analyzed.
In Figure 10, the system eigenvalue trajectory is shown when the droop coefficient KDC changes from 2 to 50. It can be seen from the results that even when the droop coefficient KDC increases to an almost exaggerated value, the system eigenvalues only remain distributed near the imaginary axis and do not cross over to the right half-plane. Therefore, even when the droop coefficient KDC is increased to an exaggerated value, the system does not become unstable, and the impact of KDC on the system stability is not significant within this wide range of variation.

4. Simulation Analysis

4.1. Verification of Impact of Droop Coefficient on MTDC System Stability

To verify the impact of the droop coefficient KDC on system stability, a simulation model of the four-terminal MMC-MTDC system as shown in Figure 6 is constructed in PSCAD/EMTDC. The simulation result is shown in Figure 11. When the droop coefficient KDC is increased from 5 to 50 at 31 s, the system quickly regains stability after a short period of fluctuation and does not become unstable, which validates the stability analysis results. It can be concluded that even if the droop coefficient KDC is increased significantly to 50, the system will not become unstable. Therefore, the impact of droop coefficient KDC on MTDC system stability is not significant. When the frequency–voltage droop coefficient KDC is adjusted, its impact on the overall stability of the MTDC system can be neglected.

4.2. Validation of Frequency Support Effect of OWF-MTDC

To validate the frequency support effect of the proposed control method under load disturbance, the MMC-MTDC system integrating OWFs shown in Figure 6 was constructed in PSCAD/EMTDC. The onshore IEEE 3-machine 9-bus system consists of a hydro generator G1 with IEEE G3 type speed governing system and steam generators G2, G3 with IEEE G1 type speed governing systems. The parameters of the WTGS and AC system are shown in Table 3 and Table 4, respectively. From the above impedance analysis, the droop coefficient KDC does not obviously affect the MTDC system stability. Thus, KDC can be determined based on the frequency deviation and allowable voltage deviation. Considering the power grid operation specification, the frequency deviation Δf of the power system is generally controlled within 2% (1 Hz), and the DC voltage deviation Δvdc is set within 15% [31]. Therefore, the droop coefficient KDC in this paper is set to 7.5. A sudden load step of 5% was set at 50 s, and the simulation results under MPPT without additional control and the proposed control method are shown in Figure 12.
As shown in Figure 12, the WTGS without additional control always operates at the maximum power point and does not respond to the onshore grid frequency deviation, where the frequency nadir is 49.37 Hz and the steady state frequency is 49.84 Hz under the disturbance. When the MTDC system adopts the proposed control method, the OWFs reserve 10% of their maximum available power, i.e., OWF1 reserves 4.3 MW and OWF2 reserves 10 MW. After the load step, the rotor kinetic energy and reserved power of the WTGSs are quickly released, and the additional output power provides virtual inertia and damping to the AC system for frequency support. The additional power is correlated with the reserve power, as shown in Figure 12c,d. Moreover, the MMC provides virtual inertia to the AC system by the DC capacitor, and the DC voltage deviation is positively correlated with the frequency deviation. Specifically, the maximum DC voltage deviation does not exceed 10%, as shown in Figure 12b, indicating that the droop coefficient is set appropriately. With the proposed control method, the frequency nadir is 49.71 Hz, and the maximum frequency deviation is reduced by 53.97% compared with the case without frequency support control, and the steady-state frequency is 49.87 Hz, which is 0.03 Hz higher than the case without frequency support control. In summary, the proposed control method can effectively provide frequency support to the onshore AC system without affecting the stability of the WTGSs and the MTDC system.

4.3. Simulation Results with Different Frequency–Voltage Droop Coefficients

In order to verify the impact of the frequency–voltage droop coefficient on the MTDC system stability as discussed in Section 3, the cases with different KDC are conducted. The simulation results of DC voltage and frequency with different KDC under a 5% sudden load step at 50 s are shown in Figure 13.
It can be seen in Figure 13 that the increase in frequency–voltage droop coefficient does not affect the stability of the system, verifying the stability analysis in Section 3. As KDC increases, the DC capacitor releases more energy, making the DC voltage drop more severely, which then raises the frequency nadir. This indicates that the virtual inertia control of the MMC can effectively provide frequency support to the onshore AC system, of which the performance is determined by the droop coefficient KDC. Considering that the voltage deviation should be kept within 30 kV, the maximum value of KDC is set to 24. However, since the voltage deviation is directly related to the frequency deviation, if the power droop coefficients of WTGSs are increased, the frequency nadir can be significantly increased, and the maximum value of KDC can also be correspondingly increased.

4.4. Simulation Results with Different Power Droop Coefficients

In order to investigate the influence of the wind turbine power droop coefficient KP (including droop coefficient of OWF1 KP1 and the droop coefficient of OWF2 KP2) on the system, several sets of power droop coefficients were added while keeping the GSVSC frequency–voltage droop coefficient KDC fixed at 7.5. The simulation results under each parameter with a 5% sudden load step at 50 s are shown in Figure 14. It can be seen from Figure 14 that the WTGS power droop control has a significant frequency raising effect. As KP increases, the OWFs output more additional power after the frequency event, and the frequency nadir of the AC system is raised while the steady-state frequency deviation is reduced. Since the DC voltage under the virtual inertia control of the DC capacitor is directly related to the frequency, the DC voltage is also raised. Therefore, under the premise of increasing the WTGS power droop coefficient, a higher frequency–voltage droop coefficient can be set within the allowable range of DC voltage deviation, which can further raise the lowest frequency point of the AC system. At the same time, it can be seen from the simulation results that changing the WTGS droop coefficient only affects the frequency support effect and does not affect the system stability. Therefore, the DC impedance modeling in Section 3 is reasonable for the simplification of MMC1 and MMC2 and does not affect the stability analysis results.

4.5. Simulation Results with Different Wind Speeds

The wind speed exhibits variability during actual operation. To evaluate the effectiveness of the proposed method across a range of wind speeds, simulation tests are conducted for OWFs with different wind speeds. WTGSs operating under low wind speeds are unsuitable for power reserve purposes. Conversely, when the wind speed surpasses the rated value, the rotor speed and output power remain constant at the rated level. In this case study, wind speeds of 7 m/s, 8 m/s, 10 m/s, and 13 m/s are selected for all the OWFs. The frequency–voltage droop coefficient KDC of the GSVSC is fixed at 7.5, while the virtual inertia constant H and the frequency–power droop coefficient KP are determined based on (4) and (5). Figure 15 illustrates the simulation results under different wind speeds, where subfigure (b) represents the additional output power of a single OWF with different wind speeds. To assess system performance, a sudden 5% load step is applied at 50 s.
As it can be seen from the results, the rotor speed and reserve power increase with wind speed, thereby the virtual inertia constant and droop coefficient are increased. Then, with a higher wind speed, the frequency nadir under the same disturbance was raised, as shown in Figure 15a, and the additional output power of OWF increases, as shown in Figure 15b. The simulation results prove that the proposed method can flexibly adjust the control coefficients according to the real-time wind speed, leading to improved frequency support performance, and the WTGSs can operate stably in the allowed wind speed range.

5. Conclusions

This paper proposes a frequency support control method for an OWF-MTDC system based on the DC side stability analysis of the MTDC system. For the WTGSs with power reserve, the rotor virtual inertia control and frequency–power droop control are designed to enable frequency regulation. For the MTDC system, the frequency–voltage droop control is designed for the MMC to provide virtual inertia by the use of the DC capacitor. The detailed DC side impedance of the MTDC system is modeled considering the MMCs under constant power control and DC voltage control. The effect of frequency–voltage droop coefficient on the MTDC system stability is then investigated based on the model, of which the results show that the proposed frequency support control is tolerant of control coefficients in terms of stability consideration. The proposed control method enables the WTGSs and the MTDC system to respond to onshore grid frequency fluctuation in a timely manner, providing additional frequency support to the onshore AC system. Simulation results show that the proposed method can reduce the maximum frequency deviation of the system by 53.97% and raises the steady-state frequency by 0.03 Hz under a disturbance. By changing the frequency–voltage droop coefficient of the MMC and the power droop coefficient of the WTGSs, the system stability is not affected, verifying the stability analysis results. The simulation results with different wind speeds prove that the proposed method can flexibly adjust the control coefficients according to the wind speed, leading to improved frequency support performance. In summary, the proposed method has a fast response speed and great frequency support performance, which effectively improves the inertia and damping coefficient of the power system and further enhances the frequency stability of the onshore power grid. In future work, we will study the time sharing coordination of virtual inertia control and droop control to further improve the frequency support performance.

Author Contributions

Conceptualization, H.H. and Q.L. (Qun Li); methodology, H.H. and Q.L. (Qiang Li); validation, H.H.; investigation, Q.L. (Qun Li); resources, Q.L. (Qun Li) and Q.L. (Qiang Li); writing—original draft preparation, H.H.; writing—review and editing, Q.L. (Qiang Li); supervision, Q.L. (Qun Li); project administration, Q.L. (Qun Li); funding acquisition, Q.L. (Qun Li). All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Science and Technology Project of State Grid Corporation of China, grant number 5100-202118472A-0-5-ZN.

Data Availability Statement

All the data supporting the reported results have been included in this paper.

Conflicts of Interest

The authors declare no conflict of interest.

Appendix A

It can be seen from Figure 8 that the AC side linearization dynamic equation of the MMC can be represented as
Δ u s d Δ u s q = Δ u c d Δ u c q s L T + R T ω 0 L T ω 0 L T s L T + R T Z T Δ i d Δ i q
where “Δ” represents small signal disturbance.
The internal current control model of the MMC is the same under different outer loop control methods, and the generated output voltage reference values ucref,d and ucref,q are
u cref , d u cref , q = K c ( s ) 0 0 K c ( s ) G c i ref , d i ref , q K c ( s ) ω 0 L T ω 0 L T   K c ( s ) G LT i d i q + u s d u s q
where Kc(s) = kcp + kci/s, kcp, and kci are the proportional and integral coefficients, respectively.
After small signal perturbations around the steady-state point, (A2) can be expressed as
Δ u cref , d Δ u cref , q = K c ( s ) 0 0 K c ( s ) G c Δ i ref , d Δ i ref , q K c ( s ) ω 0 L T ω 0 L T   K c ( s ) G LT Δ i d Δ i q + Δ u s d Δ u s q
The voltage reference values ucref,d and ucref,q output by the current inner loop are modulated to obtain the equivalent output voltages ucd and ucq on the AC side of the converter. After substituting (A1) into (A3), the voltage quantities usd and usq at the PCC point can be eliminated, and the direct relationship between the current at the MMC outlet and its reference value can be obtained as
G c Δ i ref , d Δ i ref , q = Ζ T + G LT Δ i d Δ i q
When the constant active power control is adopted, the active power on the AC side of the MMC is controlled to a specific value, and the power outer loop of constant power control can be expressed as
i d ref = K p ( s ) ( P ref P )
where Pref is the power reference value, P is the real-time measured active power value at the PCC point, and Kp(s) is the transfer function of the PI control loop for the power outer loop, which can be expressed as
K p ( s ) = k pp + k pi / s
where kpp and kpi are proportional and integral parameters of the PI loop for the outer power control.
There is a certain difference between the active power measured at the PCC (P) and the active power on the AC side of the ECCS (Pac). Pac is the real-time power at the outlet of the MMC on the AC side, which can be represented by
P = 3 2 ( u s d i d + u s q i q )
Linearizing (A7) near the steady operating point, the expression for power perturbation can be obtained as
Δ P = 3 2 u s d 0 u s q 0 Δ i d Δ i q + 3 2 i d 0 i q 0 Δ u s d Δ u s q
Substituting Equations (A7) and (A8) into Equation (A5) can obtain the current reference values iref,d and iref,q for the current inner loop, and these values can be linearized around the steady-state point, i.e.,
Δ i ref , d Δ i ref , q = 3 2 K p ( s ) u s d 0 u s q 0 0 0 G u 0 Δ i d Δ i q + i d 0 i q 0 0 0 G i 0 Δ u s d Δ u s q
Similarly, by substituting (A1) into (A9), the voltage disturbance quantities Δusd and Δusq at the PCC point can be eliminated as
Δ i ref , d Δ i ref , q = 3 2 K p ( s ) G u 0 G i 0 Z T Δ i d Δ i q + G i 0 Δ u c d Δ u c q
By combining (A1) and (A10), the disturbance quantities Δiref,d and Δiref,q can be eliminated. The disturbance quantities Δiref,d and Δiref,q can be represented by Δucd, Δucq, Δid, and Δiq. Therefore, the relationship between the voltage disturbance quantities Δucd, Δucq and current disturbance quantities Δid, Δiq at the AC outlet of the MMC can be obtained as
Δ u c d Δ u c q = 3 2 K p ( s ) G i 0 1 G c 1 G LT + Z T + 3 2 K p ( s ) ( G u 0 G i 0 Z T ) G iA Δ i d Δ i q
As mentioned earlier, the key to establishing ZP(V) is to obtain the relationship between Δvdc and ΔPac, and the expression for ΔPac is shown in (18). To calculate the DC impedance of the MMC station, (A11) needs to be substituted into (18) to eliminate the electrical disturbance quantities Δucd, Δucq, Δid, and Δiq on the AC side. Therefore, the relationship between Δvdc and ΔPac can be obtained as
Δ P a c = 3 2 u c d 0 u c q 0 G iA 1 + i d 0 i q 0 m d 0 m q 0 G A Δ v dc
where md0 and mq0 are the modulation of d-axis and q-axis, respectively, and their expressions are
m d 0 = u c d 0 / v dc 0 m q 0 = u c q 0 / v dc 0
According to the power disturbance balance between the DC side and the AC side of the ECCS, the ΔPac can be approximately equal to the ΔPdc, and the relationship between the Δvdc and the Δidc can be obtained by substituting the ΔPac of (A12) into (15), i.e.,
Δ i dc = G A Δ v dc v dc 0 P dc 0 v dc 0 2 Δ v dc
(A14) describes the relationship between voltage and current disturbance on the DC side. After sorting out, the expression of ZP can be calculated as
Z P ,   de = Δ v dc Δ i dc = v dc 0 i dc 0 3 2 u c d 0 u c q 0 T G c 1 G LT + Z T + 3 2 K p ( s ) ( G u 0 G i 0 Z T ) 1 3 2 K p ( s ) G i 0 + i d 0 i q 0 T m d 0 m q 0 1

Appendix B

Substituting (31) into (A4) obtains
G c K v ( s ) 0 ( G P ( s ) Δ P Δ v dc ) = Ζ T + G LT Δ i d Δ i q
According to the expression of ΔP in (A8), it can be obtained that
K v ( s ) 0 Δ P = 3 2 K v ( s ) u s d 0 u s q 0 0 0 G u 0 Δ i d Δ i q + i d 0 i q 0 0 0 G i 0 Δ u s d Δ u s q
Introducing (A17) into (A16) obtains
3 2 K v ( s ) G P ( s ) G c G u 0 Δ i d Δ i q + G i 0 Δ u s d Δ u s q = G c K v ( s ) 0 Δ v dc + Z T + G LT Δ i d Δ i q
Substituting (A1) into (A18), the voltage quantities usd and usq at the PCC can be eliminated as
3 2 K v ( s ) G P ( s ) G c G u 0 G i 0 Z T Δ i d Δ i q + G i 0 Δ u c d Δ u c q = G c K v ( s ) 0 Δ v dc + Z T + G LT Δ i d Δ i q
Let
G K = 3 2 K v ( s ) G P ( s ) G c
It can be obtained that
G K G u 0 G K G i 0 Z T Z T G LT G iv Δ i d Δ i q = ( G K G i 0 ) G uv Δ u c d Δ u c q + G c K v ( s ) 0 Δ v dc
The balance of power disturbance between AC and DC sides can be expressed as
v dc 0 Δ i dc + Δ v dc i dc 0 = 3 2 u c d 0 u c q 0 Δ i d Δ i q + 3 2 i d 0 i q 0 Δ u c d Δ u c q
Introducing (A21) into (18) obtains
v dc 0 Δ i dc + Δ v dc i dc 0 = 3 2 u c d 0 u c q 0 G iv 1 G uv Δ u c d Δ u c q + G c K v ( s ) 0 Δ v dc + 3 2 i d 0 i q 0 Δ u c d Δ u c q
Further processing can result in
v dc 0 Δ i dc = 3 2 u c d 0 u c q 0 G iv 1 G uv + i d 0 i q 0 Δ u c d Δ u c q + 3 2 u c d 0 u c q 0 G iv 1 G c K v ( s ) 0 i dc 0 Δ v dc = 3 2 u c d 0 u c q 0 G iv 1 G uv + i d 0 i q 0 m d 0 m q 0 + 3 2 u c d 0 u c q 0 G iv 1 G c K v ( s ) 0 i dc 0 G V Δ v dc
The essence of ZV is the relationship between the small signal disturbance Δvdc of DC voltage and the response Δidc of DC current, so the expression of ZV can be obtained from (A24) as
Z V = Δ v dc Δ i dc = v dc 0 G V

References

  1. Wang, W.Y.; Li, Y.; Cao, Y.J.; Hager, U.; Rehtanz, C. Adaptive droop control of VSC-MTDC system for frequency support and power sharing. IEEE Trans. Power Syst. 2018, 33, 1264–1274. [Google Scholar] [CrossRef]
  2. Peng, Q.; Liu, T.Q.; Wang, S.L.; Qiu, Y.F.; Li, X.Y.; Li, B.H. Determination of droop control coefficient of multi-terminal VSC-HVDC with system stability consideration. IET Renew. Power Gener. 2018, 12, 1508–1515. [Google Scholar] [CrossRef]
  3. Sun, K.; Yao, W.; Fang, J.K.; Ai, X.M.; Wen, J.Y.; Cheng, S.J. Impedance modeling and stability analysis of grid-connected DFIG-based wind farm with a VSC-HVDC. IEEE J. Emerg. Sel. Top. Power Electron. 2020, 8, 1375–1390. [Google Scholar] [CrossRef]
  4. Xiong, Y.X.; Yao, W.; Wen, J.F.; Lin, S.Q.; Ai, X.M.; Fang, J.K.; Wen, J.Y.; Cheng, S.J. Two-level combined control scheme of VSC-MTDC integrated offshore wind farms for onshore system frequency support. IEEE Trans. Power Syst. 2021, 36, 781–792. [Google Scholar] [CrossRef]
  5. Wang, Y.; Nguyen, T.L.; Xu, Y.; Li, Z.M.; Tran, Q.-T.; Caire, R. Cyber-physical design and implementation of distributed event-triggered secondary control in islanded microgrids. IEEE Trans. Ind. Appl. 2019, 55, 5631–5642. [Google Scholar] [CrossRef]
  6. Li, Y.S.; Zhang, H.G.; Liang, X.D.; Huang, B.N. Event-triggered-based distributed cooperative energy management for multienergy systems. IEEE Trans. Ind. Inform. 2019, 15, 2008–2022. [Google Scholar] [CrossRef]
  7. Guan, M.Y. Scheduled power control and autonomous energy control of grid-connected energy storage system (ESS) with virtual synchronous generator and primary frequency regulation capabilities. IEEE Trans. Power Syst. 2022, 37, 942–954. [Google Scholar] [CrossRef]
  8. Li, Z.; Wei, Z.A.; Zhan, R.P.; Li, Y.Z.; Tang, Y.; Zhang, X.-P. Frequency support control method for interconnected power systems using VSC-MTDC. IEEE Trans. Power Syst. 2021, 36, 2304–2313. [Google Scholar] [CrossRef]
  9. Xu, B.; Zhang, L.W.; Yao, Y.; Yu, X.D.; Yang, Y.X.; Li, D.D. Virtual inertia coordinated allocation method considering inertia demand and wind turbine inertia response capability. Energies 2021, 14, 5002. [Google Scholar] [CrossRef]
  10. Jiang, Q.; Zeng, X.Y.; Li, B.H.; Wang, S.L.; Liu, T.Q.; Chen, Z.; Wang, T.X.; Zhang, M. Time-sharing frequency coordinated control strategy for PMSG-based wind turbine. IEEE J. Emerg. Sel. Topics Circuits Syst. 2022, 12, 268–278. [Google Scholar] [CrossRef]
  11. Zeng, X.Y.; Liu, T.Q.; Wang, S.L.; Dong, Y.Q.; Li, B.H.; Chen, Z. Coordinated control of MMC-HVDC system with offshore wind farm for providing emulated inertia support. IET Renew. Power Gener. 2020, 14, 673–683. [Google Scholar] [CrossRef]
  12. Xiong, Y.X.; Yao, W.; Yao, Y.H.; Fang, J.K.; Ai, X.M.; Wen, J.Y.; Cheng, S.J. Distributed cooperative control of offshore wind farms integrated via MTDC system for fast frequency support. IEEE Trans. Ind. Electron. 2023, 70, 4693–4704. [Google Scholar] [CrossRef]
  13. Kheshti, M.; Lin, S.Y.; Zhao, X.W.; Ding, L.; Yin, M.H.; Terzija, V. Gaussian distribution-based inertial control of wind turbine generators for fast frequency response in low inertia systems. IEEE Trans. Sustain. Energy 2022, 13, 1641–1653. [Google Scholar] [CrossRef]
  14. Tu, G.G.; Li, Y.J.; Xiang, J. Coordinated rotor speed and pitch angle control of wind turbines for accurate and efficient frequency response. IEEE Trans. Power Syst. 2022, 37, 3566–3576. [Google Scholar] [CrossRef]
  15. Wang, X.; He, Y.G.; Gao, D.W.; Wang, Z.Y.; Muljadi, E. Cooperative output regulation of large-scale wind turbines for power reserve control. IEEE Trans. Energy Convers. 2023, 38, 1166–1177. [Google Scholar] [CrossRef]
  16. Ge, X.L.; Zhu, X.H.; Fu, Y.; Xu, Y.S.; Huang, L.L. Optimization of reserve with different time scales for wind-thermal power optimal scheduling considering dynamic deloading of wind turbines. IEEE Trans. Sustain. Energy 2022, 13, 2041–2050. [Google Scholar] [CrossRef]
  17. Peng, Q.; Jiang, Q.; Yang, Y.H.; Liu, T.Q.; Wang, H.; Blaabjerg, F. On the stability of power electronics-dominated systems: Challenges and potential solutions. IEEE Trans. Ind. Appl. 2019, 55, 7657–7670. [Google Scholar] [CrossRef]
  18. Kou, P.; Liang, D.L.; Wu, Z.H.; Ze, Q.J.; Gao, L. Frequency support from a DC-grid offshore wind farm connected through an HVDC link: A communication-free approach. IEEE Trans. Energy Convers. 2018, 33, 1297–1310. [Google Scholar] [CrossRef]
  19. Peng, Q.; Fang, J.Y.; Yang, Y.H.; Liu, T.Q.; Blaabjerg, F. Maximum virtual inertia from DC-link capacitors considering system stability at voltage control timescale. IEEE J. Emerg. Sel. Topics Circuits Syst. 2021, 11, 79–89. [Google Scholar] [CrossRef]
  20. Xu, Z.G.; Li, B.B.; Han, L.J.; Hu, J.L.; Wang, S.B.; Zhang, S.G.; Xu, D.G. A complete HSS-based impedance model of MMC considering grid impedance coupling. IEEE Trans. Power Electron. 2020, 35, 12929–12948. [Google Scholar] [CrossRef]
  21. Hu, J.B.; Zhu, J.H.; Wan, M. Modeling and analysis of modular multilevel converter in DC voltage control timescale. IEEE Trans. Ind. Electron. 2019, 66, 6449–6459. [Google Scholar] [CrossRef]
  22. Lyu, J.; Zhang, X.; Cai, X.; Molinas, M. Harmonic state-space based small-signal impedance modeling of a modular multilevel converter with consideration of internal harmonic dynamics. IEEE Trans. Power Electron. 2019, 34, 2134–2148. [Google Scholar] [CrossRef] [Green Version]
  23. Lyu, J.; Zhang, X.; Huang, J.J.; Zhang, J.W.; Cai, X. Comparison of harmonic linearization and harmonic state space methods for impedance modeling of modular multilevel converter. In Proceedings of the 2018 International Power Electronics Conference (IPEC), Niigata, Japan, 20–24 May 2018; pp. 1004–1009. [Google Scholar]
  24. Li, C.; Cao, Y.J.; Yang, Y.Q.; Wang, L.; Blaabjerg, F.; Dragicevic, T. Impedance-based method for DC stability of VSC-HVDC system with VSG control. Int. J. Electr. Power Energy Syst. 2021, 130, 106975. [Google Scholar] [CrossRef]
  25. Agbemuko, A.J.; Domínguez-García, J.L.; Prieto-Araujo, E.; Gomis-Bellmunt, O. Impedance modelling and parametric sensitivity of a VSC-HVDC system: New insights on resonances and interactions. Energies 2018, 11, 845. [Google Scholar] [CrossRef] [Green Version]
  26. Amin, M.; Molinas, M.; Lyu, J.; Cai, X. Impact of power flow direction on the stability of VSC-HVDC seen from the impedance nyquist plot. IEEE Trans. Power Electron. 2017, 32, 8204–8217. [Google Scholar] [CrossRef]
  27. Paul, S.; Rather, Z.H. A novel approach for optimal cabling and determination of suitable topology of MTDC connected offshore wind farm cluster. Electr. Power Syst. Res. 2022, 208, 107877. [Google Scholar] [CrossRef]
  28. Li, Y.J.; Xu, Z.; Zhang, J.L.; Yang, H.M.; Wong, K.P. Variable utilization-level scheme for load-sharing control of wind farm. IEEE Trans. Energy Convers. 2018, 33, 856–868. [Google Scholar] [CrossRef]
  29. Dreidy, M.; Mokhlis, H.; Mekhilef, S. Inertia response and frequency control techniques for renewable energy sources: A review. Renew. Sust. Energ. Rev. 2017, 69, 144–155. [Google Scholar] [CrossRef]
  30. Huang, H.; Ju, P.; Jin, Y.; Yuan, X.; Qin, C.; Pan, X.; Zang, X. Generic system frequency response model for power grids with different generations. IEEE Access 2020, 8, 14314–14321. [Google Scholar] [CrossRef]
  31. Zhu, J.B.; Hu, J.B.; Huang, W.; Wang, C.S.; Zhang, X.; Bu, S.Q.; Li, Q.; Urdal, H.; Booth, C.D. Synthetic inertia control strategy for doubly fed induction generator wind turbine generators using lithium-ion supercapacitors. IEEE Trans. Energy Convers. 2018, 33, 773–783. [Google Scholar] [CrossRef]
Figure 1. OWF-MTDC system configuration.
Figure 1. OWF-MTDC system configuration.
Electronics 12 03029 g001
Figure 2. MPPT curve and d% reserved power curve.
Figure 2. MPPT curve and d% reserved power curve.
Electronics 12 03029 g002
Figure 3. Diagram of the additional power control with frequency support.
Figure 3. Diagram of the additional power control with frequency support.
Electronics 12 03029 g003
Figure 4. Virtual inertia control of MMC.
Figure 4. Virtual inertia control of MMC.
Electronics 12 03029 g004
Figure 5. Flow chart of the frequency control of OWF-MTDC system.
Figure 5. Flow chart of the frequency control of OWF-MTDC system.
Electronics 12 03029 g005
Figure 6. Topology of the four-terminal OWF-MTDC system.
Figure 6. Topology of the four-terminal OWF-MTDC system.
Electronics 12 03029 g006
Figure 7. Structure and average value model of MMC: (a) structure of MMC; (b) average value model of MMC.
Figure 7. Structure and average value model of MMC: (a) structure of MMC; (b) average value model of MMC.
Electronics 12 03029 g007
Figure 8. Typical vector current control system of MMC.
Figure 8. Typical vector current control system of MMC.
Electronics 12 03029 g008
Figure 9. Comparison between Zsys and simulation results.
Figure 9. Comparison between Zsys and simulation results.
Electronics 12 03029 g009
Figure 10. System eigenvalue trajectory when KDC changes.
Figure 10. System eigenvalue trajectory when KDC changes.
Electronics 12 03029 g010
Figure 11. Simulation results of the impact of KDC on MTDC system stability.
Figure 11. Simulation results of the impact of KDC on MTDC system stability.
Electronics 12 03029 g011
Figure 12. Simulation results of OWF-MTDC system under a 5% sudden load step: (a) frequency variation of AC system, (b) DC voltage variation of MTDC system, (c) output power of OWF1, and (d) output power of OWF2.
Figure 12. Simulation results of OWF-MTDC system under a 5% sudden load step: (a) frequency variation of AC system, (b) DC voltage variation of MTDC system, (c) output power of OWF1, and (d) output power of OWF2.
Electronics 12 03029 g012
Figure 13. Simulation results of OWF-MTDC system with different frequency–voltage droop coefficients: (a) DC voltage variation of MTDC system and (b) frequency variation of AC system.
Figure 13. Simulation results of OWF-MTDC system with different frequency–voltage droop coefficients: (a) DC voltage variation of MTDC system and (b) frequency variation of AC system.
Electronics 12 03029 g013
Figure 14. Simulation results with different power droop coefficients: (a) frequency variation of AC system; (b) DC voltage variation of MTDC system; (c) output power of OWF1; (d) output power of OWF2.
Figure 14. Simulation results with different power droop coefficients: (a) frequency variation of AC system; (b) DC voltage variation of MTDC system; (c) output power of OWF1; (d) output power of OWF2.
Electronics 12 03029 g014
Figure 15. Simulation results with different wind speeds: (a) Frequency variation of AC system; (b) additional output power of OWF.
Figure 15. Simulation results with different wind speeds: (a) Frequency variation of AC system; (b) additional output power of OWF.
Electronics 12 03029 g015
Table 1. Electrical parameters of MMC-MTDC system.
Table 1. Electrical parameters of MMC-MTDC system.
ParameterValue
Transformer load loss0.006 pu
Transformer leakage reactance0.18 pu
Number of submodules N200
Submodule capacitance Csub15 mF
Line equivalent resistance R120.25 Ω
Line equivalent inductance L122.5 mH
Line equivalent resistance R230.5 Ω
Line equivalent inductance L235 mH
Line equivalent resistance R340.4 Ω
Line equivalent inductance L344 mH
Current limiting inductor Llim0.2 H
Arm resistance Rarm0.15 Ω
Arm inductance Larm30 mH
Table 2. Control parameters of MMC-MTDC system.
Table 2. Control parameters of MMC-MTDC system.
ParameterValue
Frequency droop coefficient KDC0.18 pu
PI transfer function of power outer loop Kp(s)200
PI transfer function of current inner loop Kc(s)15 mF
PI transfer function of voltage outer loop Kv(s)0.25 Ω
Rated DC voltage vdc02.5 mH
Table 3. Main parameters of WTGS.
Table 3. Main parameters of WTGS.
ParameterValue
Rated power SWT2 MW
Number of WTGSs in a single OWF50
Rated frequency fN50 Hz
Terminal voltage0.69 kV
Rated rotor speed ω1.2 pu
Power reserve coefficient d%10%
Wind speed of OWF18 m/s
Wind speed of OWF213 m/s
Virtual inertia of OWF1 H15 s
Virtual inertia of OWF2 H27 s
Power droop coefficient of OWF1 KP17
Power droop coefficient of OWF2 KP215
Table 4. Main parameters of AC system.
Table 4. Main parameters of AC system.
ParameterValue
Rated power of G1 SG172 MW
Rated power of G2 SG2163 MW
Rated power of G3 SG385 MW
Inertia time constant of G1 HG18 s
Inertia time constant of G2 HG26.4 s
Inertia time constant of G3 HG33.01 s
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Han, H.; Li, Q.; Li, Q. Frequency Support Control of Multi-Terminal Direct Current System Integrated Offshore Wind Farms Considering Direct Current Side Stability. Electronics 2023, 12, 3029. https://doi.org/10.3390/electronics12143029

AMA Style

Han H, Li Q, Li Q. Frequency Support Control of Multi-Terminal Direct Current System Integrated Offshore Wind Farms Considering Direct Current Side Stability. Electronics. 2023; 12(14):3029. https://doi.org/10.3390/electronics12143029

Chicago/Turabian Style

Han, Huachun, Qun Li, and Qiang Li. 2023. "Frequency Support Control of Multi-Terminal Direct Current System Integrated Offshore Wind Farms Considering Direct Current Side Stability" Electronics 12, no. 14: 3029. https://doi.org/10.3390/electronics12143029

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop