Next Article in Journal
Low-Frequency Oscillations and Force Control Capabilities as a Function of Force Level in Older Women
Previous Article in Journal
The Analysis of the Aftershock Sequences of the Recent Mainshocks in Alaska
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Modular Combined DC-DC Autotransformer for Offshore Wind Power Integration with DC Collection

Department of Electrical Engineering, Zhejiang University, Hangzhou 310058, China
*
Author to whom correspondence should be addressed.
Appl. Sci. 2022, 12(4), 1810; https://doi.org/10.3390/app12041810
Submission received: 22 November 2021 / Revised: 29 January 2022 / Accepted: 8 February 2022 / Published: 10 February 2022
(This article belongs to the Topic Innovative Techniques for Smart Grids)

Abstract

:
Offshore wind farms (OWFs) integration are attractive extensively for furnishing more robust power than land wind farms. This paper introduces a modular combined DC-DC autotransformer (MCAT), which contributes to the offshore wind power integration of DC grids with different voltage levels. Traditional DC transformers contains medium- or high-frequency converter transformers, which have the disadvantages of high manufacturing difficulty and cost. These shortcomings seriously affect the progress of commercial application of DC transformers. To solve these problems, in the proposed MCAT, converter transformers are replaced with a DC-isolation capacitor and a compensation inductor in series to reduce the footprint of offshore platforms and improve economy. Theoretical analysis is carried out for the MCAT operation principle. Selection methods of main circuit parameters for the MCAT are discussed in detail. Then, corresponding control strategies of the MCAT are proposed. Finally, the effectiveness of the proposed MCAT and its control strategies are validated by time domain simulations in PSCAD/EMTDC. The time-domain simulation results show the correctness of the main circuit parameters and the rationality of the MCAT control strategies.

1. Introduction

Offshore wind energy has drawn wide interest due to its distinctive advantages, such as rich wind resources, high utilization hours, and no need to occupy land resources [1]. Recently, China has proposed to build new power systems dominated by renewable energy, which facilitates the rapid development of offshore wind farms (OWFs).
The high voltage direct current (HVDC) transmission system is preferred to the traditional AC transmission system for the grid integration of large-scale OWFs. In the conventional HVDC transmission system for OWFs, wind turbines (WTs) are integrated together with an AC collection grid and then connected to an offshore substation containing a step-up transformer and a rectifier [2]. However, OWFs based on AC collection grids need lots of AC cables, bulky step-up transformers, and large expensive offshore platforms. To address this problem, OWFs based on DC collection grids are researched broadly [3,4]. In DC-collection-grids OWFs, WTs are interconnected with DC cables and connected to DC-DC converters, and the low DC voltage is raised to the HVDC transmission voltage. Compared with AC-collection-grids OWFs, DC-collection-grids OWFs could reduce the footprint requirement and get the higher power transmission efficiency [5,6].
According to interconnection schemes of WTs, DC-collection-grids OWFs are classified into DC parallel-connection and DC series-connection schemes [7], as shown in Figure 1. In the series-connection scheme, WTs at two ends have to withstand a high DC voltage. In addition, lots of WTs will be bypassed when unexpected faults happen. If the DC voltage of the OWF falls below the threshold limit, the entire OWF will be shut down undesirably [8]. These defects definitely limit the application of DC series-connection scheme. Therefore, the DC parallel-connection scheme is adopted in this paper.
The DC parallel-connection scheme is as shown in Figure 1b. An internal DC-DC converter inside the WT boosts the low DC output voltage of AC-DC converters to the medium voltage (MV) [9]. Several WTs are connected in parallel forming an MVDC grid. Then the MV is stepped up to the high voltage (HV) by a central offshore DC-DC converter. In other words, the DC output voltage of a WT needs two-stage step-up. This two-stage step-up method allows the ratio of DC-DC converters not too large to design, and also enhances the fault-ride-through ability of the wind farm [10]. Conclusively, the DC parallel-connection scheme with the DC voltage two-stage step-up is more suitable for the OWF integration currently.
According to the classification criteria of galvanic isolation, DC-DC converters for HVDC are divided into isolated topologies and non-isolated topologies. With the help of the AC transformers, isolated topologies could achieve the requirement of the high stepping ratio and galvanic isolation, but they show characteristics of high cost and large operation losses. Non-isolated topologies require less power semiconductor devices and no need for a transformer or the transformer which does not have to be rated for the full power of the DC-DC converter [11]. Compared with isolated topologies, non-isolated topologies have a smaller footprint and less operation losses and reduce the footprint of an offshore platform which is the major part of the total cost in an OWF [12]. So non-isolated DC-DC converters are preferred to isolated DC-DC converters for OWFs based on HVDC transmission.
The primary classification of non-isolated topologies is made based on the presence of transformers, and they are divided into DC autotransformer converters and transformerless converters. [13] proposed a transformerless converter with resonant topologies. Its principle is to use the resonance as a step-up mechanism while achieving the soft switching of semiconductors at the same time. The main disadvantage of these topologies is that it is difficult to balance the sharing of currents or voltages in semiconductor devices and achieve large power transmission. Obviously, resonant topologies are not suitable for scenario where large power transmission is required, such as OWFs. A step-up unidirectional DC-DC autotransformer is briefly introduced in [14], but the footprint of this topology is still very large due to the application of converter transformers. An input-independent-output-series structure is proposed in [15] with inter-module power balancing units. A non-isolated modular DC-DC auto-transformer (MDCAT) is proposed in [16], the developed two-port submodules are connected in the input-series-output-series structure. However, the topology and control strategies of this MDCAT are complex.
Converter transformers cause extra power loss and increased cost. Aiming at improving operation efficiency and reducing the cost, this paper proposes a modular-combined DC-DC autotransformer (MCAT). In the MCAT, converter transformers are replaced by a DC-isolated capacitor and a compensation inductor in series, which are much smaller in size and cost than transformers, and do not incur additional power losses in series resonance.
The reminder of this paper is organized as follows. Section 2 describes the circuit configuration of the proposed MCAT. The selection methods of main circuit parameters for the MCAT are introduced in Section 3. Section 4 analyzes the corresponding control strategy under steady-state operation and the AC side short circuit fault recovery strategy. In addition, the recovery strategy of the internal three-phase short-circuit fault is proposed. To validate the feasibility and effectiveness of the proposed MCAT and control strategies, the simulation studies in PSCAD/EMTDC are presented in Section 5. Finally, Section 6 concludes this paper.

2. MCAT Topology and Its Operation Principles

2.1. Topological Structure

As depicted in Figure 2, two DC grids with different DC voltage levels are connected by the proposed MCAT. MMCs highlighted by blue and red colors are defined as a low voltage module (LVM) and a high voltage module (HVM), respectively. The LVM is composed of M identical MMCs including MMCL,1 to MMCL,M. Likewise, the HVM is composed of 2N identical MMCs including MMCH,1 to MMCH,2N. It is obvious that M and N are driven by voltage levels of DC grids on two sides of the MCAT.
The function of converter transformers is mainly focused on three aspects [17]:
(1)
Coordinating the AC system voltage and the AC output voltage of MMC.
(2)
Galvanic separation between the AC system and the MMC to eliminate the DC offset voltage.
(3)
Acting as the inductor to smooth the current and suppress the fault current.
According to the operation principle of the MCAT, the item (2) is an indispensable function. This paper uses a capacitor (namely DC-isolation capacitor) to withstand the DC offset voltage, so that the converter transformer is eliminated. Since the introduced DC-isolation capacitor would produce reactive power, an inductor (namely compensation inductor) is installed to compensate the reactive power and improve the MCAT operation efficiency. In order to reduce the footprint of DC-isolation capacitors and compensation inductors, the medium frequency (100 Hz~400 Hz) is applied at the MCAT AC side. AC circuit breakers are also equipped for isolating the AC fault.

2.2. Operation Principles of the MCAT

Neglecting transmission losses, the rated DC power PN transmitted from the high-voltage DC grid to the low-voltage one is described as:
P N = E high I dchigh = E low I dclow
where Ehigh and Elow are DC voltages of high-voltage and low-voltage DC grids, respectively (Ehigh > Elow); Idchigh and Idclow are DC currents of high-voltage and low-voltage DC grids, respectively. The positive direction of currents and voltages are shown in Figure 2, and the DC voltage ratio kdc (kdc > 1) is defined as:
k dc = E high E low
The transmission power of each MMC in HVM and LVM is described as:
{ P MMCH , n = ( E high E low ) I dchigh 2 N = P N 2 N ( 1 1 k dc ) P MMCL , m = E low ( I dclow - I dchigh ) M = P N M ( 1 1 k dc )
where PMMCH,n and PMMCL,m are the transmission power of the nth MMC in HVM and the mth MMC in LVM, respectively (n = 1, 2, …, 2N, m = 1, 2, …, M).
PN is transmitted through two different paths. One path is HVM-AC bus-LVM, this part of PN is delivered through the DC-AC-DC conversion and named Pdc-ac-dc. The other part of PN flows from the high-voltage DC grid to the low-voltage DC grid directly and is named Pdir. Pdc-ac-dc and Pdir are calculated as (4) and (5):
P dc - ac - dc = m = 1 M P MMCL , m = n = 1 2 N P MMCH , n = P N ( 1 1 k dc )
P dir = E low I dchigh = E low P N E high = P N k dc
PMCAT is the total capacity of the MCAT and is calculated as (6):
P MCAT = m = 1 M P MMCL , m + n = 1 2 N P M M C H , n = 2 P N ( 1 1 k dc )
Comparing (6) with (5), PMCAT depends only on Pdc-ac-dc.

3. MCAT Main Circuit Parameters Selection

MCAT main circuit parameters consist of MMC main circuit parameters, DC-isolation capacitors, and compensation inductors. As the selection methods of MMC main circuit parameters (e.g., sub-module capacitors, arm inductors, etc.,) have been discussed particularly in [18], this section only focuses on DC-isolation capacitors and compensation inductors. For the sake of clarity of this section, Table A1 with explanations of the abbreviations and symbols used in this section are provided in Appendix A.
The voltage ucj of Cj (j = 1, 2, …, M + 2N) is always composed of the DC offset voltage Uvdcj and the AC voltage Δucj, which is expressed as:
u c j = U vdc j + Δ u c j
Uvdcj is supposed to be eliminated by the DC-isolation capacitor. The degree of Δucj fluctuations could affect the stability of the AC side. In this regard, the value of capacitors should be taken as large as possible to reduce the Δucj fluctuations. On the other hand, DC-isolation capacitors need to be charged by the connected MMCs in the start or fault recovery process of MCAT and excessive value would slow down the charging rate. Therefore, DC-isolation capacitors need to be selected by considering the above two factors.
Ignoring the power losses in steady-state operation, the active power PMMCj and the reactive power QMMCj transmitted by the MMCj could be described as:
{ P MMC j = 3 U vac j I j cos δ j Q MMC j = 3 U vac j I j sin δ j
where Uvacj is the fundamental RMS (root mean square) L-L (line-line) voltage at MMCj valve side, Ij is the fundamental RMS line current at MMCj valve side, and δj is the phase angle between Uvacj and Ij. In the steady-state condition, Uvac, I, and δ of each MMC are similar. Furthermore, if MMCj adopts reactive power control with the reference value 0 pu, QMMCj will be controlled to 0, Uvacj and Ij will be in the same phase (δj = 0). Considering δj = 0 and ignoring high-order harmonics, ΔUcj is described as:
Δ U c j = I j ω C j = P MMC j 3 U vac j 1 2 π f C j
where ΔUcj is the fundamental RMS voltage of Δucj, f is the fundamental frequency at the MCAT AC side. The voltage fluctuation rate αj of Cj is defined as:
α j = 2 Δ U c j U vdc j × 100 %
where, αj is the fluctuation ratio of ucj, and it should be limited within 25% according to engineering experience in [19].
In (9) and (10), Uvac of each MMC and f in the MCAT are similar under the steady-state operation, but Uvdc and PMMC of the LVM are different from those of the HVM. As a result, parameters of DC-isolation capacitors C and compensation inductors L in HVM and LVM are supposed to be calculated respectively.

3.1. Parameter Calculation of DC-Isolation Capacitors and Compensation Inductors in HVM

In the HVM, ΔUc of each DC-isolation capacitor is almost identical because every DC-isolation capacitor has the same value, and the Uvdc of MMCH,N (and MMCH,N+1) is lowest in the HVM. According to (10), αH,N (or αH,N+1) is largest in the HVM and supposed to be calculated particularly. UvacH,N, UvdcH,N, and PMMCH,N are described as [11]:
u vH , N = u vacH , N + U vdcH , N
U vacH , N = 1.05 U dcH , N 2
U vdcH , N = ( E low + U dcH , N ) 2
P MMCH , N = P N ( 1 1 / k dc ) 2 N
where uvH,N is the voltage at MMCH,N valve side, uvacH,N and UvdcH,N are the AC component and DC component of uvH,N. UvacH,N are the fundamental RMS L-L voltage at MMCH,N valve side, UdcH,N is the DC voltage of MMCH,N. Substituting these variables into Equation (10), CH,N is expressed as follows:
C H , N = 2 ( 1 1 / k dc ) P N / 2 N 3 × 1.05 2 U dcH , N 2 π f C H , N 1 ( U dcH , N + E low ) 2 = 0.248 ( 1 1 / k dc ) P N N f α H , N U dcH , N ( U dcH , N + E low )
where αH,N denotes the rate of fluctuation of uCH,N. αH,N is an artificial technical index. After specifying αH,N, the corresponding value of CH,N could be calculated by (15). The DC-isolation capacitor and the compensation inductor are supposed to occur in series resonance at f so that they produce no reactive power. For this purpose, the calculation expression of LH,N is:
L H , N = 1 ( 2 π f ) 2 C H , N
After obtaining the values of CH,N and LH,N, the value of other DC-isolation capacitors in the HVM could be taken as the CH,N, so that their α are smaller than αH,N and αH,(N+1), as mentioned above. The values of other DC-isolation capacitors and compensation inductors in the HVM are described as:
{ C H , 1 = = C H , N = = C H , 2 N L H , 1 = = L H , N = = L H , 2 N

3.2. Parameter Calculation of DC-Isolation Capacitors and Compensation Inductors in LVM

In the LVM, the calculation of DC-isolation capacitors and compensation inductors depend on M, which is discussed as follows:
(1)
When M = 1, the DC-isolation capacitors and compensation inductors are excluded from the LVM.
(2)
When M = 2, 4, 6, …, MMCL,M/2 (and MMCL,(M/2) +1) has the lowest DC offset voltage in the LVM, and αL,M/2 (and αL,(M/2)+1) is largest correspondingly.
(3)
When M = 3, 5, 7, …, MMCL,(M−1)/2 (and MMCL,(M+3)/2) has the lowest DC offset voltage, and αL, (M−1)/2 (and αL, (M+3)/2) is largest correspondingly.
Take case (2) as an example to calculate DC-isolation capacitors and compensation inductors. UvacL,M/2, UvdcL,M/2, and PMMCL,M/2 are expressed as [17]:
u vL , M / 2 = u vacL , M / 2 + U vdcL , M / 2
U vacL , M / 2 = 1.05 U dcL , M / 2 2
U vdcL , M / 2 = U dcL , M / 2 2
P MMCL , M / 2 = ( 1 1 / k dc ) P N M
where uvL,M/2 is the voltage at MMC L,M/2 valve side, uvacL,M/2 and UvdcL,M/2 are the AC component and DC component of uvL,M/2. UvacL,M/2 are the fundamental RMS L-L voltage at MMCL,M/2 valve side, UdcL,M/2 is the DC voltage of MMCL,M/2. PMMCL,M/2 is the power transmitted by MMCL,M/2. Substituting these variables into (10), CL,M/2 is described as:
C L , M / 2     = 2 ( 1 1 / k dc ) P N / M 3 × 1.05 2 U dcL , M / 2 2 π f C L , M / 2 1 U dcL , M / 2 2 = 0.496 ( 1 1 / k dc ) P N M f α L , M / 2 U dcL , M / 2 2
where αL,M/2 is the fluctuation ratio of uCL,M/2 of CL,M/2. After specifying αL,M/2, the corresponding value of CL,M/2 could be calculated by (22). The DC-isolation capacitor and the compensation inductor occur in series resonation at resonance frequency f so that they produce no reactive power. Therefore, the calculation expression of LL,M/2 is:
L L , M / 2 = 1 ( 2 π f ) 2 C L , M / 2
After obtaining the values of CL,M/2 and LL,M/2, the value of other DC-isolation capacitors in the LVM could be taken as the CL,M/2, so that their α are smaller than αL,M/2 and αL,(M/2)+1, as mentioned above. The values of other DC-isolation capacitors and compensation inductors in the LVM are described as:
{ C L , 1 = C L , 2 = = C L , M / 2 = = C L , M L L , 1 = L L , 2 = = L L , M / 2 = = L L , M

4. Control Strategy of the MCAT

4.1. Dynamic Characteristics of the AC Side in the MCAT

When neglecting the fluctuation of the voltage of the MMC sub-module capacitor, the internal AC fundamental equivalent circuit of the MCAT in the steady-state is shown in Figure 3 [19,20,21]. Here, udiffdj and udiffqj are the dq axis components of the differential mode voltage udiffj output by MMCj on the valve side [18], idj and iqj are the dq axis components of the current Ij at MMCj valve side, and ubusd and ubusq are the dq axis components of Bcom voltage ubus. L0 and R0 are the MMCj arm inductor and resistor respectively [22,23,24,25].
Cj and Lj are series resonance in the fundamental circuit, and the circuit equation can be listed from Figure 3:
{ u diffd j = ( R + L d d t ) i d j ω 0 L i q j + u busd u diffq j = ( R + L d d t ) i q j + ω 0 L i d j + u busq
where L′ = L0/2, R′ = R0/2. Kirchhoff’s current law (KCL) for Bcom is written as:
{ j = 1 M + 2 N i d j = 0 j = 1 M + 2 N i q j = 0
where idj and iqj are obtained by Equation (25). Considering that L’ is much larger than R’ and substituting idj and iqj into Equation (26), the following equation is obtained as:
{ u busd = j = 1 M + 2 N u diffd j / ( M + 2 N ) u busq = j = 1 M + 2 N u diffq j / ( M + 2 N )
Equation (27) shows that the AC bus voltages ubusd and ubusq can be regulated by MMC.

4.2. MCAT Control Strategy in Normal Operation

One typical scenario is that the high-voltage side of the MCAT is connected to the DC main grid which could be equivalent to a constant DC voltage source. The voltage of the low-voltage DC grid is required to be kept stable under control of the connected MCAT. In MCAT, the control of each MMC is independent and has the same inner loop control, while outer loop control strategy is different. The inner loop control has been introduced in [18], and this section focuses on the outer loop control. Different parts of MCAT adopt different outer loop control strategies. For this, the outer loop control strategy of the MCAT is discussed as follows.
The entire LVM is aimed to keep Elow stability because of connecting with the low-voltage DC grid directly, so they adopt DC voltage control as shown in Figure 4a. Udc and QS are the DC voltage and reactive power at MMC (LVM and MMCH,N+1 to MMCH,2N) valve side, U dc * and Q s * are the command references of Udc and QS. idmax and iqmax are used to limit i d * and i q * .
udiffd and udiffq of MMCs are varied in response to the variation of the transmission power of the MCAT [16], which causes the AC bus voltage ubus fluctuations. Therefore, certain MMCs are supposed to not only control ubus but also serve as a power balance node [26,27]. MMCH,1 to MMCH,N (or MMCH,N+1 to MMCH,2N) in the HVM serve as the balance node and adopt passive control as shown in Figure 4b [28,29,30]. u busd * and u busq * are the command references of ubusd and ubusq. Uvacd and uvacq are the dq axis components of Uvac.
Since Ehigh and Elow are controlled by the DC main grid and the LVM, respectively, MMCH,N+1 to MMCH,2N should adopt DC voltage control to keep voltages of passive-control MMCs stable.
The AC side control strategies of the LVM and MMCH,N+1 to MMCH,2N are aimed at reducing power losses, so they adopt reactive power control with reference value 0 pu as shown in Figure 4a.
According to the above analysis, the AC and DC side control strategy in the MCAT normal operation is as shown in Table 1.

4.3. MCAT AC-Side Short-Circuit Fault Recovery Strategy

When an AC side short-circuit fault occurs at the internal AC bus of the MCAT, the voltage of the AC bus drops rapidly, causing the decrease of the power transmitted by AC bus and generating a large fault current. For this, MCAT are quickly blocked and AC circuit breakers are opened. After the transient fault is cleared, it is necessary to close the circuit breakers and unblock the MCAT to recover the power transmission. In order to maintain the voltages of DC-isolation capacitors stable, MMCs adopting passive control in the MCAT should be switched to DC voltage control with reference value U dc * and reactive power control with reference value 0 pu when recovering, that is:
U dc * = ( E high E low ) M
After the DC voltages of these MMCs are stabilized, they are switched to passive control again, and the system resumes steady-state operation.

5. Simulation Study

5.1. Test System

As shown in Figure 5, a 100 MW OWF with the MCAT is established in PSCAD/EMTDC. There are four clusters in this model, and each cluster is represented by a 25 MW aggregated permanent magnets synchronous generators based on WTs (PMSG-WTs). The output DC voltage of the aggregated WT is 2.96 kV, and then requires two step-up DC-DC stages to reach the high voltage for DC transmission. The DC-DC converter in the WT boosts the DC voltage from 2.96 kV to 100 kV first, and then the MCAT steps up the DC voltage from 100 kV to 300 kV. The internal DC-DC converters employ dual active bridge (DAB) topology. The parameters of equivalent PMSG and the DAB converters are listed in Table 2.
For the sake of simplicity, MCAT employs only three MMCs. When αH,1 is specified as 20%, substitute f = 100 Hz, kdc = 3, P = 100 MW, UdcH,1 = 100 kV and N = 1 into Equations (9) and (10), then CH,1 is calculated as 41.3 μF and LH,1 is 84.3 mH. CL,1 and LL,1 are excluded from the MCAT because of the symmetrical monopole construction. CH,2 and LH,2 are equal to 41.3 μF and 84.3 mH. The voltage rating across the MCAT is are ±150 kV/±50 kV. Parameters of the MCAT, onshore converter, and HVDC cable are as shown in Table 3 and Table 4. The control strategy of the MCAT is listed in Table 5.

5.2. Simulation of Wind Speed Variation

To validate the performance of the MCAT during wind speed variation, the transient-state process is designed as follows: at t = 1.0 s, wind speed reduces from 12 m/s to 8 m/s, and then maintains 8 m/s for 2.5 s, finally, rises to 10 m/s. Figure 5 shows the dynamic process of the test system.
Figure 6a illustrates that the transmission power of each MMC varies according to the wind speed quickly and stably. Figure 6b,c shows that the AC output current of each MMC and DC currents on both sides of the MCAT responds to the change of wind speed fast. Figure 6d,e shows the DC voltage of each MMC and DC voltages on both sides of MCAT, which are well balanced and stable. Figure 6f shows that the fluctuation of uCH,1 and uCH,2 is within 1.2 pu, proving the calculation of DC-isolation capacitors and compensation inductors are correct in Section 3. Figure 6g demonstrates that the AC bus voltage are balanced well. Conclusively, the simulation results validate the feasibility of the proposed MCAT and the effectiveness of the control strategy.

5.3. Simulation of the Recovery Strategy

At t = 0 s, the test system is in steady-state. The sequences of the fault, applied control, and the protection measures are as follows:
(1)
At t = 0.2 s, the three-phase short circuit fault occurs at the AC bus, and the fault time lasts for 0.1 s. At t = 0.202 s, the MCAT, DAB converters inside WTs and onshore converters are blocked. An AC chopper facilitates the WT to consume the surplus energy and limits the DC overvoltage. At t = 0.206 s, the fault current reduces to 0 due to the blocked MCAT.
(2)
At t = 0.3 s, the MCAT is unblocked, while the control strategy of MMCH,1 is switched from passive control to DC voltage control (reference value is 100 kV) and reactive power control (reference value is 0 MVar). At the same time, DAB converters inside WTs and onshore converters are unblocked. At t = 0.6 s, MMCH,1 is switched to passive control again. Figure 6 shows the simulation diagram of fault response characteristics of the test system.
Figure 7a–e shows currents and voltages in the test system. When the three-phase short-circuit fault occurs at the AC bus, the maximum value of fault current reaches 0.75 kA at about 0.201 s, then the fault current is cut off rapidly. At t = 0.206 s, blocking the MCAT make the DC current drop to 0, but UL,1 would reach 1.2 pu because of the imbalance of power transmission. Since the AC bus is not grounded, its voltage is not dropped to 0. At t = 0.40 s, Idclow reaches 2 pu due to violent fluctuation of transmitted power. Therefore, the threshold value of overcurrent protection should be adjusted to prevent the MCAT from blocking again. At t = 0.8 s, the currents and voltages in the test system are in steady-state again.
Figure 7f,g shows the simulation results of uCH,1, uCH,2, and power changes of each MMC. At t = 0.3 s, CH,1 and CH,2 have temporary overvoltage, and uCH,1 reaches twice as the rated voltage. The transient process of capacitors voltages lasts for 0.4 s. At t = 0.8 s, the MCAT transmits rated power again.
Figure 7h shows the AC voltage of the AC bus could reach stable operation rapidly.

6. Conclusions

This paper presents the MCAT without the transformers. In the MCAT, the expensive converter transformers are substituted with the DC-isolation capacitor and compensation inductor in series to reduce the footprint of the offshore platforms. The selection methods of main circuit parameters for the MCAT are discussed in detail. Then, the control strategies of the MCAT are investigated under the steady-state operation and the AC fault recovery occurring at the AC bus. A detailed complicated OWF simulation model is constructed and the feasibility and effectiveness of the proposed MCAT and corresponding control strategies are validated. The conclusions are as follows:
  • The proposed MCAT utilizes the DC-isolation capacitor to isolate the DC offset voltage of the converter transformers. The application of the compensation inductors facilitates improving the operation efficiency of the MCAT. The time-domain simulation results show that the calculation method of the main circuit parameters is correct, and the calculated values are highly consistent with the simulated values.
  • Ignoring the dynamic characteristics of MMC submodules, the output characteristics of the MCAT and the AC bus voltage could be regulated by MMCs adopting DC voltage control, reactive power control, and passive control strategies, respectively. The time-domain simulation proves that the voltage across the MCAT can remain stable under the condition of wind speed changes, and the output power can quickly respond to the wind speed changes. This indicates that the MCAT has favorable voltage control performance.
  • The fault recovery strategy proposed in this paper can help the MACT to quickly enter steady state. The test system is built in PSCAD/EMTDC, and the time-domain simulation shows that the MCAT could resume operation in a short time after the AC fault, which is conducive to maintaining the stable operation of the OWF.

Author Contributions

Conceptualization, Z.Z. and Z.X.; methodology, Z.X.; software, Z.Z.; validation, Y.S.; formal analysis, Y.S.; investigation, Y.S.; resources, Z.X.; data curation, Z.X.; writing—original draft preparation, Y.S.; writing—review and editing, Z.Z.; visualization, Z.Z.; supervision, Z.Z. and Z.X.; project administration, Z.X.; funding acquisition, Z.Z. and Z.X. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Data available on request due to privacy.

Conflicts of Interest

The authors declare no conflict of interest.

Appendix A

Table A1. Explanations of the abbreviations and symbols used in this section.
Table A1. Explanations of the abbreviations and symbols used in this section.
SymbolsExplanations of SymbolsSymbolsExplanations of Symbols
ucjthe voltage of CjuvacL,M/2AC component of uvL,M/2
UvdcjDC component of ucjUvdcH,NDC component of uvH,N
ΔucjAC component of ucjUvdcL,M/2DC component of uvL,M/2
Uvacjfundamental RMS L-L voltage at MMCj valve sideUvacH,NFundamental component of uvacH,N
Ijfundamental RMS line current at MMCj valve sideUvacL,M/2Fundamental component of uvacL,M/2
δjthe phase angle between Uvacj and IjUdcH,NDC voltage of MMCH,N
ΔUcjfundamental RMS voltage of ΔucjUdcL,M/2DC voltage of MMCL,M/2
ffundamental frequency at the MCAT AC sideuvH,Nthe voltage at MMCH,N valve side
αjfluctuation ratio of ucjuvL,M/2the voltage at MMC L,M/2 valve side
αH,Nfluctuation ratio of uCH,NuvacH,NAC component of uvH,N
αL,M/2fluctuation ratio of uCL,M/2

References

  1. Wang, Q.; Yu, Z.; Ye, R.; Lin, Z.; Tang, Y. An ordered curtailment strategy for offshore wind power under extreme weather conditions considering the resilience of the grid. IEEE Access 2019, 7, 54824–54833. [Google Scholar] [CrossRef]
  2. Bresesti, P.; Kling, W.L.; Hendriks, R.L.; Vailati, R. HVDC connection of offshore wind farms to the transmission system. IEEE Trans. Energy Convers. 2007, 22, 37–43. [Google Scholar] [CrossRef]
  3. Elliott, D.; Bell, K.R.W.; Finney, S.J.; Adapa, R.; Brozio, C.; Yu, J.; Hussain, K. A comparison of AC and HVDC options for the connection of offshore wind generation in Great Britain. IEEE Trans. Power 2016, 31, 798–809. [Google Scholar] [CrossRef] [Green Version]
  4. Engel, S.P.; Stieneker, M.; Soltau, N.; Rabiee, S.; Stagge, H.; de Doncker, R.W. Comparison of the modular multilevel DC converter and the dual-active bridge converter for power conversion in HVDC and MVDC grids. IEEE Trans. Power Electron. 2015, 30, 124–137. [Google Scholar] [CrossRef]
  5. Lumbreras, S.; Ramos, A. Offshore wind farm electrical design: A review. Wind Energy 2013, 16, 459–473. [Google Scholar] [CrossRef]
  6. Taherbaneh, M.; Jovcic, D.; Taisne, J.P.; Nguefeu, S. DC fault performance and cost analysis of dc grids for connecting multiple offshore wind farms. In Proceedings of the 2013 IEEE Grenoble PowerTech (POWERTECH), Grenoble, France, 16–20 June 2013. [Google Scholar]
  7. Deng, F.; Chen, Z. Operation and control of a DC-grid offshore wind farm under DC transmission system faults. IEEE Trans. Power Deliv. 2013, 28, 1356–1363. [Google Scholar] [CrossRef]
  8. Robinson, J.; Jovcic, D.; Joos, G. Analysis and design of an offshore wind farm using a MV DC grid. IEEE Trans. Power Del. 2010, 25, 2164–2173. [Google Scholar] [CrossRef]
  9. Lian, Y.; Adam, G.; Holliday, D.; Finney, S. Medium-voltage DC/DC converter for offshore wind collection grid. IET Renew. Power Gener. 2016, 5, 651–660. [Google Scholar] [CrossRef]
  10. Hu, P.; Yin, R.; Wei, B.; Luo, Y.; Blaabjerg, F. Modular Isolated LLC DC/DC Conversion System for Offshore Wind Farm Collection and Integration. IEEE J. Emerg. Sel. Top. Power Electron. 2021, 9, 6713–6725. [Google Scholar] [CrossRef]
  11. Hu, P.; Yin, R.; He, Z.; Wang, C. A Modular Multiple DC Transformer Based DC Transmission System for PMSG Based Offshore Wind Farm Integration. IEEE Access 2020, 8, 15736–15746. [Google Scholar] [CrossRef]
  12. Páez, J.D.; Frey, D.; Maneiro, J.; Bacha, S.; Dworakowski, P. Overview of DC-DC Converters Dedicated to HVDC Grids. IEEE Trans. Power Deliv. 2019, 34, 119–128. [Google Scholar]
  13. Parastar, A.; Kang, Y.C.; Seok, J.-K. Multilevel modular DC/DC power converter for high-voltage DC-connected offshore wind energy applications. IEEE Trans. Ind. Electron. 2015, 5, 2879–2890. [Google Scholar] [CrossRef]
  14. Lin, W. DC-DC autotransformer with bidirectional DC fault isolating capability. IEEE Trans. Power Electron. 2015, 31, 5400–5410. [Google Scholar] [CrossRef]
  15. Li, X.Y.; Zhu, M.; Su, M.; Ma, J.; Li, Y.R.; Cai, X. Input-independent and output-series connected modular DC–DC converter with intermodule power balancing units for MVdc Integration of distributed PV. IEEE Trans. Power Electron. 2020, 35, 1622–1636. [Google Scholar] [CrossRef]
  16. Chen, Y.; Wang, H.; Zhu, M.; Liu, M.; Cai, X. Modular DC-DC auto-transformer: Topology, operation, and system design. IET Power Electron. 2021, 14, 2289–2302. [Google Scholar] [CrossRef]
  17. Xu, Z.; Tu, Q.; Guan, M. Voltage Source Converter Based HVDC Power Transmission Systems, 2nd ed.; China Machine Press: Beijing, China, 2013. [Google Scholar]
  18. Xu, Z. Voltage Source Converter Based HVDC Power Transmission Systems, 2nd ed.; China Machine Press: Beijing, China, 2016. [Google Scholar]
  19. Xu, Z.; Xiao, H.; Zhang, Z. Selection methods of main circuit parameters for modular multilevel converters. IET Renew. Power Gener. 2016, 10, 788–797. [Google Scholar] [CrossRef]
  20. Sun, C.; Zhang, J.; Cai, X.; Shi, G. Voltage balancing control of isolated modular multilevel dc-dc converter for use in dc grids with zero voltage switching. IET Power Electron. 2016, 9, 270–280. [Google Scholar] [CrossRef]
  21. Tu, Q.; Xu, Z.; Xu, L. Reduced switching-frequency modulation and circulation current suppression for modular multilevel converters. IEEE Trans. Power Deliv. 2011, 26, 2009–2017. [Google Scholar]
  22. Xiang, W.; Lin, W.; Xu, L.; Wen, J. Enhanced Independent Pole Control of Hybrid MMC-HVDC System. IEEE Trans. Power Deliv. 2018, 33, 861–872. [Google Scholar] [CrossRef] [Green Version]
  23. Yao, W.; Jiang, L.; Wen, J.; Wu, Q.; Cheng, S. Wide-Area Damping Controller for Power System Interarea Oscillations: A Networked Predictive Control Approach. IEEE Trans. Control Syst. Technol. 2015, 23, 27–36. [Google Scholar] [CrossRef]
  24. Luth, T.; Merlin, M.M.C.; Green, T.C.; Hassan, F.; Barker, C.D. High-frequency operation of a DC/AC/DC system for HVDC applications. IEEE Trans. Power Electron. 2014, 29, 4107–4115. [Google Scholar] [CrossRef] [Green Version]
  25. Wu, Y.; Lu, Z.; He, Z. Study on the protection strategies of HVDC grid for overhead line application. CSEE 2016, 36, 3726–3734. [Google Scholar]
  26. Li, X.; Xu, Z.; Zhang, Z. Enhanced Ride-Through Capability Under Rectifier-Side AC Fault for Series LCC-MMC Hybrid HVDC System. IEEE Access 2021, 9, 153050–153057. [Google Scholar] [CrossRef]
  27. Suo, Z.; Li, G.; Xu, L.; Li, R.; Wang, W.; Chi, Y. Hybrid modular multilevel converter based multi-terminal DC/DC converter with minimized full-bridge submodules ratio considering DC fault isolation. IET Renew. Power Gener. 2016, 10, 1587–1596. [Google Scholar] [CrossRef] [Green Version]
  28. Ruddy, J.; Meere, R.; O’Donnell, T. A Comparison of VSC-HVDC with Low Frequency AC for Offshore Wind Farm Design and Interconnection. Energy Procedia 2015, 80, 185–192. [Google Scholar] [CrossRef] [Green Version]
  29. Yu, F.; Lin, W.; Wang, X.; Xie, D. Fast voltage-balancing control and fast numerical simulation model for the modular multilevel converter. IEEE Trans. Power Deliv. 2015, 30, 220–228. [Google Scholar] [CrossRef]
  30. Zhao, W. HVDC Engineering Technology, 2nd ed.; China Electric Power Press: Beijing, China, 2011. [Google Scholar]
Figure 1. DC collection grids of OWF: (a) DC series-connection OWF; (b) DC parallel-connection OWF.
Figure 1. DC collection grids of OWF: (a) DC series-connection OWF; (b) DC parallel-connection OWF.
Applsci 12 01810 g001
Figure 2. Schematic diagram of the MCAT topology.
Figure 2. Schematic diagram of the MCAT topology.
Applsci 12 01810 g002
Figure 3. Equivalent circuit of the inner AC circuit of the MCAT.
Figure 3. Equivalent circuit of the inner AC circuit of the MCAT.
Applsci 12 01810 g003
Figure 4. Schematic diagram of the MCAT outer loop control: (a) MMCH,N+1 to MMCH,2N and LVM; (b) MMCH,1 to MMCH,N
Figure 4. Schematic diagram of the MCAT outer loop control: (a) MMCH,N+1 to MMCH,2N and LVM; (b) MMCH,1 to MMCH,N
Applsci 12 01810 g004
Figure 5. Diagram of the simulation system.
Figure 5. Diagram of the simulation system.
Applsci 12 01810 g005
Figure 6. Simulation results of wind speed variation: (a) Active power transmitted by the MCAT; (b) A phase AC output current of MMCs; (c) DC currents of high-voltage and low-voltage DC grids respectively; (d) DC voltages of MMCs; (e) DC voltages of high-voltage and low-voltage DC grids respectively; (f) voltages of CH,1 and CH,2; (g) A phase AC voltage of the AC bus.
Figure 6. Simulation results of wind speed variation: (a) Active power transmitted by the MCAT; (b) A phase AC output current of MMCs; (c) DC currents of high-voltage and low-voltage DC grids respectively; (d) DC voltages of MMCs; (e) DC voltages of high-voltage and low-voltage DC grids respectively; (f) voltages of CH,1 and CH,2; (g) A phase AC voltage of the AC bus.
Applsci 12 01810 g006
Figure 7. Simulation results of fault and recovery process: (a) Three-phase short circuit currents; (b) A phase AC output current of MMCs; (c) DC currents of high-voltage and low-voltage DC grids respectively; (d) DC voltages of MMCs; (e) DC voltages of high-voltage and low-voltage DC grids respectively; (f) active power transmitted by MMCs; (g) voltages of CH,1 and CH,2; (h) A phase voltage of the AC bus.
Figure 7. Simulation results of fault and recovery process: (a) Three-phase short circuit currents; (b) A phase AC output current of MMCs; (c) DC currents of high-voltage and low-voltage DC grids respectively; (d) DC voltages of MMCs; (e) DC voltages of high-voltage and low-voltage DC grids respectively; (f) active power transmitted by MMCs; (g) voltages of CH,1 and CH,2; (h) A phase voltage of the AC bus.
Applsci 12 01810 g007
Table 1. MCAT control strategy in normal operation.
Table 1. MCAT control strategy in normal operation.
ModulesControl Mode
LVMd-axis: DC voltage control
q-axis: Reactive power control
MMCH,N+1 to MMCH,2N (HVM)d-axis: DC voltage control
q-axis: Reactive power control
MMCH,1 to MMCH,N (HVM)Passive control
Table 2. Parameters of the aggregated WT.
Table 2. Parameters of the aggregated WT.
ItemValueItemValue
Rated capacity/MVA25d-axis inductance/pu0.41
Rated voltage/kV2.96q-axis inductance/pu0.77
Frequency/Hz10Field flux/pu0.83
Inertia constant/s2.5DAB converter rated capacity/MVA28
Stator resistance/pu0.1DAB converter rated input voltage/kV2.96
DAB converter rated output voltage/kV100
Table 3. Parameter in the MCAT.
Table 3. Parameter in the MCAT.
ItemMMCL,1MMCH,1/MMCH,2
Rated MMC capacity/MVA7040
Rated voltage Udc/kV100100
AC side frequency/Hz100100
Rated submodule voltage/kV2.02.0
Number of submodules per arm5050
Submodule capacitance/μF666666
Arm inductor L0/H0.0760.076
CH,1, CH,2/μF 41.3
LH,1, LH,2/mH 84.3
Table 4. Parameters of the onshore converter and HVDC cable.
Table 4. Parameters of the onshore converter and HVDC cable.
Item ValueItemValue
Rated MMC capacity/MVA200Rated submodule voltage/kV2.0
Rated voltage/kV300Number of submodules per arm150
Transformer rated power/MVA240Submodule capacitance/μF666
Transformer radio220/157.5Arm inductor L0/H0.076
Transformer short-circuit inductance0.15Smoothing reactor/H0.05
HVDC cable resistance/Ω4.5HVDC cable inductance/mH20
Table 5. Control mode and reference value of the MCAT.
Table 5. Control mode and reference value of the MCAT.
ModulesControl ModeReference Value
MMCL,1d-axis: DC voltage control
q-axis: Reactive power control
100 kV;
0 Mvar
MMCH,2d-axis: DC voltage control
q-axis: Reactive power control
100 kV;
0 Mvar
MMCH,1Passive control
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Song, Y.; Zhang, Z.; Xu, Z. Modular Combined DC-DC Autotransformer for Offshore Wind Power Integration with DC Collection. Appl. Sci. 2022, 12, 1810. https://doi.org/10.3390/app12041810

AMA Style

Song Y, Zhang Z, Xu Z. Modular Combined DC-DC Autotransformer for Offshore Wind Power Integration with DC Collection. Applied Sciences. 2022; 12(4):1810. https://doi.org/10.3390/app12041810

Chicago/Turabian Style

Song, Yuanjian, Zheren Zhang, and Zheng Xu. 2022. "Modular Combined DC-DC Autotransformer for Offshore Wind Power Integration with DC Collection" Applied Sciences 12, no. 4: 1810. https://doi.org/10.3390/app12041810

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop