Review

Green Gas for Grid as an Eco-Friendly Alternative Insulation Gas to SF6: A Review

1
School of Port and Transportation Engineering, Zhejiang Ocean University, Zhoushan 316022, China
2
Hangzhou Guozhou Power Technology Co., Ltd., Hangzhou 310015, China
3
Forensic Safety Section, National Forensic Service Busan Institute, Yangsan 50612, Korea
4
Department of Electrical and Electronics Engineering, Korea Maritime and Ocean University, Busan 49112, Korea
*
Authors to whom correspondence should be addressed.
Appl. Sci. 2020, 10(7), 2526; https://doi.org/10.3390/app10072526
Submission received: 3 March 2020 / Revised: 2 April 2020 / Accepted: 3 April 2020 / Published: 7 April 2020
(This article belongs to the Special Issue Environmental Friendly Technologies in Power Engineering)

Abstract

:

Featured Application

Insulation design of gas-insulated electrical power facilities using eco-friendly green gas for a grid (g3) to replace SF6 that causes environmental concerns.

Abstract

This paper deals with a review of the state-of-the-art performance investigations of green gas for grid (g3) gas, which is an emerging eco-friendly alternative insulation gas for sulfur hexafluoride (SF6) that will be used in gas-insulated power facilities for reducing environmental concerns. The required physical and chemical properties of insulation gas for high-voltage applications are discussed, including dielectric strength, arc-quenching capability, heat dissipation, boiling point, vapor pressure, compatibility, and environmental and safety requirements. Current studies and results on AC, DC, and lightning impulse breakdown voltage, as well as the partial discharge of g3 gas, are provided, which indicate an equivalent dielectric strength of g3 gas with SF6 after a proper design change or an increase in gas pressure. The switching bus-transfer current test, temperature rise test, and liquefaction temperature calculation also verify the possibility of replacing SF6 with g3 gas. In addition, the use of g3 gas significantly reduces theabovementioned environmental concerns in terms of global warming potential and atmosphere lifetime. In recent years, g3 gas-insulated power facilities, including switchgear, transmission line, circuit breaker, and transformer, have been commercially available in the electric power industry.

1. Introduction

Sulfur hexafluoride (SF6) has been used as the most popular insulation gas in gas-insulated power facilities, such as switchgear (GIS), circuit breaker (GCB), transmission line (GIL), and transformer (GIT), since 1947. This is because SF6 has an exceptional combination of physical and chemical properties for high-voltage applications, including high-dielectric strength (three times that of air at atmospheric pressure), arc-quenching capability, thermal conductivity, thermal stability, nonflammability, nontoxicity, nonexplosive, and chemical inertness [1,2,3,4]. As a result, SF6-insulated equipment can be designed with reduced size, high reliability, and economic efficiency [5,6]. It is widely employed in space-limited locations such as city substations, offshore plants, or wind-power plants [7].
However, SF6 was labeled as one of the greenhouse gases in the Kyoto Protocol and Paris Agreements owing to its excessive size, radiative effect, and atmospheric lifetime [8,9,10,11,12]. The global warming potential (GWP) of SF6 is 23,500 times that of carbon dioxide (CO2) over a 100-year time horizon and is 32,600 times that of CO2 over a 500-year time horizon. The atmospheric lifetime of SF6 is 3200 years, whereas that of CO2 is only 30–90 years [1]. It was reported that 1 kg of SF6 released into the atmosphere has the equivalent global warming impact as 23.5 tons of CO2 [13]. Therefore, emission and consumption of SF6 must be controlled by the year 2020 and regulations have been implemented to reduce the environmental impact caused by SF6 [14,15,16]. In addition, SF6 decomposes into lower fluorides of sulfur when an electrical discharge such as an arc, spark, or corona occurs. Some decomposition byproducts, including disulfur decafluoride (S2F10), sulfur tetrafluoride (SF4), and hydrogen fluoride (HF), are known to be highly reactive, corrosive, and toxic, which cause great concerns regarding equipment lifetime and personnel safety [17,18].
Negative impacts have led the power industry to seek an eco-friendly alternative insulation gas to partially or completely replace SF6. Studies have been carried out to investigate the potential of natural gases such as CO2 [19] and nitrogen (N2) [20], and dry air, vacuum, SF6 gas mixture [20,21,22], and fluorinated gases with reduced GWP such as trifluoroiodomethane (CF3I) [4,13,14,23,24], perfluorocarbons (PFCs) [1,25], as well as hydrofluoroolefins (HFOs) [7,26]. Unfortunately, all of them have respective drawbacks, making them unsuitable for application in high-voltage gas-insulated equipment.
Recently, green gas for grid (g3), which was developed in collaboration by General Electric and 3M Company, has been regarded as the latest generation insulation gas and is the most promising candidate for replacing SF6. G3 is a gas mixture that is composed of C4F7N (NovecTM 4710) and CO2 or N2, which aims to reduce the environmental impact and to find a compromise between the dielectric performance and the minimum operating temperature of the apparatus [26,27,28]. Properties of g3 gas have been individually studied in the past five years, whereas a comprehensive overview of g3 gas for applications in high-voltage gas-insulated equipment has not been presented until now. This paper firstly discusses the required physical and chemical properties of gas for high-voltage insulation applications and then carries out a review on the state-of-the-art performance investigations of g3 gas.

2. Required Physical and Chemical Properties of Insulation Gas

An environmentally sustainable insulation gas alternative to SF6 should be compliant with the stringent requirements of high-voltage applications [29,30]. The physical and chemical properties include
  • High-dielectric strength;
  • Good arc-quenching capability;
  • High heat dissipation (high thermal conductivity);
  • Low boiling point and high vapor pressure at low temperature;
  • Compatibility with other materials; and
  • Design compactness.
In addition, it also has to meet environmental and safety requirements, such as
  • Low GWP;
  • No ozone depletion potential (ODP);
  • Low toxicity; and
  • Nonflammable and nonexplosive.

2.1. Dielectric Strength

The dielectric strength is investigated by AC, DC, and lightning impulse breakdown voltage, which is performed in the electrode arrangement and practical gas-insulated power facilities. Breakdown mechanisms of insulation gases can be theoretically explained by Paschen’s law and the Townsend theory [31,32]. The AC and DC breakdown voltages are tested by raising the applied voltage at a constant rate until the breakdown occurs. The lightning impulse breakdown voltage, which is represented by 50% breakdown strength, is determined by the up-and-down method by applying a 1.2/50 s standard lightning pulse voltage. Since it is used for determining the basic insulation level of a system, the lightning impulse test is a crucial test. The breakdown test, under the same condition, is repeated multiple times so that the mean value and standard deviation of the breakdown voltage are calculated by evaluating the gas performance [28,33]. Various conditions should be taken into account for determining the breakdown voltage, including the homogenous and inhomogeneous field, surface roughness, insulation defects, free-moving conductive particles, and contamination [34,35,36,37].
In addition to the breakdown voltage, partial discharge (PD) is the other criterion for evaluating the dielectric strength. According to the International Electrotechnical Commission (IEC) 60270, PD is a localized electrical discharge that only partially bridges the insulation between conductors, and it can or cannot occur adjacent to a conductor [38]. It occurs at any point in the insulation system where the electric field strength exceeds the breakdown strength of gas. Therefore, PD is regarded as an early stage of breakdown [39,40,41]. PD characteristics, in terms of partial discharge inception voltage (PDIV), discharge magnitude, and pulse count as a function of gas pressure and insulation distance, are used to compare the insulation performance of alternative gases [42,43,44].

2.2. Arc-Quenching Capability

Insulation gases should have the ability to interrupt a large current during the switching operation of the circuit breaker [45,46]. Important gas properties for arc interruption are required. The insulation gas should be electronegative to capture the freed electron fast and to reduce its moving speed [47]. As arc temperature is more than 10,000 K; gases should have high thermal conductivity to quickly cool down the temperature. In addition, molecules may be dissociated at a high temperature. The fast dielectric recovery is, therefore, required to recombine gas to form its original structure [36]. The arc-interrupting ability is evaluated by the thermal-interrupting test and the dielectric-recovery test. The arc conductivity, at hundreds of nanoseconds before current zero, is used as a performance indicator of the thermal-interrupting test [48,49]. The dielectric recovery test is currently done by a computational fluid dynamic of gas flow [50].

2.3. High Heat Dissipation (High Thermal Conductivity)

High heat dissipation capability is not only required to ensure arc-quenching ability but is also essential to transmit heat from the conductor and contact that is caused by the large current [51,52]. It is specified in the IEC 62271 that the highest temperature of the busbar and enclosure must not exceed 105 °C and 70 °C, respectively. The maximum allowable temperature rise during the steady-state operation of the busbar must not exceed 65 K, and that of the enclosure is 30 K [53]. Heat-dissipation performance of alternative gases can be determined by temperature rise testing in actual operation and simulated calculation, such as the analytical method and the finite element method [30,51,52,54].

2.4. Boiling Point and High Vapor Pressure at Low Temperature

In the Institute of Electrical and Electronics Engineers (IEEE) C37.100.1 standard, the minimum ambient operating temperature required for the outdoor switchgear is −30 °C [55]. The most frequent minimum temperatures requested by the main users of electrical switchgear are −15 °C and −25 °C [56]. To avoid liquefaction and to ensure the medium remains gaseous within the operational temperature range of the power apparatus, alternative gas should have a low boiling point and high vapor pressure at low temperatures [7,57]. Correlation between saturated vapor pressure and temperature data of gas mixtures can be obtained by the Wagner equation, which is given by
ln p p r = ( a τ + b τ 1.5 + c τ 3 + d τ 6 ) T T c
where p and pc are the partial pressure and critical pressure of gas mixtures, and T and Tc are the thermodynamic temperature and critical temperature, respectively [27,58].

2.5. Compatibility with Other Materials

Alternative insulation gases are not chemically as inert as SF6 and might react with other substances such as metals, spacers, insulators, etc. As a result, the serviceable lifetime of power facilities may be significantly diminished. Therefore, intensive investigations about material compatibility between the new gas as well as its decomposition and the other used materials are required, which can be done in long-term aging tests at increased temperatures [59].

2.6. Design Compactness

The most desirable alternative gas is the substitute that can be used in existing SF6-insulated facilities without significant changes in structure, operation, and ratings [36]. In addition, power facilities designed with an alternative gas should have a similar footprint to SF6 units and avoid an increase in space.

2.7. Global Warming Potential

According to the Intergovernmental Panel on Climate Change (IPCC), the GWP is defined as an index of the climate impact added to the climate system by a greenhouse gas relative to that added by CO2 [60]. It is calculated as the ratio of the time-integrated radiative forcing due to 1 kg of the gas emitted to the atmosphere relative to that of 1 kg of CO2 over an integration time horizon (ITH), which can be expressed by
GWP = 0 I T H R x C x 0 e x p [ ( t ) / τ x ] d t 0 I T H R c o 2 C C O 2 ( t ) d t
where R and C are the radiative forcing per unit mass and the atmospheric concentration of the compound, respectively; t and x are the time and compound of interest; and τ is the lifetime of compound [61]. Commonly, ITH of 20, 100, and 500 years are used.
The GWP of a gas mixture is calculated as a weighted average, derived from the sum of the weight fractions of the individual gas multiplied by their GWP [62,63].
GWP m i x t u r e = [ ( G a s   X % × GWP ) + ( G a s   Y % × GWP ) + + ( G a s   N % × GWP ) ]
where % is the contribution by weight with a weight tolerance of 1%.

2.8. Ozone Depletion Potential (ODP)

As the environmental impact of SF6 is the main reason to search for a substitutable gas, any alternative gas must not increase the environmental concerns and have an ozone depletion potential of zero.

2.9. Toxicity

Any alternative gas and its byproducts should have minimal toxicity to ensure that it can be safely handled as it is procured, transported, maintained, and disposed of, and that it is not harmful when the gas is released to the atmosphere. Important indicators of toxicity are acute toxicity, chronic toxicity, as well as medium- and long-term toxic effects [56]. Acute toxicity is characterized by a lethal concentration at 50% mortality (LC50) in 4 h. LC50 is expressed in parts per million (ppm), and a low value corresponds to high-gas toxicity. The acute toxicity of a gas mixture is determined by the calculation of the toxicity for all relevant ingredients [64]. Chronic toxicity is presented by the time-weighted average (TWA) and measured in ppm in 8 h. The TWA should be higher than 50 ppm in the switchgear factories to ensure workers continue without adverse effects. Medium- and long-term toxic effects are carcinogenic, mutagenic, and toxic for reproduction [56,59].

3. Green Gas for Grid

Although NovecTM 4710 has excellent dielectric strength and an arc-quenching ability, it cannot be used alone due to its high-liquefaction temperature. Therefore, it is necessary to mix it with other gases such as CO2 and N2. Addictive NovecTM 4710 in gas mixtures is in the range of 5–20% [26,27]. Table 1 shows the fundamental physical and chemical properties of SF6, NovecTM 4710, CO2, and N2.
The dielectric strength of g3 gas has been investigated by breakdown voltage and PD. Figure 1 shows the AC breakdown voltage depending on the NovecTM 4710 and CO2 mixture ratio, as well as the gas pressure in the uniform field that was configured using parallel disk electrodes with a gap distance of 2.54 mm [66]. The AC breakdown voltage was also measured on a 145 kV GIS with NovecTM 4710 ratio from 0% to 20% and CO2. It was indicated that the dielectric strength of pure CO2 was equivalent to about 40% that of SF6 at atmosphere pressure. Adding 6% to 7% of NovecTM 4710 doubled the dielectric strength, and g3 gas with 18% to 20% of NovecTM 4710 had the equivalent dielectric strength to SF6 at atmosphere pressure [30,67,68]. Breakdown tests under AC at different pressures and electrode distances were conducted in plane–plane, sphere–plane, rod–plane, and needle–plane electrode configurations. In the uniform field, equivalent dielectric strength to SF6 at 100 kPa can be reached by a mixture containing 15% NovecTM 4710. In the nonuniform and highly nonuniform fields, SF6 exhibited higher dielectric strength than a 20% mixture. The 20% NovecTM 4710/80% CO2 mixture at 100–120 kPa was verified as an optimal potential replacement of SF6 as the dielectric medium in MV switchgears if attention is paid to the equipment design to avoid nonuniform fields [44]. The comparison of AC breakdown voltages in the sphere-to-sphere electrode arrangement showed that the 3.7% NovecTM 4710/96.3% CO2 mixture constituted a good compromise between high-voltage apparatus insulation and a low ambient temperature application [28].
The positive and negative DC breakdown tests were carried out in a plane–plane electrode arrangement. As shown in Figure 2, the negative DC breakdown strengths of 4% NovecTM 4710/96% CO2 and 8% NovecTM 4710/92% CO2 mixtures at 0.7 MPa were 81.21% and 96.48% of the value for SF6 at 0.5 MPa [57,69]. The lightning breakdown voltages of 3.7% NovecTM 4710/96.3% CO2 at pressures of 0.88 MPa and 1.04 MPa were almost equivalent to that of SF6 at 0.55 MPa and 0.65 MPa, respectively [28].
PDIVs of SF6 and NovecTM 4710/CO2 were measured in protrusions on the conductor and enclosure of GIS. As shown in Figure 3, PDIVs in g3 gas with 4% NovecTM 4710/96% CO2 in protrusion defects were measured as 76–84% of that of SF6. In addition, the average apparent charge and pulse count of PD in g3 were higher compared with those in SF6 [70]. The PDIV in NovecTM 4710/N2 showed that the dielectric strength of the gas mixture was weaker than that of pure SF6 [27].
The switching bus-transfer current test was carried out on a 420 kV disconnector over a 100 close and open operation under 1600 A and 20 V. Comparison of the arcing time between NovecTM 4710/CO2 gas mixture and SF6 is shown in Figure 4. It indicates that the arcing time of g3 gas proved to be stable, and the average arcing time is about 12 ms, compared with a typical value of 15 ms for SF6 [67]. The arc-quenching capability was verified according to IEC 62271-100, also indicating that g3 gas maintained the appropriate dielectric withstanding ability after repeated interruptions [68,71,72].
Temperature rise tests of g3 gas were performed on a fully equipped three-phase GIS bay, and the results are shown in Figure 5. There were temperature rise differences of 5 K to 6 K between the gas mixtures and SF6 [26,67]. The temperature rise can be compensated for by typical measures such as adding cooling fins to the enclosure or machining slots and holes to conductors to improve convection around live parts of the GIS.
NovecTM 4710 has a liquefaction temperature of −4.7 °C at 0.1 MPa, which makes it impossible to be applied in gas-insulated power facilities alone. N2 or CO2 is used as a buffer gas to increase the liquefaction temperature. The liquefaction temperature of NovecTM 4710/N2 and NovecTM 4710/CO2 gas mixture at different gas ratios and pressures can be calculated according to Equation (1). The results are illustrated in Figure 6. To meet the minimum ambient operating temperature requirement of −30 °C, NOVECTM 4710 should be at least at 13% at 0.2 Mpa in the NovecTM 4710/N2 and NovecTM 4710/CO2 mixture.
Materials of the gas-insulated structure have been found to be compatible with the NovecTM 4710. There is no research so far indicting the chemical reaction of NovecTM 4710 with other materials.
According to Equation (3), the GWP of g3 gas mixed with CO2 or N2 can be calculated according to the Intergovernmental Panel on Climate Change and the Regulation No 842/2006 of the European Parliament and the Council of 17 May 2006 on Certain Fluorinated Greenhouse Gases [62,63]. Figure 7 shows the GWP of the g3 gas mixture with NovecTM 4710 ratio up to 20%. The GWPs of 20% NovecTM 4710/80% CO2 and NovecTM 4710/80% N2 are 1104 and 1334, which are only 4.7% and 5.7% that of SF6, respectively. Therefore, the application of g3 gas results in a significant reduction in GWP.
In addition, g3 gas has an ODP of zero, and its atmospheric lifetime is much shorter than that of SF6. g3 is not a carcinogenic and mutagenic gas, and is classified as nontoxic, nonflammable, and nonexplosive [61,70].
g3 gas has been verified as an effective and high-performance substitute of SF6 for environmentally sustainable high-voltage applications. At present, g3 gas-insulated power facilities are commercially available for GIS up to 145 kV, GIL and GCB up to 420 kV, and GIT up to 245 kV, after stringent laboratory and equipment testing [30]. These facilities feature the same dimensional footprint as SF6 equipment, while significantly reducing greenhouse gas emissions.

4. Conclusions

As a new potential alternative insulation gas to SF6, g3 that is composed of NovecTM 4710 and CO2 or N2 shows its high performance as an insulation medium of gas-insulated power facilities. This paper presents a comprehensive overview of g3 gas for applications in high-voltage, gas-insulated equipment, and conclusions are as follows:
  • From the AC/DC breakdown voltage and partial discharge characteristics, the addition of a few ratios of NovecTM 4710 to the buffer gas significantly increases the dielectric strength of the gas mixture, which is almost equivalent to that of SF6.
  • At the same time, g3 presents a good compromise between high dielectric strength and low ambient temperature requirements, which met the requirement of the minimum ambient operating temperature of power facilities.
  • In addition, the switching bus-transfer current test, temperature rise test, and liquefaction temperature calculation also verified the validity of g3 gas for high-voltage insulation applications.
  • As for environmental concerns, g3 gas reduces the GWP of more than 94% compared with SF6. It has an ODP of zero and an atmospheric lifetime as short as 30 years, which is only 1% of that of SF6.
From the laboratory and equipment testing, g3 is verified as the most promising eco-friendly alternative insulation gas to SF6 developed for the SF6-free gas-insulated power facilities. It is a potential alternative for electrical equipment with a drastically reduced environmental impact while featuring the same structure, operation, ratings, and footprint of existing equipment.

Author Contributions

Conceptualization, B.P., G.W., and H.S.; methodology, B.P., H.S., J.S., and H.-K.J.; validation, G.W., J.S., and H.-K.J.; formal analysis, J.S. and G.-S.K.; investigation, H.S., J.S., and H.-K.J.; writing—original draft preparation, B.P. and G.W.; writing—review and editing, H.S. and H.-K.J.; supervision, J.S. and G.-S.K.; project administration, G.W. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Beroual, A.; Haddad, A. Recent advances in the quest for a new insulation gas with a low impact on the environment to replace sulfur hexafluoride (SF6) gas in high-voltage power network applications. Energies 2017, 10, 1216. [Google Scholar] [CrossRef] [Green Version]
  2. Li, X.; Zhao, H.; Murphy, A.B. SF6-alternative gases for application in gas-insulated switchgear. J. Phys. D: Appl. Phys. 2018, 51, 153001. [Google Scholar] [CrossRef]
  3. Haddad, A.; Warne, D.F. Advances in High Voltage Engineering, 1st ed.; The Institution of Engineering and Technology: Stevenage, UK, 2004; pp. 37–73. [Google Scholar] [CrossRef] [Green Version]
  4. Zhao, S.; Xiao, D.; Xue, P.; Zhong, R.; Deng, Y. Analysis of insulation performance and polar effect of CF3I/CO2 mixtures. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 1364–1370. [Google Scholar] [CrossRef]
  5. Glaubitz, P.; Stangherlin, S.; Biasse, J.M.; Meyer, F.; Dallet, M.; Prufert, M.; Kurte, R.; Saida, T.; Uehara, K.; Prieur, P.; et al. CIGRE position paper on the application of SF6 in transmission and distribution networks. ELECTRA 2014, 274, 34–39. [Google Scholar]
  6. Wang, G.M.; Kil, G.S. Measurement and analysis of partial discharge using an ultra-high frequency sensor for gas insulated structures. Metrol. Meas. Syst. 2017, 24, 515–524. [Google Scholar] [CrossRef]
  7. Western Power Distribution. SF6 Alternatives—A Literature Review on SF6 Gas Alternatives for Use on the Distribution Network; Western Power Distribution: Wales, UK, 2018; pp. 6–39. [Google Scholar]
  8. United Nations. Kyoto Protocol to the United Nations Framework Convention on Climate Change; United Nations: Rome, Italy, 1998; pp. 1–19. [Google Scholar]
  9. United Nations. Paris Agreement—United Nations Framework Convention on Climate Change; United Nations: Rome, Italy, 2015. [Google Scholar]
  10. Okubo, H.; Beroual, A. Recent trend and future perspectives in electrical insulation techniques in relation to sulfur hexafluoride (SF6) substitutes for high voltage electric power equipment. IEEE Electr. Insul. Mag. 2011, 27, 34–42. [Google Scholar] [CrossRef]
  11. Widger, P.; Haddad, A. Evaluation of SF6 leakage from gas insulated equipment on electricity networks in Great Britain. Energies 2018, 11, 2037. [Google Scholar] [CrossRef] [Green Version]
  12. Christophorou, L.G.; Olthoff, J.K.; Brunt, R.J.V. Sulfur hexafluoride and the electric power industry. IEEE Electr. Insul. Mag. 1997, 13, 20–24. [Google Scholar] [CrossRef]
  13. Kieffel, Y.; Biquez, F.; Ponchon, P. Alternative gas to SF6 for use in high voltage switchgears: G3. In Proceedings of the International Conference on Electricity Distribution, Lyon, France, 15–18 June 2015; pp. 1–5. [Google Scholar]
  14. Zhao, S.; Xiao, D.; Xue, P.; Zhong, R.; Deng, Y. Experimental research on polarity effect of CF3I/N2 mixture under lightning impulse. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 1357–1363. [Google Scholar] [CrossRef]
  15. European Environment Agency. Regulation (EU) No 517/2014 of the European parliament and of the council of 16 April 2014 on fluorinated greenhouse gases and repealing Regulation (EC) No 842/2006 text with EEA relevance. Off. J. Eur. Union 2014, 150, 195–230. [Google Scholar]
  16. Department for Environment. Food & Rural Affairs and Environment Agency (DEFRA) of UK Government. Calculate the Carbon Dioxide Equivalent Quantity of an F gas; UK Government: London, UK.
  17. Dervos, T.C.; Vassiliou, P. Sulfur hexafluoride(SF6): Global environmental effects and toxic byproduct formation. J. Air Waste Manag. Assoc. 1995, 50, 137–141. [Google Scholar] [CrossRef] [PubMed]
  18. Tsai, W.T. The decomposition products of sulfur hexafluoride (SF6): Reviews of environmental and health risk analysis. J. Fluor. Chem. 2007, 128, 1345–1352. [Google Scholar] [CrossRef]
  19. Goshima, H.; Tanimura, A.; Tsuru, S.; Yaegashi, Y.; Fujie, E.; Okubo, H. Fundamental insulation characteristics of high-pressure CO2 gas under actual equipment conditions. IEEE Trans. Dielectr. Electr. Insul. 2007, 14, 83–90. [Google Scholar] [CrossRef]
  20. Rokunohe, T.; Yagihashi, Y.; Endo, F.; Oomori, T. Fundamental insulation characteristics of air, N2, CO2, N2/O2, and SF6/N2 mixed gases. Electr. Eng. Jpn. 2006, 155, 9–17. [Google Scholar] [CrossRef]
  21. Qiu, Y.; Kuffel, E. Comparison of SF6/N2 and SF6/CO2 gas mixtures as alternatives to SF6 gas. IEEE Trans. Dielectr. Electr. Insul. 1999, 6, 891–895. [Google Scholar] [CrossRef]
  22. Beroual, A.; Khaled, U.; Coulibaly, M.L. Experimental investigation of the breakdown voltage of CO2, N2, and SF6 gases, and CO2–SF6 and N2–SF6 mixtures under different voltage waveforms. Energies 2018, 11, 902. [Google Scholar] [CrossRef] [Green Version]
  23. Katagiri, H.; Kasuya, H.; Mizoguchi, H.; Yanabu, S. Investigation of the performance of CF3I gas as a possible substitute for SF6. IEEE Trans. Dielectr. Electr. Insul. 2008, 15, 1424–1429. [Google Scholar] [CrossRef]
  24. McCain, W.C.; Macko, J. Toxicity review for iodotrifluoromethane (CF3I). In Proceedings of the Halon Options Technical Working Conference, Albuquerque, NM, USA, 17–29 April 1999; pp. 242–253. [Google Scholar]
  25. Hikita, M.; Ohtsuka, S.; Okabe, S.; Kaneko, S. Insulation characteristics of gas mixtures including perfluorocarbon gas. IEEE Trans. Dielectr. Electr. Insul. 2008, 15, 1015–1022. [Google Scholar] [CrossRef]
  26. Kieffel, Y.; Biquez, F. SF6 alternative development for high voltage switchgears. In Proceedings of the Electrical Insulation Conference, Washington, DC, USA, 7–10 June 2015; pp. 379–383. [Google Scholar] [CrossRef]
  27. Li, Y.; Zhang, X.; Chen, Q.; Fu, M.; Zhuo, R.; Xiao, S.; Chen, D.; Tang, J. Study on the dielectric properties of C4F7N/N2 mixture under highly non-uniform electric field. IEEE Access 2018, 6, 42868–42875. [Google Scholar] [CrossRef]
  28. Nechmi, H.E.; Beroual, A.; Girodet, A.; Vinson, P. Fluoronitriles/CO2 gas mixture as promising substitute to SF6 for insulation in high voltage applications. IEEE Trans. Dielectr. Electr. Insul. 2016, 23, 2587–2593. [Google Scholar] [CrossRef]
  29. Seeger, M.; Smeets, R.; Yan, J.; Ito, H.; Claessens, M.; Dullni, E.; Franck, C.M.; Gentils, F.; Hartmann, W.; Kieffel, Y.; et al. Recent development of alternative gases to SF6 for switching applications. ELECTRA 2017, 291, 26–29. [Google Scholar]
  30. Kieffel, Y.; Irwin, T.; Ponchon, P.; Owens, J. Green gas to replace SF6 in electrical grids. IEEE Power Energy Mag. 2014, 14, 32–39. [Google Scholar] [CrossRef]
  31. Malik, N.H.; Al-Arainy, A.A.; Qureshi, M.I. Electrical Insulation in Power System, 1st ed.; MARCEL DEKKER: New York, NY, USA, 1997; pp. 1–110. [Google Scholar]
  32. Ryan, H.M. High-Voltage Engineering and Testing, 3rd ed.; The Institution of Engineering and Technology: Stevenage, UK, 2003; pp. 631–674. [Google Scholar] [CrossRef]
  33. Hoshina, Y.; Sato, M.; Shiiki, M.; Hanai, M.; Kaneko, E. Lightning impulse breakdown characteristics of SF6 alternative gases for gas-insulated switchgear. IEE Proc. Sci. Meas. Technol. 2006, 153, 1–6. [Google Scholar] [CrossRef]
  34. Cookson, A.H. Review of high-voltage gas breakdown and insulators in compressed gas. IEE Proc. Phys. Sci. Meas. Instr. Manag. Educ. 1981, 128, 303–312. [Google Scholar] [CrossRef]
  35. Radmilovic-Radjenovic, M.; Lee, J.K.; Iza, F.; Park, G.Y. Particle-in-cell simulation of gas breakdown in microgaps. J. Phys. D: Appl. Phys. 2005, 38, 950–954. [Google Scholar] [CrossRef] [Green Version]
  36. Christophorou, L.G.; Olthoff, J.K.; Greem, D.S. Gases for Electrical Insulation and Arc Interruption: Possible Present and Future Alternatives to Pure SF6; United States Department of Commerce Technology Administration, National Institute of Standards and Technology: Maryland, MD, USA, 1997; pp. 1–29.
  37. Laghari, J.R.; Qureshi, A.H. A review of particle-contaminated gas breakdown. IEEE Trans. Dielectr. Electr. Insul. 1981, 16, 388–398. [Google Scholar] [CrossRef]
  38. International Electrotechnical Commission. High-Voltage Test Techniques-Partial Discharge Measurements; IEC 60270; IEC: Geneva, Switzerland, 2015. [Google Scholar]
  39. Wang, G.M.; Kim, S.J.; Kil, G.S.; Kim, S.W. Optimization of wavelet and thresholding for partial discharge detection under HVDC. IEEE Trans. Dielectr. Electr. Insul. 2017, 24, 200–208. [Google Scholar] [CrossRef]
  40. Wang, G.M.; Jo, H.E.; Kim, S.J.; Kim, S.W.; Kil, G.S. Measurement and analysis of partial discharges in SF6 gas under HVDC. Measurement 2016, 91, 351–359. [Google Scholar] [CrossRef]
  41. Okubo, H.; Yamada, T.; Takahashi, T.; Toda, T. Partial discharge inception and breakdown characteristics in gas mixtures with SF6. In Gaseous Dielectrics VIII, 1st ed.; Christophorou, L.G., Olthoff, J.K., Eds.; Springer: Boston, MA, USA, 1998; pp. 289–294. [Google Scholar]
  42. Zhang, B.; Uzelac, N.; Cao, Y. Fluoronitrile/CO2 Mixture as an eco-friendly alternative to SF6 for medium voltage switchgears. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 1340–1350. [Google Scholar] [CrossRef]
  43. Wang, G.M.; Kil, G.S.; Ji, H.G.; Lee, J.H. Disturbance elimination for partial discharge detection in the spacer of gas-insulated switchgears. Energies 2017, 10, 1762. [Google Scholar] [CrossRef] [Green Version]
  44. Okubo, H.; Yamada, T.; Hatta, K.; Hayakawa, N.; Yuasa, S.; Okabe, S. Partial discharge and breakdown mechanisms in ultra-dilute SF6 and PFC gases mixed with N2 gas. J. Phys. D: Appl. Phys. 2002, 35, 2760–2765. [Google Scholar] [CrossRef]
  45. Taki, M.; Maekawa, D.; Odaka, H.; Mizoguchi, H.; Yanabu, S. Interruption capability of CF3I gas as a substitution candidate for SF6 gas. IEEE Trans. Dielectr. Electr. Insul. 2007, 14, 341–346. [Google Scholar] [CrossRef]
  46. Kosse, S.; Nikolic, P.G.; Kachelriess, G. Holistic evaluation of the performance of today’s SF6 alternatives proposals. In Proceedings of the International Conference & Exhibition on Electricity Distribution, Glasgow, UK, 12–15 June 2017; pp. 210–213. [Google Scholar] [CrossRef] [Green Version]
  47. Xiao, S.; Zhang, X.; Tang, J.; Liu, S. A review on SF6 substitute gases and research status of CF3I gases. Energy Rep. 2018, 4, 486–496. [Google Scholar] [CrossRef]
  48. Smeets, R.P.P.; Kertész, V.; Nishiwaki, S.; Suzuki, K. Performance evaluation of high-voltage circuit breakers by means of current zero analysis. In Proceedings of the IEEE/PES Transmission and Distribution Conference and Exhibition, Yokohama, Japan, 6–10 October 2002; pp. 424–429. [Google Scholar] [CrossRef]
  49. Ahmethodzic, A.; Smeets, R.P.P.; Kertész, V.; Kapetanovic, M.; Sokolija, K. Design improvement of a 245-kV SF6 circuit breaker with double-speed mechanism through current zero analysis. IEEE Trans. Power Del. 2010, 25, 2496–2503. [Google Scholar] [CrossRef]
  50. Petchanka, A.; Reichert, F.; Gonzalez, J.J.; Freton, P. Modelling of the deformation of PTFE-nozzles in a high voltage circuit breaker due to multiple interruptions. J. Phys. D Appl. Phys. 2016, 49, 135201. [Google Scholar] [CrossRef]
  51. Novák, B. Comparison of heat transfer in air and SF6 in high voltage GIS. In Proceedings of the Electrical Insulation Conference, Ottawa, ON, Canada, 2–5 June 2013; pp. 85–89. [Google Scholar] [CrossRef]
  52. Novák, B.; Koller, L. Steady-state heating of gas insulated busbars. In Proceedings of the IEEE/PES Transmission and Distribution Conference and Exhibition, Orlando, FL, USA, 7–10 May 2012; pp. 1–7. [Google Scholar] [CrossRef]
  53. International Electrotechnical Commission. High-Voltage Switchgear and Controlgear-Part 1: Common Specifications for Alternating Current Switchgear and Controlgear; IEC 62271-1; IEC: Geneva, Switzerland, 2017. [Google Scholar]
  54. Chen, G.; Tu, Y.; Wang, C.; Cheng, Y.; Jiang, H.; Zhou, H.; Jin, H. Analysis on temperature distribution and current-carrying capacity of GIL filled with Fluoronitriles-CO2 gas mixture. J. Electr. Eng. Technol. 2018, 13, 2402–2411. [Google Scholar] [CrossRef]
  55. Institute of Electrical and Electronics Engineers. IEEE Standard of Common Requirements for High Voltage Power Switchgear Rated Above 1000V; IEEE C37.100.1; IEEE: New York, NY, USA, 2018. [Google Scholar]
  56. Preve, C.; Piccoz, D.; Maladen, R. Validation methods of SF6 alternative gas. In Proceedings of the International Conference on Electricity Distribution, Lyon, French, 15–18 June 2015; pp. 1–5. [Google Scholar]
  57. Wang, C.; Cheng, Y.; Tu, Y.; Chen, G.; Yuan, Z.; Xiao, A.; Owens, J.; Zhang, A.; Mi, N. Characteristics of C3F7CN/CO2 as an alternative to SF6 in HVDC-GIL systems. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 1351–1356. [Google Scholar] [CrossRef]
  58. Zhang, X.; Chen, Q.; Zhang, J.; Li, Y.; Xiao, S.; Zhuo, R.; Tang, J. Experimental study on power frequency breakdown characteristics of C4F7N/CO2 gas mixture under quasi-homogeneous electric field. IEEE Access 2019, 7, 19100–19108. [Google Scholar] [CrossRef]
  59. Hyrenbach, M.; Zache, S. Alternative insulation gas for medium-voltage switchgear. In Proceedings of the Petroleum and Chemical Industry Conference Europe, Berlin, Germany, 14–16 June 2016. [Google Scholar] [CrossRef]
  60. Intergovernmental Panel on Climate Change. Climate Change 2013; Cambridge University Press: New York, NY, USA, 2013; pp. 159–254. [Google Scholar]
  61. Owens, J.G. Greenhouse gas emission reductions through use of a sustainable alternative to SF6. In Proceedings of the IEEE Electrical Insulation Conference, Montreal, QC, Canada, 19–22 June 2016; pp. 535–538. [Google Scholar] [CrossRef]
  62. European Environment Agency. Regulation (EC) No 842/2006 of the European parliament and of the council of 17 May 2006 on certain fluorinated greenhouse gases. Off. J. Eur. Union 2006, 15, 1–11. [Google Scholar]
  63. European Fluorocarbons Technical Committee. F Gas Regulation Implementation and Compliance. Available online: https://www.fluorocarbons.org/efctc-f-gas-regulation-implementation-compliance/ (accessed on 2 December 2019).
  64. European Environment Agency. Regulation (EC) No 1272/2008 of the European parliament and of the council of 16 December 2008 on classification, labelling and packaging of substances and mixtures, amending and repealing Directives 67/548/EEC and 1999/45/EC, and amending Regulation (EC) No 1907/2006. Off. J. Eur. Union 2008, 353, 1–50. [Google Scholar]
  65. Rabie, M.; Franck, C.M. Assessment of eco-friendly gases for electrical insulation to replace the most potent industrial greenhouse gas SF6. Environ. Sci. Technol. 2018, 52, 369–380. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  66. 3M Company. NovecTM 4710 Insulating Gas; 3M Company: Saint Paul, MN, USA, 2017. [Google Scholar]
  67. Kieffel, Y.; Girodet, A.; Biquez, F.; Ponchon, P.; Owens, J.; Costello, M.; Bulinski, M.; San, R.V.; Werner, K. SF6 alternative development for high voltage switchgears. In Proceedings of the CIGRE 2014, Paris, France, 24–29 August 2014. [Google Scholar]
  68. Kieffel, Y.; Biquez, F.; Vigouroux, D. Characteristics of g3—An alternative to SF6. In Proceedings of the International Conference & Exhibition on Electricity Distribution, Glasgow, UK, 12–15 June 2017; pp. 54–57. [Google Scholar] [CrossRef]
  69. Tu, Y.; Cheng, Y.; Wang, C.; Ai, X.; Zhou, F.; Chen, G. Insulation characteristics of fluoronitriles/CO2 gas mixture under DC electric field. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 1324–1331. [Google Scholar] [CrossRef]
  70. Wang, G.M.; Kim, W.H.; Kil, G.K.; Kim, S.W.; Jung, J.R. Green gas for grid as an eco-friendly alternative insulation gas to SF6: From the perspective of partial discharge under AC. Appl. Sci. 2019, 9, 651. [Google Scholar] [CrossRef] [Green Version]
  71. Wang, G.M.; Shen, J.H.; Liu, D.M.; Kim, S.W.; Kil, G.S. Green gas for grid as an eco-friendly alternative insulation gas to SF6: From the perspective of PD initiated by metallic particles under DC. J. Electr. Eng. 2020, 1, 43–48. [Google Scholar] [CrossRef]
  72. International Electrotechnical Commission. High-Voltage Switchgear and Controlgear—Part 100: Alternating Current Circuit-Breakers; IEC 62271-100; IEC: Geneva, Switzerland, 2017. [Google Scholar]
Figure 1. AC breakdown voltage depending mixture ratio and gas pressure [66].
Figure 1. AC breakdown voltage depending mixture ratio and gas pressure [66].
Applsci 10 02526 g001
Figure 2. DC breakdown strength of the NovecTM 4710/carbon dioxide (CO2) mixture depending on gas ratio and pressure [57].
Figure 2. DC breakdown strength of the NovecTM 4710/carbon dioxide (CO2) mixture depending on gas ratio and pressure [57].
Applsci 10 02526 g002
Figure 3. Partial discharge inception voltages of SF6 and g3 in the protrusion defects [70].
Figure 3. Partial discharge inception voltages of SF6 and g3 in the protrusion defects [70].
Applsci 10 02526 g003
Figure 4. Arcing time of NovecTM 4710/CO2 gas mixture and SF6 [26].
Figure 4. Arcing time of NovecTM 4710/CO2 gas mixture and SF6 [26].
Applsci 10 02526 g004
Figure 5. Temperature rise results in switchgear (GIS) filled with the NovecTM 4710/CO2 gas mixture and sulfur hexafluoride (SF6) [67].
Figure 5. Temperature rise results in switchgear (GIS) filled with the NovecTM 4710/CO2 gas mixture and sulfur hexafluoride (SF6) [67].
Applsci 10 02526 g005
Figure 6. Liquefaction temperature of the gas mixture at different gas ratios and pressures. (a) NovecTM/Nitrogen (N2) [27] and (b) NovecTM/CO2 [58].
Figure 6. Liquefaction temperature of the gas mixture at different gas ratios and pressures. (a) NovecTM/Nitrogen (N2) [27] and (b) NovecTM/CO2 [58].
Applsci 10 02526 g006
Figure 7. Global warming potential of g3 gas mixture.
Figure 7. Global warming potential of g3 gas mixture.
Applsci 10 02526 g007
Table 1. Fundamental physical and chemical properties [20,25,65].
Table 1. Fundamental physical and chemical properties [20,25,65].
Chemical FormulaSF6C4F7NCO2N2
Molecular weight (g/mol)146.0619544.0128.014
Number of electrons7748167
Relative dielectric strength to SF61>2<0.4<0.4
Liquefaction pressure at −30 °C (MPa)0.520.03111.43-
Freezing point (°C)−51−118−78.5−210
Boiling point at 0.1 Mpa (°C)−63−4.7−79−196
Ozone depletion potential0000
Global warming potential (GWP)23,500210010
Atmospheric lifetime (year)3200305–200-
Toxicity (LC 50 (rat))>500,00010,000–15,000>300,000-
FlammabilityNoNoNoNo
CorrosionNoNoNoNo

Share and Cite

MDPI and ACS Style

Pan, B.; Wang, G.; Shi, H.; Shen, J.; Ji, H.-K.; Kil, G.-S. Green Gas for Grid as an Eco-Friendly Alternative Insulation Gas to SF6: A Review. Appl. Sci. 2020, 10, 2526. https://doi.org/10.3390/app10072526

AMA Style