Next Article in Journal
The Influence of Organic and Mineral Fertilizers on the Quality of Soil Organic Matter and Glomalin Content
Next Article in Special Issue
Real-Time Temperature Distribution Monitoring in Chinese Solar Greenhouse Using Virtual LAN
Previous Article in Journal
Utilization of Vertical Cordon System to Improve Source-Sink Balance and Wine Aroma under Water Shortage Conditions of Maturana Blanca
Previous Article in Special Issue
Greenhouse Thermal Effectiveness to Produce Tomatoes Assessed by a Temperature-Based Index
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Modeling-Based Energy Performance Assessment and Validation of Air-To-Water Heat Pump System Integrated with Multi-Span Greenhouse on Cooling Mode

1
Smart Agriculture Innovation Center, Kyungpook National University, Daegu 41566, Korea
2
Department of Bio-Industrial Machinery Engineering, Institute of Agricultural and Life Sciences, Gyeongsang National University, Jinju 52828, Korea
3
Department of Agricultural Engineering, Kyungpook National University, Daegu 41566, Korea
*
Author to whom correspondence should be addressed.
Agronomy 2022, 12(6), 1374; https://doi.org/10.3390/agronomy12061374
Submission received: 14 April 2022 / Revised: 2 June 2022 / Accepted: 2 June 2022 / Published: 7 June 2022
(This article belongs to the Special Issue Frontier Studies in Agricultural Greenhouse Equipment and Systems)

Abstract

:
The purpose of this study was to conduct a modeling-based energy performance assessment and validation of an air-to-water heat pump (AWHP) system, in the cooling mode, integrated with a multi-span greenhouse using TRNSYS software. We used the building energy simulation (BES) model to investigate the performance characteristics of the AWHP system for greenhouse cooling. We modelled the components of the AWHP system, including the fan coil unit (FCU), water storage tank, and water circulation pump integrated with the greenhouse model. The proposed model included all the components of the experimental system. We validated the proposed model by comparing the simulation results with those obtained from field experiments. We investigated the cooling energy supply to the multi-span greenhouse, greenhouse internal air temperature, heat pump (HP) output temperature, and coefficient of performance (COP). We evaluated the performance of our model by calculating the Nash–Sutcliffe efficiency (NSE) coefficient of all the validated components. Furthermore, we performed linear regression analyses (R2) to determine the relationship between the different parameters. NSE values of 0.87, 0.81, and 0.93, for the greenhouse internal air temperature, the energy supply to the greenhouse, and the HP output water temperature, respectively, validated the prediction accuracy of the model. Moreover, R2 values of 0.83 and 0.39 indicated that cooling loads are more dependent on ambient solar radiation than ambient air temperature. Furthermore, an R2 value of 0.91 showed a linear relationship between the HP’s energy consumption and ambient air temperature. The average daily COP of the HP system was 2.9. Overall, the simulation results showed acceptable correlation with the experimental results. The high NSE values validated the high predictive power of the model. The proposed validation model can be used to improve the performance of systems by optimizing the control strategies and capacities of the equipment (e.g., the HP, the FCU, and the area of the greenhouse). We have provided detailed information to enable engineers, researchers, and consultants to implement the model for their specific needs.

1. Introduction

Globally, fossil fuels satisfy most of our energy demands. It is projected that the total use of energy worldwide will grow by 44% from 2006 to 2030. There is a surge in energy demand owing to a growing population and industrialization [1]. This trend will not only cause scarcity in terms of fossil fuel supplies but will increase environmental pollution and CO2 emissions [2]. In addition to other effects, the worldwide increase in oil prices is a major concern. Moreover, the expected increase in the world’s population to 9.8 billion by 2050 is an area of focus in the context of achieving global sustainability [3]. Owing to climate change and consequent extreme weather conditions in both winter and summer, the growth of protected horticultural facilities is increasing globally to meet sustainability goals. According to a recent report, energy consumption in the world food chain is almost 30% of the total global energy demand, which is mostly met by fossil fuels [4]. The desired microclimate in agricultural facilities is maintained by providing cooling/heating and artificial lighting, which increases the energy consumption. The cost of energy has become one of the major factors in greenhouse farming [5]. The use of fossil fuels in greenhouse farming not only increases production costs [6] but increases environmental pollution and CO2 emissions. The worldwide growth of environmentally controlled agriculture facilities requires innovative solutions to meet energy demands with cost-effective and sustainable energy technologies. Among the different energy-saving strategies proposed for the greenhouse sector, the use of alternative energy sources has been identified as a potential solution [7]. Several types of heat pumps (HPs) with different specifications are used globally for buildings and greenhouses [8]. Two types of HPs are used to provide heating and cooling energy: ground -and air-source HPs. Ground-source HPs are more efficient but are more expensive than air-source HPs [9].
TRNSYS is a graphical and extremely flexible software which is used to simulate the behavior of transient systems. It is used for the simulation and performance assessment of systems such as solar, geothermal, building energy, load and structure, electrical, hydronics, and storage systems as well as HPs and solar applications [10]. It is a versatile component-based simulation tool with a series of programs and addons that enable the development of simple and complex energy systems and their components [11]. It has different libraries containing numerous components for the modeling of energy systems, including a wide range of heating ventilation and air-conditioning (HVAC) components for building, industrial, residential, and commercial HVAC systems. TRNSYS is used globally, and its building model is compliant with the general technical requirements of ANSI/ASHRAE Standard 140-2001 and the European Directive on the Energy Performance of Buildings [12].
Many studies have used TRNSYS for the simulation of ground source HPs for greenhouse heating. In one study, Chargui et al. [13] evaluated a geothermal HP in the heating mode to provide heat energy to a greenhouse. In another study [14], the HP and the geometry and performance of a cooling tower system were investigated using the TRNSYS software. The system optimization results were validated by several theoretical and experimental studies. Chargui et al. [15] simulated a dual-source HP system for heating a single house. They evaluated the temperature and energy operation in winter using different operating conditions; the results indicated that the system provided acceptable results under all operating conditions. Safa et al. conducted two studies in 2015 [16,17] to investigate the performance of air source heat pump and ground source heat pump (GSHP) systems using TRNSYS software and evaluated the cooling and heating coefficient of performance (COP) of the system. The efficiencies of different components of the system were analyzed. Mehrpooya et al. 2015 [18] designed and optimized the application of a combined solar collector and geothermal heat-pump system in greenhouse farming. The study calculated the COP of the system and evaluated technical and economic factors. Ruiz-Calvo et al. [19] optimized the design and operation of the GSHP using TRNSYS software for the heating and cooling of buildings. The model was validated against experimental data; it accurately predicted the system behavior. Jonas et al. (2017) performed TRNSYS-based modeling and the simulation of a combined solar system and HP [20]. Park et al. [21] investigated the application of a solar thermal seasonal storage system in a greenhouse. The TRNSYS software was used to analyze the dynamic performance of the system. The simulation was performed by modeling a solar thermal seasonal storage system consisting of a borehole thermal energy storage system, solar collector, storage tank, heat exchanger, boiler, pump, and controller. The results of the study satisfied the heating energy demands of the proposed system. Lamrani et at. developed a TRNSYS model and investigated the performance of an indirect hybrid solar wood dryer. The results showed that the maximum discrepancy did not exceed 10% [22]. To solve the problem of high energy consumption in winter and summer, Yang et al. [23] recently presented a study on a groundwater source HP system for a plant factory that lacked an operation strategy. The study reported a significant reduction in the energy demand of the plant factory. TRNSYS is a flexible, component-based tool for the dynamic simulation of a system; each component is called a “Type” in TRNSYS. Bordignon et al. [24] recently presented a novel type of simulation for a reversible water-to-water HP. This type of system was used to simulate different configurations of the system under different weather conditions. The study highlighted the importance of integrated simulations when evaluating complex multi-energy systems.
TRNSYS has been used in many studies for greenhouse and energy system modeling. A number of our studies have used TRNSYS for greenhouse structural modeling. Rasheed et al. [6] used the TRNSYS software to study the effect of single-span greenhouse design parameters from the perspective of energy conservation. Furthermore, they identified passive energy-saving options of single-span greenhouses by evaluating different thermal screens and their control effect on the heat energy demand of the greenhouse using the same program [25]. Two of our studies [26,27] on multi-span greenhouse energy saving options were conducted using TRNSYS software, and the proposed model was validated. In a recent study [28], we proposed and validated an air-to-water heat pump (AWHP) model using TRNSYS in the heating mode under the climatic conditions of Deagu, South Korea. Statistical analyses of the validation results encouraged us to doubt the model. Many other studies have used TRNSYS to simulate different building and energy systems. The studies mentioned above represent a small number of studies demonstrating the use of TRNSYS for different types of heat-pump modeling. Studies on the use of HPs to fulfil the cooling energy demand of greenhouses are limited. Currently, the use of air source HPs is rapidly increasing because of their low cost and ease of installation. According to the best of our knowledge and the literature reviewed and cited, the studies conducted previously on this topic were from specific point of view, and research on the use of this particular air-to-water heat pump specifically for greenhouse cooling is lacking. The cooling energy demand of the greenhouse and the performance of the AWHP could be different under different climatic conditions. Ensuring the accurate performance of the system is generally a difficult task for any designer or researcher [29]. Therefore, there is a need to develop a combined simulation model of a greenhouse with an AWHP system considering all the physical parameters of the whole system in order to evaluate the system’s efficiency under specific weather conditions. In the previous section, an AWHP model was developed using the TRNSYS program, and the proposed model was validated using experimental data in the heating mode [28].
The objective of this study was to conduct a modeling-based energy performance assessment and validation of an AWHP system, in the cooling mode, integrated with a multi-span greenhouse. Furthermore, the feasibility of the use of the air-to-water heat pump to fulfil the cooling energy demand of the studied greenhouse was investigated. The modeling of the greenhouse could help to predict the total and maximum cooling energy demand, which could be used to determine the capacity of the heat pump system under local weather conditions. The ability of the model to predict the greenhouse cooling energy demand and supply energy was tested by comparing the predicted results with the results obtained experimentally. The components that were modeled included a fan coil unit (FCU), the storage tank (ST) to HP supply and the return water temperature, the ST temperature, the ST to greenhouse supply and the return temperature, the greenhouse internal air temperature, and the COP of the HP. In addition, we validated the quantitative performance and accuracy of the results statistically using the Nash–Sutcliffe efficiency (NSE) coefficient. Detailed information on each step was gathered in order to make the model convenient in terms of reuse, integration, extension, and compression. Researchers can use this model for dynamic thermal simulations in the context of specific greenhouse designs and control requirements and energy system selections and capacities according to local weather conditions and specific crop needs. This work will increase reliance on sustainable and renewable energy to ensure more stable, reliable, and resilient energy sources of greenhouse heating and cooling. Moreover, site-specific analysis under local weather conditions could help to increase the COP of the heat pump.

2. Materials and Methods

2.1. Description of Experimental Setup

This study was performed using an AWHP with a cooling capacity of 65 kW and a water ST with a capacity of 50 m3. The technical specifications of the equipment used in the AWHP are listed in Table 1. This setup was used to analyze the cooling performance of a small-sized three-span rectangular, Venlo-roofed, north-south (N-S) oriented greenhouse. The greenhouse roof was covered with horticultural glass (HG, 4 mm), a shading screen (commercial name—PH 66) was used under the roof, and the side walls were covered with polycarbonate (PC, 16 mm). Roof vents were employed for natural ventilation inside the greenhouse, with the opening and closing of the vents determined by an air temperature inside the greenhouse of 30 °C. The greenhouse was further divided into three equal parts to create different climatic conditions for different experiments; each part’s dimensions were 8 m × 16.3 m × 7.6 m, with a floor area of 130.4 m2. HG material of 4 mm was used for the divider. Each partition in the greenhouse featured two fan coil systems with a cooling capacity of 18 kW (Table 1). The total floor area cooled was 391.6 m2, with a total volume of 2362.8 m3. The cooling setpoint on each compartment was set at 25 °C. The deployment and retraction of the shading screen were determined by an outside solar radiation intensity of >0.5 kW·m−2. The greenhouse and the entire experimental setup were located at Kyungpook National University, Daegu, South Korea (latitude 35.53° N, longitude 128.36° E, elevation 48 m). Figure 1a–d show the experimental three-span greenhouse, water storage tank, AWHP, and FCU. The experiments were conducted from 1 June 2021 to 31 September 2021, during a typical summer (cooling period).
During the experiment, weather data inside and outside the greenhouse were recorded from 1 June to 31 September 2021 during summer period in Daegu, South Korea. The data was acquired by installing a sensor network at the site. The data was used as an input to the developed BES model of a greenhouse with an integrated AWHP. The data recorded inside the greenhouse were the air temperature and relative humidity, which were recorded using MTV Active and Ridder sensors. Figure 2 shows the mean outside air temperature and solar radiation for reference purposes. The solar radiation data were measured both inside and outside the greenhouse using a horizontally placed SR05-D2A2-TMBL, Hukseflux sensor. The wind speed and direction were measured outside the greenhouse at a height of 10 m with a Clima Sensor US, Thies Clima. Ambient pressure data were obtained from the Korean Meteorological Administration (KMA). Table 2 lists the characteristics and sensitivities of all the recorded weather variables obtained from the catalog. The data obtained from the sensors were at a 10-min interval. However, the data was interpolated to a 1-min interval to make it comparable with the simulation results.
The actual experimental setup consisted of three AWHPs; however, in this study, only one AWHP was in operation, as it met the energy demand of the FCU. Other HPs were installed at the site for the future extension of the greenhouse. The water ST stored cold water from the AWHP and supplied it to the greenhouse when cooling to the setpoint internal air temperature. We monitored the water flow rate and temperature at various locations, namely the ST to HP supply and the return temperature and flow rate and the ST to greenhouse supply and the return temperature and flow rate (Figure 3). We acquired water temperature data using a HortiMax Omni Transducer, Ridder sensor. The FS-WLH 40 and FLSTRONIC sensors (Table 2) were used to measure the water flow rate. The cooling energy supply from the AWHP to the water storage tank and from the water ST to the greenhouse was calculated using Equation (1).
Q = × cp   ×   Δ T
where Q is the cooling capacity of the AWHP (kW), is the mass flow of water (kg·s−1), cp is the specific heat capacity of water (kW·kg−1·°C−1), and ΔT is the temperature difference between the supply and return temperatures (°C). The COP of the HP was calculated using Equation (2):
COP = Q P HP
where PHP is the power usage of the AWHP (kW).

2.2. Modeling and Simulation

The modeling was divided into two steps. In the first step, we developed a multi-span greenhouse model and a HP model including other components, an FCU, a water ST, and pumps. Figure 4 shows the simulation studio (the main interface of the TRNSYS program) connecting all the components of the greenhouse model. The modeling of the greenhouse considered all the physical aspects and control settings of the experimental greenhouse (Section 2.1), including its design, covering, and screen materials and its thermal screen, ventilation, day/night and seasonal internal temperature controls, while simultaneously considering different thermal phenomena, i.e., the three-dimensional shortwave and longwave radiative exchange, airflow exchanges, and the ground and convective heat transfer coefficients.
Each component has a special name in TYRNSYS called a “Type.” The components used in the BES modeling of the multi-span greenhouse (Figure 4) and their descriptions are as follows: The greenhouse description is passed to the component using a “.idf” file prepared via the 3D modeling of the greenhouse using Transys3d (an add-on of Google SketchUpTM) program and imported into TRNSBuild (a building interface of the TRNSYS program, TYPE 56). The greenhouse covering and screen material properties were input into the Lawrence Berkeley National Laboratory Windows 7.7 program, creating the DOE-2 file of the materials, which was readable by TRNSBuild. Table 3 shows the physical, thermal, radiometric, and air permeability properties of the covering and screen materials, while Table 4 shows the steel (greenhouse structure pipes) and ground properties used in the simulation. The covering material properties were chosen from a previous study [30]. Meanwhile, the shading screen properties were experimentally measured, the thermal conductivity was measured using a thermal conductivity meter, the radiometric properties were measured using the energy balance method, and the air flow was measured with a laboratory-designed air suction device. The details of these measuring procedures were presented in a recent study [31]. TRNSBuild managed the thermal model of the building, and to account for natural ventilation into the greenhouse, TRNSYFLOW was used. TRNSFLOW (a ventilation module of the TRNSYS program) coupled the airflow network with the thermal model to simulate the effect of the natural ventilation that is handled in “TYPE 56.” This component was used to simulate the thermal behavior of the greenhouse with natural ventilation. All heat transfer calculations were performed in this component. The thermal conductivity of the materials was used to calculate the thermal conduction of the surface. Equations (3) and (4) are the governing equations for calculating the convective and radiative heat transfers for the greenhouse surfaces.
Q Conv =   h conv   ( T o T i )
Q rad =   σ   ε 0   ( T o 4   T sky   4 )
where Q Conv is the convective heat transfer (kJ·h−1·m−2·k−1), h conv is the convective heat transfer coefficient (kJ·h−1·m−2·k−1), T o is the outside surface temperature (°C), T i is the inside surface temperature (°C), Q r is the radiative heat flux to the surface (kJ·h−1·m−2·k−1), σ is the Stephen–Boltzmann constant (W·m−2·k−1), ε 0 is the long-wave emissivity (-), and T sky is the sky temperature (°C).
The airflow caused by natural ventilation inside the greenhouse was estimated using TRNFLOW in TRNSBuild. There are different options for creating an airflow network in TRNFLOW, for example, through large openings, creaks, fans, and straight ducts. We used a large opening window as it was the option that was best suited to the context of a greenhouse. Equation (5) provides the equation to calculate the airflow for a large opening window:
1 > 2 = C d 0 H 2 ρ ( z ) f 1 > 2 ( z ) · ( z   ·   tan α ) 2   ·   W 2 ( z   ·   tan α ) 2 +   W 2 · dz  
where is the air mass flow rate (kg·h−1), 1−>2 is the flow direction from one air node to another (-), C d is the discharge coefficient (-), H is the total height of the window (m), ρ (z) is the air density (kg·m−3) at height z, z is the height of the opening (m), α is the angle of the window opening (o), W is the width of the rectangular opening (m), f (z) is the pressure difference at height z (pa).
In the simulation studio, the weather data processors (Type 9) were linked to Type 56 to simulate the effect of an ambient environment using the user-provided weather data file (the field-measured weather data from 1 June to 31 September 2021). Type 33 (a psychrometric chart) was used to calculate the dew-point temperature using the dry bulk temperature and humidity ratio. Type 165 (a controller) was used to control the natural ventilation of the multi-span greenhouse, i.e., the opening and closing of the roof. Type 65 (a result plotter) was used to plot and compare results. Type 25 (a printer) was used to obtain the results for the user-provided external files. An equation editor was used to introduce different user-defined equations. Type 518 (monthly forcing functions) is a scheduler that was used to input screen opening and closing schedules, which change monthly. Type 16 (a solar radiation processor) was used to calculate the total, beam, reflected, and diffuse radiation on all the tilted greenhouse surfaces. Solar radiation data are typically estimated for a horizontal surface. This component interpolates the data related to the position of the sun to estimate the beam, reflected, and diffuse radiation on horizontal and tilted surfaces when only the total horizontal solar radiation is input. The solar radiation processor estimates the diffuse radiation fraction on the horizontal surface as a function of the clearness index, solar altitude angle, relative humidity, and ambient temperature. Equation (6) expresses the relationship [32]:
I d I = 0.426 kt 0.256 sin ( α s ) + 0.00349 T amb   + 0.0734 ( rh 100 )  
The horizontal beam radiation is calculated by the difference between the total radiation and the diffuse component provided by Equation (7).
I b = I I d
where I is the total radiation of the horizontal surface (kJ·h−1·m−2), I d is the diffuse radiation of the horizontal surface (kJ·h−1·m−2), kt is the clearness index, α s is the solar altitude angle (o), T amb is the ambient temperature (°C), and rh is relative humidity (%).
The model calculates the total radiation on a tilted surface using Equation (8) by estimating and adding the beam, diffuse, and reflected radiation on the tilted surface (Equation (9)).
I T = I bT + I gT   + I dT  
I T = I b · COS θ COS θ z + I · 0.5 ( 1 cos β )   ρ g + I d   ·   0.5 ( 1 + cos β )
where I T is the total radiation on the tilted surface (kJ·h−1·m−2), I bT is the beam radiation of the tilted surface (kJ·h−1·m−2), I gT   is the ground-reflected radiation on the tilted surface (kJ·h−1·m−2), I dT   is the diffuse radiation of the tilted surface (kJ·h−1·m−2), θ is the incident angle of the beam radiation (o), θ z is the solar zenith angle (o), β is the slope of the surface(o), and ρ g is the reflectance of the ground (-).
Type 69 (the sky temperature) was used to calculate the sky temperature using the ambient temperature, dew point temperature, beam, and diffuse radiation on a horizontal surface. These parameters were further used by Type 56 to estimate the longwave radiation exchange from external surfaces. The mathematical reference for this component is shown in Equation (10):
T sky =   T amb   ( ε 0 + 0.8 ( 1 ε 0 )   C cover   ) 0.25
where T sky is the sky temperature (°C), T amb is the ambient temperature (°C), ε 0 is the emittance of the clear sky (−), C cover is the cloudiness factor of the sky. The cloudiness factor of the sky is calculated internally as a ratio of diffuse to global radiation, where 0 indicates a clear sky and 1 indicates a fully cloud-covered sky.
Figure 5 shows a simulation studio picture of the AWHP system and the connections between components. Type 941, from the TRNSYS Tess library, was used to model the AWHP. This model works on the principle of the water stream rejecting energy in the cooling mode and absorbing energy in the heating mode. The model is based on user-defined performance data files containing catalog data for the water capacity and power for cooling/heating. The cooling performance data file (Table A1) and the data sheet provided by the manufacturer of the HP in the cooling mode are listed in Table A2 of Appendix A. The model uses the water temperature, flow rate, relative humidity, and entering air temperature at the inlet as inputs to calculate the water temperature at the outlet. The component reads the temperatures of the water and air entering the system and interpolates these with the cooling/heating performance data. The HP is controlled using an on/off signal. The capacity and power are used as functions for the entering water temperature. Equation (11) provides the mathematical reference for the calculation.
T water ,   out = T water ,   in   + q · water water   Cp water  
where T water ,   out is the temperature of the HP’s water output (°C), T water ,   in   is the temperature of the HP’s water inlet (°C), q · water is the energy drawn by the water (kJ·h−1), water   is the water flowrate (kg·h−1), and Cp water is the specific heat of the water (kJ·kg−1·k−1).
Table 1 lists the rated heating capacity and power consumption of the HP. Type 4 (a water ST) was used to model a stratified tank with variable inlet positions. Type 114 (a circulation pump) delivers water to the HP at a constant speed. From the ST to the greenhouse, cold water was provided using a Type 3 (a variable speed circulation pump) with a Type 22 proportional integral (PI) derivative controller to control the mass flow rate with feedback control. Type 108 (thermostat), a five-stage thermostat with an on/off control function, was used to control the circulation pump and FCU using the greenhouse’s internal temperature setpoint. Type 709 (a pipe) is used to deliver water from the ST to the greenhouse. Energy loss from the pipes is considered in the model. Type 928 (a fan coil unit) was used to simulate the FCU to exchange the cooling energy inside the greenhouse. This model uses the stream of the air passing across the fan and the coil containing either hot or cold water. The model relies on the energy exchange between the air stream and water in the coil. It uses the water temperature, water flow rate, and return air temperature as inputs and outputs the water temperature and flowrate after energy exchange, outlet air temperature, and cooling/heating transfer to air. If the coil water temperature is less than the temperature of the air exiting the fan, the system will operate in the cooling mode and vice versa in the heating mode. This type uses many equations to calculate the functions detailed in the manual, and the governing equations are used to obtain the desired output. The water flow rate was the same as the inlet flow rate, and the water outlet temperature was calculated using Equation (12):
T water ,   out = T water ,   in   + T water ,   in   +   T air ,   fan Cp water
where T air ,   fan is the temperature of air entering the fan (°C).
The output of the model is the fan heat loss to the surroundings; therefore, the enthalpy of the air exiting the fan is computed using Equation (13):
h air , fan = h air ,   mix   + q air ,   fan   air ,   fan
where h air , fan is the enthalpy of the exiting air (kJ·kg−1), h air ,   mix is the enthalpy of the air mixing (kJ·kg−1), q air ,   fan   is the energy drawn by the fan, which is the output of the model, indicating the fan energy loss to the surrounding (kJ·h−1), air ,   fan is the mass flowrate of air leaving the fan and is equal to the mass flowrate of air entering the fan (kg·h−1)

2.3. Statistical Analysis of BES Model

Statistical analyses were performed to predict the performance of the BES model using the NSE coefficient and to compare the experimentally measured data with the BES model’s output. This coefficient quantitatively describes the accuracy of the model results, indicating how well the plot of the observed versus simulated data fits the 1:1. Its value ranges from −∞ to 1, and the closer the values are to 1, then the better the predictive power of the model. The NSE is mathematically expressed using Equation (3). The performance rating for NSE values is NSE > 0.9 = very good, 0.8–0.9 = good, 0.65–0.80 = acceptable, and <0.6 = unsatisfactory [33]. The mathematical description is shown in Equation (14):
NSE = 1 [ i = 0 n ( T i exp   T i sim   ) 2 i = 0 n ( T i exp   T i mean   ) 2 ]
where T i exp is the experimental value, T i sim is the simulated value, T i mean is the mean of the experimental values, and n is the total number of observations.

3. Results and Discussion

The proposed AWHP system integrated with the multi-span greenhouse BES model was validated by comparing the computed supply cooling energy, internal air temperature of the greenhouse, HP output temperature, and ST temperature with those obtained experimentally under the same physical and operating conditions. Validation analyses were conducted during the summer (1 June to 31 September 2021) in Deagu, South Korea.
Figure 6 shows the results for the greenhouse internal temperature under three different conditions: first, with natural ventilation and a shading screen, second, without natural ventilation (fully closed greenhouse), and third, using a reference temperature setpoint for cooling. The results show that the inside temperature of the greenhouse is greater than the reference temperature setpoint value during this period; therefore, cooling is required to control the inside temperature of the greenhouse. Moreover, the results revealed that from mid-Jul to mid-August, both daytime and nighttime cooling is required because of the high greenhouse temperature. The cooling energy demand of the greenhouse was determined using the proposed greenhouse model (Figure 4) at 25 °C (cooling setpoint at 25 °C). We determined the monthly maximum value of the cooling energy demand for the same period. Figure 7 shows the monthly cooling energy demand using the recorded ambient weather data (detailed in Section 2.1). To evaluate the performance of the heating system, it is important to determine the maximum monthly cooling energy demand of the greenhouse. The results showed that at the end of July, for the 391.2 m2 of greenhouse, a maximum cooling energy of 168.6 kW and 0.43 kW·m−2 (Table 5) is required when the outside solar radiation level is as high as 1.01 kW·m−2. The maximum values obtained determine the capacity of the HP system. Moreover, from mid-Jul to mid-August, both day-and nighttime cooling are required to meet the required temperature conditions inside the greenhouse. The heating pump system has to operate continuously (24 h) to meet the energy requirement.
Figure 8a–d presents the results for the cooling energy supply from the ST to the greenhouse with the ambient solar radiation for the analyzed months, i.e., June, July, August, and September, respectively. The results reveal a consistent correlation between the experimental and simulation results. The NSE values of 0.87, 0.87, 0.85, and 0.86, presented in Figure 9a–d, confirmed the accuracy of the simulation model in predicting that the cooling energy supply was sufficient for June, July, August, and September, respectively. The results show that the maximum cooling energy provided to the greenhouse was 0.23 kW·m−2, as the maximum cooling capacity of the two FCUs in each compartment were 36 kW, which was 0.27 kW·m−2 per unit area of greenhouse. The HP and water ST capacities were much higher, and could fulfil the cooling energy demand of the greenhouse, but the installed FCU had a lower capacity. Both the HP and FCU capacities, wherein the maximum cooling capacities are 65 kW and 36 kW, respectively, are shown in Figure 10, confirming the above statement.
Figure 11 shows the greenhouse internal temperatures obtained via the simulation as well as experimentally, with the ambient temperature for the period 1 June to 23 September 2021. The experimental data from 23–28 July 2021 and the last week of September were missing; hence, the results for up until 23 September 2021 are presented. The simulated greenhouse internal temperature results correlated consistently with the experimentally measured temperatures. The NSE values shown in Figure 12 for each month were 0.81, 0.67, 0.82, and 0.76, respectively. The results are acceptable for all months except July. The value in July (0.67) was slightly lower because some experimental data were missed by the sensors. The overall performance analysis results show that the proposed BES model is sufficiently accurate when predicting the internal air temperature of a multi-span greenhouse. The monthly maximum temperature in the greenhouse using the supplied energy shown in Figure 8 was 33 °C, whereas the greenhouse cooling setpoint was 25 °C. Therefore, the FCU capacity must be increased to obtain the desired temperature inside the greenhouse.
Figure 13 depicts a comparison of the model and field results regarding the monthly cooling load vs. the monthly ambient solar radiation and air temperature. These comparisons were made to determine the relationship between the cooling load with ambient solar radiation and the air temperature by following the approach proposed by Safa et al. [34,35]. The results of linear regression analysis revealed that the cooling load is more dependent on ambient solar radiation than the ambient temperature, as, according to linear regression analysis (R2) of the solar radiation, a value of 0.83 correlates well compering with 0.39, a R2 value of the ambient air temperature. In addition, Figure 13a,b shows that the simulated R2 values of 0.83 and 0.39 are more accurate than the equivalent experimental values, 0.79 and 0.35, for both analyses, respectively.
After the successful validation of the cooling energy supply and greenhouse internal temperature, experiments were conducted concerning the HP output water temperature. Figure 14a shows a comparison of the between the experimental and simulated results for June 2021 concerning the outlet water temperature of the HP. The normal operation of the HP in the cooling mode was repeated daily; therefore, only one month of analysis results are presented here. The results show that the HP produces water with temperatures between 12 and 7 °C. Figure 14b shows a good 1:1 fit line between the experimental and simulation results and an NSE value of 0.93, indicating an acceptable prediction by the HP model.
Figure 15 shows the daily average COPs values between the experimental and model results. The analysis was carried out for the period 1 July to 31 August 2021. The average seasonal value of the COP over the complete analysis period was 2.9. The maximum COP deviation between the experimental and simulated results was 0.8. The simulated value was smooth over the analysis time, while a few outliers were observed in the experimentally calculated values owing to the sensitivity of the water sensor to the sudden change in the water temperature. The overall validation results indicate that the results are within the manufacturer’s data range.
We further calculated the electric consumption of the HP over every hour of its operation. Figure 16a presents the electric consumption of the HP in the cooling mode with an ambient temperature for two days. The results are presented for the period when the HP was operated for 24 h. A short time period was selected, as the HP function did not change throughout the analysis period. The results showed that at peak operating conditions, the maximum power consumption of the HP was approximately 22 KW during the day, when maximum cooling was required, and 10 kW at night, when less cooling was required. The electricity consumption showed a linear trend with the ambient air temperature. In Figure 16b, which depicts the linear relationship between both the parameters of the HP, an R2 value of 0.90 confirmed the trend.
Figure 17 shows the simulation model output for the temperature of the water supply and its return to the ST from the greenhouse and HP. The results are shown for the period 1–10 August 2021. A longer duration was not required as the operation is repetitive. The results indicate that the difference between the greenhouse supply and return temperatures was 6 °C, with a maximum flow rate of 4500 Lhr−1, while the HP supply and return temperatures were less than 2 °C, and the flow rate of water was 42,000 Lhr−1. The results show that the proposed model can simulate the entire system and estimate the energy supply.
Considering the outcomes of this study, the proposed model has the potential to evaluate AWHP systems along with water storage tanks integrated with multi-span greenhouses. This work promotes and advances the development of work towards the use of renewable energy sources in greenhouse farming and maximizes the related economic benefit by increasing the profitability of greenhouse farming. In a future study, we will apply the model under different weather conditions to establish a feasible way of increasing the COP to achieve sustainability in greenhouse farming.

4. Conclusions

In this study, an experimentally validated BES model of an AWHP and a water ST was proposed to satisfy the cooling energy requirements of a three-span greenhouse. The proposed model was validated by comparing its computational results with the experimental results. Furthermore, the performance of the BES model was confirmed using the NSE coefficient. The results of this study are detailed below.
  • The validation results for the cooling energy supplied to the greenhouse showed NES values of 0.87, 0.87, 0.85, and 0.86, for June, July, August, and September, respectively.
  • The validation results for the air temperature inside the greenhouse showed NES values of 0.81, 0.67, 0.82, and 0.76, for June, July, August, and September, respectively.
  • The observed R2 values of the experimental and simulated cooling loads compared with solar radiation were 0.83 and 79, respectively.
  • The observed R2 values of the experimental and simulated cooling loads compared with the outside air temperature were 0.39 and 35, respectively.
  • The R2 results demonstrate that the cooling load is more dependent on solar radiation rather than the outside air temperature. Moreover, the R2 value of the simulated data was more accurate than that of the experimental data, which could be due to a prediction error relating to the water temperature and flowrate sensors and the high predictive power of the simulation model.
  • A comparison of the results for the HP water output temperature showed an NSE value of 0.93, which demonstrates the high accuracy of the simulation model.
  • An R2 value of 0.90 demonstrated the high dependency of the electric power used by the HP on the ambient air temperature. With an increase in ambient temperature, the electric power consumed by the HP increased.
  • The maximum cooling energy demand for the greenhouse at an internal air temperature setpoint of 25 °C was observed to be 0.4 kW·m−2. This result could be due to the lower cooling capacity of the FCU; the maximum cooling energy provided to the greenhouse was 0.2 kW·m−2.
  • The desired control over the temperature inside the greenhouse was not achieved in the cooling mode because the FCU capacity was not sufficient to fulfil the high cooling energy demand in Daegu, South Korea (latitude 35.53° N, longitude 128.36° E, elevation 48 m).
  • The results concerning the power of the HP and FCU revealed that the HP has the potential to supply more energy. To utilize the HP’s energy fully, the number of FCUs or the capacity of the FCU should be increased.
  • The results for the daily average COP value of the HP during the extreme hot months of July and August showed a good correlation, with an overall average COP of 2.9.
  • A data sheet used to calculate the cooling capacity is provided for the HP model (PSET-C60W-MIDEA). In addition, data file for the cooling performance of the AWHP, which is a necessary input to the simulation model, is also provided.
Overall, the simulation results correlate well with the experimental results. The high NSE values reveal the high predictive power of the model. The proposed model can be used for optimizing the control strategies and capacities of the equipment (e.g., the HP, FCU, and area of the greenhouse) so that the overall system can be improved. Detailed information on each step has been provided to enable engineers, researchers, and consultants to adapt the model for their specific needs. The prediction of the maximum cooling energy demand under local weather conditions will help individuals to decide on the capacities of the system’s components, including the heat pump, fan coil units, water storage tank, and circulation pump. Moreover, the AWHP simulation model can aid in the search for a feasible way to increase the COP.

Author Contributions

Conceptualization, A.R. and H.W.L.; methodology, A.R.; software, A.R.; validation, A.R. and H.T.K.; formal analysis, A.R.; investigation, A.R.; resources, H.W.L. and H.T.K.; data curation, A.R. and H.T.K.; writing—original draft preparation, A.R.; writing—review and editing, A.R., H.T.K. and H.W.L.; visualization, H.T.K. and H.W.L.; supervision, H.W.L.; project administration, H.W.L.; funding acquisition, H.W.L. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported by the Korea Institute of Planning and Evaluation for Technology in Food, Agriculture, Forestry (IPET) through the Agriculture, Food, and Rural Affairs Convergence Technologies Program for Educating Creative Global Leader, funded by the Ministry of Agriculture, Food, and Rural Affairs (MAFRA) (717001-7). This work was supported by the Korea Institute of Planning and Evaluation for Technology in Food, Agriculture, and Forestry (IPET) through the Agricultural Energy Self-Sufficient Industrial Model Development Program, funded by the Ministry of Agriculture, Food, and Rural Affairs (MAFRA) (120096-3). This research was supported by the Basic Science Research Program through the National Research Foundation of Korea (NRF), funded by the Ministry of Education (NRF-2019R1I1A3A01051739).

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

Symbols
QCooling capacity of the AWHP (kW)
Mass flow rate of air (kg·h−1)
cpSpecific heat capacity of water (kW·kg−1·°C−1),
PHPPower usage of AWHP ((kW)
Q Conv Convective heat transfer (kJ·h−1·m−2·k−1)
h conv Convective heat transfer coefficient (kJ·h−1·m−2·k−1)
T o Outside surface temperature (°C)
T i Inside surface temperature (°C)
Q r Radiative heat flux to the surface (kJ·h−1·m−2·k−1)
T sky Sky temperature (°C)
C d Discharge coefficient (-)
HTotal height of window (m)
z Height of window opening (m)
WWidth of rectangular opening (m),
f(z)Pressure difference at height z (pa)
1−>2Flow direction from one air node to another (-)
ITotal radiation of horizontal surface (kJ·h−1·m−2)
I d Diffuse radiation of horizontal surface (kJ·h−1·m−2)
ktClearness index (-)
T amb Ambient temperature (°C)
rhRelative humidity (%)
I T Total radiation on tilted surface (kJ·h−1·m−2)
I bT Beam radiation on tilted surface (kJ·h−1·m−2)
I gT   Ground reflected radiation on tilted surface (kJ·h−1·m−2)
I dT   Diffuse radiation on tilted surface (kJ·h−1·m−2)
T sky Sky temperature (°C)
C cover Cloudiness factor of sky (-)
T water ,   out Temperature of HP water output (°C)
T water ,   in   Temperature of HP water input (°C)
q · water Energy drawn by water (kJ·h−1)
water   Water flowrate (kg·h−1)
12 Air mass flow rate from one zone to another (kg·h−1)
T air ,   fan Enthalpy of exiting air (kJ·kg−1)
h air ,   mix Enthalpy of air mixing (kJ·kg−1)
q air ,   fan   Energy drawn by fan (kJ·h−1)
air ,   fan Mass flowrate of air leaving the fan (kg·h−1)
Greek Symbols
σ Stephen–Boltzmann constant (W·m−2·k−1)
ε Long-wave emissivity (-)
ρ   ( z ) Air density at height z (kg·m−3)
α Angle of window opening (o)
α s Solar altitude angle (o)
θ Incident angle of beam radiation (o)
θ z Solar zenith angle (o)
β Slope of surface (o)
ρ g Ground reflectance (-)
ε 0 Emittance of clear sky (-)
Abbreviations
COPCoefficient of performance
NSENash–Sutcliffe efficiency
HPHeat pump
FCUFan coil unit
AWHPAir-to-water heat pump

Appendix A

Table A1 lists the cooling performance data file used as an input to the simulation. The data sheet provided by the manufacturer, including the testing conditions of the HP (in the cooling mode) is listed in Table A2.
Table A1. Cooling performance data file of AWHP.
Table A1. Cooling performance data file of AWHP.
101214161820T_water_in
212530354046T_air_in
1.120.881!Fraction capacity and power at T_air = 21deg. C and T_water_in = 10
1.0540.908!Fraction capacity and power at T_air = 25deg. C and T_water_in = 10
0.9940.936!Fraction capacity and power at T_air = 30deg. C and T_water_in = 10
0.940.965!Fraction capacity and power at T_air = 35deg. C and T_water_in = 10
0.8811.013!Fraction capacity and power at T_air = 40deg. C and T_water_in = 10
0.811.064!Fraction capacity and power at T_air = 46deg. C and T_water_in = 10
1.1980.913!Fraction capacity and power at T_air = 21deg. C and T_water_in = 12
1.1260.941!Fraction capacity and power at T_air = 25deg. C and T_water_in = 12
1.060.97!Fraction capacity and power at T_air = 30deg. C and T_water_in = 12
11!Fraction capacity and power at T_air = 35deg. C and T_water_in = 12
0.9391.05!Fraction capacity and power at T_air = 40deg. C and T_water_in = 12
0.8661.102!Fraction capacity and power at T_air = 46deg. C and T_water_in = 12
1.270.95!Fraction capacity and power at T_air = 21deg. C and T_water_in = 14
1.1910.978!Fraction capacity and power at T_air = 25deg. C and T_water_in = 14
1.1191.009!Fraction capacity and power at T_air = 30deg. C and T_water_in = 14
1.0541.04!Fraction capacity and power at T_air = 35deg. C and T_water_in = 14
0.9921.092!Fraction capacity and power at T_air = 40deg. C and T_water_in = 14
0.9161.146!Fraction capacity and power at T_air = 46deg. C and T_water_in = 14
1.3540.973!Fraction capacity and power at T_air = 21deg. C and T_water_in = 16
1.2681.003!Fraction capacity and power at T_air = 25deg. C and T_water_in = 16
1.191.034!Fraction capacity and power at T_air = 30deg. C and T_water_in = 16
1.1181.066!Fraction capacity and power at T_air = 35deg. C and T_water_in = 16
1.0541.12!Fraction capacity and power at T_air = 40deg. C and T_water_in = 16
0.9761.19!Fraction capacity and power at T_air = 46deg. C and T_water_in = 16
1.410.995!Fraction capacity and power at T_air = 21deg. C and T_water_in = 18
1.3181.026!Fraction capacity and power at T_air = 25deg. C and T_water_in = 18
1.2341.058!Fraction capacity and power at T_air = 30deg. C and T_water_in = 18
1.1581.09!Fraction capacity and power at T_air = 35deg. C and T_water_in = 18
1.0941.145!Fraction capacity and power at T_air = 40deg. C and T_water_in = 18
1.0151.202!Fraction capacity and power at T_air = 46deg. C and T_water_in = 18
1.4641.007!Fraction capacity and power at T_air = 21deg. C and T_water_in = 20
1.3661.038!Fraction capacity and power at T_air = 25deg. C and T_water_in = 20
1.2761.07!Fraction capacity and power at T_air = 30deg. C and T_water_in = 20
1.1951.103!Fraction capacity and power at T_air = 35deg. C and T_water_in = 20
1.1321.158!Fraction capacity and power at T_air = 40deg. C and T_water_in = 20
1.0521.216!Fraction capacity and power at T_air = 46deg. C and T_water_in = 20
Table A2. Data sheet of the AWHP operating in cooling mode.
Table A2. Data sheet of the AWHP operating in cooling mode.
Cold Water Outlet Temp.Ambient Temp °C
212530354046
CapacityPowerCapacityPowerCapacityPowerCapacityPowerCapacityPowerCapacityPower
°CkWkWkWkWkWkWkWkWkWkWkWkW
0572.7718.7668.5219.3464.6419.9461.1020.5557.2521.5852.6722.66
0675.2319.0570.7719.6466.7020.2562.9920.8759.0821.9254.4123.01
0777.8519.4473.1720.0468.9020.6665.0021.3061.0422.3756.2723.48
0880.2620.0275.3620.6470.9021.2866.8221.9462.8123.0457.9724.19
0982.5220.2277.4120.8472.7621.4968.5122.1564.4723.2659.5724.42
1085.6520.5280.2721.1675.3821.8170.9122.4866.8023.6161.7924.79
1188.0420.7282.4421.3677.3322.0272.6822.7168.5423.8463.4725.03
1290.0621.0384.2421.6878.9522.3574.1323.0469.9824.1964.8725.40
1391.6621.1985.6721.8580.2122.5375.2523.2271.1124.3865.9925.60
1493.9421.3487.7222.0082.0522.6876.9023.3872.7524.5567.5825.78
1595.1521.4588.7622.1182.9522.7977.6723.5073.5524.6768.4125.91
Capacity calculation standard for cooling: inlet/outlet water temperature: 12 °C/7 °C; ambient temperature: 35 °C. The grey box refers to nominal data.

References

  1. Jakhar, S.; Soni, M.; Gakkhar, N. Historical and recent development of concentrating photovoltaic cooling technologies. Renew. Sustain. Energy Rev. 2016, 60, 41–59. [Google Scholar] [CrossRef]
  2. Pandey, A.; Tyagi, V.; Jeyraj, A.; Selvaraj, L.; Rahim, N.; Tyagi, S. Recent advances in solar photovoltaic systems for emerging trends and advanced applications. Renew. Sustain. Energy Rev. 2016, 53, 859–884. [Google Scholar] [CrossRef]
  3. Arora, N.K.; Mishra, I. United nations sustainable development goals 2030 and environmental sustainability: Race against time. Environ. Sustain. 2019, 2, 339–342. [Google Scholar] [CrossRef] [Green Version]
  4. Gilbert, N. One-third of our greenhouse gas emissions come from agriculture. Nature 2012, 31, 10–12. [Google Scholar] [CrossRef]
  5. Rasheed, A.; Lee, J.W.; Lee, H.W. Evaluation of overall heat transfer coefficient of different greenhouse thermal screens using building energy simulation. Prot. Hortic. Plant Fact. 2018, 27, 294–301. [Google Scholar] [CrossRef]
  6. Rasheed, A.; Lee, J.; Lee, H. Development and optimization of a building energy simulation model to study the effect of greenhouse design parameters. Energies 2018, 11, 1–19. [Google Scholar] [CrossRef] [Green Version]
  7. Gorjian, S.; Ebadi, H.; Najafi, G.; Chandel, S.S.; Yildizhan, H. Recent advances in net-zero energy greenhouses and adapted thermal energy storage systems. Sustain. Energy Technol. Assess. 2021, 43, 100940. [Google Scholar] [CrossRef]
  8. Dongellini, M.; Morini, G.L. On-off cycling losses of reversible air-to-water heat pump systems as a function of the unit power modulation capacity. Energy Convers. Manag. 2019, 196, 966–978. [Google Scholar] [CrossRef]
  9. Benli, H.; Durmuş, A. Evaluation of ground-source heat pump combined latent heat storage system performance in greenhouse heating. Energy Build. 2009, 41, 220–228. [Google Scholar] [CrossRef]
  10. Sinha, S.; Chandel, S.S. Review of software tools for hybrid renewable energy systems. Renew. Sustain. Energy Rev. 2014, 32, 192–205. [Google Scholar] [CrossRef]
  11. Rasheed, A.; Lee, J.W.; Lee, H.W. A review of greenhouse energy management by using building energy simulation. Prot. Hortic. Plant Fact. 2015, 24, 317–325. [Google Scholar] [CrossRef]
  12. Klein, S.A. Trnsys, a Transient System Simulation Program; Solar Energy Laborataory, University of Wisconsin-Madison: Madison, WI, USA, 2017. [Google Scholar]
  13. Chargui, R.; Sammouda, H.; Farhat, A. Geothermal heat pump in heating mode: Modeling and simulation on trnsys. Int. J. Refrig. 2012, 35, 1824–1832. [Google Scholar] [CrossRef]
  14. Chargui, R.; Sammouda, H.; Farhat, A. Numerical simulation of a cooling tower coupled with heat pump system associated with single house using trnsys. Energy Convers. Manag. 2013, 75, 105–117. [Google Scholar] [CrossRef]
  15. Chargui, R.; Sammouda, H. Modeling of a residential house coupled with a dual source heat pump using trnsys software. Energy Convers. Manag. 2014, 81, 384–399. [Google Scholar] [CrossRef]
  16. Safa, A.A.; Fung, A.S.; Kumar, R. Performance of two-stage variable capacity air source heat pump: Field performance results and trnsys simulation. Energy Build. 2015, 94, 80–90. [Google Scholar] [CrossRef]
  17. Safa, A.A.; Fung, A.S.; Kumar, R. Heating and cooling performance characterisation of ground source heat pump system by testing and trnsys simulation. Renew. Energy 2015, 83, 565–575. [Google Scholar] [CrossRef]
  18. Mehrpooya, M.; Hemmatabady, H.; Ahmadi, M.H. Optimization of performance of combined solar collector-geothermal heat pump systems to supply thermal load needed for heating greenhouses. Energy Convers. Manag. 2015, 97, 382–392. [Google Scholar] [CrossRef]
  19. Ruiz-Calvo, F.; Montagud, C.; Cazorla-Marín, A.; Corberán, J.M. Development and experimental validation of a trnsys dynamic tool for design and energy optimization of ground source heat pump systems. Energies 2017, 10, 1510. [Google Scholar] [CrossRef] [Green Version]
  20. Jonas, D.; Theis, D.; Felgner, F.; Frey, G. A trnsys-based simulation framework for the analysis of solar thermal and heat pump systems. Appl. Sol. Energy 2017, 53, 126–137. [Google Scholar] [CrossRef]
  21. Park, S.-M.; Seo, T.-B. A study on performance of seasonal borehole thermal energy storage system using trnsys. J. Korean Sol. Energy Soc. 2018, 38, 37–47. [Google Scholar] [CrossRef]
  22. Lamrani, B.; Khouya, A.; Draoui, A. Energy and environmental analysis of an indirect hybrid solar dryer of wood using trnsys software. Sol. Energy 2019, 183, 132–145. [Google Scholar] [CrossRef]
  23. Yang, G.; Shi, H.; Xu, D.; Shen, Z.; Zhang, Z.; Shen, H.; Wang, Z. Energy consumption analysis of a ground water-source heat pump for the plant factory based on trnsys simulation. EDP Sci. 2021, 267, 01047. [Google Scholar] [CrossRef]
  24. Bordignon, S.; Emmi, G.; Zarrella, A.; De Carli, M. Energy analysis of different configurations for a reversible ground source heat pump using a new flexible trnsys type. Appl. Therm. Eng. 2021, 197, 117413. [Google Scholar] [CrossRef]
  25. Rasheed, A.; Na, W.H.; Lee, J.W.; Kim, H.T.; Lee, H.W. Optimization of greenhouse thermal screens for maximized energy conservation. Energies 2019, 12, 3592. [Google Scholar] [CrossRef] [Green Version]
  26. Rasheed, A.; Kwak, C.S.; Na, W.H.; Lee, J.W.; Kim, H.T.; Lee, H.W. Development of a building energy simulation model for control of multi-span greenhouse microclimate. Agronomy 2020, 10, 1236. [Google Scholar] [CrossRef]
  27. Rasheed, A.; Kwak, C.S.; Kim, H.T.; Lee, H.W. Building energy an simulation model for analyzing energy saving options of multi-span greenhouses. Appl. Sci. 2020, 10, 6884. [Google Scholar] [CrossRef]
  28. Rasheed, A.; Na, W.H.; Lee, J.W.; Kim, H.T.; Lee, H.W. Development and validation of air-to-water heat pump model for greenhouse heating. Energies 2021, 14, 4714. [Google Scholar] [CrossRef]
  29. Nemś, A.; Nemś, M.; Świder, K. Analysis of the possibilities of using a heat pump for greenhouse heating in polish climatic conditions—A case study. Sustainability 2018, 10, 3483. [Google Scholar] [CrossRef]
  30. Valera, M.D.; Molina, A.F.; Alvarez, M.A. Protocolo De Auditoría Energética En Invernaderos. Auditoría Energética De Un Invernadero Para Cultivo De Flor Cortada En Mendigorría; Instituto para la diversificacion y ahorro de la energia: Madrid, Spain, 2008. [Google Scholar]
  31. Rabiu, A.; Na, W.-H.; Akpenpuun, T.D.; Rasheed, A.; Adesanya, M.A.; Ogunlowo, Q.O.; Kim, H.T.; Lee, H.-W. Determination of overall heat transfer coefficient for greenhouse energy-saving screen using trnsys and hotbox. Biosyst. Eng. 2022, 217, 83–101. [Google Scholar] [CrossRef]
  32. Reindl, D.T.; Beckman, W.A.; Duffie, J.A. Diffuse fraction correlations. Sol. Energy 1990, 45, 1–7. [Google Scholar] [CrossRef]
  33. Ritter, A.; Munoz-Carpena, R. Performance evaluation of hydrological models: Statistical significance for reducing subjectivity in goodness-of-fit assessments. J. Hydrol. 2013, 480, 33–45. [Google Scholar] [CrossRef]
  34. Safa, A.A.; Fung, A.S.; Kumar, R. Comparative thermal performances of a ground source heat pump and a variable capacity air source heat pump systems for sustainable houses. Appl. Therm. Eng. 2015, 81, 279–287. [Google Scholar] [CrossRef]
  35. Le, K.X.; Huang, M.J.; Shah, N.N.; Wilson, C.; Artain, P.M.; Byrne, R.; Hewitt, N.J.J.A.E. Techno-economic assessment of cascade air-to-water heat pump retrofitted into residential buildings using experimentally validated simulations. Appl. Energy 2019, 250, 633–652. [Google Scholar] [CrossRef]
Figure 1. Field picture of: (a) Experimental greenhouse; (b) water ST; (c) AWHP; (d) FCU at Daegu (latitude 35.53° N, longitude 128.36° E).
Figure 1. Field picture of: (a) Experimental greenhouse; (b) water ST; (c) AWHP; (d) FCU at Daegu (latitude 35.53° N, longitude 128.36° E).
Agronomy 12 01374 g001
Figure 2. Ambient solar radiation and air temperature.
Figure 2. Ambient solar radiation and air temperature.
Agronomy 12 01374 g002
Figure 3. Schematic diagram of the AWHP and the location of the sensors.
Figure 3. Schematic diagram of the AWHP and the location of the sensors.
Agronomy 12 01374 g003
Figure 4. TRNSYS simulation studio showing model components: Yellow box: greenhouse 3D model (TRNSBuild), blue box: solar radiation processor, red box: HP model macro.
Figure 4. TRNSYS simulation studio showing model components: Yellow box: greenhouse 3D model (TRNSBuild), blue box: solar radiation processor, red box: HP model macro.
Agronomy 12 01374 g004
Figure 5. TRNSYS simulation studio showing model components; Yellow box: FCU, green box: ST, black box: HP, red box: greenhouse model macro.
Figure 5. TRNSYS simulation studio showing model components; Yellow box: FCU, green box: ST, black box: HP, red box: greenhouse model macro.
Agronomy 12 01374 g005
Figure 6. Greenhouse internal temperature: (Temp 1) with natural ventilation and shading; (Temp 2) fully closed greenhouse without natural ventilation; (Temp 3) reference temperature for cooling.
Figure 6. Greenhouse internal temperature: (Temp 1) with natural ventilation and shading; (Temp 2) fully closed greenhouse without natural ventilation; (Temp 3) reference temperature for cooling.
Agronomy 12 01374 g006
Figure 7. Greenhouse cooling energy demand at a 25 °C temperature setpoint along with the ambient solar radiation.
Figure 7. Greenhouse cooling energy demand at a 25 °C temperature setpoint along with the ambient solar radiation.
Agronomy 12 01374 g007
Figure 8. Experimental vs. simulated cooling energy supply to the greenhouse: (a) June; (b) July; (c) August; (d) September.
Figure 8. Experimental vs. simulated cooling energy supply to the greenhouse: (a) June; (b) July; (c) August; (d) September.
Agronomy 12 01374 g008
Figure 9. Statistical analysis of measured vs. computed cooling loads of the greenhouse for the months (a) June, (b) July, (c) August, and (d) September.
Figure 9. Statistical analysis of measured vs. computed cooling loads of the greenhouse for the months (a) June, (b) July, (c) August, and (d) September.
Agronomy 12 01374 g009
Figure 10. HP and FCU cooling capacity.
Figure 10. HP and FCU cooling capacity.
Agronomy 12 01374 g010
Figure 11. Monthly measured vs. computed greenhouse air temperature for the months (a) June, (b) July, (c) August, and (d) September.
Figure 11. Monthly measured vs. computed greenhouse air temperature for the months (a) June, (b) July, (c) August, and (d) September.
Agronomy 12 01374 g011
Figure 12. Statistical analysis of measured vs. computed greenhouse air temperature for the months (a) June, (b) July, (c) August, and (d) September.
Figure 12. Statistical analysis of measured vs. computed greenhouse air temperature for the months (a) June, (b) July, (c) August, and (d) September.
Agronomy 12 01374 g012
Figure 13. Statistical analyses of monthly simulated and experimental cooling load vs. (a) monthly solar radiation and (b) monthly ambient temperature.
Figure 13. Statistical analyses of monthly simulated and experimental cooling load vs. (a) monthly solar radiation and (b) monthly ambient temperature.
Agronomy 12 01374 g013
Figure 14. (a) HP output water temperature; (b) statistical analysis of HP output water temperature.
Figure 14. (a) HP output water temperature; (b) statistical analysis of HP output water temperature.
Agronomy 12 01374 g014
Figure 15. Daily average COP value for the period July–August 2021.
Figure 15. Daily average COP value for the period July–August 2021.
Agronomy 12 01374 g015
Figure 16. (a) HP electric power consumption against outside air temperature; (b) statistical analysis of HP electric power consumption against outside air temperature.
Figure 16. (a) HP electric power consumption against outside air temperature; (b) statistical analysis of HP electric power consumption against outside air temperature.
Agronomy 12 01374 g016
Figure 17. Comparison of the output water temperatures of the simulation model.
Figure 17. Comparison of the output water temperatures of the simulation model.
Agronomy 12 01374 g017
Table 1. Technical specification of the AWHP system.
Table 1. Technical specification of the AWHP system.
ComponentPropertiesSpecification
Heat pumpModelPSET-C60W (MIDEA)
Cooling capacity65 kW
Power consumption21.9
Voltage380 V–415 V, 3-phase, 60 Hz
RefrigerantR-410a
Water storage tankStorage fluidWater
Storage capacity50 m3
Water circulation pumpModelWilo TOP-S 40/7
Max. fluid temperature130 °C
Max. fluid temperature−20 °C
Power consumption390 W
Fan coil unitModelIN-FCG0016-L
Cooling capacity18 kW
Power consumption393 W
Airflow rate83 m3 · m−1
Table 2. Characteristics of the recorded weather data.
Table 2. Characteristics of the recorded weather data.
Weather ParameterUnitTime IntervalSensorAccuracy of Sensors
Air temperature°C10 minMTV Active, Ridder±1%
Relative humidity%10 minMTV Active, Ridder±2%
Solar radiationW·m−210 minSR05-D2A2-TMBL, HuksefluxIEC 61724-1:2017 standard, Class C, Basic
Wind speedm·s−110 minClima Sensor US, Thies Clima±5%
Wind directiondegrees10 minClima Sensor US, Thies Clima±5% of meas. value
Water temperature°C10 minHortiMax Omni Transducer, Ridder±5%
Water flowrateLiter10 minFS-WLH 40, FLSTRONIC±1% of measured. value
Ambient pressurehPa10 minPTB-220TS, VAISALA±5% hPa
Table 3. Physical and thermal properties of the greenhouse coverings and thermal screens.
Table 3. Physical and thermal properties of the greenhouse coverings and thermal screens.
Cover CharacteristicsCoveringScreen
HGPCPH_66
Solar transmittance front0.890.780.38
Solar transmittance back0.890.780.38
Solar reflectance front0.080.140.50
Solar reflectance back0.080.140.48
Visible radiation transmittance front0.910.750.38
Visible radiation transmittance back0.910.750.38
Visible radiation reflectance front0.080.150.50
Visible radiation reflectance back0.080.150.48
Thermal radiation transmittance 0.10.020.35
Thermal radiation emission front0.900.890.48
Thermal radiation emission back0.900.890.55
Conductivity (W·m−1· K−1)0.10.190.06
Air permeability (m2)1.49 × 10−11
Thickness (mm)4160.24
Table 4. Opaque materials’ properties.
Table 4. Opaque materials’ properties.
MaterialThickness (m)Thermal Conductivity
(kJ·h−1·m−1·K−1)
Thermal Capacity
(kJ·kg−1·K−1)
Density
(kJ·m−3)
Convective Heat Transfer Coefficient
(kJ·h−1·m−2·K−1)
FrontBack
Steel0.04541.878001164
Ground0.1000.970.752900110.001
Table 5. TRNSYS-estimated maximum cooling load of the greenhouse.
Table 5. TRNSYS-estimated maximum cooling load of the greenhouse.
Solar Radiation (kW·m−2)Greenhouse Setpoint Temp (°C)Greenhouse Cooling Area (m2)Max Cooling Load (kW)Max Cooling Load per Unit Area (kW·m−2)
1.0125391.2168.60.43
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Rasheed, A.; Kim, H.T.; Lee, H.W. Modeling-Based Energy Performance Assessment and Validation of Air-To-Water Heat Pump System Integrated with Multi-Span Greenhouse on Cooling Mode. Agronomy 2022, 12, 1374. https://doi.org/10.3390/agronomy12061374

AMA Style

Rasheed A, Kim HT, Lee HW. Modeling-Based Energy Performance Assessment and Validation of Air-To-Water Heat Pump System Integrated with Multi-Span Greenhouse on Cooling Mode. Agronomy. 2022; 12(6):1374. https://doi.org/10.3390/agronomy12061374

Chicago/Turabian Style

Rasheed, Adnan, Hyeon Tae Kim, and Hyun Woo Lee. 2022. "Modeling-Based Energy Performance Assessment and Validation of Air-To-Water Heat Pump System Integrated with Multi-Span Greenhouse on Cooling Mode" Agronomy 12, no. 6: 1374. https://doi.org/10.3390/agronomy12061374

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop