Article

Multi-Functional Isolated Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems

Department of Electronic Engineering, National Kaohsiung University of Science and Technology, Kaohsiung 811213, Taiwan
*
Author to whom correspondence should be addressed.
Sustainability 2022, 14(18), 11169; https://doi.org/10.3390/su141811169
Submission received: 12 August 2022 / Revised: 30 August 2022 / Accepted: 2 September 2022 / Published: 6 September 2022
(This article belongs to the Special Issue Renewable Energy: Technologies and Challenges)

Abstract

:
This paper proposes a novel multi-function isolated three-port bidirectional DC–DC converter for a stand-alone photovoltaic (PV) system. The proposed topology was composed of a unidirectional step-up converter and a bidirectional step-up/step-down converter that only required one set of complementary PWM signals to control any operation mode and used multiple operating stages to improve the practicability of the converter. In addition, the proposed topology had the function of inductance energy leakage recovery to improve the conversion efficiency and used synchronous rectification technology to reduce the conduction losses from passive components. This paper implemented a 500 W converter to verify the feasibility of the proposed converter by theoretical analysis, simulation, and experiment results. The experimental results show the highest efficiency of 95.5% for the PV step-up to the DC bus, 97.8% for the PV step-down to the battery terminal, 94.5% for the battery terminal step-up to the DC bus, and 93.4% for the DC bus step-down to the battery terminal, respectively.

1. Introduction

Today’s society relies heavily on non-renewable energy, which has seriously affected the environment [1]. The supply of petrochemical energy is excessively concentrated in areas with many disputes in the world, and energy prices are easily affected by human factors. Once oil production is in short supply, it will inevitably lead to global impacts such as soaring oil prices, rising prices, and inflation. In the case of natural gas, burning natural gas produces methane, a greenhouse gas that contributes to rapid global warming when it spills into the atmosphere in large quantities. Many countries are actively developing green energy sources, such as solar energy and wind power. Solar power generation has been the focus of energy technology in response to air pollution problems, which have received increased attention. On the other hand, once a solar power generation device is set up, energy can be continuously delivered, and there is no need to consider the problem of fuel transportation. Similarly, wind power generation does not need to consider the harmful gases and waste residues produced by fossil fuels such as coal and petroleum [2]. With the installation and promotion of wind power generation and solar power generation, centralized energy generation has gradually turned into distributed energy generation, which has become an inevitable trend of future urban intelligence [3]. With the reduction in the cost of solar cells, the number of commercialized solar power supply systems is increasing day by day. At the present stage, most common PV power generation systems are equipped with energy storage systems and rely on bidirectional converters to process the direction of energy and allow the energy storage system to be charged and discharged. This has led to the trend of research on bidirectional converters in recent years. Bidirectional converters can achieve step-up and step-down adjustments through the same topology. Some scholars have successively developed three-port converters for PV power supply systems, which can be powered by PV energy and batteries. Combining the functions of two-way converters and three-port converters is bound to greatly reduce the production cost and volume. Therefore, a three-port bidirectional converter with multiple operational functions was proposed in this paper. The PV could be stepped up to a DC bus (400 V) for supplying the DC load and charging the battery at the same time, while the battery also could be stepped up to the DC bus to stabilize the entire system. In addition, the DC bus could also be stepped down to charge the battery, as shown in Figure 1.
Bidirectional DC–DC converters can be divided into non-isolated and isolated types. Non-isolated converters [4,5,6,7,8] are derived from conventional converters. This type of converter has the advantages of a lower cost and a simpler structure. However, the voltage gain of the topology is not sufficient for high-voltage conversion applications. The converter [9] uses the switched capacitor voltage doubler technique, and the quasi-Z source can achieve a wider voltage gain range and lower power switch voltage stress. However, in order to achieve wide voltage gain, the switched capacitor technology increases the component count, resulting in lower conversion efficiency of this topology than conventional quasi-Z-source converters.
Refs. [10,11] presented the most common topology of all isolated converters, which have the advantages of few components, a simple structure, a low cost, and electrical isolation. However, leakage inductance can cause voltage surges to damage components, and therefore they should not be used in high-power applications. Ref. [11] presented a forward-flyback converter and a switched capacitor voltage circuit. The topology has the advantages of leakage inductance recovery, ZVS, and high conversion efficiency, and it can effectively improve the problem of large current ripples in traditional forward-flyback converters. However, circuit control is more complicated due to the synchronous rectification technology. At the same time, in order to achieve a high conversion ratio, a higher turns ratio is required, thus increasing the volume of the transformer and reducing the power density.
In recent years, many three-port converters have been proposed [12,13,14,15,16,17,18,19,20,21]. Such converters have been widely applied to renewable energy and electric vehicles, as they have fewer components and a lower cost. The topology in [12] requires larger component counts, two sets of transformers, and an inductor on the output side. Although there are two operating modes, the volume is large, which results in high implementation costs, leakage inductance, and low efficiency. Although [13] has the function of power factor correction (PFC) and has fewer active switching parts, it has the disadvantages of a discontinuous input current and low voltage gain. Ref. [14] was derived from the improved LLC topology, which uses a coupled inductor and a secondary-side voltage doubler circuit to achieve higher voltage gain and zero-voltage switching (ZVS). It also has the advantages of leakage inductance recovery and high efficiency. However, its operating modes are fewer. Ref. [15] presented a non-isolated converter with soft switching for hybrid energy systems. The topology has the advantages of multiple input sources, high efficiency, a simple topology, and soft switching, but it possesses larger component counts and has fewer operating modes. Ref. [16] presented a non-isolated high-step-up three-port converter, in which coupled inductors are used to achieve high voltage gain. This topology possesses lower voltage stress, soft switching, and lower conduction losses, as it uses two sets of clamp circuits. Due to employing more active switches, the operating mode is more complicated. Ref. [17] employed two step-up circuits to achieve three-port bidirectional power flows, in which a clamp circuit is used to realize the soft switching. The design also reduces the number of components used and achieves higher voltage gain by combining two sets of voltage doubler rectifier circuits, thus satisfying the characteristics of high voltage gain, component sharing, and soft switching. However, four sets of magnetic components and eight capacitors are employed, resulting in a high cost and large volume. Ref. [18] designed a three-winding common-core coupled inductor combined with a full-wave frequency multiplier circuit to achieve a high step-up. This topology also has the advantages of primary and secondary leakage inductance recovery, high efficiency, a simple topology, and simple signal control. Only three switches are employed in [19], and two input sources share a single inductor, thus reducing size and cost. This topology also has the advantages of high voltage gain, low voltage stress, few active components, and simple control, and it does not require an excessive turns ratio or non-extreme duty cycle. However, there are fewer operating modes, and the topology is more complicated.

2. Circuit Architecture and Operational Principles

This paper proposed a three-port isolated bidirectional DC/DC converter for solar energy systems. Its circuit topology is shown in Figure 2a. The proposed topology mainly combines a unidirectional boost converter and a bidirectional step-up/step-down converter. The PV (VPV) can be stepped up to a DC bus (VH 400 V) for supplying the DC load and charging the battery at the same time, and the battery (VBat) also can be stepped up to the DC bus. In addition, the DC bus can also be stepped down to charge the battery. This topology includes switches S1S6, a transformer, an inductor (L), and capacitors C1C3. The structure of this circuit is simple, and only one set of complementary signals is needed for control in different operating modes. It has leakage inductance recovery to reduce energy consumption, and it has four operating stages to achieve multiple operating functions under various conditions.
The operating current direction of the converter in this paper is shown in Figure 2b. The circuit was divided into four working modes for discussion and analysis. Stage one stepped up the output of PV (VPV) to the high-voltage side (VH) of the DC bus; stage two stepped down the output of the PV (VPV) to charge the battery; stage three stepped up the battery output (VB) to the high-voltage side (VH); and stage four stepped down the high-voltage side (VH) to charge the battery.
In order to simplify the analysis of the circuit, this study made the following assumptions:
(1)
Capacitors CPV, CBat, and C1C3 are large enough to keep the output voltage as a constant voltage source.
(2)
Switches S1S6 are ideal components.
(3)
The inductor current is operated in a continuous conduction mode (CCM).
(4)
The switching period is T; the time when the switch turns on is DT, and the time when the switch turns off is (1-D)T.

2.1. Stage One: PV Output Is Stepped Up to the High-Voltage Side (VH) of the DC Bus

Figure 3 shows the waveforms of the key components operating in stage one. In this stage, switches S1 and S2 are both turned off, and the energy is transmitted through the body diodes of switches S5 and S6. This operation is divided into five modes in this stage, and the equivalent circuits are shown in Figure 4a–e.
(1)
Mode 1 [t0–t1]
At t = t0, the equivalent circuit is shown in Figure 4a. In this mode, switches S3 and S4 are turned off, and leakage inductance Lk and capacitor C1 store energy through the parasitic capacitance of switch S3. The parasitic capacitance of switch S4 and magnetizing inductance Lm transmit energy to the secondary side through the transformer. The energy of capacitor C2 is transferred to the VH and charges capacitor C3 at the same time. This mode ends when switch S4 is turned on.
(2)
Mode 2 [t1–t2]
When t = t1, the equivalent circuit is shown in Figure 4b. In this mode, switch S4 is turned on, and switch S3 is turned off. The PV output (VPV) stores energy in leakage inductance Lk and magnetizing inductance Lm and transfers the energy to the secondary side through the transformer for charging capacitor C2. Capacitor C3 releases energy to the VH through the body diode of switch S5 and the secondary side of the transformer. Mode 2 ends when switch S4 is turned off.
(3)
Mode 3 [t2–t3]
At t = t2, the equivalent circuit is shown in Figure 4c. This mode is a dead time for switches S3 and S4. At this time, the leakage inductance releases energy to the magnetizing inductance Lm, the transformer, the parasitic capacitance of switch S4, and capacitor C1, and stores energy in capacitor C2 through the body diode of switch S5. Capacitor C3 releases energy to the VH through the body diode of switch S5 and the secondary side of the transformer. Mode 3 ends when switch S3 is turned on.
(4)
Mode 4 [t3–t4]
At t = t3, the equivalent circuit is shown in Figure 4d. In this mode, switch S3 is turned on, and switch S4 is turned off. Leakage inductance Lk releases energy to the transformer and capacitor C1, and the secondary side of the transformer stores energy in capacitor C3 through the body diode of switch S6. Capacitor C2 releases energy to the VH through the body diode of switch S6 and the secondary side of the transformer. When the energy of leakage inductance Lk drops to zero, mode 4 ends.
(5)
Mode 5 [t4–t5]
At t = t4, the equivalent circuit is shown in Figure 4e. In this mode, switch S3 is turned on, and switch S4 is turned off. At this time, magnetizing inductance Lm and capacitor C1 release energy to the transformer, and the secondary side of the transformer stores energy in capacitor C3 through the body diode of switch S6. Capacitor C2 releases energy to the VH through the body diode of the switch and the secondary side of the transformer. Mode 5 ends when switch S3 is turned off.

2.2. Stage Two: PV Output Is Stepped Down to Charge the Battery

Figure 5 shows the waveforms of the key components in stage two. This stage is divided into two operating modes in one switching cycle. Switches S3S6 are turned off. The equivalent circuits are shown in Figure 6a,b.
(1)
Mode 1 [t0–t1]
At t = t0, the equivalent circuit is shown in Figure 6a. In this mode, switch S1 is turned on, and switch S2 is turned off. Inductor L releases energy to the battery (VBat) through switch S1. Mode 1 ends when switch S1 is turned off.
(2)
Mode 2 [t1–t2]
At t = t1, the equivalent circuit is shown in Figure 6b. In this mode, switch S1 is turned off, and S2 is turned on. PV output VPV stores energy in inductor L, and the energy of inductor L charges the battery at the same time. Mode 2 ends when switch S2 is turned off.

2.3. Stage Three: Battery Output Is Stepped Up to the VH of the DC Bus

Figure 7 shows the waveforms of the key components of stage three. This operating mode is divided into five modes in one switching cycle, and its equivalent circuits are shown in Figure 8a–e.
(1)
Mode 1 [t0–t1]
At t = t0, the equivalent circuit is shown in Figure 8a. In this mode, switches S1S6 continue to be turned off from the previous mode. Leakage inductance Lk and the parasitic capacitance of switch S3 release energy to capacitor C1, capacitor C2 stores energy through the secondary side of the transformer, and capacitor C3 releases energy to the VH through the secondary side of the transformer. Mode 1 ends when switches S1 and S3 are turned on.
(2)
Mode 2 [t0–t1]
At t = t1, the equivalent circuit is shown in Figure 8b. In this mode, switches S1 and S3 are turned on, and switches S2 and S4 are turned off. At this time, the battery terminal (VBat) stores energy in inductor L, and leakage inductance Lk releases energy to capacitor C1 to recover the leakage inductance energy. Magnetizing inductance Lm stores energy in capacitor C3 through the secondary side of the transformer, and capacitor C2 releases energy to the VH through the body diode of switch S6 and the secondary side of the transformer. Mode 2 ends when the energy of leakage inductance Lk is zero.
(3)
Mode 3 [t2–t3]
At t = t2, the equivalent circuit is shown in Figure 8c. In this mode, switches S1S4 are kept in the previous mode. At this time, leakage inductance Lk and capacitor C1 release energy to magnetizing inductance Lm and transfer it to the secondary side of the transformer. The remaining operating states are the same as in the previous mode. Mode 3 ends when switches S1 and S3 are turned off.
(4)
Mode 4 [t3–t4]
At t = t3, the equivalent circuit is shown in Figure 8d. In this mode, all switches are turned off. Magnetizing inductance Lm releases energy to capacitor C3 through the secondary side of the transformer and the body diode of switch S6, and capacitor C2 releases energy to the VH through the body diode of switch S6 and the secondary side of the transformer. Mode 4 ends when switches S2 and S4 are turned on.
(5)
Mode 5 [t4–t5]
At t = t4, the equivalent circuit is shown in Figure 8e. In this mode, switches S2 and S4 are turned on. Battery terminal VBat and inductor L release energy to the transformer and store energy in magnetizing inductor Lm. The secondary side of the transformer transfers energy to capacitor C2 through the body diode of switch S5, and capacitor C3 releases energy to the VH through the body diode of switch S5 and the secondary side of the transformer. Mode 5 ends when switches S2 and S4 are turned off.

2.4. Stage Four: The High-Voltage Side (VH) Is Stepped Down to Charge the Battery

Figure 9 shows the waveforms of the key components in stage four. This operating mode is divided into six modes in one switching cycle, and the equivalent circuits are shown in Figure 10a–f.
(1)
Mode 1 [t0–t1]
At t = t0, the equivalent circuit is shown in Figure 10a. In this mode, switches S1S6 are all turned off following the previous mode. Capacitor C2 releases energy to parasitic capacitor CS5 of switch S5, while parasitic capacitor CS6 of switch S6 releases energy to capacitor C3. Leakage inductance Lk transfers energy to parasitic capacitance CS2 of switch S2 and the input capacitance (CPV) of the PV terminal through the body diode of switch S4. Mode 1 ends when switches S1, S3, and S6 are turned on.
(2)
Mode 2 [t0–t1]
At t = t1, the equivalent circuit is shown in Figure 10b. Switches S1, S3, and S6 are turned on in this mode. The VH transfers energy to capacitor C2 and the secondary side of the transformer, while capacitor C3 also transfers energy to the primary side through the secondary side of the transformer. Leakage inductance Lk releases energy to capacitor C1 for leakage inductance recovery, magnetizing inductance Lm stores energy through the primary side of the transformer while capacitor CPV transfers energy to parasitic capacitor CS4 of switch S4, and inductor L releases energy to the battery terminal VBat. Mode 2 ends when the energy of leakage inductance Lk is zero.
(3)
Mode 3 [t2–t3]
At t = t2, the equivalent circuit is shown in Figure 10c. Switches S1, S3, and S6 are turned on in this mode. At this time, leakage inductance Lk and capacitor C1 release energy to magnetizing inductance Lm. The other operating state is the same as in the previous Mode. Mode 3 ends when switches S1, S3, and S6 are turned off.
(4)
Mode 4 [t3–t4]
At t = t3, the equivalent circuit is shown in Figure 10d. All switches are turned off in this mode. Capacitor C3 discharges energy to parasitic capacitor CS6 of switch S6, parasitic capacitor CS5 of switch S5 transfers energy to capacitor C2, parasitic capacitor CS4 of switch S4 transfers energy to capacitor CPV, capacitor C1 releases energy to parasitic capacitance CS3 of switch S3, and inductor L releases energy to the battery terminal VBat through the body diode of switch S1. Mode 4 ends when switches S2, S4, and S5 are turned on.
(5)
Mode 5 [t4–t5]
At t = t4, the equivalent circuit is shown in Figure 10e. Switches S2, S4, and S5 are turned on in this mode. Capacitor C2 is charged by the transformer, capacitor C3 transfers energy through the secondary side to the primary side of the transformer, and inductor L stores energy through magnetizing inductor Lm and capacitor CPV. Mode 5 ends when the current in magnetizing inductance Lm is greater than that of leakage inductance Lk.
(6)
Mode 6 [t5–t6]
At t = t5, the equivalent circuit is shown in Figure 10f. Switches S2, S4, and S5 are turned on in this mode. Capacitor C2 transfers energy to the primary side through the secondary side of the transformer, the VH stores energy in capacitor C3 and at the same time transfers energy to the primary side through the secondary side of the transformer, and inductor L stores energy through magnetizing inductor Lm, capacitor CPV, and the primary side of the transformer. Mode 6 ends when switches S2, S4, and S5 are turned off.

3. Steady-State Analysis

This section discusses and analyzes the voltage gain ratio and switching component stress, respectively. In order to simplify the analysis of the circuit, the same assumptions were also made, as in the above section.

3.1. Voltage Gain Analysis

(1)
Stage One
In stage one, the PV output VPH is stepped up to the VH when switch S3 is turned on and switch S4 is turned off, and the body diode of switch S5 is reverse biased. According to Kirchhoff’s voltage law, the voltage across magnetizing inductance Lm is as follows:
V L m = L m d i L m d t = V C 3 n
The inductor current decreases linearly with time when switch S3 is closed. The variation in the inductor current with time is calculated as:
Δ i L m Δ t = Δ i L m D T = V C 3 n L m
( Δ i L m )on can be derived as follows when switch S3 is turned on:
( Δ i L m ) o n = V C 3 D T n L m
When switch S3 is turned off and S4 is turned on, the PV terminal stores energy in magnetizing inductance Lm, and the voltage across the inductance is:
V L m = V P V = L m d i L m d t = V C 2 n
Similarly, the inductor current changes linearly with time when switch S3 is turned off. The variation in inductor current with time is as follows:
Δ i L m Δ t = Δ i L m ( 1 D ) T = V P V L m
( Δ i L m ) o f f = V P V ( 1 D ) T L m
According to the voltage-second balance, the variation in the inductor current must be zero in a steady-state operation:
( Δ i L m ) o n + ( Δ i L m ) o f f = 0
V C 3 D T n L m + V P V ( 1 D ) T L m = 0
After simplifying Equation (8), the voltage gain of VPV and VC3 can be obtained as:
V C 3 V P V = ( 1 D ) D n
Because:
V H = V C 2 + V C 3
After substituting (3) and (6) into (7), the voltage gain of the high-voltage side and the PV port can be obtained:
V H V P V = n D
According to Equation (11), the relationship between duty cycle D, turns ratio n, and the voltage gain (VH/VPV) of stage one can be obtained, as shown in Figure 11. Among them, the turns ratio n and duty cycle D used in this paper were 4 and 0.33, respectively; therefore, the voltage gain (VH/VPV) was 12.12.
(2)
Stage Two
In stage two, the VPH is stepped down to charge the battery Vbat. When switch S1 is turned on, the voltage across inductor L is:
V L = V B a t = L d i L d t
Δ i L Δ t = Δ i L m D T = V Bat L
( Δ i L )on can be derived as follows when switch S1 is turned on:
( Δ i L ) o n = ( V Bat L ) D T
When switch S1 is turned off and switch S2 is turned on, the voltage across the inductor L is:
V L = V Bat V PV = L di L dt
di L dt = V Bat V PV L
At this time, ( Δ i L ) o f f is:
( Δ i L ) o f f = ( V Bat V PV L ) ( 1 D ) T
According to the voltage-second balance, the variation in the inductor current must be zero in a steady-state operation:
( Δ i L ) o n + ( Δ i L ) o f f = 0
( V Bat L ) D T + ( V Bat V PV L ) ( 1 D ) T = 0
After simplifying Equation (19), the voltage gain in this stage can be obtained as:
V Bat V PV = 1 D
According to Equation (20), the relationship between duty cycle D and the voltage gain (VBat/VPV) of stage two can be obtained, as shown in Figure 12. In this stage, duty cycle D was designed to be 0.5, and the voltage gain (VBat/VPV) was 0.5.
(3)
Stage Three
In this stage, the Vbat is stepped up to the VH. When switches S1 and S3 are turned on, the voltages of inductance L and magnetizing inductance Lm can be obtained by Kirchhoff’s voltage law, respectively:
V L = L di L dt = V B a t
V L m = L m di Lm dt = V C 3 n
When switches S1 and S3 are turned on and switches S2 and S4 are turned off, the inductor current increases linearly with time. The current variation of inductance L and magnetizing inductance Lm with time can be calculated as follows:
Δ i L Δ t = Δ i L D T = V B a t L
Δ i Lm Δ t = Δ i Lm DT = V C 3 L m n  
Δ i L   and Δ i L m can be obtained as follows:
( Δ i L ) o n = V B a t D T L
( Δ i L m ) o n = V C 3 D T L m n  
When switches S1 and S3 are turned off and switches S2 and S4 are turned on, the inductor current does not change instantaneously. The voltage across inductance L and magnetizing inductance Lm is:
V L = ( V Bat V L m ) = L di L dt
V L m = V C 2 n = L m di L m dt  
When switches S1 and S3 are turned off, the current variation of inductance L and magnetizing inductance Lm with time is:
Δ i L Δ t = Δ i L ( 1 D ) T = ( V Bat V Lm ) L
( Δ i L ) o f f = ( V Bat V Lm ) ( 1 D ) T L  
Δ i Lm Δ t = Δ i L m ( 1 D ) T = V C 2 L m n
( Δ i Lm ) o f f = V C 2 ( 1 D ) T L m n  
According to the voltage-second balance, the change in the inductor current must be zero in a steady-state operation:
( Δ i L ) o n + ( Δ i L ) o f f = 0
V B a t D T L + ( V Bat V Lm ) ( 1 D ) T L = 0  
Simplifying (34), the relationship between VBat and VL can be obtained as:
V L = V Bat 1 D  
Similarly,
( Δ i L m ) o n + ( Δ i Lm ) o f f = 0
V C 3 D T L m n + V C 2 ( 1 D ) T L m n = 0  
Simplifying (37) obtains (38):
V C 2 + V C 3 n D = V C 2 n  
Because:
V C 2 + V C 3 = V H
Substituting (28) and (38) into (39) obtains (40):
V H n D = L m  
Simplifying (34) and (40) obtains the voltage gain of stage three as follows:
V H V B a t = n ( 1 D ) D  
The relationship between duty cycle D, turns ratio n, and the voltage gain (VH/VBat) of stage three can be obtained, as shown in Figure 13. Among them, the turns ratio n and duty cycle D designed in this paper were 4 and 0.5, respectively; therefore, the voltage gain (VH/VBat) was 16.6.
(4)
Stage Four
In this stage, the VH is stepped down to charge the Vbat. When switches S1, S3, and S6 are turned on, the voltages of inductance L and magnetizing inductance Lm can be obtained from Kirchhoff’s voltage law:
V L = L di L dt = V B a t
V L m = L m di Lm dt = V C 3 n = V H V C 2 n
When switches S1, S3, and S6 are turned on and switches S2, S4, and S5 are turned off, the current increases linearly with time. The current variation of inductance L and magnetizing inductance Lm with time can be calculated as:
Δ i L Δ t = Δ i L D T = V B a t L  
Δ i Lm Δ t = Δ i Lm D T = V C 3 L m n = V H V C 2 L m n  
( Δ i L ) o n   and ( Δ i L m ) o n can be obtained as follows:
( Δ i L ) o n = V B a t D T L
( Δ i L m ) o n = ( V H V C 2 ) D T L m n
When switches S1, S3, and S6 are turned off and switches S2, S4, and S5 are turned on, the inductor current does not change instantaneously. The voltage across inductance L and magnetizing inductance Lm is:
V L = ( V Bat V L m ) = ( V Bat V C 2 n ) = L di L dt
V L m = V C 2 n = L m di L m dt
Similarly, when switches S1, S3, and S6 are turned off, the current variation of inductance L and magnetizing inductance Lm with time is:
Δ i L Δ t = Δ i L ( 1 D ) T = ( V Bat V Lm ) L
( Δ i L ) o f f = ( V Bat V Lm ) ( 1 D ) T L
Δ i Lm Δ t = Δ i L m ( 1 D ) T = V C 2 L m n
( Δ i Lm ) o f f = V C 2 ( 1 D ) T L m n
According to the voltage-second balance, the change in the inductor current must be zero in a steady-state operation:
( Δ i L m ) o n + ( Δ i Lm ) o f f = 0
( V H V C 2 ) D T L m + V C 2 ( 1 D ) T L m = 0
Simplifying (55), the relationship between VC2 and VH can be obtained as:
V C 2 = V H D
Similarly,
( Δ i L ) o n + ( Δ i L ) o f f = 0
V B a t D T L + ( V Bat V C 2 n ) ( 1 D ) T L = 0
Simplifying (58) obtains (59):
V B a t V C 2 = 1 D n
By substituting (56) into (59) and simplifying the equation, the voltage gain of stage four can be obtained as:
V B a t V H = ( 1 D ) D n
The relationship between duty cycle D, turns ratio n, and the voltage gain (VBat/VH) of stage four can be obtained, as shown in Figure 14. Among them, the turns ratio n and duty cycle D designed in this paper were 4 and 0.5, respectively; therefore, the voltage gain (VBat/VH) was 0.0625. It could be seen that the voltage gain (VBat/VH) could be increased by reducing duty cycle D or increasing turns ratio n.

3.2. Voltage Stress Analysis

The voltage stress on the components of the proposed topology can be deduced from the ON–OFF state of the switches. The voltage stress of switch S1 can be derived from the ON state of mode 5 in stage four, as shown in Figure 10e and as follows:
V S 1 V Lm = 0
By substituting (49) and (56) into (61), the voltage stress of switch S1 can be obtained:
V S 1 =   V H D   n
The voltage stress of switch S2 can be deduced from the state of mode 2 in stage four, as shown in Figure 10b and as follows:
V S 2 =   V H D   n
The voltage stress of switch S3 can be derived from the state of mode 5 in stage four, as shown in Figure 10e and as follows:
V S 3 =   V H   n
The voltage stress of switch S4 can be derived from the state of mode 3 in stage four, as shown in Figure 10c and as follows:
V S 4 =   V H   n
The voltage stress of switch S5 can be derived from the state of mode 2 in stage four, as shown in Figure 10b and as follows:
V S 5 = V H
The voltage stress of switch S6 can be derived from the state of mode 5 in stage four, as shown in Figure 10e and as follows:
V S 6 = V H
The voltage stress of capacitor CPV is VPV.
V C P V = V P V
The voltage stress of capacitor CBat is VBat.
V C B a t = V B a t
The voltage stress of capacitor C2 is:
V C 2 = V H ( 1 D )
The voltage stress of capacitor C3 is:
V C 3 = V H D

3.3. Magnetic Component Design

Since the proposed converter operates in CCM, this section presents the design of inductance L and magnetizing inductance Lm.
(1)
Design of Inductor L
The maximum and minimum inductor current (iLmax and iLmin) can be expressed as follows when switch S1 is turned on and off:
i L ( m a x ) = i L +   Δ i L   2
i L ( m i n ) = i L   Δ i L   2
Because:
i L = i B a t
According to the energy conservation principle, the ideal transformer conversion efficiency is 100%, and the input power (PBat) is equal to the output power (PH):
P B a t = P H
V B a t i B a t = V H i H
By substituting (41) and (74) into (76) and replacing output current iH with output resistance RH on the high-voltage side, the equation can be simplified as follows:
i L = V B a t n 2 [ ( 1 D ) D ] 2 R H
Substituting (25) and (77) into (72) and (73) obtains:
i L ( m a x ) = V B a t n 2 [ ( 1 D ) D ] 2 R H + V B a t D T 2 L
i L ( m i n ) = V B a t n 2 [ ( 1 D ) D ] 2 R H V B a t D T 2 L
Due to all of the inductances of the converters in this paper working in CCM, iL is always greater than zero. If the converter operates in the boundary conduction mode (BCM), iL(min) is equal to zero. Therefore, the boundary value between the continuous and discontinuous inductor current is expressed as:
i L ( m i n ) = 0 = V B a t n 2 [ ( 1 D ) D ] 2 R H V B a t D T 2 L
According to the above equation, the value of inductance L(BCM) can be obtained by substituting switching frequency f and simplifying the equation:
L ( B C M ) = ( 1 D ) 2 D 3 R H 2 f n 2
It can be seen from (81) that the value of inductance L can be designed by switching frequency f, transformer turns ratio n, and duty cycle ratio D to determine whether the converter operates in BCM, CCM, or the discontinuous conduction mode (DCM). The turns ratio n was set at 4 in this paper, and the switching frequency f was 40 kHz. Substituting the above parameters into (81) obtains the inductance value, as shown in Figure 15. When the value of inductance L is greater than L(BCM), the converter will operate in CCM; conversely, when the value of inductance L is lower than L(BCM), it will operate in DCM.
(2)
Design of Magnetizing Inductance (Lm)
The maximum and minimum magnetizing inductor current (iLm(max) and iLm(min)) can be expressed as follows when switch S4 is turned on and off:
i L m ( m a x ) = i L m +   Δ i L m   2
i L m ( m i n ) = i L m   Δ i L m   2
Because:
i B a t = i L m D
Similarly,
P B a t = P H
V B a t i B a t = V H i H
By substituting (41) and (84) into (86) and replacing output current iH with output resistance RH on the high-voltage side, the equation can be simplified as follows:
i L m = V B a t n 2 ( 1 D ) 2 D 3 R H
Substituting (32) into (72) and (73) obtains:
i L m ( m a x ) = V B a t n 2 ( 1 D ) 2 D 3 R H + V C 2 ( 1 D ) T 2 L m n
i L m ( m i n ) = V B a t n 2 ( 1 D ) 2 D 3 R H V C 2 ( 1 D ) T 2 L m n
If the converter operates in BCM, iLm(min) is equal to zero. Therefore:
i L m ( m i n ) = 0 = V B a t n 2 [ ( 1 D ) D ] 2 R H V C 2 ( 1 D ) T 2 L m n
By substituting duty cycle T into (90) and simplifying the equation, magnetizing inductance L m ( B C M ) can be obtained:
L m ( B C M ) = ( 1 D ) 2 D 3 R H 2 f n
It can be seen that L m ( B C M ) can be determined by switching frequency f, transformer turns ratio n, and duty cycle ratio D. Figure 16 shows the relationship between magnetizing inductance Lm and the duty ratio D. The proposed converter operates in CCM when the value of magnetizing inductance Lm is greater than   L m ( B C M ) ; conversely, when the value of magnetizing inductance Lm is lower than L m ( B C M ) , it will operate in DCM.

4. Experimental Results

The electrical specifications and component parameters of the proposed converter are listed in Table 1. Figure 17 shows the implemented circuit in this paper. In this paper, the PV voltage was 48 V, the Vbat was 24 V, and the VH was 400 V.
Figure 18a–e shows the measured waveforms of stage one operating under a full load (500 W). Figure 18a shows the measured waveforms vgs3, vds3, and ids3 of switch S3. It can be seen that when switch S3 was turned on, ids3 started to rise from a negative to a positive current, leakage inductance current iLk was released by switch S3, and the leakage inductance is recovered. Figure 18b shows the measured waveforms (vgs4, vds4, and ids4) of switch S4. It can be seen that magnetizing inductance Lm stored energy through switch S4. Figure 18c shows the measured waveforms vgs4, vds5, and ids5. In this stage, in order to avoid circuit malfunctions caused by an unbalanced magnetic flux on the secondary side, the current flowed through the body diode of switch S5. Figure 18d shows the measured waveforms vgs3, vds6, and ids6. The current flowed through the body diodes of switch S6. Figure 18e shows the measured waveform vgs3, the primary-side current in1, and the secondary-side current in2 of the transformer.
Figure 19a–c show the measured waveforms of stage two operating under a full load (500 W). Figure 19a shows the measured waveforms (vgs1, vds1, and ids1) of switch S1. It can be seen that switch S1 had synchronous rectification characteristics in this stage. Figure 19b shows the measured waveforms (vgs2, vds2, and ids2) of switch S2. Figure 19c shows the measured waveforms of vgs2, vds2, and iL. It can be seen that inductor L stored energy while switch S2 was turned on and released energy while switch S2 was turned off.
Figure 20a–h show the measured waveforms of stage three operating under full load (500 W). Figure 20a shows the measured waveforms vgs1, vds1, and ids1 of switch S1, and it can be seen that inductor L stored energy through switch S1. Figure 20b shows the measured waveforms (vgs2, vds2, and ids2) of switch S2. Figure 20c shows the measured waveforms (vgs3, vds3, and ids3) of switch S3. When switch S3 was turned on, current ids3 started to turn from a negative current to a positive current, and leakage inductance current iLk was released and recovered energy through switch S3. Figure 20d shows the measured waveforms (vgs4, vds4, and ids4) of switch S4. Figure 20e shows the measured waveforms vgs4, vds5, and ids5. Figure 20f is the measured waveforms vgs3, vds6, and ids6. In this mode, the energy flowed through the body diode of switch S6. Figure 20g shows the measured waveform vgs1, inductor current iL, and the transformer primary-side current in1. Figure 20h shows the measured waveform vgs1, the transformer primary-side current in1, and the transformer secondary-side current in2.
Figure 21a–g show the measured waveforms of stage four operating under a full load (500 W). Figure 21a shows the measured waveforms (vgs1, vds1, and ids1) of switch S1. It can be seen that inductor L released energy through switch S1 at this time. Figure 21b shows the measured waveforms (vgs2, vds2, and ids2) of switch S2. It can be seen that inductor L stored energy through switch S2. Figure 21c shows the measured waveforms (vgs3, vds3, and ids3) of switch S3. Current ids3 started to rise from positive to negative, and the leakage inductance current iLk released and recovered energy through switch S3. The energy was transferred to the magnetizing inductance Lm. Figure 21d shows the measured waveforms (vgs4, vds4, and ids4) of switch S4. Figure 21e shows the measured waveforms (vgs5, vds5, and ids5) of switch S5. Figure 21f shows the measured waveforms (vgs6, vds6, and ids6) of switch S6. Figure 21g shows the measured waveforms vgs1, the transformer primary-side current in1, and the transformer secondary-side current in2.
Figure 22 shows the load variation in the step-up mode. When the output load was step changed from a half load to a full load, it can be seen that the output voltage (VH/VBat) was stable and not greatly affected by load changes.
Figure 23a–d show the efficiency curves of the proposed converter in this paper. Figure 23a shows the highest efficiency was 95.5% at an output power of 200 W, and the efficiency at the full load of 500 W was 92.3%. Figure 23b shows the highest efficiency was 97.8% at an output power of 150 W, and the efficiency was 95.7% at the full load of 500 W. Figure 23c shows the highest efficiency was 94.5% at an output power of 150 W, and the efficiency was 87% at the full load of 500 W. Figure 23d shows the highest efficiency was 93.4% at an output power of 150 W, and the efficiency was 88.3% at the full load of 500 W.
Figure 24 presents the power loss analysis of the proposed converter operated in step-up mode (stage three) and under full load. It can be seen that the switching loss and conduction loss of all power switches account for a large proportion of the overall power loss.
Figure 25 presents the power loss analysis of the proposed converter operated in step-down mode (stage four) and under full load. It can be also seen that the switching loss and conduction loss of all switches account for a large proportion of the overall power loss.
Figure 26 shows the efficiency comparison between this paper and Refs. [15,16,17,18,19] operating under the step-up/step-down mode. Refs. [15,16] employed more passive components, causing poor efficiency. Ref. [18] had higher conversion efficiency in the step-down mode, but its disadvantage was a low voltage gain ratio. Ref. [19] had the highest efficiency under the step-up mode, but its implemented power was only 300 W, and the total component count was too high, which limited its application. Overall, the proposed topology had a higher voltage gain ratio and efficiency compared to Refs. [15,16,17,18,19].
To illustrate the feasibility and performance of the proposed converter, Table 2 shows the performance comparison between the proposed converter and Refs. [15,16,17,18,19]. It can be seen that the proposed topology possessed a higher voltage conversion ratio, and the implemented power was also higher than that found in other literature. Only one set of complementary PWM signals was used in each mode, ensuring that there were many stages, and the control was simple. A galvanic isolation feature was used to protect the circuit operation.

5. Conclusions

This paper proposed a novel three-port bidirectional DC–DC converter. The steady-state analysis of the component design and the experimental results verified the feasibility and practicability of the proposed converter. The proposed converter had the following advantages: (1) a simple structure; (2) only one set of complementary signals used in each stage, providing simple control; (3) leakage inductance recovery; (4) multiple operating stages, which improved the practicability of the proposed converter; and (5) an electrical isolation feature to protect the low-voltage input side. Finally, in terms of the measured efficiency, the highest efficiency of the PV output stepped up to the high-voltage-side mode was 95.5%, and the highest efficiency of the PV terminal stepped down to the battery was 97.8%. The highest efficiency was 94.5% when the battery was stepped up to the high-voltage side, and the highest efficiency was 93.4% when the high-voltage side was stepped down to the battery.

Author Contributions

Conceptualization, Y.-E.W.; methodology, Y.-E.W. and R.-R.H.; formal analysis, Y.-E.W. and R.-R.H.; investigation, R.-R.H.; resources, Y.-E.W.; writing—original draft preparation, Y.-E.W.; writing—review and editing, Y.-E.W.; project administration, Y.-E.W.; funding acquisition, Y.-E.W. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Facing Global Warming-Taiwan Response. Available online: http://www.tri.org.tw/unfccc/ (accessed on 25 June 2021).
  2. Bureau of Energy Ministry of Economic. Available online: https://www.re.org.tw/default.aspx (accessed on 25 June 2021).
  3. Taiwan Power Company Nuclear Energy Safety. Available online: https://www.taipower.com.tw/tc/page.aspx?mid=203&cid=148&cchk=f8477804-f7b0-49c9-8ec6-3a1ba86ff2df (accessed on 15 July 2021).
  4. Pressman, A.I.; Billings, K.; Morey, T. Switching Power Supply Design, 3rd ed.; Chuan Hwa Publishing Ltd.: New Taipei City, Taiwan, 2012. [Google Scholar]
  5. Yi, W. Principles and Practical Design Techniques of Switching Power Converters (Case Design Oriented), 3rd ed.; Wensheng Book Store: Taipei City, Taiwan, 2018. [Google Scholar]
  6. Hart, D.W. Power Electronics; Tung Hua Book Co., Ltd.: Taipei City, Taiwan, 2013. [Google Scholar]
  7. Aharon, I.; Kuperman, A.; Shmilovitz, D. Analysis of Dual-Carrier Modulator for Bidirectional Noninverting Buck–Boost Converter. IEEE Trans. Power Electron. 2015, 30, 840–848. [Google Scholar] [CrossRef]
  8. Jia, L.; Sun, X.; Zheng, Z.; Ma, X.; Dai, L. Multimode Smooth Switching Strategy for Eliminating the Operational Dead Zone in Noninverting Buck–Boost Converter. IEEE Trans. Power Electron. 2020, 35, 3106–3113. [Google Scholar] [CrossRef]
  9. Zhang, Y.; Liu, Q.; Gao, Y.; Li, J.; Sumner, M. Hybrid Switched-Capacitor/Switched-Quasi-Z-Source Bidirectional DC–DC Converter With a Wide Voltage Gain Range for Hybrid Energy Sources EVs. IEEE Trans. Ind. Electron. 2019, 66, 2680–2690. [Google Scholar] [CrossRef]
  10. New Newsletter Magazine Network. Available online: https://www.2cm.com.tw/2cm/zh-tw/tech/F58656FF8411490C873E820579FE24C0 (accessed on 6 July 2021).
  11. Wai, R.; Zhang, Z. Design of High-Efficiency Isolated Bidirectional DC/DC Converter With Single-Input Multiple-Outputs. IEEE Access 2019, 7, 87543–87560. [Google Scholar] [CrossRef]
  12. Li, W.; Xu, C.; Luo, H.; Hu, Y.; He, X.; Xia, C. Decoupling-controlled triport composited DC/DC converter for multiple energy interface. IEEE Trans. Ind. Electron. 2015, 62, 4504–4513. [Google Scholar] [CrossRef]
  13. Wang, F.; Li, L.; Zhong, Y.; Shu, X. Flyback-Based Three-Port Topologies for Electrolytic Capacitor-Less LED Drivers. IEEE Trans. Ind. Electron. 2017, 64, 5818–5827. [Google Scholar] [CrossRef]
  14. Uno, M.; Oyama, R.; Sugiyama, K. Partially Isolated Single-Magnetic Multiport Converter Based on Integration of Series-Resonant Converter and Bidirectional PWM Converter. IEEE Trans. Power Electron. 2018, 33, 9575–9587. [Google Scholar] [CrossRef]
  15. Faraji, R.; Farzanehfard, H.; Esteki, M.; Khajehoddin, S.A. A lossless passive snubber circuit for three-port DC-DC converter. IEEE J. Emerg. Sel. Top. Power Electron. 2020, 9, 1905–1914. [Google Scholar] [CrossRef]
  16. Faraji, R.; Farzanehfard, H. Soft-switched nonisolated high step-up three-port DC–DC converter for hybrid energy systems. IEEE Trans. Power Electron. 2018, 33, 10101–10111. [Google Scholar] [CrossRef]
  17. Dobakhshari, S.S.; Fathi, S.H.; Milimonfared, J. A new soft-switched three-port DC/DC converter with high voltage gain and reduced number of semiconductors for hybrid energy applications. IEEE Trans. Power Electron. 2020, 35, 3590–3600. [Google Scholar] [CrossRef]
  18. Wu, Y.-E.; Hsu, K.-C. Novel Three-Port Bidirectional DC/DC Converter with Three-Winding Coupled Inductor for Photovoltaic System. Energies 2020, 13, 1132. [Google Scholar] [CrossRef]
  19. Chien, L.-J.; Chen, C.-C.; Chen, J.-F.; Hsieh, Y.-P. Novel Three-Port Converter With High-Voltage Gain. IEEE Trans. Power Electron. 2014, 29, 4693–4703. [Google Scholar] [CrossRef]
  20. Wu, Y.-E. Novel High Step-up/Step-down Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems. Energies 2022, 15, 5257; [Google Scholar] [CrossRef]
  21. Wu, Y.-E.; Hsiao, S.-L. Novel High-Efficiency Three-Port Bidirectional Step-up/Step-down DC–DC Converter for Photovoltaic Systems. Sustainability 2021, 13, 7913. [Google Scholar] [CrossRef]
Figure 1. Application system diagram of three-port bidirectional DC/DC converter.
Figure 1. Application system diagram of three-port bidirectional DC/DC converter.
Sustainability 14 11169 g001
Figure 2. Proposed three-port bidirectional converter: (a) circuit architecture; (b) operating current direction of the proposed converter.
Figure 2. Proposed three-port bidirectional converter: (a) circuit architecture; (b) operating current direction of the proposed converter.
Sustainability 14 11169 g002aSustainability 14 11169 g002b
Figure 3. Waveforms of the key components in stage one.
Figure 3. Waveforms of the key components in stage one.
Sustainability 14 11169 g003
Figure 4. Operating equivalent circuits of stage one: (a) mode 1; (b) mode 2; (c) mode 3; (d) mode 4; and (e) mode 5.
Figure 4. Operating equivalent circuits of stage one: (a) mode 1; (b) mode 2; (c) mode 3; (d) mode 4; and (e) mode 5.
Sustainability 14 11169 g004
Figure 5. Waveforms of the key components in stage two.
Figure 5. Waveforms of the key components in stage two.
Sustainability 14 11169 g005
Figure 6. Operating equivalent circuits of stage two: (a) mode 1; (b) mode 2.
Figure 6. Operating equivalent circuits of stage two: (a) mode 1; (b) mode 2.
Sustainability 14 11169 g006aSustainability 14 11169 g006b
Figure 7. Waveforms of the key components in stage three.
Figure 7. Waveforms of the key components in stage three.
Sustainability 14 11169 g007
Figure 8. Operating equivalent circuits of stage three: (a) mode 1; (b) mode 2; (c) mode 3; (d) mode 4; and (e) mode 5.
Figure 8. Operating equivalent circuits of stage three: (a) mode 1; (b) mode 2; (c) mode 3; (d) mode 4; and (e) mode 5.
Sustainability 14 11169 g008aSustainability 14 11169 g008b
Figure 9. Waveforms of the key components in stage four.
Figure 9. Waveforms of the key components in stage four.
Sustainability 14 11169 g009
Figure 10. Equivalent circuit diagrams of stage four: (a) mode 1; (b) mode 2; (c) mode 3; (d) mode 4; (e) mode 5; and (f) mode 6.
Figure 10. Equivalent circuit diagrams of stage four: (a) mode 1; (b) mode 2; (c) mode 3; (d) mode 4; (e) mode 5; and (f) mode 6.
Sustainability 14 11169 g010aSustainability 14 11169 g010b
Figure 11. Relationship between the voltage gain (VH/VPV) of stage one and duty cycle D.
Figure 11. Relationship between the voltage gain (VH/VPV) of stage one and duty cycle D.
Sustainability 14 11169 g011
Figure 12. Relationship between the voltage gain (VBat/VPV) of stage two and duty cycle D.
Figure 12. Relationship between the voltage gain (VBat/VPV) of stage two and duty cycle D.
Sustainability 14 11169 g012
Figure 13. Relationship between the voltage gain (VH/VBat) of stage three and duty cycle D.
Figure 13. Relationship between the voltage gain (VH/VBat) of stage three and duty cycle D.
Sustainability 14 11169 g013
Figure 14. Relationship between the voltage gain (VBat/VH) of stage four and duty cycle D.
Figure 14. Relationship between the voltage gain (VBat/VH) of stage four and duty cycle D.
Sustainability 14 11169 g014
Figure 15. Inductor L operating in the BCM.
Figure 15. Inductor L operating in the BCM.
Sustainability 14 11169 g015
Figure 16. Magnetizing inductance Lm operating in the BCM.
Figure 16. Magnetizing inductance Lm operating in the BCM.
Sustainability 14 11169 g016
Figure 17. Photograph of the proposed converter.
Figure 17. Photograph of the proposed converter.
Sustainability 14 11169 g017
Figure 18. Measured waveforms of stage one: (a) vgs3, vds3, and ids3; (b) vgs4, vds4, and ids4; (c) vgs4, vds5, and ids5; (d) vgs3, vds6, and ids6; and (e) vgs3, in1, and in2.
Figure 18. Measured waveforms of stage one: (a) vgs3, vds3, and ids3; (b) vgs4, vds4, and ids4; (c) vgs4, vds5, and ids5; (d) vgs3, vds6, and ids6; and (e) vgs3, in1, and in2.
Sustainability 14 11169 g018
Figure 19. Measured waveforms of stage two: (a) vgs1, vds1, and ids1; (b) vgs2, vds2, and ids2; (c) vgs2, vds2, and iL.
Figure 19. Measured waveforms of stage two: (a) vgs1, vds1, and ids1; (b) vgs2, vds2, and ids2; (c) vgs2, vds2, and iL.
Sustainability 14 11169 g019
Figure 20. Measured waveforms of stage three: (a) vgs1, vds1, and ids1; (b) vgs2, vds2, and ids2; (c) vgs3, vds3, and ids3; (d) vgs4, vds4, and ids4; (e) vgs4, vds5, and ids5; (f) vgs3, vds6, and ids6; (g) vgs1, iL, and in1; (h) vgs1, in1, and in2.
Figure 20. Measured waveforms of stage three: (a) vgs1, vds1, and ids1; (b) vgs2, vds2, and ids2; (c) vgs3, vds3, and ids3; (d) vgs4, vds4, and ids4; (e) vgs4, vds5, and ids5; (f) vgs3, vds6, and ids6; (g) vgs1, iL, and in1; (h) vgs1, in1, and in2.
Sustainability 14 11169 g020aSustainability 14 11169 g020b
Figure 21. Measured waveforms of stage four: (a) vgs1, vds1, and ids1; (b) vgs2, vds2, and ids2; (c) vgs3, vds3, and ids3; (d) vgs4, vds4, and ids4; (e) vgs5, vds5, and ids5; (f) vgs6, vds6, and ids6; and (g) vgs1, in1, and in2.
Figure 21. Measured waveforms of stage four: (a) vgs1, vds1, and ids1; (b) vgs2, vds2, and ids2; (c) vgs3, vds3, and ids3; (d) vgs4, vds4, and ids4; (e) vgs5, vds5, and ids5; (f) vgs6, vds6, and ids6; and (g) vgs1, in1, and in2.
Sustainability 14 11169 g021aSustainability 14 11169 g021b
Figure 22. Step variation of the output load of the proposed topology: (a) step-up mode; (b) step-down mode.
Figure 22. Step variation of the output load of the proposed topology: (a) step-up mode; (b) step-down mode.
Sustainability 14 11169 g022
Figure 23. Efficiency curve of the proposed converter: (a) stage one; (b) stage two; (c) stage three; (d) stage four.
Figure 23. Efficiency curve of the proposed converter: (a) stage one; (b) stage two; (c) stage three; (d) stage four.
Sustainability 14 11169 g023aSustainability 14 11169 g023b
Figure 24. Power loss analysis of the proposed converter operated in step-up mode (stage three).
Figure 24. Power loss analysis of the proposed converter operated in step-up mode (stage three).
Sustainability 14 11169 g024
Figure 25. Power loss analysis of the proposed converter operated in step-down mode (stage four).
Figure 25. Power loss analysis of the proposed converter operated in step-down mode (stage four).
Sustainability 14 11169 g025
Figure 26. Comparison of efficiency: (a) step-up mode; (b) step-down mode [15,16,17,18,19].
Figure 26. Comparison of efficiency: (a) step-up mode; (b) step-down mode [15,16,17,18,19].
Sustainability 14 11169 g026
Table 1. Electrical specifications and component parameters of the proposed topology.
Table 1. Electrical specifications and component parameters of the proposed topology.
ParameterSpecification
Input PV voltage VPV48 V
Battery voltage VBat24 V
High-side voltgae VH400 V
Maximus output battery power500 W
Maximus output load bus power500 W
Switching frequency fs40 kHz
ComponentModelSpecification
S1, S2, S3 and S4IRFP4568PbF150 V/171 A
S5 and S6IXFH60N50P3500 V/60 A
C1Electroytic Capacitor50 μF/100 V
C2 and C3Electroytic Capacitor330 μF/450 V
LMPP Ring Core40 μH
LmMPP Ring Core170 μH
Table 2. Comparison of related literature of three-port bidirectional converters.
Table 2. Comparison of related literature of three-port bidirectional converters.
Item/Ref.[15][16][17][18][19]Proposed Converter
Voltage of input/battery/output (V)48/40/40030/48/40030/24/40024/24/20024/48/40048/24/400
Rated power200 W150 W200 W500 W300W500 W
MOSFETs343436
Diodes763350
Capacitors458465
Magnetic elements224222
Efficiency of step-up mode92.9%95.3%95.5%95.3%94%94.5%
Voltage gain of step-up mode PV-DC bus 1 + N 1 D 1 + N 1 D N 1 D N 1 D 1 + N 1 D N ( 1 D ) D
Voltage gain of step-down mode DC bus-Battery 1 D 1 + N D 1 D N 1 D N 1 D 1 + N ( 1 D ) D N
Switching frequency100 kHz50 kHz100 kHz50 kHz50 kHz40 kHz
IsolatedNONOYesYesNOYes
Operational mode343334
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Wu, Y.-E.; Hong, R.-R. Multi-Functional Isolated Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems. Sustainability 2022, 14, 11169. https://doi.org/10.3390/su141811169

AMA Style

Wu Y-E, Hong R-R. Multi-Functional Isolated Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems. Sustainability. 2022; 14(18):11169. https://doi.org/10.3390/su141811169

Chicago/Turabian Style

Wu, Yu-En, and Rui-Ru Hong. 2022. "Multi-Functional Isolated Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems" Sustainability 14, no. 18: 11169. https://doi.org/10.3390/su141811169

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop