Optimized Circulating Current Control and Enhanced AC Fault Ride-through Capability Using Model Predictive Control for MMC-HVDC Applications

by
Jahangeer Badar Soomro
1,
Faheem Akhtar Chachar
1,
Madad Ali Shah
1,
Abdul Aziz Memon
1,
Faisal Alsaif
2,* and
Sager Alsulamy
3
1
Department of Electrical Engineering, Sukkur IBA University, Sukkur 65200, Pakistan
2
Department of Electrical Engineering, College of Engineering, King Saud University, Riyadh 11421, Saudi Arabia
3
Sustainable Energy Research Group, Energy & Climate Change Division, Faculty of Engineering & Physical Sciences, University of Southampton, Southampton SO16 7QF, UK
*
Author to whom correspondence should be addressed.
Energies 2023, 16(13), 5159; https://doi.org/10.3390/en16135159
Submission received: 18 May 2023 / Revised: 11 June 2023 / Accepted: 22 June 2023 / Published: 4 July 2023
(This article belongs to the Special Issue Electrical Power System Dynamics: Stability and Control II)

Abstract

:
This paper presents a novel model predictive control (MPC) approach for suppressing circulating currents in MMC-based HVDC systems. The proposed MPC eliminates the need for PI-regulators and pulse width modulators, resulting in improved dynamic response and controllability. The methodology demonstrates exceptional efficacy in controlling output current and addressing voltage ripple concerns associated with sub module (SM) capacitors. An innovative, communication-free fault ride-through (FRT) method is also introduced, eliminating the need for a DC chopper and ensuring rapid recovery following faults. To overcome the computational challenges associated with the traditional MPC algorithm, an aggregate model of the MMC is proposed, significantly reducing predicted states, hardware requirements, and calculations. Simulations validate the robustness of the proposed MPC control algorithm in tracking AC side current, suppressing circulating current, and regulating capacitor voltages under various scenarios. Future research will explore system expansion, integration with renewable energy sources, and hardware-in-loop setup testing for further validation.

1. Introduction

HVDC is preferred over HVAC due to its higher efficiency, lower transmission losses, and ability to transmit power over long distances with lower costs. HVDC allows for asynchronous interconnections between grids with different frequencies and has a smaller footprint and lower electromagnetic interference compared to HVAC [1,2]. Additionally, HVDC technology is becoming increasingly advanced and cost-effective, making it a more attractive option for large-scale power transmission projects [3,4].
In HVDC projects, two converter topologies are commonly used: line-commutated converter (LCC) and voltage-source converter (VSC). While LCC converters have been widely used in HVDC projects for many years, VSC converters have gained popularity due to their superior performance and flexibility [5,6]. VSC converters are capable of reactive power control, which allows better system stability and control, and they are able to operate with a wider range of power flow directions. Within the VSC topology, the MMC, as shown in Figure 1, is considered a robust topology due to its ability to operate even with a high number of faulty components, making it ideal for high-voltage applications. Additionally, MMCs offer high power quality and low harmonic distortion, making them suitable for sensitive loads such as hospitals and data centers [7].
AC fault, such as voltage dip on the grid side in MMC-HVDC, can result in DC link fluctuation issues which stem from power imbalances between the sending-end converter (SEC) and receiving-end converter (REC) [8,9]. These imbalances jeopardize the performance of the MMC-HVDC system. Current grid code requirements mandate that the load receives constant and desired power even during AC fault, such as voltage dip [10]. Consequently, it is crucial to develop a communication-free, robust AC FRT technique that ensures smooth and ripple-free DC link voltages and can be validated through testing under AC fault, such as voltage dip.
Unmanageable circulating currents within MMCs can result in a range of adverse consequences, such as increased power losses, overheating of components, voltage instability, harmonic distortion, and diminished system reliability [11,12,13,14,15]. A review of the literature indicates a need for integrated control strategies that not only suppress circulating currents but also tackle the issue of capacitor voltage ripple (CVR).
In this research work, we introduce a comprehensive control strategy for the MMC-HVDC system that is characterized by its robustness, demonstrated through its AC FRT capability and internal dynamics control. Our approach effectively minimizes circulating current and addresses the problem of capacitor voltage ripple. Furthermore, we propose a communication-free improved FRT method, eliminating the need for a DC chopper.

2. Comparison with Previous Research

Various circulating current suppression and capacitor voltage balancing approaches have been extensively investigated for MMCs. In [16], an arm-level control scheme using the vector current control principle and a proportional resonant (PR) controller was proposed. The scheme’s validity was demonstrated by comparing it with leg-level control based on a PR controller. In [17], an integral backstepping controller (IBS) outperformed the PR controller in suppressing circulating current and reducing CVR. In [18], an adaptive proportional integral (API) controller was shown to be more effective than the PR controller in suppressing circulating current. In [19], sliding mode control (SMC) was used to control output and circulating current, and its effectiveness was compared with the traditional PR controller. While these methods have been implemented at the unit level, their integration into HVDC systems and resilience in different fault scenarios have not been explored [16,17,18,19].
SM CVR and circulating current reduction in MMCs are challenging during AC fault (voltage dip). Exceeding safe limits can lead to converter tripping and stability issues. Strategies addressing MMC SM CVR and circulating current under AC fault, such as voltage dip conditions, are reported in the literature [20,21]. The goal is to ensure that CVR and circulating current operate within safe limits. However, studies focused on internal dynamic control (circulating current and CVR) without addressing outer loop implementation. Research was limited to unit-level MMC control and excluded transient analysis under different AC and DC faults [20,21].
Extensive research has been conducted on AC faults within HVDC. For HVDC systems, safeguarding against DC side faults has consistently been a primary research interest [22]. Various scholars have put forth diverse control and protection approaches to enhance the AC FRT capabilities of HVDC systems, as seen in references [23,24,25,26,27]. The stringent need for FRT in ensuring the grid’s secure functioning during transients with minimal power disruptions serves as the motivation for these challenges [28]. Nonetheless, the risks associated with this requirement can be substantial during faults, such as power imbalances and increased DC bus voltage, potentially leading to damage to the DC cable in the event of symmetrical and asymmetrical faults. Under such circumstances, swift control measures can help rectify imbalances in DC voltage and power. Moreover, a HVDC system necessitates a high-quality power supply with a reduced THD when inverters are used to power passive loads from DC buses. Voltage dips, whether single or three-phase, can result in considerable damage to electrical equipment [29].
Certain suggested FRT systems, which concentrate on linking two AC grids, rely on a communication channel. For example, the study presented in [30] discovered that the point of common coupling (PCC) voltages observed on both ends of the DC link dictate the active power set point for the slave terminal. Consequently, the active power reference is automatically reduced if a voltage dip occurs on either side of the DC link. While employing a communication link generally leads to improved DC voltage performance, it also incurs additional costs and carries the risk of communication failure.
Furthermore, minimal efforts have been made to address voltage dip issues for passive loads in HVDC systems. The proposed remedies typically involve drawing a higher current from the grid during faults to keep the DC bus voltage stable. This approach necessitates the design of an oversized converter, which is not a cost-effective solution. A control method aimed at diminishing temporary voltage dips (AC FRT) for HVDC systems utilizing MMC was introduced in [31]. The goal was to employ the internal energy retained in MMC to deliver consistent power to passive loads during grid voltage dips. Nevertheless, the circulating current and CVR issues were not the primary focuses of these studies.
To overcome the issues mentioned above, in this research paper, MPC has been proposed for suppressing circulating currents in MMC-HVDC systems using the MATLAB/SIMULINK environment. The principal contributions of this research work include:
  • The proposed MPC has no need for PI-regulators and pulse width modulators, thereby significantly enhancing dynamic response and controllability.
  • The proposed MPC shows remarkable effectiveness not only in regulating circulating currents but also in controlling output current and addressing the voltage ripple issues linked to SM capacitors.
  • Proposal of a novel communication-free, improved FRT method, eliminating the need for a DC chopper.
  • The advanced FRT method guarantees quick recovery post-fault occurrence while effectively keeping DC link and capacitor voltages within safe boundaries.
The conventional MPC algorithm necessitates the evaluation of all potential switching states during each control period [32,33], making it a laborious and time-consuming process. For instance, with n = 10 SMs, the number of combinations can be calculated using the binomial coefficient 3 C 2 N N = 554,268, where for each phase, there are C 2 N N = 184,756 combinations. Consequently, even with advanced microprocessors, traditional MPC remains impractical. However, this study presents a novel approach by proposing an aggregate model of the MMC, which eliminates the need for voltage sorting of capacitors. This innovation significantly reduces the number of predicted states, hardware requirements for sorting, and computational complexity.
A high-level summary is presented in Table 1, providing a comparison between the proposed method and existing approaches.

3. Proposed MPC for MMC-HVDC System

Among the advanced control strategies, MPC is the one that has gained significant attention in HVDC MMC applications. Although it was impractical at first to apply the technique to applications that had greater switching frequencies due to extensive calculations that would take a long time to complete, the MPC approach is increasingly being utilized for controlling power converters, owing to advancements in processor speed and features like rapid response, the straightforward integration of nonlinearities, adaptability to various objectives, and the presence of uncomplicated modulation methods [34]. The main characteristic of MPC is the use of the system model to examine the future behavior of the controlled variables. Based on this information, the controller provides optimal gate drives for the switches of the MMC to operate at optimal conditions. Figure 2 illustrates the block diagram of the suggested MPC approach for MMC.
The objectives of the MPC are to track the AC current and restrict the circulating current. The algorithm achieves those objectives by performing the following tasks:
  • Anticipating the performance of controlled variables across all potential switching states;
  • Assessing the cost function corresponding to each prediction;
  • Choosing the switching state that results in a minimized cost function.

3.1. AC Current Tracking

The objective of the tracking of the AC current is to maintain the ac side current of MMC at a reference value. Figure 3 shows the single-phase equivalent diagram of three-phase MMC.
Where i u j and i l j are the upper and lower arm currents, u j p and u j n are the upper and lower arm voltages, e j is the grid side voltage, and i d i f f j is the inner unbalanced current. Based on Figure 3, the equation for the voltage of the MMC can be written as Equation (2), where L = l + L / 2 and R = r + R / 2 .
L d i j ( t ) d t = e j ( t ) u j n ( t ) u j p ( t ) 2 R i j
Applying Euler approximation on (2), the ac side current can be written as Equation (3).
i j ( t + T s ) = T s R + L e j ( t + T s ) u j n ( t + T s ) u j p ( t + T s ) 2 + L T s i j ( t )
where T s is the sampling time, i j ( t + T s ) and i j ( t ) are the predicted and measured currents, respectively, and e j ( t + T s ) is the grid side one step forward voltage. If T s is assumed to be a very small value, then e j ( t + T s ) will become e j ( t ) . Here, u j p ( t + T s ) and u j n ( t + T s ) are the one step forward predicted upper and lower arm capacitor voltages inserted in SMs. Thus, the cost function of the ac current tracking is defined as:
J 1 = | i j r e f ( t + T s ) i j ( t + T s ) |

3.2. Restricting Circulating Current

The objective is to restrict the circulating current to the reference value so that the efficiency of the system is improved. The voltage and the inner unbalanced current equation are shown in Equations (5) and (6).
i j d i f f = i u j + i l j 2
L d i j d i f f ( t ) d t = V d c 2 u j n ( t ) + u j p 2
Applying Euler approximation on (6), the expression for the circulating current becomes:
i j d i f f ( t + T s ) = T s 2 L V d c u j n ( t + T s ) u j p ( t + T s ) + i j d i f f ( t )
where i j d i f f ( t ) and i j d i f f ( t + T s ) are the measured and predicted circulating current and i j d i f f ( t ) can be calculated from (5); u j p ( t + T s ) and u j n ( t + T s ) are the one step forward predicted upper and lower arm capacitor voltages inserted in submodules. Thus, the cost function of the circulating current is defined as:
J 2 = | i j d i f f _ r e f ( t + T s ) i j d i f f ( t + T s ) |

3.3. Cost Function

The cost function assesses all the predicted states within each control period, selecting the optimal switching states that minimize the cost. It can comprise multiple subsets of cost functions, achieving diverse objectives simultaneously through the use of weighting factors [35]. The cost function might incorporate control objectives like lowering switching frequency, reducing common-mode voltage, decreasing reactive power, and minimizing current ripple to manage the MMC. The algorithm’s cost function is formulated as depicted in Equation (1).
j m = λ 1 J 1 + λ 2 J 2
Generally, the MPC approach uses weighing factors to combine subsets of the cost function into a single cost function. The procedure to determine the weighting factors is based on the empirical method presented in [36].
Figure 4 is the flow diagram of MPC that demonstrates the implementation process of the algorithm. The subsets of the cost function J 1 and J 2 are calculated based on Equations (3) and (7) and then the algorithm evaluates the cost function J m for all possible switching states and selects the one with the minimum value for J m . These switching states are applied to the SMs and the algorithm eventually tracks the ac current and restricts the circulating current.

4. Proposed System Description

A 220MVA MMC-HVDC system is examined in the Matlab/Simulink environment. The simulated system has a DC bus voltage of 135 kV and is a 51-level MMC-HVDC system connected to a 66 kV grid. The load system consists of a 110 MW passive load. The performance of the simulation is improved by using an aggregate modelling method. The system is used in islanded mode, which means that the rectifier controls the DC bus voltage while the inverter primarily controls the AC voltage of the passive network. For the control of the system, the MPC algorithm is used, which has the primary functions of AC current tracking and suppressing the circulating current. The power electronic converters are very sensitive to an overcurrent that can last up to several cycles. To address this issue, a three-phase static thyristor AC breaker bypass system is implemented and synced with the grid. MMC and grid parameters are shown in Table 2 and load parameters are summarized in Table 3. The detailed MPC control system applied on MMC 1 and MMC 2 station on an MMC-HVDC system is shown in Figure 5.

5. Result Discussions

5.1. Simulation Results for Proposed MPC-Based MMC-HVDC under Steady-State Operation

A crucial component of the converter’s viability is determining its startup and steady-state operation. The startup charging current is controlled by inserting the charging resistors, providing the converter with initial energy. The circuit breaker is energized in 0.1 s, as can be observed in Figure 6a,b. The breaker and controllers can be systematically operated, and the converter can charge up the SMs capacitors and reach steady state in less than one second. The grid voltage is kept at its nominal value, which is 66 kV. Circulating current suppression and DC voltage regulation of the rectifier are turned on at 0.1 and 0.4 s, respectively, which are controlled using the MPC algorithm. They enhanced the power quality and reduced THD of MMC inverter voltage, and the inverter current adheres to IEEE guidelines, as demonstrated in the magnified sections of Figure 6c and Figure 6d, respectively.
Figure 7a shows the power delivered from the inverter to the load. The nominal power of the system is 220 MW, while the load requirement is 110 MW. The MMC inverter provides constant power to the load at 0.5 p.u. The power drawn from the grid is also 0.5 p.u. as per the requirement of the load, which can be seen in Figure 7b. Figure 7c shows the DC bus power, and it can be observed that after reaching the steady state, the power has significantly lower deviations. Figure 7d presents the outcomes of simulations for DC link voltages. The suggested MPC-based circulating current suppression strategy has been implemented, resulting in more stable DC link voltages. By not requiring an extra controller, the proposed MPC-based circulating current regulation technique prevents the introduction of ripple components into the DC link voltages.
The suggested MMC-based HVDC system addresses circulating current and capacitor CVR challenges. The proposed MPC-based circulating current suppression strategy effectively reduces the circulating current for MMC rectifier and MMC inverter stations, as demonstrated in Figure 8a and Figure 8b, respectively. The magnitude of circulating current for both MMC rectifier and inverter stations is 0.05 per unit (PU), which is below 10% of the nominal current in accordance with grid regulations. As depicted in Figure 9a,b, the MMCs’ capacitor voltage for rectifier and inverter stations consistently operates within safe limits, preventing converter shutdown. Furthermore, the capacitor voltages remain balanced and exhibit decreased capacitor voltage fluctuations.
The proposed MPC-based control demonstrates strong performance in managing internal dynamics, effectively reducing circulating current and CVR issues. Consequently, the arm currents of the rectifier and inverter exhibit enhanced current quality and reduced harmonics, as illustrated in Figure 10a and Figure 10b, respectively.
Besides improved control of internal dynamics, the proposed MPC algorithm demonstrates strong performance in tracking the AC current, as depicted in Figure 11. The measured current closely aligns with the reference, underscoring the effectiveness of the suggested MPC approach. Finally, Figure 12 demonstrates that the proposed MPC control maintains a standard modulation index value of 0.8 PU, which ensures the prevention of over-modulation and under-modulation problems during MMC operation.

5.2. Simulation Results for Proposed MPC-Based MMC-HVDC under AC Fault (Voltage Dip)

The resilience of the proposed system has been evaluated in the face of AC faults, such as voltage dips. One of the significant features of the MMC is its ability to mitigate voltage dips occurring in the external grid. The voltage dip is modeled in the main source, which can be controlled to supply reduced voltage amplitude at any phase for a short duration. A voltage dip of 50% in magnitude for 75 milliseconds was introduced to assess the effectiveness of the proposed MPC algorithm, as shown in Figure 13a. It can be observed that only the grid-side voltage is affected, with a 50% decrease in magnitude, resulting in a slight increase in the grid-side current, as shown in Figure 13b. The converter station can readily accommodate this slight increase in the grid-side current. It should be noted that the MMC inverter voltage and inverter current (load side) remain unaffected by the AC fault (voltage dip), as shown in Figure 13c and Figure 13d, respectively. Moreover, the MMC inverter voltage and inverter currents maintain an excellent sinusoidal waveform, following IEEE standards.
In the presence of an AC fault, such as a voltage dip, the DC bus voltage stays above 0.8 per unit, as depicted in Figure 14a. This demonstrates the suitable dimensioning of the converters and the resilience of the proposed MPC algorithm. Additionally, during the dip, the power drawn from the grid side diminishes, as illustrated in Figure 14c, while the load consistently receives constant power, as shown in Figure 14d, due to the robustness of the algorithm. The DC bus power returns to its steady-state value, ensuring FRT capability under voltage dip conditions, as displayed in Figure 14b.
The circulating current of both MMCs under voltage dip is illustrated in Figure 15a,b. It becomes apparent that during the voltage dip, the circulating current of the rectifier experiences an increase due to the rise in grid-side current, whereas the inverter’s circulating current exhibits minimal fluctuation since the inverter-side current remains constant throughout the voltage dip. The MPC algorithm stabilizes the circulating current back to its steady state once the voltage dip concludes. During the voltage dip, the submodule capacitor is expected to safely discharge its stored energy to offset the energy loss induced by the voltage sag, as demonstrated in Figure 16a,b. The capacitor voltages remain within secure boundaries both during and after the fault. Furthermore, the circulating current not only stays within the acceptable range during the fault but is also effectively suppressed.
The circulating current flowing into the arm is effectively suppressed by the MPC, resulting in purely sinusoidal arm currents, as illustrated in Figure 17a,b. Figure 18 presents the tracking of AC current by the MPC algorithm, demonstrating that the measured AC current accurately follows the reference, regardless of the voltage dip. The rectifier’s modulation index, displayed in Figure 19, reveals a reduction by half during a voltage dip, which is attributed to the nominal current drawn by the MMC from the grid during the dip. Once the voltage dip ends, the modulation index returns to the standard value of 0.8. This observation confirms the efficacy of the proposed algorithm.
The comprehensive analysis presented above indicates that the developed system exhibits robust performance in both steady-state and voltage dip scenarios. It maintains the DC bus voltage at the standard level while ensuring consistent power delivery to the load, even during transient voltage dips. The proposed MPC algorithm effectively suppresses the circulating current, controls the capacitor voltage, robustly tracks the AC current, and maintains the modulation index at its standard value.

6. Conclusions

This paper presents the novel MPC algorithm to mitigate transient voltage dips for the MMC-HVDC system. The MPC algorithm is implemented and tested on various scenarios such as steady-state conditions and AC fault, such as three-phase voltage dips at the grid side. To develop the control algorithm, two cost functions are utilized: one for tracking the AC side current and another for suppressing the circulating current. The simulation results demonstrate the robustness of the proposed MPC control algorithm, which effectively tracks the AC current and suppresses the circulating current and regulates capacitor voltages to comply with grid standards. Importantly, the developed MPC strategies efficiently manage the DC bus voltage, ensuring stable and desired power delivery to the connected load during AC faults. The proposed control strategies have demonstrated their effectiveness through validations on point-to-point HVDC systems. However, considering the global trend towards MTDC systems, it is essential to extend these tests to assess the suitability and performance of the strategies in MMC-based MTDC systems. This extension will address the emerging challenges and requirements in the evolving power transmission landscape. Although the current study provides a comprehensive analysis of AC FRT for MMC-HVDC systems, it does not cover DC FRT mechanisms. Therefore, future research should explore the development and implementation of effective DC FRT strategies to enhance the resilience and reliability of MMC-HVDC systems during DC-side faults. Additionally, expanding the system and testing it with the integration of renewable energy sources will be a focus for future research. The performance of the proposed control strategies will be analyzed in a hardware-in-the-loop (HIL) setup, further enhancing the scope of this study.

Author Contributions

Conceptualization, J.B.S.; data curation, A.A.M.; formal analysis, A.A.M. and S.A.; funding acquisition, F.A. and S.A.; investigation, M.A.S.; methodology, J.B.S.; project administration, M.A.S. and F.A.; software, J.B.S.; supervision, F.A.C.; validation, J.B.S.; writing—original draft, J.B.S.; writing—review and editing, F.A.C. and F.A. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

Not applicable.

Acknowledgments

This work was supported by the Researchers Supporting Project number (RSPD2023R646), King Saud University, Riyadh, Saudi Arabia.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Soomro, J.B.; Akhtar, F.; Hussain, R.; Ansari, J.A.; Munir, H.M. A Detailed Review of MMC Circuit Topologies and Modelling Issues. Int. Trans. Electr. Energy Syst. 2022, 2022, 8734010. [Google Scholar] [CrossRef]
  2. Gomis-Bellmunt, O.; Bassols, J.S.; Prieto-Araujo, E.; Cheah-Mane, M. Flexible converters for meshed HVDC grids: From Flexible AC transmission systems (FACTS) to Flexible DC grids. IEEE Trans. Power Deliv. 2019, 35, 2–15. [Google Scholar] [CrossRef]
  3. Soomro, J.B.; Akhter, F.; Ali, S.; Bukhari, S.S.H.; Sami, I.; Ro, J.-S. Modified Nearest Level Modulation for Full-Bridge Based HVDC MMC in Real-Time Hardware-in-Loop Setup. IEEE Access 2021, 9, 114998–115005. [Google Scholar] [CrossRef]
  4. Ali, S.; Soomro, J.B.; Mughal, M.; Chachar, F.A.; Bukhari, S.S.H.; Ro, J.-S. Power quality improvement in HVDC MMC with modified nearest level control in real-time HIL based setup. IEEE Access 2020, 8, 221712–221719. [Google Scholar] [CrossRef]
  5. Chandio, H.R.; Chachar, F.A.; Soomro, J.B.; Ansari, J.A.; Munir, H.M.; Zawbaa, H.M.; Kamel, S. Control and protection of MMC-based HVDC systems: A review. Energy Rep. 2023, 9, 1571–1588. [Google Scholar] [CrossRef]
  6. Cui, S.; Lee, H.-J.; Jung, J.-J.; Lee, Y.; Sul, S.-K. A comprehensive AC-side single-line-to-ground fault ride through strategy of an MMC-based HVDC system. IEEE J. Emerg. Sel. Top. Power Electron. 2018, 6, 1021–1031. [Google Scholar] [CrossRef]
  7. Cui, S.; Lee, H.-J.; Jung, J.-J.; Lee, Y.; Sul, S.-K. A comprehensive AC side single line to ground fault ride through strategy of a modular multilevel converter for HVDC system. In Proceedings of the 2015 IEEE Energy Conversion Congress and Exposition (ECCE), Montreal, QC, Canada, 20–24 September 2015; pp. 5378–5385. [Google Scholar]
  8. Luo, Y.; Yi, P.; Xiaofu, X.; Jiang, W.; Yonghui, S. DC fault ride-through method for full-bridge MMC-based MTDC systems. J. Eng. 2019, 2019, 3175–3179. [Google Scholar] [CrossRef]
  9. Xin, Y.; Lou, W.; Li, G.; Jiang, S.; Wang, T.; Yang, Y. AC fault ride-through coordinated control strategy of LCC-MMC hybrid DC transmission system connected to passive networks. Int. J. Electr. Power Energy Syst. 2021, 131, 107076. [Google Scholar] [CrossRef]
  10. Zhou, Z.; Chen, Z.; Wang, X.; Du, D.; Yang, G.; Wang, Y.; Hao, L. AC fault ride through control strategy on inverter side of hybrid HVDC transmission systems. J. Mod. Power Syst. Clean Energy 2019, 7, 1129–1141. [Google Scholar] [CrossRef] [Green Version]
  11. Qingrui, T.; Xu, Z.; Xu, L. Reduced switching-frequency modulation and circulating current suppression for modular multilevel converters. IEEE Trans. Power Deliv. 2011, 26, 2009–2017. [Google Scholar] [CrossRef]
  12. Qingquan, L.; Li, B.; He, J.; Prieto-Araujo, E.; Spier, D.W.; Lyu, H.; Gomis-Bellmunt, O. A novel design of circulating current control target to minimize SM capacitance in MMC. Int. J. Electr. Power Energy Syst. 2022, 143, 108432. [Google Scholar]
  13. Miguel, M.; Bueno, E.; Sanz, I.; Rodríguez, F.J. New approaches to circulating current controllers for modular multilevel converters. Energies 2017, 10, 86. [Google Scholar]
  14. Behrooz, B.; Debnath, S.; Saeedifard, M. Circulating current suppression of the modular multilevel converter in a double-frequency rotating reference frame. IEEE Trans. Power Electron. 2015, 31, 783–792. [Google Scholar]
  15. Nasiru, B.K.; Dahidah, M.; Ethni, S.; Muhammad, M. Lifetime and reliability im-provements in modular multilevel converters using controlled circulating current. J. Power Electron. 2021, 21, 1611–1620. [Google Scholar]
  16. Waqar, U.; Busarello, T.D.; Zeb, K.; Khan, M.A.; Yedluri, A.K.; Kim, H.-J. Control Strategy Based on Arm-Level Control for Output and Circulating Current of MMC in Stationary Reference Frame. Energies 2021, 14, 4160. [Google Scholar]
  17. Muhammad, I.; Uddin, W.; Zeb, K.; Khan, I.; Islam, S.U.; Khan, M.A.; Kim, H.J. Output Current Control of Modular MultiLevel Converter Using BackStepping Controller. In Proceedings of the 2019 15th International Conference on Emerging Technologies (ICET), Peshawar, Pakistan, 2–3 December 2019; pp. 1–5. [Google Scholar]
  18. Ishfaq, M.; Uddin, W.; Zeb, K.; Khan, I.; Islam, S.U.; Khan, M.A.; Kim, H.J. A new adaptive approach to control circulating and output current of modular multilevel converter. Energies 2019, 12, 1118. [Google Scholar] [CrossRef] [Green Version]
  19. Waqar, U.; Zeb, K.; Khan, M.A.; Ishfaq, M.; Khan, I.; Islam, S.; Kim, H.-J.; Park, G.S.; Lee, C. Control of output and circulating current of modular multilevel converter using a sliding mode approach. Energies 2019, 12, 4084. [Google Scholar]
  20. Songda, W.; Teodorescu, R.; Chaudhary, S.K. Capacitor voltage ripple reduction methods of modular multilevel converter under unbalanced fault conditions: A comparison. In Proceedings of the 2018 IEEE International Power Electronics and Application Conference and Exposition (PEAC), Shenzhen, China, 4–7 November 2018; pp. 1–6. [Google Scholar]
  21. Songda, W.; Bao, D.; Gontijo, G.; Chaudhary, S.; Teodorescu, R. Modeling and Mitigation Control of the Submodule-Capacitor Voltage Ripple of a Modular Multilevel Converter under Unbalanced Grid Conditions. Energies 2021, 14, 651. [Google Scholar]
  22. Nazmus, S.M.; Azad, S.P.; Kazerani, M. A critical review of modular multilevel converter con-figurations and submodule topologies from DC fault blocking and ride-through capabilities viewpoints for HVDC applica-tions. Energies 2022, 15, 4176. [Google Scholar]
  23. Xinyu, L.; Xu, Z.; Wang, G.; Li, X. Accurate estimation on AC short-circuit current for grid-connected MMC-HVDC system considering FRT and various control modes. Int. J. Electr. Power Energy Syst. 2022, 136, 107683. [Google Scholar]
  24. Ashrafi, N.S.H.; Liu, Z.; Chen, Z.; Bak-Jensen, B.; Hu, S. Protection system of multi-terminal MMC-based HVDC grids: A survey. In Proceedings of the 2022 International Conference on Power Energy Systems and Applications (ICoPESA), Singapore, 25–27 February 2022; pp. 167–177. [Google Scholar]
  25. Mahmoud, M.E.; Izzularab, M.A.; Zhang, X.-P. Technical treating and riding-through symmetrical grid faults for MMC-HVDC connected offshore wind farms. In Proceedings of the 2022 23rd International Middle East Power Systems Conference (MEPCON), Cairo, Egypt, 13–15 December 2022; pp. 1–6. [Google Scholar]
  26. Wenqiang, W.; Jia, K.; Hou, L.; Sun, J.; Liu, B. Coordinated control strategy to enhance FRT capacity for offshore wind farms connected MMC-HVDC. In Conference Proceedings of 2021 International Joint Conference on Energy, Electrical and Power Engineering: Power Electronics, Energy Storage and System Control in Energy and Electrical Power Systems; Springer Nature: Singapore, 2022; pp. 255–261. [Google Scholar]
  27. Carolin, H.; Goertz, M.; Wenig, S.; Bisseling, A.; Suriyah, M.; Leibfried, T. On Fault-Ride-Through Performance in MMC-HVDC Applications Controlled as a Virtual Synchronous Machine. IEEE Trans. Energy Convers. 2022, 37, 2803–2812. [Google Scholar]
  28. Haihan, Y.; Chen, W.; Wu, H.; Cao, W.; He, G.; Li, G. Enhanced AC Fault Ride-Through Control for MMC-Integrated System Based on Active PCC Voltage Drop. J. Mod. Power Syst. Clean Energy 2022, 1–15. [Google Scholar]
  29. Kordkheili, H.; Farhan, S.; Hamzeh, M. AC Fault ride-through strategy for MMC-based HVDC systems with short lines. In Proceedings of the 2023 14th Power Electronics, Drive Systems, and Technologies Conference (PEDSTC), Babol, Iran, 31 January–2 February 2023; pp. 1–6. [Google Scholar]
  30. Adam, G.P.; Ahmed, K.H.; Finney, S.J.; Williams, B.W. AC fault ride-through capability of a VSC-HVDC transmission systems. In Proceedings of the 2010 IEEE Energy Conversion Congress and Exposition, Atlanta, GA, USA, 12–16 September 2010; pp. 3739–3745. [Google Scholar] [CrossRef]
  31. Endre, S.T. Development of a Power Quality Conditioning System for Particle Accelerators. Ph.D. Thesis, Norwegian University of Science and Technology, Trondheim, Norway, 2018. [Google Scholar]
  32. Cortes, P.; Kouro, S.; La Rocca, B.; Vargas, R.; Rodriguez, J.; Leon, J.I.; Vazquez, S.; Franquelo, L.G. Guidelines for weighting factors design in model predictive control of power converters and drives. In Proceedings of the 2009 IEEE International Conference on Industrial Technology, Churchill, VIC, Australia, 10–13 February 2009; pp. 1–7. [Google Scholar]
  33. Perez, M.A.; Fuentes, E.; Rodriguez, J. Predictive current control of ac-ac modular multilevel converters. In Proceedings of the 2010 IEEE International Conference on Industrial Technology, Via del Mar, Chile, 14–17 March 2010; pp. 1289–1294. [Google Scholar]
  34. Riar, B.S.; Geyer, T.; Madawala, U.K. Model Predictive Direct Current Control of Modular Multilevel Converters: Modeling, Analysis, and Experimental Evaluation. IEEE Trans. Power Electron. 2015, 30, 431–439. [Google Scholar] [CrossRef]
  35. Liu, P.; Wang, Y.; Cong, W.; Lei, W. Grouping-Sorting-Optimized Model Predictive Control for Modular Multilevel Converter with Reduced Computational Load. IEEE Trans. Power Electron. 2015, 31, 1896–1907. [Google Scholar] [CrossRef]
  36. Yuebin, Z.; Daozhuo, J.; Jie, G.; Pengfei, H.; Zhiyong, L. Control of modular multilevel converter based on stationary frame under unbalanced AC system. In Proceedings of the 2012 Third International Conference on Digital Manufacturing & Automation, Guilin, China, 31 July–2 August 2012; pp. 293–296. [Google Scholar]
Figure 1. Three-phase equivalent structure of an MMC.
Figure 1. Three-phase equivalent structure of an MMC.
Energies 16 05159 g001
Figure 2. Block diagram of proposed MPC.
Figure 2. Block diagram of proposed MPC.
Energies 16 05159 g002
Figure 3. Single-phase equivalent of three-phase MMC.
Figure 3. Single-phase equivalent of three-phase MMC.
Energies 16 05159 g003
Figure 4. Flowchart of proposed MPC algorithm.
Figure 4. Flowchart of proposed MPC algorithm.
Energies 16 05159 g004
Figure 5. Detailed MPC control system applied on proposed system description.
Figure 5. Detailed MPC control system applied on proposed system description.
Energies 16 05159 g005
Figure 6. (a) Grid voltage to the rectifier station. (b) Grid current. (c) Inverter voltage. (d) Inverter current.
Figure 6. (a) Grid voltage to the rectifier station. (b) Grid current. (c) Inverter voltage. (d) Inverter current.
Energies 16 05159 g006
Figure 7. (a) Power delivered from inverter to load. (b) Power consumed by rectifier. (c) DC bus power and (d) DC bus voltage.
Figure 7. (a) Power delivered from inverter to load. (b) Power consumed by rectifier. (c) DC bus power and (d) DC bus voltage.
Energies 16 05159 g007aEnergies 16 05159 g007b
Figure 8. (a) Circulating current of MMC rectifier; (b) circulating current of MMC inverter.
Figure 8. (a) Circulating current of MMC rectifier; (b) circulating current of MMC inverter.
Energies 16 05159 g008
Figure 9. (a) SM capacitor voltage of MMC rectifier; (b) SM capacitor voltage of MMC inverter.
Figure 9. (a) SM capacitor voltage of MMC rectifier; (b) SM capacitor voltage of MMC inverter.
Energies 16 05159 g009
Figure 10. (a) MMC arm current rectifier; (b) MMC arm current inverter.
Figure 10. (a) MMC arm current rectifier; (b) MMC arm current inverter.
Energies 16 05159 g010
Figure 11. AC Current tracking by MPC algorithm.
Figure 11. AC Current tracking by MPC algorithm.
Energies 16 05159 g011
Figure 12. Modulation index of MMC rectifier.
Figure 12. Modulation index of MMC rectifier.
Energies 16 05159 g012
Figure 13. Results under AC fault (Voltage Dip): (a) grid voltage to the rectifier station; (b) grid current; (c) inverter voltage; (d) inverter current.
Figure 13. Results under AC fault (Voltage Dip): (a) grid voltage to the rectifier station; (b) grid current; (c) inverter voltage; (d) inverter current.
Energies 16 05159 g013aEnergies 16 05159 g013b
Figure 14. Results under AC fault (voltage dip): (a) DC bus voltage; (b) DC bus power; (c) power consumed by rectifier; (d) power delivered from inverter to load.
Figure 14. Results under AC fault (voltage dip): (a) DC bus voltage; (b) DC bus power; (c) power consumed by rectifier; (d) power delivered from inverter to load.
Energies 16 05159 g014
Figure 15. Results under AC fault (voltage dip): (a) circulating current of MMC rectifier; (b) circulating current of MMC inverter.
Figure 15. Results under AC fault (voltage dip): (a) circulating current of MMC rectifier; (b) circulating current of MMC inverter.
Energies 16 05159 g015
Figure 16. Results under AC fault (voltage dip): (a) SM capacitor voltage of MMC rectifier; (b) SM capacitor voltage of MMC inverter.
Figure 16. Results under AC fault (voltage dip): (a) SM capacitor voltage of MMC rectifier; (b) SM capacitor voltage of MMC inverter.
Energies 16 05159 g016aEnergies 16 05159 g016b
Figure 17. Results under AC fault (voltage dip): (a) MMC arm current rectifier; (b) MMC arm current inverter.
Figure 17. Results under AC fault (voltage dip): (a) MMC arm current rectifier; (b) MMC arm current inverter.
Energies 16 05159 g017
Figure 18. AC Current tracking by MPC algorithm under AC fault (voltage dip).
Figure 18. AC Current tracking by MPC algorithm under AC fault (voltage dip).
Energies 16 05159 g018
Figure 19. Modulation index of MMC rectifier under AC fault (voltage dip).
Figure 19. Modulation index of MMC rectifier under AC fault (voltage dip).
Energies 16 05159 g019
Table 1. Comparison between proposed method and existing approaches.
Table 1. Comparison between proposed method and existing approaches.
Study Ref.Control MethodMajor Findings and Limitations
[16]Vector current control with PR controllerValidated at arm level, performed better than leg-level control with PR controller. No HVDC integration or fault scenario resilience tested.
[17]Integral backstepping controller (IBS)Suppressed circulating current and reduced CVR more effectively than PR controller. No HVDC integration or fault scenario resilience tested.
[18]Adaptive proportional integral (API) controllerMore effective than PR controller in suppressing circulating current. No HVDC integration or fault scenario resilience tested.
[19]Sliding mode control (SMC)Controlled output and circulating current effectively compared to PR controller. No HVDC integration or fault scenario resilience tested.
[20,21]Various MMC SM CVR and circulating current control under AC faultEnsured safe operation limits during AC faults. No transient analysis under different AC and DC faults.
[22,23,24,25,26,27]Various control and protection approaches for HVDCEnhanced AC FRT capabilities, yet risks were present during faults, causing power imbalances and increased DC bus voltage.
[30]FRT systems with communication linkAchieved improved DC voltage performance but at the cost of potential communication failure and additional costs.
[31]Control method aimed at diminishing voltage dips for HVDCUsed internal energy of MMC to provide consistent power during voltage dips. Did not focus on circulating current and CVR issues.
This StudyProposed model predictive control (MPC)Effectively regulated circulating currents and controlled output current. Eliminated need for PI-regulators and pulse width modulators. Proposed a novel communication-free, improved FRT method.
Table 2. MMC and grid parameters.
Table 2. MMC and grid parameters.
ParametersSymbolsValueUnit
grid voltage (line–line) v s 66,000V
grid frequencyF50Hz
dc-link voltageVdc135,000V
arm resistancerarm0.5
arm inductancelarm0.0207mH
number of SMsn50
SMs CapacitanceCSM15mF
Table 3. Load parameters.
Table 3. Load parameters.
ParametersSymbolsValueUnit
nominal power for convertersPnom220MW
nominal apparent power for convertersSnom220MVA
nominal line currentInom1.9kA
startup resistance for inrushrstartup17
load active power nominalPload110MW
load reactive power nominalQload0VAR
apparent load powerSload110MVA
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Soomro, J.B.; Chachar, F.A.; Shah, M.A.; Memon, A.A.; Alsaif, F.; Alsulamy, S. Optimized Circulating Current Control and Enhanced AC Fault Ride-through Capability Using Model Predictive Control for MMC-HVDC Applications. Energies 2023, 16, 5159. https://doi.org/10.3390/en16135159

AMA Style

Soomro JB, Chachar FA, Shah MA, Memon AA, Alsaif F, Alsulamy S. Optimized Circulating Current Control and Enhanced AC Fault Ride-through Capability Using Model Predictive Control for MMC-HVDC Applications. Energies. 2023; 16(13):5159. https://doi.org/10.3390/en16135159

Chicago/Turabian Style

Soomro, Jahangeer Badar, Faheem Akhtar Chachar, Madad Ali Shah, Abdul Aziz Memon, Faisal Alsaif, and Sager Alsulamy. 2023. "Optimized Circulating Current Control and Enhanced AC Fault Ride-through Capability Using Model Predictive Control for MMC-HVDC Applications" Energies 16, no. 13: 5159. https://doi.org/10.3390/en16135159

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop