Article

Design of State Feedback Current Controller for Fast Synchronization of DFIG in Wind Power Generation Systems

1
Department of Electrical Engineering, College of Engineering, Majmaah University, Almajmaah 11952, Saudi Arabia
2
Department of Electrical Engineering, College of Engineering, Assuit University, Assuit 71515, Egypt
3
Sustainable Energy Technologies Center, King Saud University, Riyadh 11421, Saudi Arabia
4
Department of Electrical Engineering, Mansoura University, Mansoura 35516, Egypt
5
Electrical Engineering Department, College of Engineering, King Saud University, Riyadh 11421, Saudi Arabia
6
Saudi Electricity Company Chair in Power System Reliability and Security, King Saud University, Riyadh 11421, Saudi Arabia
7
Electrical Engineering Department, College of Engineering, Sohag University, Sohag 82524, Egypt
8
Electrical Engineering Department, College of Engineering, Kerala Technological University, Kerala 695034, India
9
Department of Mechanical and Industrial Engineering, College of Engineering, Majmaah University, Almajmaah 11952, Saudi Arabia
*
Author to whom correspondence should be addressed.
Energies 2019, 12(12), 2427; https://doi.org/10.3390/en12122427
Submission received: 16 May 2019 / Revised: 18 June 2019 / Accepted: 20 June 2019 / Published: 24 June 2019
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
Doubly-fed induction generators (DFIGs) are widely used in wind energy conversion systems. The dynamic features of DFIGs make it important to focus on designing high-performance control schemes. However, the dynamic characteristics of such generators depend on nonlinear parameters, such as stator flux, stator current, and rotor current, which increase the overall system complexity. In addition, the DFIG Wind Energy Conversion Systems (WECSs) size is growing beyond 7 MW, which increases stress on both the mechanical drive train and the power circuits during connection to the grid. Such stress and dynamic features cannot be neglected. Therefore, robust controllers must be implemented which have the ability to support the dynamic frequencies of wind energy to ensure system stability in grid connection mode and during subsequent use. Conventional vector control configurations that use proportional-integral controllers have various drawbacks, such as parameter tuning difficulties, mediocre dynamic performance, and reduced robustness. In this study, we focused on improving DFIG synchronization to the grid by applying state feedback current controllers with a feedforward component to smooth the connection to the grid, as well as to improve the steady-state and transient characteristics of the controller. State feedback controllers are proposed to replace the proportional-integral controllers on both the rotor and grid sides. The proposed controller is designed using a multivariable system and feedforward control for input reference and incorporating disturbances into the control equations for fast synchronization and transient responses. To demonstrate the advantages of this controller, experimental studies are presented for both the transient and steady states.

1. Introduction

Doubly-fed induction generators (DFIGs) have been widely used for both grid-connected and standalone wind energy conversion systems (WECSs). The main advantages of a DFIG are its efficient four-quadrant active and reactive power capability, flexibility for variable-speed wind turbines, lower converter equipment cost compared to permanent magnet synchronous generators or squirrel-cage-based wind power topologies with full power inverters, and lower power loss compared to synchronous and asynchronous generators with full-scale converters [1,2,3]. Currently, 50% of the wind energy market uses DFIG systems owing to their cost and size advantages [4,5].
Conventional grid-connected DFIG topologies use a back-to-back converter in the rotor circuit and the stator is connected directly to the grid, as depicted in Figure 1. The back-to-back converter consists of a rotor-side converter (RSC) and a grid-side converter (GSC). The RSC provides a magnetizing current to the rotor windings and controls both active and reactive power at the stator terminals. Furthermore, the RSC controls the stator active power to extract the maximum possible power from wind and enhance power quality through harmonic current filtering [6,7,8,9]. The RSC is also used to smooth stator synchronization with the grid in a zero current connection and a negligible effect to the supply and the generator. Moreover, the RSC should be designed to fulfil the grid code requirements to minimize the connection currents on the net connecting point. The main function of the GSC is to maintain a constant DC link voltage, regardless of power flow direction, and to control the magnitude and direction of rotor reactive power. The GSC is also used to remove reactive power pulsation under unbalanced conditions [10,11,12].
Power converter performance largely depends on the accuracy of the implemented control strategy. Therefore, converter current controller performance is one of the most critical issues in power electronics circuits. The quality of a current controller can be evaluated based on several basic requirements [13]:
  • Over a wide output frequency range, both phase and amplitude errors should be zero.
  • The controller should have a fast-dynamic response.
  • The effects of load parameters changes should be compensated for.
  • Constant or limited switching frequencies should ensure reasonable lifetimes for power electronics semiconductor devices.
  • Total harmonic distortion should be minimized.
The current controller techniques listed in the literature can be divided into two main categories [14,15,16]: linear and nonlinear controllers. Proportional-integral (PI) stationary and synchronous, state feedback, and deadbeat controllers are examples of linear control techniques. These methods were introduced in [17,18].
The stationary PI technique has a major drawback in its inherent amplitude and phase error. To solve this problem and perform error compensation, several solutions have been proposed, such as using additional phase-locked loop (PLL) circuits [19] or feedforward correction [20]. However, when using asynchronous PI controller, the fundamental component error can be regulated to zero [20], but dynamic properties are still an issue.
Another well-known controller, namely, the deadbeat controller, was designed to ensure strong dynamic responses [21]. The main advantages of this controller are that voltage measurements are not required to generate current references [22]. However, this controller suffers from a serious drawback in the form of inherent delays due to calculations. Furthermore, this controller does not include an integral control, which introduces steady-state errors.
The nonlinear controller category includes fuzzy logic controllers (FLC) and hysteresis controllers. A hysteresis current controller is typically implemented for the sake of simplicity. This method does not require any prior information regarding load parameters and has fast response. However, based on a fixed hysteresis band, this current controller has a narrow band of switching frequencies for minimizing the peak-to-peak current ripple at all points of the fundamental frequency wave [23].
Another nonlinear controller, the FLC, is typically implemented as an alternative to a conventional PI compensator [24,25]. For this controller, the design steps and controller accuracy depend on the knowledge and experience of the user.
To compensate for these drawbacks, a state feedback controller working with stationary or synchronous rotating coordinates can replace a conventional PI controller. In this controller, a feedback gain matrix can be calculated to ensure sufficient damping. Furthermore, an integral component can be added to minimize steady-state error to zero. Reference and disturbance inputs are used as feedforward signals and then added to the feedback control law to reduce transient error. The performance of the state feedback controller has been discussed in a few papers, which have indicated superior performance compared to conventional PI controllers.
Several articles have proposed methods by which to synchronize the DFIG to the grid. In [26], stator-flux oriented control was applied to the RSC to control the active and reactive power of the stator individually. However, the idea of this paper is to start the DFIG as a motor and then reverse the operation to operate as a generator which leads to a large inrush current with low power factor. In [27,28], a generated induced stator voltage is adjusted to be equal to the grid voltage by controlling the rotor flux. These articles guarantee a zero current connection which has no effect on both the generator and the grid. However, these studies proposed a synchronization process with the PI controllers which are used to control the magnitude and angle of the stator voltage. However, using such consecutive PI controllers slows the dynamic response and deteriorate the overall controller performance.
The proposed synchronization method can be implemented at any wind speed between the cut-in and cut-out speed and at any rotating speed of the wind turbine quickly and smoothly. This feature is very important during the grid faults such as voltage dips when the wind generation system is disconnected by the protective relays from the grid. The proposed method guarantees a fast and soft reconnecting of the system at any speed and with null current. To guarantee fast and smooth synchronization, state feedback current controllers are proposed to replace the PI current controllers for both converters. To demonstrate the validity and exceptional performance of the proposed control algorithm, an experimental setup was designed and implemented. Finally, a comparison between the proposed method and a PI controller in the synchronization process is presented.

2. System Description

In DFIG-based WECSs, when ignoring the stator core and copper losses, all active and reactive power is supplied by both the stator and rotor. A maximum power point tracker is typically implemented to maximize the stator active power, which is extracted from the wind turbine. Regarding the rotor rotational speed, rotor power can be either supplied to or drawn from the grid depending on the operating speed. The grid feeds the rotor when the rotor rotates at sub-synchronous speeds and the rotor current lags behind the rotor voltage by less than 90°. At super-synchronous speeds, the rotor windings feed power to the grid and the rotor voltage jumps to nearly 180° ahead of the stator voltage, where the slip value is negative [29,30,31].

2.1. DFIG Model

DFIG equations are similar to those for a squirrel-cage induction generator. The only modification to the equations is that the DFIG rotor terminals are not short-circuited. DFIG characteristic equations can be derived from the equivalent circuit in a synchronously rotating direct quadrature (dq) frame, as shown in [32].
The DFIG equations can be represented in a Park frame by the following equations [32]:
{ v d s = R s i d s + d λ d s d t ω e λ q s v q s = R s i q s + d λ q s d t + ω e λ d s v d r = R r i d r + d λ d r d t ω s l λ q r v q r = R r i q r + d λ q r d t + ω s l λ d r }
where
  • L m : Magnetizing inductance;
  • L s : Stator self-inductance;
  • L r : Rotor self-inductance;
  • R s : Stator resistance;
  • R r : Rotor resistance;
  • λ d q s : Stator dq-axis flux linkage;
  • λ d q r : Rotor dq-axis flux linkage;
  • ω e , ω s l Synchronous and slip speed;
  • i d q s , i d q r : Stator and rotor dq-axis currents;
  • v d q s , v d q r : Stator and rotor dq-axis voltages.
{ λ d s = L s i d s + L m i d r λ q s = L s i q s + L m i q r λ d r = L m i d s + L r i d r λ q r = L m i q s + L r i q r }
In the case of stator-flux-oriented control, the d-axis is aligned with the flux vector. Therefore, the q-axis flux is zero and the main flux is the d-axis component.
The stator flux angle θ s   is calculated from the flux components of the stationary coordinate system as follows:
{ λ d s s = ( v d s s R s i d s s ) d t λ q s s = ( v q s s R s i q s s ) d t }
θ s = tan 1 λ q s s λ d s s
where the superscript ‘s’ refers to the stationary coordinate system.
If the stator resistance is negligibly small, Equation (1) can be rewritten to calculate the stator d-axis flux as
λ d s = v q s / ω e
The d- and q-axis components of the rotor flux equations can be determined from the stator flux and currents where the stator voltage vector is aligned with the q axis, which means it advances the stator flux vector by 90°. Then, the stator voltage is expressed as
v q s = v s
As a result of Equations (3) to (6), the stator current components can be written as
{ i q s = L m L s i q r i d s = ( λ d s L m i d r ) / L s }
and d-axis current is as follow:
i d s = ( v q s / ω e L m i d r ) / L s
By ignoring the power losses, the active power can be expressed as a function the d- and q-axis stator voltages and currents as follows:
P s = 3 2 ( v q s i q s + v d s i d s ) = 3 2 L m L s v q s i q r
Because the voltage d-axis component is zero, controlling the q-axis component of the rotor current controls the injected stator active power to the grid as
P s = 3 2 ( v q s i q s + v d s i d s ) = 3 2 L m L s v q s i q r
The reactive power can be controlled by adjusting the rotor D-axis current as
Q s = 3 2 ( v q s i d s v d s i q s )   = 3 2 L m L s v q s ( i m s i d r )
If the magnitude of the magnetizing current i m s is kept constant, then the active and reactive power can be controlled linearly by regulating both the d- and q-axis currents. The control procedure for the RSC and GSC is detailed in the following section.

2.2. Rotor-Side Control

The power extracted from the wind at any wind speed and turbine rotational speed is calculated as follows [33]:
P t = 1 2 ρ π R 2 υ 3 C p ( β , λ )    
where
  • ρ : standard air specific density [kg/m3];
  • C p : power coefficient;
  • β : pitch angle of the turbine blades [degrees];
  • υ : wind speed [m/s];
  • λ : tip-speed ratio (TSR);
  • R : blade radius [m].
Figure 2 presents the turbine blade’s power variation with wind speed and rotational speed. The maximum power output occurs at a particular rotational speed.
The maximum power is defined as
P max = 0.5 ρ π R 2 C p max υ 3
This condition occurs when Cpmax is the maximum tip-speed-ratio is equal to λ o p t which largely depends on the blade design.
The relationship between the turbine power and generator output power is calculated as
P e = P m J ω m d ω m d t B t ω m 2
where Pe is the generator electrical power, J is the system moment of inertia, Bt is the friction coefficient, and ω m is the blade rotational speed.
By substituting the maximum power from (13) into (14), the DFIG maximum generated power Pe, max at each time step can be calculated as follows [34]:
P e , max = P m , max J ω m , o p t d ω m , o p t d t B t ω m , o p t 2
where ω m , o p t = λ o p t υ R is the turbine speed that corresponds to the maximum mechanical power. By ignoring the generator iron and copper losses, the maximum stator active power Ps, max can be calculated as [35]:
P s , max P e , max
The calculated P s , max from (16) is then used by the RSC controller to determine the optimal rotational speed as a stator active power reference (i.e., P s , max * ) for maximum power point tracking.
By calculating the stator active power, the control block diagram of the stator power is presented in Figure 3a. The PI controller gains for the active and reactive power controllers are Kpp, Kip, Kpq, and Kiq; respectively. The rotor reference q-axis current i q r * is then calculated as the output of the active power controller and input for the inner current control loop. The rotor instantaneous q-axis current is then calculated from the sensed three-phase rotor currents and controlled to produce a reference q-axis rotor voltage. Normally, the output reactive power of the wind power conversion system is controlled as zero to keep unity power factor of the stator voltage and current. The stator reactive power is controlled to the desired value to produce the reference d-axis rotor voltage as shown in Figure 3b. One can see how the outer stator power feedback loop produces the rotor reference d-axis current i d r * for the inner current feedback control loop. The reference q-axis rotor voltage is then produced by controlling the rotor d-axis component.
However, the DFIG synchronization mode control is different from the power mode control. To synchronize the DFIG with the grid, smooth connection of the DFIG to the grid is achieved when the stator voltage amplitude, frequency and phase are equal to the grid voltage before closing the switch between the stator and the grid. The rotor side controller is activated to calculate the excitation current for the grid synchronization and power control loops. The excitation current generates the generator flux which builds-up the stator terminal voltages while the turbine accelerates until it reaches a certain value (e.g., 80% of the rated speed). At the same moment, the dc-link voltage in the bidirectional converter is soon charged. In addition, the stator frequency is almost the same as the grid, and the stator voltage amplitude is also the same as that of the grid. Even slightly different frequencies may cause the phase difference between the two voltages. To compensate the phase difference between the stator EMF νds and grid voltage, the phase difference compensation component δ θ s l is added to the calculated slip angle as shown in Figure 4 [36]. The compensation component δ θ s l is calculated by controlling the stator d-axis voltage component to be zero, equal to the grid d-axis voltage.
Once this process has been accomplished, the stator-side contactor is closed, and the generator is connected to the grid and then the power control mode starts. The generator power reference is set to the maximum value and the system is fully integrated to the grid. The sequence of synchronization is shown in Figure 5 and the overall control system for both synchronization mode and running mode is shown in Figure 6. The grid voltages eab and ebc are measured and transformed to dq-axis components eds and eqs; respectively. Similarly, the rotor currents iar and ibr are measured and used to obtain the dq-axis currents which are idr and iqr; respectively. v q r * and v d r * are the reference rotor dq-axis voltages, while v a r * , v b r * and v c r * are the RSC reference voltages.

3. Grid-Side Multivariable State Feedback Control

The goal of the GSC is to maintain a constant DC link voltage and boost it to a level that is higher than the amplitude of the line-line voltage. The DC link voltage is regulated to the reference value by using a PI controller. Any variation in the DC link voltage causes a change in the Q-axis reference current. The reactive power (or power factor) is controlled by using the D-axis reference current.
Figure 7 presents the voltage source-pulse width modulation (VS-PWM) converter equivalent circuit for each phase. The circuit voltage equation can be derived from the figure as [37]
e s = R i s + L d i s d t + v r
where,
  • es: source voltage;
  • is: source current;
  • vr: converter input voltage;
  • R: line resistance;
  • L: boost inductor.
A state-space model for the converter can be obtained by expressing (17) in a synchronous frame as
x . = A x + B u + E d
y = C x
where,
  • x: state vector;
  • x . : derivative of the space vector with respect to time;
  • u: input or control vector;
  • d: input disturbance vector;
  • y: output vector;
  • A: system matrix;
  • B: input matrix;
  • C: output matrix;
  • E: disturbance matrix.
Additionally,
x = [ i d s i q s ] ,    u = [ v d r v q r ] , d = [ e d s e q s ]
A = [ R L           ω ω         R L    ] ,      B = [ 1 L             0 0              1 L ]
E = B ,     C = [ 1          0 0          1 ] ,
and ω is the angular frequency of the source. The state variables x are the source currents, the input vectors u are the converter input voltages in the DQ axis, the disturbance d is the source voltage in the DQ axis, and the output y is the equal to source current.

3.1. State Feedback Control

Equations (18) and (19) define the state space model for any time-invariant linear multivariable system. When t , the control target is [38,39]
x . 0     a n d y y r
where yr is a reference output.
Because state feedback control is known to be a type of proportional control, the system performance in a steady state is inaccurate based on model uncertainty. This disadvantage can be overcome by introducing an integral control function to minimize steady-state error. The integral control function for the error p is defined as
p = 0 t ( y y r ) d t
Assuming that the reference output and disturbances are constant, substituting the derivative of (20) into (17) yields the following differential equations:
p . = y y r = C x y r
By transforming these equations into matrix form, an augmented state model can be expressed as
[ x . p . ] = [ A       0 C       0 ] [ x p ] + [ B 0 ] u + [ E        0 0       I ] [ d y r ]
In a steady state, the derivatives of the space vector and error approach zero because the disturbances and output references are assumed to be constant. Therefore, the steady-state solutions x s , p s , and u s , where the subscript “s” denotes a steady-state value, must satisfy the following equation:
[ E        0 0       I ] [ d y r ] = [ A       0 C       0 ] [ x s p s ] [ B 0 ] u s
Substituting (23) into (22) yields
[ x . p . ] = [ A       0 C       0 ] [ x x s p p s ] + [ B 0 ] ( u u s )
To represent the deviations in these solutions from the steady state, a definition for new variables is introduced as follows:
z = [ z 1 z 2 ] = [ x x s p p s ]     ( z . = [ x . p . ] )
v = u u s
Equation (29) can be defined in the standard state space equation as follows:
z . = A ^ z + B ^ x
where
A ^ = [ A        0 C        0 ] , B ^ = [ B 0 ]     
The system in (27) is controllable when linear state feedback control can be applied. In such cases, the system can be expressed as follows:
v = K z      = K 1 z 1 + K 2 z 2
where
  • K: feedback gain matrix;
  • K1 and K2: partitioned matrices.
The partitioned matrices are derived via pole placement. By substituting from (24), (25), and (28), the control law is obtained as
u = K 1 x + K 2 p = K 1 x + K 2 0 t ( y y r ) d t

3.2. Feedforward Control

By using an integral controller, static errors can be regulated to be zero. However, system dynamic errors may be large during transients and disturbances. To reduce transient errors and the effect of disturbances, feedforward control can be used. To derive feedforward control equations, both reference inputs and disturbance inputs are used. The deviation of the output from the reference can be calculated as
y ˜ = y y r
The control system can be defined based on (18), (19), and (30) as follows:
[ x . y ˜ ] = [ A       B C       0 ] [ x u ] + [ E        0 0       I ] [ d y r ]
The left-hand side of (31) becomes zero when the steady state reaches the steady-state condition. In this case,
[ x s u s ] = G ^ 1 H ^ [ d y ]
where
G ^ = [ A            B C            0 ] , H ^ = [ E               0 0              1 ] .
Now, deviations from the steady state can be expressed using new variables as
x ˜ = x x s        ( x ˜ . = x . ) , u ˜ = u u s
By substituting (33) into (32), we get
x ˜ . = A x ˜ + B u ˜ ,      y ˜ = C x ˜
The new relationship is the same and is defined as
u = K 1 x + [ K 1        I ] [ x s u s ]
By substituting (32) into (35), we get
u = K 1 x + K f f [ d y r ]
where the feedforward gain is defined as
K f f = [ K 1         I ] G ^ 1 H ^ = [ K f f 1       K f f 2 ]
The state variables, disturbances, and reference input equations comprise the total control equation, which is derived by substituting the integral control equation (20) into (36). The resulting control equation is written as follows:
u = K 1 x + K 2 0 t ( y y r ) d t + K f f [ d y r ]
To illustrate the total control law in (37), a block diagram for the current controller, including the feedback and feedforward components, is presented in Figure 8.

3.3. Pole placement technique

A pole placement method is used to obtain the feedback and feedforward gain matrices for (37) by using the generalized control conical form (GCCF). The open-loop system equation is defined as follows:
x . = A x + B u
where x is a vector of size n × 1, A is a gain matrix of size n × m, u is a vector of size m × 1, and the dimension of the gain B is m. This equation can be transformed into the GCCF through the transformations described below.
z . = A G z + B G u
where
  • A G = b l o c k d i g o n a l ( A γ 1    A γ 2 ... A γ m )
  • B G = b l o c k d i g o n a l ( b γ 1    b γ 2 ... b γ m )
and γ i is the controller variable gain with a rank equal to u.
That is to say,
γ 1 γ 2 ... γ m = n
i = 1 m γ i = γ 1 + γ 2 + ... + γ m = n
A γ i and b γ i are matrices of rank γ i × γ i and γ i × 1 , respectively, and have the forms
A γ i = [ 0     1     0 ... 0     0 0     0     1 ... 0     0 ... ... ... ... ... ... 0     0     0 ... 1     0 0     0     0 ... 0     1 0     0     0 ... 0     0 ] ,     b γ i = [ 0 0 . 0 0 1 ]
To derive the GCCF in (40), three transformations can be performed on (39):
  • Replace the basis of the state variable x = Tz, such that the determinant of T not equal to zero.
    Equation (43) then takes the form of
    z . = T 1 A T z + T 1 B T u = A ¯ G z + B ¯ G u
  • Replace the basis of the control variables as
    u = F w
    The rank of F is m x m, where the determinant of F not equal to zero. When (48) is implemented, (47) becomes
    z . = T 1 A T z + T 1 B F w = A ¯ G z + B G w
  • Introduce state feedback as
    w = v H z = v H T 1 x
The ranks of H and v are m x m and m x 1, respectively. Substituting the matrix w from (46) into (45) yields
z . = [ T 1 A T T 1 B F H ] z + [ T 1 B F ] z      = [ A ¯ G B G H ] z + B G v = A G z + B G v
The T, T−1, F, and H matrices are required to calculate the gains. The multivariable system controllability matrix can be defined as
M c = [ b 1    A b 1 ... A γ 1 1 b 1 | ... | b m    A b m ... A γ m 1 b m ]
Inverting (48) yields (49):
M c 1 = [ . . e i j T . . ]
where j = 1 , 2 , ... , γ i and i = 1, 2,…, m. The bottom row of each partitioned submatrix M c 1 is used to form a transformation matrix T1 of the form
T 1 = [ e 1 γ 1 T     e 1 γ 1 T A ... e 1 γ 1 T A γ 1 1 | ... | e m γ m T    e m γ m T A ... e m γ m T A γ m 1 ] T
T is calculated by taking the inverse of (31). F is derived from (44) and H is derived from (46).
The state feedback control is applied as
v = Γ z
Then,
z . = ( A G + B G Γ ) z = A d z
Ad is a closed-loop matrix that can be written as
A d = b l o c k d i g o n a l ( A d 1    A d 2 ... A d m )
A formal expression for Γ can be obtained because
B G T B G = I m
This leads to the expression
Γ = B G T [ A d A G ]
By returning to the original state space,
u = F w     = F [ G H ] T 1 x     = K x
where
K = F [ G H ] T 1
.
The feedback and feedforward controller components are depicted in Figure 9. The controller gain, K = [0.0075, 5.2].
The actual DC link voltage V d c is measured and compared to the voltage reference V d c * . The difference signal is then minimized by the DC link voltage controller. The output of the controller produces an inverter current reference i q e * and i d e * . The grid voltages and three-phase line currents are sensed and transformed into d- and q-frame axes. The dq currents and voltages are then used in conjunction with the state feedback matrix (56) to develop feedback voltage reference components. Similarly, both the source voltage and reference currents from the d and q axis components are combined with the feedforward gain matrix in (37) to develop the feedforward components of the inverter input voltage reference, which are then transformed and used to modulate the inverter.

4. Experimental Results

Experiments were performed to study the performance of the multivariable state controller separately from the DFIG system. Several tests of the real operation of an insulated gate bipolar transistor (IGBT)-based PWM inverter in different conditions were conducted. It is desirable for the WECS to be implemented with hardware (motor-generator set) to test system operations in a laboratory. Figure 10 presents the experimental setup in the laboratory, which consists of a DFIG driven by a wind simulator, back-to-back converters, and digital signal processor (DSP) TMS320C33 control boards. The parameters of the wind turbine and DFIG can be found in Appendix A.
The synchronization process starts by accelerating the wind turbine simulator which is mechanically coupled with the DFIG. This step may take long time depends on the system inertia. During the acceleration, the DC-link capacitor is charged through the GSC. After the DC-link is charged, the rotor state feedback dq current controllers are started to build up the stator voltage. After inducing the stator voltage, it is necessary to synchronize the stator to the grid, which is applicable at any rotating speed when the stator terminals are open. The electromagnetic torque is zero in this stage. The switch between stator terminals and grid is switched on when the stator and grid voltages are equal in amplitude and frequency.
Figure 11 shows the rotor current variation from sub to super-synchronous speed. It is clear that the speed varies from sub to super-synchronous smoothly when a back-to-back converter is used. As the rotor speed increases, the rotor power decreases to zero and increases in the reverse direction. Theoretically, the rotor power reverses its direction at a synchronous speed. However, the zero-crossing doesn’t occur at the synchronous speed due to the different system losses such as rotor and converter losses.

4.1. Synchronization Assessment

To connect the DFIG with the grid, the grid-side controller synchronizes the stator and grid voltages by building up the stator voltage by controlling the rotor d-axis current. The phase shift between the two voltages is compensated for by using the proposed PLL algorithm. This synchronization process takes place in a nearly coupled cycle.
The synchronization process is depicted in Figure 8, when the stator voltage is synchronized with the grid voltage. Figure 12a shows the connection process of a certain phase voltage of stator voltages with the corresponding phase of grid voltage. From zero stator voltage, the rotor d-axis current is controlled in order to build up the stator voltage in a short time. Meanwhile, the phase shift between the two voltages is compensated as shown in Figure 12b. This process takes place in an almost one cycle. To demonstrate the superiority of state feedback over PI controller, the synchronization process is performed as shown in Figure 13. The synchronization takes about two cycles, which is twice the synchronization time of the proposed method.

4.2. Power Control Mode

In Figure 14, the controller performance is investigated during a periodic speed variation. The minimum and maximum values are respectively 6 m/s and 8 m/s; respectively. In the power optimization region (at low wind speeds less than 12 m/s), the pitch angle controller is passive, keeping the pitch angle constant to the optimal value which is zero for the considered wind turbine. Meanwhile, the power controller controls the active power to the active power reference value provided by the maximum power tracker. Thus, the active power follows the wind speed pattern as shown in Figure 14b. Meanwhile, the rotor q-axis current component and generator torque follow the same pattern as shown in Figure 14c,d. To maintain the output power factor to unity, the reactive is adjusted to zero and the d-axis current remains constant as shown in Figure 14e,f.
Figure 15 presents the controller performance with step changes in wind speed. The wind speed increases in increments of 2 [m/s], starting from 5 [m/s]. For wind speeds less than 12 m/s, the pitch angle controller does not operate because the pitch angle is zero for the considered wind turbine. The power controller controls the real power component to extract the maximum possible power.
The power controller response at lower wind speeds is faster than the response at higher wind speeds. At wind speeds higher than 12 m/s, the pitch angle controller begins to operate to reduce the stress on the turbine blades.
Next, the stochastic nature of real wind speeds has been simulated. Figure 16 presents the DFIG parameters under turbulent wind speeds, where the mean wind speed is 10 m/s and the turbulence intensity is 20%. The active power changes when the wind speeds lower than 10 m/s, but it is maintained at the rated value when the wind speed increases beyond the rated value.
To test the proposed controller performance, the stator reactive power reference was changed in a step from 0 to 1750 Var, as shown in Figure 17. The actual reactive power follows the changes and the rotor d-axis current follows the reference as shown in Figure 17a,b. The measured stator and rotor currents are depicted in Figure 18a,b. It is obvious that the currents are almost sinusoidal.

4.3. GSC Controller Assessment

To investigate the performance of the inverter separately, the terminals were connected to a variable load. For the case of a step change in the inverter load, Figure 19 and Figure 20 present the DC link voltage, and d- and q-axis current transient responses. From these figures, one can see that the transient responses from the two controllers are nearly the same, except that the overshoot in the q-axis current of the PI controller is slightly larger than that of the multivariable state feedback control. Furthermore, the performance of the latter controller is satisfactory in both transient and steady states.
Finally, the root mean square error (RMSE) for the rotor quadrature axis current in case of PI and state feedback controller, since this component controls the stator active power. Table 1 shows RMSE values which demonstrate a very small difference between the two controllers.
To test the validity of state feedback controllers when a unbalanced grid-voltage occurs, the amplitude of phase voltages e b s and e c s are reduced to produce unbalanced grid voltage as shown in Figure 21. The unbalanced rotor currents are analysed to the positive and negative sequence components. Four state feedback current controllers are used to control the dq-axis positive and negative rotor currents. The main objective of these controllers is to regulate the stator active and reactive power in the pre-determined level by regulating the rotor positive sequence dq-axis components. Meanwhile, the rotor negative sequence dq-axis current components are controlled to eliminate the generator torque pulsation.
Figure 22a shows the active power waveform when the reactive power ripples are controlled. The active power has large amount or pulsations around the reference value which is 2kW. Figure 22b shows the reactive power of the stator with an average value of 0 and no pulsation. Figure 22c shows the generator torque at this time and the pulsation component is very small. The generator speed oscillations decreased for about 0.25 [rpm] due to torque pulsation reduction in Figure 22d. Therefore, in order to reduce the torque ripple of the DFIG when unbalanced grid-voltage occurs, the stator reactive power pulsations should be eliminated.

5. Conclusions

This paper presented a multivariable state feedback current controller for the DFIG in starting and running modes. The detailed design of the GSC controller was derived using the pole placement technique from multivariable system regulation theory. The GSC controller has two main parts: the outer DC link voltage controller, which is a PI controller, and the inner d- and q-axis current controllers, which are state feedback controllers. The outer voltage controller incorporating integral control regulates the DC link voltage with strong dynamics and zero steady state error. The inner current controllers guarantee fast transient responses and excellent dynamic performance. The RSC is controlled to extract the maximum possible power from wind and to control the stator reactive power. The inner loops of the reactive and active power controllers are the d- and q-axis current controllers, respectively. Both current controllers use multivariable state feedback to ensure excellent dynamic performance, which is necessary for the synchronization mode and control mode since the wind speed changes continuously and rapidly. For both the GSC and RSC, the control strategy is able to provide excellent performance under different operating conditions, and shows the ability to connect the DFIG in about one cycle. This performance is achieved by using both feedforward and feedback components for the input references and disturbances.

Author Contributions

Conceptualization, A.G.A.-K; Methodology, A.G.A.-K and A.S.A.; Software, K.S. and M.S.A.-S.; Validation, P.R.P, A.M.E. and G.R.B.; Formal Analysis, I.T.; Investigation, A.G.A.-K; Resources, A.S.A.; Data Curation, K.S.; Writing-Original Draft Preparation, A.G.A.-K; Writing-Review & Editing, A.S.A. and M.S.A.-S.; Visualization, P.R.P; Supervision; Project Administration, A.G.A.-K, G.R.B; Funding Acquisition, A.S.A.

Acknowledgments

The authors extend their appreciation to the Deanship of Scientific Research at Majmaah University for funding this work under project number No (RGP-2019-19).

Conflicts of Interest

The authors declare no conflicts of interest.

Appendix A

The specifications for the induction machine used for testing are shown in Table A1 and Table A2: three-phase, four poles, 230 [V], 50 [Hz], 3 [kW].
Table A1. Parameters of the Turbine Blade Model.
Table A1. Parameters of the Turbine Blade Model.
ParametersValue
Blade radius0.95 [m]
Max. power conv. coeff.0.45
Optimal tip-speed ratio7
Cut-in speed4 [m/s]
Rated wind speed13 [m/s]
Table A2. Parameters of the 3 kW Squirrel-Cage Induction Generator.
Table A2. Parameters of the 3 kW Squirrel-Cage Induction Generator.
ParametersValue
Stator resistance0.93 [Ω]
Rotor resistance0.533 [Ω]
Iron loss resistance190 [Ω]
Stator leakage inductance0.003 [H]
Rotor leakage inductance0.003 [H]
Mutual inductance0.076 [H]

References

  1. Abo-Khalil, A.G.; Alghamdi, A.; Tlili, I.; Eltamaly, A. Current Controller Design for DFIG-based Wind Turbines Using State Feedback Control. IET Renew. Power Gener. 2019. [Google Scholar] [CrossRef]
  2. Abo-Khalil, A.G.; Kim, H.G.; Lee, D.C.; Seok, J.K. Maximum Output Power Control of Wind Generation System Considering Loss Minimization of Machines. In Proceedings of the Industrial Electronics Conference IECON, Busan, South Korea, 2–6 November 2004; pp. 1676–1681. [Google Scholar]
  3. Eltamaly, A.M.; Alolah, A.I.; Farh, H.M. Maximum power extraction from utility-interfaced wind turbines. In New Developments in Renewable Energy; InTechOpen: Rijeka, Croatia, 2013. [Google Scholar] [CrossRef]
  4. Abo-Khalil, A.G.; Lee, D.C.; Seok, J.K. Variable Speed Wind Power Generation System Based on Fuzzy Logic Control for Maximum Output Power Tracking. In Proceedings of the Power Electronics Specialists Conference, Aachen, Germany, 20–25 June 2004; pp. 2039–2043. [Google Scholar]
  5. Eltamaly, A.M.; Alolah, A.I.; Abdel-rahman, M.H. Modified DFIG control strategy for wind energy applications. In Proceedings of the Power Electronics Electrical Drives Automation and Motion (SPEEDAM), Pisa, Italy, 14–16 June 2010; pp. 653–658. [Google Scholar]
  6. Abo-Khalil, A.G. Control system of DFIG for Wind Power Generation Systems; LAP LAMBERT Academic Publishing: Riga, Latvia, ISBN-10: 3659649813, ISBN-13: 978-3659649813; 2015. [Google Scholar]
  7. Koutroulisand, E.; Kalaitzakis, K. Design of a maximum power tracking system for wind-energy-conversion applications. IEEE Trans. Ind. Electron. 2006, 532, 486–494. [Google Scholar] [CrossRef]
  8. Abo-Khalil, A.G. Impacts of Wind Farms on Power System Stability. In Wind Farms; InTech: Rijeka, Croatia, 2013; ISBN 980-953-307-562-9. [Google Scholar] [Green Version]
  9. Cardenas, R.; Pena, R.; Alepuz, S. Overview of control systems for the operation of DFIGs in wind energy applications. IEEE Trans. Ind. Electron. 2013, 60, 2776–2798. [Google Scholar] [CrossRef]
  10. Ramtharan, G.; Ekanayake, J.B.; Jenkins, N. Frequency support from doubly fed induction generator wind turbines. IET Renew. Power Gener. 2007, 1, 3–9. [Google Scholar] [CrossRef]
  11. Abo-Khalil, A.G.; Ab-Zied, H. Sensorless Control for DFIG Wind Turbines Based on Support Vector Regression. In Proceedings of the Industrial Electronics Conference IECON, Montreal, QC, Canada, 25–28 October 2012; pp. 3475–3480. [Google Scholar]
  12. Abad, G.; Lopez, J.; Rodriguez, L. Doubly Fed Induction Machine: Modeling and Control for Wind Energy Generation Applications; Wiley: Hoboken, NJ, USA, 2011. [Google Scholar]
  13. Kazmierkowski, M.P.; Malesani, L. Current control techniques for three-phase voltage-source PWM converters: A Survey. IEEE Trans. Ind. Appl. 1998, 45, 691–703. [Google Scholar] [CrossRef]
  14. Abo-Khalil, A.G.; Alyami, S.; Sayed, K.; Alhejji, A. Dynamic Modeling of Wind Turbines Based on Estimated Wind Speed under Turbulent Conditions. Energies 2019, 12, 1907. [Google Scholar] [CrossRef]
  15. Xiao, S.; Geng, H.; Zhou, H.; Yang, G. Analysis of the control limit for rotor-side converter of doubly fed induction generator-based wind energy conversion system under various voltage dips. IET Renew. Power Gener. 2013, 7, 71–81. [Google Scholar] [CrossRef]
  16. Dai, M.; Marwali, M.N.; Jung, J.-W.; Keyhani, A.A. A three-phase four-wire inverter control technique for a single distributed generation unit in island mode. IEEE Trans. on Power Electron. 2008, 23, 322–331. [Google Scholar] [CrossRef]
  17. Rodriguez, J.; Lai, J.-S.; Peng, F.Z. Multilevel inverters: A survey of topologies, controls, and applications. IEEE Trans. Ind. Electron. 2002, 49, 724–738. [Google Scholar] [CrossRef]
  18. Zhong, Q.-C.; Liang, J.; Weiss, G.; Feng, C.M.; Green, T.C. H∞ Control of the Neutral Point in Four-Wire Three-Phase DC–AC Converters. IEEE Trans. Ind. Electron. 2006, 53, 1594–1602. [Google Scholar] [CrossRef]
  19. Chung, S.-K. Phase-locked loop for grid-connected three-phase power conversion systems. IEE Proc. Electr. Power Appl. 2000, 147, 213–219. [Google Scholar] [CrossRef]
  20. Delghavi, M.B.; Yazdani, A.N. An adaptive feedforward compensation for stability enhancement in droop-controlled inverter-based microgrids. IEEE Trans. Power Deliv. 2011, 26, 1764–1773. [Google Scholar] [CrossRef]
  21. Mohamed, Y.A.; El-Saadany, E.F. An improved deadbeat current control scheme with a novel adaptive self-tuning load model for a three-phase PWM voltage-source inverter. IEEE Trans. Ind. Electron. 2007, 54, 747–759. [Google Scholar] [CrossRef]
  22. Zhang, X.; Zhang, W.; Chen, J.; Xu, D. Deadbeat control strategy of circulating currents in parallel connection system of three-phase PWM converter. IEEE Trans. Energy Convers. 2014, 29, 406–417. [Google Scholar]
  23. Prabhakar, N.; Mishra, M.K. Dynamic hysteresis current control to minimize switching for three-phase four-leg VSI topology to compensate nonlinear load. IEEE Trans. Ind. Electron. 2010, 25, 1935–1942. [Google Scholar] [CrossRef]
  24. Karim-Davijani, H.; Sheikjoleslami, A.; Livani, H.; Karimi-Davijani, M. Fuzzy logic control of doubly fed induction generator wind turbine. World Appl. Sci. J. 2009, 6, 499–508. [Google Scholar]
  25. Dannehl, J.; Wessels, C.; Fuchs, F.W. Limitations of voltage-oriented PI current control of grid-connected PWM rectifiers with LCL filters. IEEE Trans. Ind. Electron. 2009, 56, 380–388. [Google Scholar] [CrossRef]
  26. Pena, R.; Clare, J.C.; Asher, G.M. Doubly fed induction generator using back-to-back PWM converters and its application to variable speed wind-energy generation. IEE Proc.: Electr. Power Appl. 1996, 143, 231–241. [Google Scholar] [CrossRef]
  27. Wong, K.C.; Ho, S.L. Cheng, K.W.E. Direct Voltage Control for Grid Synchronization of Doubly-fed Induction Generators. Electr. Power Compon. Syst. 2008, 36, 960–976. [Google Scholar] [CrossRef]
  28. Abo-Khalil, A.G.; Kim, H.G.; Lee, D.C.; Lee, S.-H. Grid Connection of Doubly-Fed Induction Generators in Wind Energy Conversion System. In Proceedings of the 5th International Power Electronics and Motion Control Conference (IPEMC 2006), Shanghai, China, 14–16 August 2006; pp. 1–5. [Google Scholar]
  29. KO, H.S. Supervisory voltage control scheme for grid-connected wind farms. Ph.D. Thesis, University of British Columbia, Vancouver, BC, Canada, 2006. [Google Scholar]
  30. Baroudi, J.A.; Dinavahi, V.; Knight, A.M. A review of power converter topologies for wind generators. Renewable Energy 2007, 32, 2369–2385. [Google Scholar] [CrossRef]
  31. Muyeen, S.M.; Al-Durra, A.; Hasanien, H. Modeling and Control Aspects of Wind Power Systems; InTech: Rijeka, Croatia, 2013. [Google Scholar]
  32. Duong, M.Q.; Leva, S.; Mussetta, M.; Le, K.H. A Comparative Study on Controllers for Improving Transient Stability of DFIG Wind Turbines During Large Disturbances. Energies 2018, 11, 480. [Google Scholar] [CrossRef]
  33. Rezaei, E.; Tabesh, A.; Ebrahimi, M. Dynamic model and control of DFIG wind energy systems based on power transfer matrix. IEEE Trans. Power Delivery 2012, 27, 1485–1493. [Google Scholar] [CrossRef]
  34. Abo-Khalil, A.G. Synchronization of DFIG Output Voltage to Utility Grid in Wind Power System. Renew. Energy 2012, 44, 193–198. [Google Scholar] [CrossRef]
  35. Abo-Khalil, A.G.; Berrouche, Y.; Barhoumi, E.M.; Baseer, A.M.; Praveen, R.P.; Awan, A.-B. A Low-cost PMSG Topology and Control Strategy for Small-Scale Wind Power Generation Systems. Int. J. Eng. Sci. Res. Technol. 2016, 585–592. [Google Scholar] [CrossRef]
  36. Park, H.G.; Abo-Khalil, A.G.; Lee, D.C. Wind turbine simulators considering turbine dynamic characteristics. Trans. Korean Inst. Electr. Eng. 2008, 57, 617–624. [Google Scholar]
  37. Abo-Khalil, A.G. A new wind turbine simulator using a squirrel-cage motor for wind power generation systems. In Proceedings of the Power Electronics and Drive Systems (PEDS), Singapore, 5–8 December 2011; pp. 750–755. [Google Scholar]
  38. Yang, L.; Xu, Z.; Østergaard, J.; Dong, Z.Y.; Wong, K.P. Advanced control strategy of DFIG wind turbines for power system fault ride through. IEEE Trans. Power Syst. 2012, 27, 713–722. [Google Scholar] [CrossRef]
  39. Yaramasu, V.; Wu, B.; Sen, P.C.; Kouro, S.; Narimani, M. High-power wind energy conversion systems: State-of-the-art and emerging technologies. Proc. IEEE 2015, 103, 740–788. [Google Scholar] [CrossRef]
Figure 1. Basic configuration of the proposed WECS.
Figure 1. Basic configuration of the proposed WECS.
Energies 12 02427 g001
Figure 2. Wind turbine characteristic curves: wind turbine output power [Watt] vs. rotational speed [rpm].
Figure 2. Wind turbine characteristic curves: wind turbine output power [Watt] vs. rotational speed [rpm].
Energies 12 02427 g002
Figure 3. (a) Active power control loop, (b) reactive power control loop
Figure 3. (a) Active power control loop, (b) reactive power control loop
Energies 12 02427 g003
Figure 4. Phase difference compensation for synchronization.
Figure 4. Phase difference compensation for synchronization.
Energies 12 02427 g004
Figure 5. Sequence of synchronization.
Figure 5. Sequence of synchronization.
Energies 12 02427 g005
Figure 6. Active and reactive power control for synchronization mode and running mode.
Figure 6. Active and reactive power control for synchronization mode and running mode.
Energies 12 02427 g006
Figure 7. Equivalent circuit for VS- PWM.
Figure 7. Equivalent circuit for VS- PWM.
Energies 12 02427 g007
Figure 8. Block diagram for multivariable state feedback control with feedforward control.
Figure 8. Block diagram for multivariable state feedback control with feedforward control.
Energies 12 02427 g008
Figure 9. The control block diagram for the PWM grid-side inverter.
Figure 9. The control block diagram for the PWM grid-side inverter.
Energies 12 02427 g009
Figure 10. Layout of the experimental equipment.
Figure 10. Layout of the experimental equipment.
Energies 12 02427 g010
Figure 11. Rotor current variation due to speed transition.
Figure 11. Rotor current variation due to speed transition.
Energies 12 02427 g011
Figure 12. Grid synchronization instant for state feedback controller: (a) stator and grid voltages, (b) stator and grid phase-angles.
Figure 12. Grid synchronization instant for state feedback controller: (a) stator and grid voltages, (b) stator and grid phase-angles.
Energies 12 02427 g012
Figure 13. Grid synchronization instant for PI controller: (a) stator and grid voltages, (b) stator and grid phase-angles.
Figure 13. Grid synchronization instant for PI controller: (a) stator and grid voltages, (b) stator and grid phase-angles.
Energies 12 02427 g013
Figure 14. Generator performance with periodic changes in wind speed: (a) wind speed, (b) Stator active power, (c) rotor q-axis current, (d) generator electromagnetic torque, (e) rotor d-axis current, (f) stator reactive power.
Figure 14. Generator performance with periodic changes in wind speed: (a) wind speed, (b) Stator active power, (c) rotor q-axis current, (d) generator electromagnetic torque, (e) rotor d-axis current, (f) stator reactive power.
Energies 12 02427 g014
Figure 15. Generator performance with step changes in wind speed: (a) wind speed, (b) generator speed, (c) generator output power, (d) rotor q-axis current, (e) pitch angle.
Figure 15. Generator performance with step changes in wind speed: (a) wind speed, (b) generator speed, (c) generator output power, (d) rotor q-axis current, (e) pitch angle.
Energies 12 02427 g015
Figure 16. Generator performance with continuous wind speed variation: (a) wind speed, (b) generator speed, (c) generator output power, (d) rotor q-axis current, (e) pitch angle.
Figure 16. Generator performance with continuous wind speed variation: (a) wind speed, (b) generator speed, (c) generator output power, (d) rotor q-axis current, (e) pitch angle.
Energies 12 02427 g016
Figure 17. Reactive power control: (a) stator reactive power and reference, (b) rotor-side d-axis current and reference.
Figure 17. Reactive power control: (a) stator reactive power and reference, (b) rotor-side d-axis current and reference.
Energies 12 02427 g017
Figure 18. DFIG currents after synchronization. (a) 3-phase stator currents, (b) 3-phase rotor currents.
Figure 18. DFIG currents after synchronization. (a) 3-phase stator currents, (b) 3-phase rotor currents.
Energies 12 02427 g018
Figure 19. Transient response of PI controller for a step change in the load. (a) grid-side q-axis current and reference; (b) grid-side d-axis current and reference; (c) DC-link voltage and reference.
Figure 19. Transient response of PI controller for a step change in the load. (a) grid-side q-axis current and reference; (b) grid-side d-axis current and reference; (c) DC-link voltage and reference.
Energies 12 02427 g019
Figure 20. State feedback controller transient response for a step change in the load. (a) grid-side q-axis current and reference; (b) grid-side d-axis current and reference; (c) DC-link voltage and reference.
Figure 20. State feedback controller transient response for a step change in the load. (a) grid-side q-axis current and reference; (b) grid-side d-axis current and reference; (c) DC-link voltage and reference.
Energies 12 02427 g020
Figure 21. Unbalanced grid voltage.
Figure 21. Unbalanced grid voltage.
Energies 12 02427 g021
Figure 22. Generator torque for control eliminating the ripple (a) Stator active power (b) Stator reactive power (c) generator torque (d) generator speed.
Figure 22. Generator torque for control eliminating the ripple (a) Stator active power (b) Stator reactive power (c) generator torque (d) generator speed.
Energies 12 02427 g022
Table 1. RMSE (p.u) for the rotor quadrature current.
Table 1. RMSE (p.u) for the rotor quadrature current.
ControllerValue
PI0.04
State feedback0.0296

Share and Cite

MDPI and ACS Style

Abo-Khalil, A.G.; Alghamdi, A.S.; Eltamaly, A.M.; Al-Saud, M.S.; R. P., P.; Sayed, K.; Bindu, G.R.; Tlili, I. Design of State Feedback Current Controller for Fast Synchronization of DFIG in Wind Power Generation Systems. Energies 2019, 12, 2427. https://doi.org/10.3390/en12122427

AMA Style

Abo-Khalil AG, Alghamdi AS, Eltamaly AM, Al-Saud MS, R. P. P, Sayed K, Bindu GR, Tlili I. Design of State Feedback Current Controller for Fast Synchronization of DFIG in Wind Power Generation Systems. Energies. 2019; 12(12):2427. https://doi.org/10.3390/en12122427

Chicago/Turabian Style

Abo-Khalil, Ahmed G., Ali S. Alghamdi, Ali M. Eltamaly, M. S. Al-Saud, Praveen R. P., Khairy Sayed, G. R. Bindu, and Iskander Tlili. 2019. "Design of State Feedback Current Controller for Fast Synchronization of DFIG in Wind Power Generation Systems" Energies 12, no. 12: 2427. https://doi.org/10.3390/en12122427

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop