Next Article in Journal
A Review of Dendrophthoe pentandra (Mistletoe): Phytomorphology, Extraction Techniques, Phytochemicals, and Biological Activities
Next Article in Special Issue
Structural Optimization of Annular Thermoelectric Module Applied to Liquefied Natural Gas Cold Energy Recovery
Previous Article in Journal
A Model Based on the Random Forest Algorithm That Predicts the Total Oil–Water Two-Phase Flow Rate in Horizontal Shale Oil Wells
Previous Article in Special Issue
The Impact of Air Source Heat Pump on the Production Performance of Broiler Chicks
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

First Law Optimization and Review of Double and Triple-Effect Parallel Flow Vapor Absorption Refrigeration Systems

Department of Mechanical Engineering, Maulana Mukhtar Ahmad Nadvi Technical Campus, Malegaon 423203, Maharashtra, India
Processes 2023, 11(8), 2347; https://doi.org/10.3390/pr11082347
Submission received: 17 June 2023 / Revised: 1 July 2023 / Accepted: 3 August 2023 / Published: 4 August 2023

Abstract

:
Parallel flow double and triple-effect vapor absorption cooling systems (VACS) are trying to meet the challenges of vapor compression cooling systems due to their better performance. Therefore, the present study deals with the review, thermodynamic analysis, and optimization of operating parameters for both double and triple-effect VACS. Lithium bromide water was selected as the working fluid, while liquified petroleum gas (LPG) and compressed natural gas (CNG) were taken as the source of energy to drive both the VACS. Detailed First Law analysis, i.e., coefficient of performance (COP), was examined along with the optimization of operating parameters (such as salt concentration and operating generators temperature at different pressure levels) and the volume flow rate of the gases. Optimization was carried out for maximum COP of the VACS using an iterative technique. Our results show that the COP of the triple-effect system was approximately 32% higher than the double effect, while 15–20% less consumption of the gases (LPG and CNG) was observed. The most optimum stage for the operation of triple-effect VACS was reached at Te = 4 °C and Tc = Ta = 30 °C, Tg = 180 °C, Tc4 = 104 °C, Tc3 = 66 °C, Z1 = 0.5, and Z2 = 0.45.

1. Introduction

VACS are receiving more attention in the published literature as a means of cooling production from different renewable sources, such as solar energy [1], geothermal energy [2], and clean energy [3,4], with many processes switching from energy-intensive vapor compression cooling systems (VCCS). The only drawback of VACS over VCCS is their lower coefficient of performance and high capital investment [5]. However, with development of the systems, current VACS reach the performance of VCCS [6]. The performance of VACS largely depends on the structure (e.g., single to fourth-effect or other) as well as the properties of the working fluids [7]. Mixtures of VACS are environmentally friendly, have less purchasing cost, and are easily available in the market. Additionally, several mixtures have been tested, and a plethora of research has been reported on different suitable mixtures [8]. A few mixtures have been investigated, such as LiBr/H2O and NH3/H2O [9], whereas other ionic liquids [10], inorganic salts [11], and organic [12] have also been examined. Yanbin Qin et al. [13] used low-GWP mixtures R1234yf/R32 and R170/R14/R50 to operate a cooling system integrated with the Linde-Hampson system.
In addition to the mixtures, the flowsheet structure also plays a crucial role in enhancing the performance of VACS [14]. In the past literature, single-effect (SE-VACS) and double-effect VACS (DE-VACS) have been examined exhaustively along with different combinations of the working fluids [15]. Single-effect VACS have very low COPs compared to double and triple-effect VACS (TE-VACS) under different cycle constructions [16]. Talpada and Ramana [17] studied the detailed analysis of DE-VACS. Firstly, the TE-VACS concept was proposed by [18]. A plethora of research has been carried out on the modification of DE-VACS and TE-VACS [19,20]. Rasoul Nikbakhti et al. [21] reviewed in detail the absorption cooling system for the enhancement of COP. They discussed the different constructions of VACS under multiple effects. Multi-effect VACS have modifications in terms of equipment connectivity and improving operating process performance indicators [22]. T.A. Mouneer et al. [23] performed a thermodynamic analysis of novel VACS integrated with a vapor compression system.
DE-VACS and TE-VACS have two and three generators; therefore, different flow configurations of the working fluids can be possible. The most common working fluid configurations are reverse flow, parallel flow, and series flow [24]. In the previous literature, these flow configurations have been studied in detail [25]. Azhar and Siddiqui [26] presented the thermodynamic analysis of a parallel flow DE-VACS and compared the same system with its series flow configuration. They reported that parallel flow has approximately 6% more COP than series flow VACS. Additionally, they concluded that the rate of exergy destruction for parallel flow VACS is 4% lower, and the energy to drive the system is around 3% lower compared to series flow VACS. Chahartaghi et al. [27] presented two novel arrangements of parallel and series flow DE-VACS. They again concluded that parallel flow VACS have a higher COP. They defined the solution distribution ratio for parallel flow cycles, and these were optimized for maximum COP. Konwar et al. [28] presented a comparison analysis of series and parallel flow VACS. They used two different working fluids, such as water–LiCl and water–LiBr, and optimized the system for maximum COP and minimum irreversibility of both types of VACS. They concluded that the system operated with water–LiCl had lower COP than water–LiBr; however, exergy efficiency was higher at optimized conditions.
Bagheri et al. [29] performed detailed work on the basis of the second Law of Thermodynamics to simulate parallel flow DE-VACS and optimize the performance of maximum COP and exergy efficiency. They reported the maximum COP as 1.295 and maximum exergy efficiency as 22.5% at generator temperatures of 169.6 °C and 142.7 °C, respectively. Both endogenous and exogenous parts of exergy were discussed in their analysis. Exergy is the best tool to determine the location, magnitude, and sources of thermodynamic inefficiencies in any energy conversion devices [30]. Kelly et al. [31] discussed that exergy destruction (irreversibilities) has two components such as endogenous exergy destruction and exogenous exergy destruction. They discussed in detail the importance and application of both parts of exergy for any energy conversion devices, especially vapor absorption refrigeration systems. Garousi et al. [32] conducted a thermodynamic study of all three types of DE-VACS, including reverse parallel flow and parallel and series flow configurations. They discussed the pros and cons of the results of all three configurations of the double-effect VACS. Arshad et al. [33] performed optimization and thermodynamic analysis for series and parallel flow DE-VACS. It was found that the exergy efficiency of parallel flow was 6.45% higher than the series flow configuration under the same operating condition. Detail comparisons have been presented between series and parallel flow systems [33].
Ferwati et al. [34] carried out a detailed thermodynamic analysis of parallel flow double-effect VACS using an H2O–[mmim][DMP] working pair and compared the system with a conventional H2O–LiBr pair. It was concluded that the ionic pair had higher COP (around 6%) and ECOP (around 5%) than the H2O–LiBr pair. Arora et al. [35] performed a calculation of energy and exergy of parallel flow DE-VACS and reported the optimum solution distribution ratio (SDR) for maximum COP and maximum ECOP of the system. The optimum temperatures in each component at optimum SDR are reported in their paper. It can be concluded that the SDR also play an important role in the case of the parallel flow absorption–refrigeration cycle. Ahmed and Gilani discussed the performance of a commercial absorption chiller under a double-effect parallel flow arrangement [36]. They presented energy and exergy performance and provided information regarding concentration, temperature, mass flow rate, entropy, and exergy flow at all state points of the systems. However, they failed to optimize all operating parameters under optimum SDR. Garousi et al. [32] performed interesting work to simulate the three flow configurations (series, parallel, and reverse) of DE-VACS. They discussed the pros and cons in the results of all three configurations of DE-VACS but failed to discuss the same flow configurations of TE-VACS.
The source of energy also affects the exergy performance of VACS. Renewable sources and waste heat become the best option when these sources are available; otherwise, direct-fired sources (such as the burning of fuel in the generator) will meet the requirement of multi-effect VACS when operated at night hours. Zakariya Kaneesamkandi et al. [37] demonstrated an appropriate solar collector for the operation of single and double-effect VACS. A multi-attribute decision-making model was adopted to determine the best option. Mengxiao Yu et al. [38] used industrial low-level waste heat to operate cascade absorption heat transformers and perform multi-objective optimization in terms of energy, exergy, and economic analysis. A different, new configuration of VACS was reported by Gado et al. [39]. They published a detailed review of the hybrid sorption–vapor compression refrigeration system. They presented the integration of a desiccant cooling, adsorption, and absorption system and carried out the energy, exergy, environmental, and economic analysis of the said system. Mengxiao Yu et al. [40] also used low-grade waste heat to operate a cascade absorption refrigeration system and calculate the exergy and exergoeconomic analysis of the said system. Yinglong Wang et al. [41] designed the cascade absorption heat transformer for the recovery of low-grade waste heat. They conducted advanced exergy and exergoeconomic analyses for the said system. Table 1 summarizes the results obtained for parallel flow DE-VACS and TE-VACS in the open literature.
In the open literature, exhaustive work on vapor absorption refrigeration systems has been reported for single-effect to triple-effect cycles. However, the majority of works have reported on series flow configuration. The analysis of parallel flow TE-VACS seems to be missing in the literature and also requires critical review and comprehensive study. However, parallel flow DE-VACS have been discussed in previous studies. In contrast, a few works have been reported on the direct-fired arrangement in the main generator. It is known that DE-VACS and TE-VACS operated at significantly higher generator temperatures can be achieved easily through the direct-fired arrangement. In view of this, the present study has addressed the following research gaps:
  • Review of DE-VACS and TE-VACS under different flow configurations and different heat sources.
  • Detailed energy analysis for parallel flow TE-VACS.
  • A direct-fired system has been selected for the operation of the main generator. Moreover, LPG and CNG have been taken as sources of energy because they are cheaper, less toxic, and easily available.
  • Calculation of gases required to operate the parallel flow DE-VACS and TE-VACS.
  • Optimization of operating temperature and SDRs for maximum COP.

2. System Description of VACS

Here, the modeling and working principle of both parallel flow DE-VACS and TE-VACS are discussed in detail.

2.1. Parallel Flow DE-VACS

A schematic diagram of a typical parallel flow DE-VACS is shown in Figure 1a. The absorber, evaporator, main condenser, main generator, and condenser–generator set (i.e., C3-G2) are the major parts of DE-VACS. The working of parallel flow DE-VACS is quite simple and discussed in detail by Azhar and Siddiqui [43]. In this system, the input energy is supplied only in the main generator; the other generator (G2) is operated with internal heat recovery by condenser ‘C3’. Refrigerant is generated in both generators simultaneously. The solution is divided into both generators after the absorber outlet. Initially, the solution (combination of refrigerant and absorbent) is prepared in the absorber and pumped to both generators through the preheater. In both generators, the solution is heated, and the refrigerant vapor that has been collected is released in the main condenser and transfers the phase from vapor to liquid. The liquid refrigerant is sent to the evaporator via a throttle valve. In the evaporator, the refrigerant boils and takes heat from the cooled space and then sends it to the absorber to make it a cyclic process.

2.2. Parallel Flow TE-VACS

A schematic plot of parallel flow TE-VACS is depicted in Figure 1b. The working principle is quite similar to parallel flow DE-VACS. However, in this arrangement, there are three generators; therefore, the solution is distributed in two places. Firstly, the solution is divided at the outlet of preheater 1 (i.e., PH1) and then again distributed at the outlet of preheater 2 (i.e., PH2). The refrigerant vapor is generated in all three generators and finally merged in condenser ‘C’. However, the remaining strong solution (the solution prepared after boiling the refrigerant) flows back to the absorber to complete the cycle. In the same way, the main generator is driven by the external heat source, while the other two are operated through internal heat recovery (G3 is operated through C4, and G2 is operated through C3). The cooling effect is produced at the evaporator.

3. System Modeling

To evaluate the thermodynamic performance of DE-VACS and TE-VACS, the energy balance for all components must be written through the below expression:
Mass balance:   i n m ˙     o u t m ˙ = d m c v d t ,
Energy   balance :   E ˙ i n     E ˙ o u t = d E s y s t e m d t .
After referring to Figure 1 and Figure 2, the expression for different components can be written under steady-state conditions:
Absorber :   m ˙ 7 h 7 + m ˙ 10 h 10 + m ˙ 11 h 11     m ˙ 1 h 1     m ˙ 12 h 12 = 0 ,
Solution   pump :   m ˙ 1 h 1     m ˙ 2 h 2 + W p u m p = 0 ,
Evaporator :   m ˙ 6 h 6 + m ˙ 17 h 17     m ˙ 7 h 7     m ˙ 18 h 18 = 0 ,
Main   generator :   m ˙ 3 h 3 + m ˙ 13 h 13     m ˙ 4 h 4     m ˙ 8 h 8     m ˙ 14 h 14 = 0 .
For DE and TE-VACS, the equations shall be different for a few components.
Parallel Flow DE-VACS (see Figure 1):
Condenser   C :   m ˙ 4 b h 4 b + m ˙ 4 c h 4 c + m ˙ 15 h 15     m ˙ 5 h 5     m ˙ 16 h 16 = 0 .
Generator-Condenser set (G2-C3):
m ˙ 4 h 4 + m ˙ 2 d h 2 d     m ˙ 4 a h 4 a     m ˙ 4 c h 4 c     m ˙ 8 c h 8 c = 0 ,
SDR :   Z = m 2 b m 2 a = m 2 b m 1 .
Concentration at 8d:
X 8 d = 1.0 ( Z / X g ) + ( 1.0     Z ) / X g s .
Parallel Flow TE-VACS (see Figure 2):
Condenser   C :   m ˙ 4 b h 4 b + m ˙ 4 c h 4 c + m ˙ 15 h 15     m ˙ 5 h 5     m ˙ 16 h 16 = 0 .
Generator–condenser set G3 and C4:
m ˙ 4 h 4 + m ˙ 2 h h 2 h     m ˙ 4 a h 4 a     m ˙ 4 c h 4 c     m ˙ 8 c h 8 c .
Generator–condenser set G2 and C3:
m ˙ 4 b h 4 b + m ˙ 4 c h 4 c + m ˙ 2 d h 2 d     m ˙ 4 d h 4 d     m ˙ 4 f h 4 f     m ˙ 8 g h 8 g = 0 .
Solution distribution ratio:
Z 1 = solution   entering   in   PH 2 solution   leaving   from   PH 1 = m 2 b m 2 a ,   Z 2 = solution   entering   in   main   generator solution   leaving   from   PH 2 = m 2 f m 2 e .
LiBr–salt concentration:
X J 1 = X 8 d = 1.0 ( Z 2 / X g ) + ( 1.0 Z 2 ) / X g 3 ,     X J 2 = X 8 h = 1.0 ( Z 2 / X g ) + ( 1.0     Z 2 ) / X g 3 ,
C O P = Q e Q g + W p
where
Q e = m ˙ 7 h 7     m ˙ 6 h 6 = m ˙ 18 h 18     m ˙ 17 h 17   and   Q g = m ˙ 4 h 4     m ˙ 3 h 3 + m ˙ 8 h 8 = m ˙ 14 h 14     m ˙ 13 h 13 .

3.1. Modeling of Energy Sources (LPG and CNG)

In the present work, the two gases were selected as the source to operate the main generator of the VACS. These gases are eco-friendly, economical, and less toxic. The detailed calculation of the volume flow rate of each gas was carried out in previous articles [6,44]. Here, only heat release is written through each gas, such as CNG (QC) and LPG (QL) and their volume flow rate (Vfuel):
Q L = 51,615.8     17.68 × T p + 273.15     2.52 × 1 0 3 × T p + 273.15 2 ,
Q C = 53,364.84 18.87 × T p + 273.15 2.0 × 1 0 3 × T p + 273.15 2 ,
V f u e l = Q g Q f u e l × v g a s ;   m 3 s 1 .
For different gases such as CNG and LPG, Equation (18) will change accordingly.

3.2. Assumption and Solution Technique of the Present Work

In the present manuscript, certain assumptions were taken from [45], who simplified the simulation under steady-state conditions. Table 2 shows the operating conditions for the simulation of DE-VACS and TE-VACS. LiBr–water solution and refrigerant properties are taken from [46,47,48]. To execute the simulation of both DE-VACS and TE-VACS, computer codes were developed and written in FORTRAN 90. The calculation process is very simple, first considering fixed parameters described in Table 2. The generator concentration is increased in the loop, and the generator temperature is calculated with the help of the respective condenser temperature. After that, heat loads at the main generator and intermediate condenser are calculated. This calculation is repeated with increasing values of LiBr concentration of both the generator, which makes the energy balance between the intermediate generator and condenser lie within an error of ± 0.1 kJ/h. The coefficient of performance and volume flow rate of both gases are estimated for different values of the main generator temperature for fixed values of Te and Tc = Ta. For clarity of the calculation process, the algorithm of the program is shown in Figure 2.

4. Result and Discussion

LiBr–salt concentration plays an important role in the generator temperature and, ultimately, the performance of VACS. In view of this, the variation in salt concentration must be depicted. Figure 3 shows the variations in absorber concentration (Xa), all generator concentrations (Xg, Xg2, and Xg3), and crystallization concentration (Xc) with Tg at different Te of DE-VACS and TE-VACS. In Figure 3, all the condenser temperatures are fixed (Tc4 = 110 °C Tc3 = 65 °C and Tc = Ta = 30 °C), and the SDR of DE-VACS is Z = 0.36, while in triple effect, it is Z1 = 0.3 and Z2 = 0.5. It is observed from the plots of Figure 3 that Xa remains constant with the increase in Tg. The concentration of LiBr–H2O solution in the absorber is the function of the saturation temperature (Te) of the refrigerant vapor and LiBr–H2O solution temperature (Ta). Therefore, with the rise in Te, the values of Xa decrease, while on increasing the temperature Ta, the values of Xa increase. In DE-VACS, the salt concentration of generator G2 (Xg2) is lower than the salt concentration in the main generator (Xg), which is unlike the result obtained in series flow DE-VACS [43]. This is because the solution entering both generators has the same concentration (that is, Xa), and, generator G operates at a higher temperature; as a result, higher heat is supplied to it compared to generator G2. This is why more refrigerant vapor is generated in the main generator compared to generator G2. A similar effect is observed in the parallel flow TE-VACS cycle: Xg > Xg2 > Xg3, which is again unlike the result obtained for series flow TE-VACS [7].
Additionally, LiBr–H2O solution coming from generators G and G2 mix at state point 8d in parallel flow DE-VACS, while in TE-VACS, the solutions mix at state points 8d and 8h, respectively. The LiBr–salt concentration at state point 8d (X8d) lies between Xg and Xg2 in the case of parallel flow DE-VACS. Similarly, in the case of TE-VACS, the LiBr–salt concentration at state point 8d (X8d) will lie between Xg and Xg3, while at 8h (X8h) it will lie between Xg2 and Xg3, respectively. The LiBr–salt concentration at different mixing points (that is, X8d and X8h) is shown in Figure 4. Additionally, the salt concentration X8d of DE-VACS and X8h of TE-VACS have the same trend because they exit at the same location of their respective cycles. The trend of the salt concentration at state point X8d (parallel flow TE-VACS) is the same as found for Xg2. Moreover, with an increase in the evaporator temperature, the operating range of the LiBr–salt concentration of each generator increases.

4.1. Coefficient of Performance

The variation in COP of DE-VACS and TE-VACS with Tg is shown in Figure 5. The intermediate condensers temperature in both cycles is Tc3 = 65 °C (for DE-VACS and TE-VACS), Tc4 = 110 °C (for TE-VACS), and the main condenser temperature Tc = Ta = 30 °C is fixed. The SDR in parallel flow DE-VACS is taken as Z = 0.36, while in parallel flow TE-VACS it is Z1 = 0.3 and Z2 = 0.5. However, Te is varied from 4 °C to 10 °C.
It is observed from Figure 5 that the values of COP initially increase with the rise in Tg and reach a maximum. This is due to a decline in the generator load for fixed Qe and Te. With further increase in Tg, COP terminates because the system must have either faced crystallization or energy balance must be attained in the condenser–generator set(s). Additionally, with a decrease in the values of Te, the COP of both systems decreases. Maximum COP for SDRs and fixed temperatures are marked with circles in Figure 5. Furthermore, the COP of TE-VACS is significantly higher than that of DE-VACS.

4.2. LPG and CNG Flow Rate

The flow rates of LPG and CNG with Tg for parallel flow DE-VACS and TE-VACS are depicted in Figure 6. It is observed that the LPG and CNG volume flow rate of both VACS decreases with a rise in Tg, attaining a minimum value and then becoming constant due to crystallization or energy balance between the condenser and generator sets. Further, it is also observed that the flow rate of LPG and CNG declines with a rise in the Te and the minimum flow rate shift towards low Tg. At high Te, the concentration in the absorber becomes low, which provides a large operating range of the main generator temperature. It is further observed that the flow rate of TE-VACS is lower compared to DE-VACS; the COP of TE-VACS is higher than the COP of DE-VACS. The trends of the gas flow rate are exactly the reverse of variation in the COP.
It was observed through the literature that the operation of VACS is affected by generator temperature; therefore, it is necessary to use all temperatures of the generator(s) to attain high performance. Furthermore, SDRs also affect VACS performance in the case of parallel flow configuration; therefore, optimization of SDR of parallel flow DE-VACS was discussed by Azhar and Siddiqui [43] in detail. However, the optimization of parallel flow TE-VACS needs more clarification, which has not yet been discussed in the open literature. Parallel effect TE-VACS have two SDRs (Z1 and Z2), which are also to be optimized for the best performance of the system (i.e., maximum COP/minimum flow rate). For clarity, the optimization procedure is shown in four simple steps.
In the first step of optimization, COP variation with Tg is shown for different values of Z2 in Figure 7, keeping the evaporator and all the condenser temperatures constant at Tc4 = 110 °C, Tc3 = 65 °C, Tc = Ta = 30 °C, and Te = 4 °C; SDR Z1 = 0.3 must also be constant. It was found that for each value of Z2, COP increases and then attains a maximum point that has been circled in the same Figure 7. It can be observed that the system operates at lower Tg when Z2 is low. Moreover, when Z2 increases, maximum COP also increases (up to 0.2 to 0.4) and then declines. It is also noticed that shifting the maximum values of COP shift towards lower Tg. Finally, from Figure 7, it was observed that the maximum of maximum COP is attained at Z2 = 0.4 for fixed intermediate condenser temperatures and when Z1 = 0.3.
Similarly, in the second step of optimization, SDRs Z1 and Z2 are varied, keeping other parameters (Tc3 = 65 °C and Tc4 = 110 °C) constant. Figure 8a shows the variation in maximum COP with Z2 for different values of Z1 and selects a maximum of the maximum COP. Rise in Z1 and keeping Z2 constant produces a similar effect as deliberated in the first step of optimization. It is observed from Figure 8a that the COP of VACS initially increases, attains a maximum, and then decreases slowly. It is also noticed that the rise in the Z1 curve slightly flattens and increases, and the COP peak increases up to Z1 = 0.55; after that, the curve flattens more, and COP also decreases.
The maximum of maximum COP has been circled, and both Z1 and Z2 are optimized in this step; other parameters that must be optimized in the coming step of optimization remain constant. For clear visibility of the results in Figure 8a, the optimum values of Z2 and COP obtained from Figure 8a are shown in the form of bars in Figure 8b.
From Figure 8a,b, it can be noticed that the maximum value of COP is attained at Z1 = 0.5 and Z2 = 0.4, keeping Tc3 = 65 °C and Tc4 = 110 °C as constant. In the coming step, the intermediate temperatures must be optimized. Figure 9a optimized the temperature Tc4 and presented the variation in COP with Z1, Z2, and Tc4. Again, the same method was adopted for optimization, and the code was run for different values of Tc4. It was observed that at each value of Tc4, COP initially rise, attains a maximum point, and then decreases.
At this stage, the intermediate condenser temperature Tc4 is optimized along with both SDRs. Again, for more clarity of the results, the optimum values of Z1, Z2, and COP at each Tc4 are shown in the form of bars in Figure 9b. The maximum COP attained in Figure 9a,b is at Tc4 = 114 °C, Z1 = 0.45, and Z2 = 0.45 for fixed Tc3 = 65 °C. Further, the variation in maximum COP and optimum Z1 and Z2 with Tc4 and Tg is shown in Figure 10a,b. It is thus very interesting to see that as COP increases with Tc4, Z2 increases while Z1 decreases simultaneously. In Figure 10a, it is also found that both SDRs meet at a certain value of Tc4 where the COP is near the maximum value. The same is the case with Tg in Figure 10b.
In the fourth step of optimization, the aim is to optimize the intermediate condenser/generator temperature Tc3 for higher performance. The method that was selected to optimize the other parameters Z1, Z2, and Tc4 was repeated for different values of Tc3. At each Tc3, we obtained the maximum of the maximum COP that is noted and plotted in Figure 11 in bars form. It was also observed that maximum COP was achieved at Tc3 = 66 °C, and correspondingly, all other optimized parameters were noted down. In Figure 12, all the optimized generator temperatures were plotted with COP. The method of optimization used to optimize all the operating parameters was the iterative technique. The computer code was run for different values of Z1, Z1, Tc4, and Tc3, the maximum COP was selected in each case, and finally, the most optimum value was obtained so that the design engineers could work on the same values for the fixed evaporator and main condenser/absorber temperatures. It should be clear that the all-optimum values will change once the evaporator and main condenser/absorber temperatures change. From Figure 12 it is shown that the most optimum stages reached at Te = 4 °C and Tc = Ta = 30 °C are Tg = 180 °C, Tc4 = 104 °C, Tc3 = 66 °C, Z1 = 0.5, and Z2 = 0.45.
Now, for different values of Te, the variation in maximum COP with Tg is shown in Figure 13a, keeping Tc = Ta = 30 °C fixed, yet all the operating parameters (all generator temperature and SDRs) at this stage are optimized. Similar plots can also be drawn for other values of Tc = Ta. It is also seen that COP increases with an increase in Te and shifts towards lower generator temperature. The optimum COP for each Te is marked with a circle, which is the optimum operating condition for parallel flow TE-VACS. Additionally, the optimum COP at each Te is shown in the form of bars in Figure 13b. Furthermore, the operating temperature in all three generators at different values of Te is shown in Figure 14. The main generator (Tg) has a very high temperature, and the generator G3 has a somewhat lower temperature (Tg3) than Tg. The generator G2 required a lower temperature (Tg2) than Tg3. All the generators showed decreasing temperature with an increase in Te which is obvious.
Figure 15 demonstrates a comparison study between DE-VACS and TE-VACS for Te = 4 °C and 10 °C, with Tc = Ta = 30 °C as fixed values. Additionally, the plots in Figure 15 were drawn after the optimization of operating parameters in both cycles. Here, a similar trend is found for COP, which initially increases, reaches a maximum, and then decreases. The comparison shows that the COP of parallel flow TE-VACS is approximately 32% higher than that of parallel flow DE-VACS. Furthermore, with an increase in Te, COP increases, and the optimum values of COP at higher Te shift towards lower Tg.
After the optimization of the solution distribution ratio and temperatures in the main generator and intermediate generator/condenser, CNG and LPG volume flow rates are determined with the help of Equation (18). The flow rate of CNG and LPG of both cycles are presented and compared in Figure 16 for Te = 4 °C and Tc = Ta = 30 °C. It is seen that the flow rate of CNG is significantly higher than that of LPG due to the difference in their specific volume. The specific volume of CNG is higher than that of LPG. Additionally, the minimum flow rate of LPG and CNG obtained correspond to the maximum COP in the present analysis. Furthermore, the minimum flow rate obtained for parallel flow cycles at each Te lies at a higher Tg than the series flow cycle. Therefore, it is inferred that parallel flow cycles have higher COP and lower gas requirements than series flow cycles, but they need high heat source temperatures.

5. Conclusions

In the present communication, first, a brief review was conducted on VACS under different constructions and flow configurations. Additionally, parallel flow TE-VACS were simulated, exploring the optimum operating parameters such as temperature and SDRs. The comparison of DE-VACS and TE-VACS is presented for different Te and Tc = Ta. The following observations and conclusions made from the present work are listed below:
  • For the purpose of saving high-grade energy, VACS have become quite popular recently and have been made more efficient through a plethora of studies. This review shows that current VACS are more efficient and environmentally friendly.
  • From the literature review, it was also observed that the working fluid flow configuration produces a high impact on the performance of VACS.
  • The temperature of the intermediate generator also plays a vital role in the performance of DE-VACS and TE-VACS under different flow configurations.
  • TE-VACS have around 32% higher performance than DE-VACS, while they require 15–20% less consumption of gases (LPG and CNG) to operate the system.
  • As the generator temperature plays an important role in the performance of TE-VACS, Tg, Tg2 (≈Tc3), and Tg3 (≈Tc4) are reported for maximum COP and minimum flow rates of the gases.
  • In parallel flow cycles, SDR(s) is/are also an important factor in deciding the performance optimized for maximum COP and minimum flow rate of the gases.
  • For Te = 4 °C and Tc = Ta = 30 °C, the optimum condition to run TE-VACS is Tg = 180 °C, Tc4 = 104 °C, Tc3 = 66 °C, Z1 = 0.5, and Z2 = 0.45. These values can be changed after changing the evaporator and condenser temperature.
  • Similarly, the optimum flow rate for the fixed evaporator and condenser temperatures are 0.0022 (for DE-VACS) and 0.00197278 (for TE-VACS) for LPG, while for CNG the values are 0.007082 (for DE-VACS) and 0.00620872 (for TE-VACS). These values will help engineers who are working in the field of absorption refrigeration systems. This is one of the key findings of the present manuscript.

Funding

This research received no external funding.

Data Availability Statement

Not applicable.

Conflicts of Interest

The author declares no conflict of interest.

Nomenclature

Aabsorber
Cmain condenser
COPcoefficient of performance [-]
CNGcompressed natural gas
Eevaporator
Ggenerator at which heat is supplied
hspecific enthalpy [kJ kg−1]
LPGliquefied petroleum gas
LiBrlithium bromide salt
m ˙ rate of mass flow [kg s−1]
Ppressure [kPa]
Qheat transfer rate [kJ s−1]
QCenergy from CNG [kJ kg−1 CNG]
QLenergy from LPG [kJ kg−1 LPG]
Ttemperature [°C]
Tcoldcooled space temperature
TVthrottle valve
Vgas flow rate [m3 s−1]
Wppump work [kW]
Greek Symbols:
Subscripts:
aabsorber
cmain condenser
eevaporator
gmain generator

References

  1. Meraj, M.; Khan, M.E.; Azhar, M. Performance analyses of photovoltaic thermal integrated concentrator collector combined with single effect absorption cooling cycle: Constant flow rate mode. J. Energy Resour. Technol. Trans. ASME 2020, 142, 121305. [Google Scholar] [CrossRef]
  2. Keçeciler, A.; Acar, H.İ.; Doǧan, A. Thermodynamic analysis of the absorption refrigeration system with geothermal energy: An experimental study. Energy Convers. Manag. 2000, 41, 37–48. [Google Scholar] [CrossRef]
  3. Yang, M.; Lee, S.Y.; Chung, J.T.; Kang, Y.T. High efficiency H2O/LiBr double effect absorption cycles with multi-heat sources for tri-generation application. Appl. Energy 2017, 187, 243–254. [Google Scholar] [CrossRef]
  4. Kaynakli, O.; Saka, K.; Kaynakli, F. Energy and exergy analysis of a double effect absorption refrigeration system based on different heat sources. Energy Convers. Manag. 2015, 106, 21–30. [Google Scholar] [CrossRef]
  5. Riffat, S.B.; Qiu, G. Comparative investigation of thermoelectric air-conditioners versus vapour compression and absorption air-conditioners. Appl. Therm. Eng. 2004, 24, 1979–1993. [Google Scholar] [CrossRef]
  6. Azhar, M.; Siddiqui, M.A. Optimization of operating temperatures in the gas operated single to triple effect vapour absorption refrigeration cycles. Int. J. Refrig. 2017, 82, 401–425. [Google Scholar] [CrossRef]
  7. Azhar, M.; Siddiqui, M.A. Exergy analysis of single to triple effect lithium bromide-water vapour absorption cycles and optimization of the operating parameters. Energy Convers. Manag. 2019, 180, 1225–1246. [Google Scholar] [CrossRef]
  8. Karamangil, M.I.; Coskun, S.; Kaynakli, O.; Yamankaradeniz, N. A simulation study of performance evaluation of single-stage absorption refrigeration system using conventional working fluids and alternatives. Renew. Sustain. Energy Rev. 2010, 14, 1969–1978. [Google Scholar] [CrossRef]
  9. Ahmad, T.; Azhar, M.; Sinha, M.K.; Meraj, M.; Mahbubul, I.M.; Ahmad, A. Energy analysis of lithium bromide-water and lithium chloride-water based single effect vapour absorption refrigeration system: A comparison study. Clean. Eng. Technol. 2022, 7, 100432. [Google Scholar] [CrossRef]
  10. De Araújo, H.V.; Massuchetto, L.H.P.; do Nascimento, R.B.C.; de Carvalho, S.M.R.; Dangelo, J.V.H. Thermodynamic performance analysis of a single-effect absorption refrigeration system operating with water and 1-ethyl-3-methylimidazolium-based ionic liquids mixtures. Appl. Therm. Eng. 2022, 201, 117761. [Google Scholar] [CrossRef]
  11. Saravanan, R.; Maiya, M.P. Thermodynamic comparison of water-based working fluid combinations for a vapour absorption refrigeration system. Appl. Therm. Eng. 1998, 18, 553–568. [Google Scholar] [CrossRef]
  12. Papadopoulos, A.I.; Kyriakides, A.-S.; Seferlis, P.; Hassan, I. Absorption refrigeration processes with organic working fluid mixtures—A review. Renew. Sustain. Energy Rev. 2019, 109, 239–270. [Google Scholar] [CrossRef]
  13. Qin, Y.; Li, N.; Zhang, H.; Liu, B. Thermodynamic performance of a modified −150 °C refrigeration system coupled with Linde-Hampson and three-stage auto-cascade using low-GWP refrigerants. Energy Convers. Manag. 2021, 236, 114093. [Google Scholar] [CrossRef]
  14. Ratlamwala, T.A.H.; Dincer, I.; Gadalla, M.A. Performance analysis and evaluation of a triple-effect ammonia-water absorption-refrigeration system. Int. J. Energy Res. 2013, 37, 475–483. [Google Scholar] [CrossRef]
  15. Hugo, V.; Flores, F.; Román, J.C.; Alpírez, G.M. Performance Analysis of Different Working Fluids for an Absorption Refrigeration Cycle. Am. J. Environ. Eng. 2014, 4, 1–10. [Google Scholar]
  16. Xu, Z.Y.; Wang, R.Z. Absorption refrigeration cycles: Categorized based on the cycle construction. Int. J. Refrig. 2016, 62, 114–136. [Google Scholar] [CrossRef]
  17. Talpada, J.S.; Ramana, P.V. A review on performance improvement of an absorption refrigeration system by modification of basic cycle. Int. J. Ambient. Energy 2019, 40, 661–673. [Google Scholar] [CrossRef]
  18. Ohuchi, T.; Usui, S.; Fukuda, T.N.A. Multistage Absorption Refrigeration System. U.S. Patent 4,520,634, 4 June 1985. [Google Scholar]
  19. Domínguez-Inzunza, L.A.; Hernández-Magallanes, J.A.; Sandoval-Reyes, M.; Rivera, W. Comparison of the performance of single-effect, half-effect, double-effect in series and inverse and triple-effect absorption cooling systems operating with the NH3-LiNO3 mixture. Appl. Therm. Eng. 2014, 66, 612–620. [Google Scholar] [CrossRef]
  20. Maryami, R.; Dehghan, A.A. An exergy based comparative study between LiBr/water absorption refrigeration systems from half effect to triple effect. Appl. Therm. Eng. 2017, 124, 103–123. [Google Scholar] [CrossRef]
  21. Nikbakhti, R.; Wang, X.; Hussein, A.K.; Iranmanesh, A. Absorption cooling systems—Review of various techniques for energy performance enhancement. Alex. Eng. J. 2020, 59, 707–738. [Google Scholar] [CrossRef]
  22. Arshi Banu, P.S.; Sudharsan, N.M. Review of water based vapour absorption cooling systems using thermodynamic analysis. Renew. Sustain. Energy Rev. 2018, 82, 3750–3761. [Google Scholar] [CrossRef]
  23. Mouneer, T.A.; Hawwash, A.A.; Aly, M.H.; Mina, E.M. Thermodynamic analysis for novel vapor compression/absorption cascade refrigeration system for LNG liquefaction processes in Egypt. Energy Convers. Manag. 2022, 270, 116238. [Google Scholar] [CrossRef]
  24. Aghdam, A.H.; Ranjbar, F.; Mahmoudi, S.M.S. Performance comparison of triple-effect parallel flow and series flow absorption refrigeration systems. J. Appl. Sci. 2008, 8, 2913–2918. [Google Scholar] [CrossRef]
  25. Wang, L.; You, S.; Zhang, H.; Li, X. Simulation of gas-fired triple-effect LiBr/water absorption cooling system with exhaust heat recovery generator. Trans. Tianjin Univ. 2010, 16, 187–193. [Google Scholar] [CrossRef]
  26. Azhar, M.; Siddiqui, M.A. First and Second Law Analyses of Double Effect Parallel and Series Flow Direct Fired Absorption Cycles for Optimum Operating Parameters. J. Energy Resour. Technol. Trans. ASME 2019, 141, 124501. [Google Scholar] [CrossRef]
  27. Chahartaghi, M.; Golmohammadi, H.; Shojaei, A.F. Performance analysis and optimization of new double effect lithium bromide–water absorption chiller with series and parallel flows. Int. J. Refrig. 2019, 97, 73–87. [Google Scholar] [CrossRef]
  28. Konwar, D.; Gogoi, T.K.; Das, A.J. Multi-objective optimization of double effect series and parallel flow water–lithium chloride and water–lithium bromide absorption refrigeration systems. Energy Convers. Manag. 2019, 180, 425–441. [Google Scholar] [CrossRef]
  29. Bagheri, B.S.; Shirmohammadi, R.; Mahmoudi, S.M.S.; Rosen, M.A. Optimization and comprehensive exergy-based analyses of a parallel flow double-effect water-lithium bromide absorption refrigeration system. Appl. Therm. Eng. 2019, 152, 643–653. [Google Scholar] [CrossRef]
  30. Morosuk, T.; Tsatsaronis, G. A new approach to the exergy analysis of absorption refrigeration machines. Energy 2008, 33, 890–907. [Google Scholar] [CrossRef]
  31. Kelly, S.; Tsatsaronis, G.; Morosuk, T. Advanced exergetic analysis: Approaches for splitting the exergy destruction into endogenous and exogenous parts. Energy 2009, 34, 384–391. [Google Scholar] [CrossRef]
  32. Garousi Farshi, L.; Seyed Mahmoudi, S.M.; Rosen, M.A.; Yari, M. A comparative study of the performance characteristics of double-effect absorption refrigeration systems. Int. J. Energy Res. 2012, 36, 182–192. [Google Scholar] [CrossRef]
  33. Arshad, M.U.; Ghani, M.U.; Ullah, A.; Güngör, A.; Zaman, M. Thermodynamic analysis and optimization of double effect absorption refrigeration system using genetic algorithm. Energy Convers. Manag. 2019, 192, 292–307. [Google Scholar] [CrossRef]
  34. Ferwati, M.S.; Ahmad, A.M.; Takalkar, G.D.; Bicer, Y. Energy and exergy analysis of parallel flow double effect H2O-[mmim][DMP] absorption refrigeration system for solar powered district cooling. Case Stud. Therm. Eng. 2021, 28, 101382. [Google Scholar] [CrossRef]
  35. Arora, A.; Dixit, M.; Kaushik, S.C. Energy and exergy analysis of a double effect parallel flow LiBr/H2O absorption refrigeration system. J. Therm. Eng. 2016, 2, 541–549. [Google Scholar] [CrossRef]
  36. Ahmed, S.; Mohammed, M.S.A.; Ul-Haq Gilani, S.I. Exergy analysis of a double-effect parallel-flow commercial steam absorption chiller. J. Appl. Sci. 2012, 12, 2580–2585. [Google Scholar] [CrossRef]
  37. Kaneesamkandi, Z.; Almujahid, A.; Salim, B. Selection of an Appropriate Solar Thermal Technology for Solar Vapor Absorption Cooling—An MADM Approach. Energies 2022, 15, 1882. [Google Scholar] [CrossRef]
  38. Yu, M.; Chen, Z.; Yao, D.; Zhao, F.; Pan, X.; Liu, X.; Cui, P.; Zhu, Z.; Wang, Y. Energy, exergy, economy analysis and multi-objective optimization of a novel cascade absorption heat transformer driven by low-level waste heat. Energy Convers. Manag. 2020, 221, 113162. [Google Scholar] [CrossRef]
  39. Gado, M.G.; Ookawara, S.; Nada, S.; El-Sharkawy, I.I. Hybrid sorption-vapor compression cooling systems: A comprehensive overview. Renew. Sustain. Energy Rev. 2021, 143, 110912. [Google Scholar] [CrossRef]
  40. Yu, M.; Cui, P.; Wang, Y.; Liu, Z.; Zhu, Z.; Yang, S. Advanced Exergy and Exergoeconomic Analysis of Cascade Absorption Refrigeration System Driven by Low-Grade Waste Heat. ACS Sustain. Chem. Eng. 2019, 7, 16843–16857. [Google Scholar] [CrossRef]
  41. Wang, Y.; Liu, Y.; Liu, X.; Zhang, W.; Cui, P.; Yu, M.; Liu, Z.; Zhu, Z.; Yang, S. Advanced exergy and exergoeconomic analyses of a cascade absorption heat transformer for the recovery of low grade waste heat. Energy Convers. Manag. 2020, 205, 112392. [Google Scholar] [CrossRef]
  42. Kaita, Y. Simulation results of triple-effect absorption cycles. Int. J. Refrig. 2002, 25, 999–1007. [Google Scholar] [CrossRef]
  43. Azhar, M.; Altamush Siddiqui, M. Comprehensive exergy analysis and optimization of operating parameters for double effect parallel flow absorption refrigeration Cycle. Therm. Sci. Eng. Prog. 2020, 16, 100464. [Google Scholar] [CrossRef]
  44. Azhar, M.; Siddiqui, M.A. Energy and Exergy Analyses for Optimization of the Operating Temperatures in Double Effect Absorption Cycle. Energy Procedia 2017, 109, 211–218. [Google Scholar] [CrossRef]
  45. Ansari, K.A.; Azhar, M.; Altamush Siddiqui, M. Exergy Analysis of Single-Effect Vapor Absorption System Using Design Parameters. J. Energy Resour. Technol. 2020, 143, 062105. [Google Scholar] [CrossRef]
  46. Pátek, J.; Klomfar, J. A computationally effective formulation of the thermodynamic properties of LiBr-H2O solutions from 273 to 500 K over full composition range. Int. J. Refrig. 2006, 29, 566–578. [Google Scholar] [CrossRef]
  47. Altamush Siddiqui, M. Optimization of Operating Parameters for Various Absorption Systems Using Renewable Energies. Ph.D. Thesis, Aligarh Muslim Univesity, Aligarh, India, 1992. [Google Scholar]
  48. Pátek, J.; Klomfar, J. A simple formulation for thermodynamic properties of steam from 273 to 523 K, explicit in temperature and pressure. Int. J. Refrig. 2009, 32, 1123–1125. [Google Scholar] [CrossRef]
Figure 1. (a) Schematic plot of direct-fired parallel flow DE-VACS. (b) Schematic plot of direct-fired parallel flow TE-VACS.
Figure 1. (a) Schematic plot of direct-fired parallel flow DE-VACS. (b) Schematic plot of direct-fired parallel flow TE-VACS.
Processes 11 02347 g001
Figure 2. Flow chart for the triple-effect parallel flow cycle.
Figure 2. Flow chart for the triple-effect parallel flow cycle.
Processes 11 02347 g002
Figure 3. Variation in LiBr–salt concentration at different locations of parallel flow DE-VACS and TE-VACS with Tg.
Figure 3. Variation in LiBr–salt concentration at different locations of parallel flow DE-VACS and TE-VACS with Tg.
Processes 11 02347 g003
Figure 4. Variation in concentration of the LiBr–salt at mixing points of DE-VACS and TE-VACS with Tg at different Te.
Figure 4. Variation in concentration of the LiBr–salt at mixing points of DE-VACS and TE-VACS with Tg at different Te.
Processes 11 02347 g004
Figure 5. Variation in COP with Tg in DE-VACS and TE-VACS (all SDRs and generators temperatures are fixed).
Figure 5. Variation in COP with Tg in DE-VACS and TE-VACS (all SDRs and generators temperatures are fixed).
Processes 11 02347 g005
Figure 6. LPG and CNG volume flow rates with Tg.
Figure 6. LPG and CNG volume flow rates with Tg.
Processes 11 02347 g006
Figure 7. COP with Tg for different Z2 (Z1 and all generator temperatures are fixed).
Figure 7. COP with Tg for different Z2 (Z1 and all generator temperatures are fixed).
Processes 11 02347 g007
Figure 8. (a) Variation in COP with Z2 for different Z1. (b) Optimum values of Z2 and COP for different Z1.
Figure 8. (a) Variation in COP with Z2 for different Z1. (b) Optimum values of Z2 and COP for different Z1.
Processes 11 02347 g008
Figure 9. (a) COP and Z2 with Z1 for different Tc4 temperatures. (b) Optimum values of Z1, Z2, and COP from (a).
Figure 9. (a) COP and Z2 with Z1 for different Tc4 temperatures. (b) Optimum values of Z1, Z2, and COP from (a).
Processes 11 02347 g009
Figure 10. Maximum COP, Z2, and Z1 with temperatures Tc4 (a) and Tg (b).
Figure 10. Maximum COP, Z2, and Z1 with temperatures Tc4 (a) and Tg (b).
Processes 11 02347 g010
Figure 11. Maximum COP with Tc3 under different Z1 and Z2.
Figure 11. Maximum COP with Tc3 under different Z1 and Z2.
Processes 11 02347 g011
Figure 12. Maximum COP, Tg, and Tc4 with temperature Tc3.
Figure 12. Maximum COP, Tg, and Tc4 with temperature Tc3.
Processes 11 02347 g012
Figure 13. (a) COP with Tg for different values of Te. (b) Optimum COP for different values of Te (all parameters are optimized).
Figure 13. (a) COP with Tg for different values of Te. (b) Optimum COP for different values of Te (all parameters are optimized).
Processes 11 02347 g013
Figure 14. Optimum generator temperatures at different evaporator temperatures (all operating parameters are optimized).
Figure 14. Optimum generator temperatures at different evaporator temperatures (all operating parameters are optimized).
Processes 11 02347 g014
Figure 15. Maximum COP of DE-VACS and TE-VACS.
Figure 15. Maximum COP of DE-VACS and TE-VACS.
Processes 11 02347 g015
Figure 16. Comparison of minimum LPG and CNG volume flow rate of DE-VACS and TE-VACS.
Figure 16. Comparison of minimum LPG and CNG volume flow rate of DE-VACS and TE-VACS.
Processes 11 02347 g016
Table 1. Result Summary of parallel flow DE-VACS and TE-VACS.
Table 1. Result Summary of parallel flow DE-VACS and TE-VACS.
Type of VACSWorking Fluid(s)Flow ConfigurationRemark on FindingsReference
Double effectH2O–LiBrSeries and ParallelComparison between series and parallel flow cycles.[26]
Double effectH2O–LiBrSeries and ParallelComparison of parallel flow with series flow and optimized the operating parameters.[27]
Double effectTwo pairs are used; H2O–LiBr and H2O–LiClSeries and ParallelDetailed comparison between series and parallel flow.[28]
Double effectH2O–LiBrParallel FlowDetailed exergy analysis and reported maximum COP and their corresponding generator’s temperature.[29]
Double effectH2O–LiBrSeries, Parallel, and Reverse FlowPerformance of all three cycles and compared them.[32]
Double effectH2O–[mmim][DMP] and H2O–LiBrParallel FlowReported thermodynamic properties of H2O–[mmim][DMP] mixture.[34]
Double effectH2O–LiBrParallelCOP and exergy destruction rate of each component.[36]
Triple effectH2O–LiBrSeries FlowCOP and exergy efficiency and exergy destruction rate of each component.[7]
Triple effectNH3–LiNO3 mixtureSeries and Inverse FlowCOP and optimized parameters.[19]
Triple effectH2O–LiBrSeries FlowCOP and optimized temperatures.[6]
Triple effectH2O–LiBrSeries Flow, Parallel, and Reverse FlowCOP, maximum pressure, and maximum temperature of the cycle under different environmental conditions.[42]
Table 2. Fixed operating conditions for DE-VACS and TE-VACS.
Table 2. Fixed operating conditions for DE-VACS and TE-VACS.
PropertiesValues
Evaporator Load300 kW
Evaporator Temperatures (Te) 4, 6, 8 and 10 °C
TcoldTe + 5.0
Absorber/main condenser temperatures30, 33, 36 and 39 °C
Intermediate condenser/generator temperature, Tc3From 45 °C to 105 °C
Intermediate condenser/generator temperature, Tc470 °C to 135 °C
Pump Efficiency, ηp, and Effectiveness, ε85% and 70%
Z, Z1, and Z20.1–0.7
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Azhar, M. First Law Optimization and Review of Double and Triple-Effect Parallel Flow Vapor Absorption Refrigeration Systems. Processes 2023, 11, 2347. https://doi.org/10.3390/pr11082347

AMA Style

Azhar M. First Law Optimization and Review of Double and Triple-Effect Parallel Flow Vapor Absorption Refrigeration Systems. Processes. 2023; 11(8):2347. https://doi.org/10.3390/pr11082347

Chicago/Turabian Style

Azhar, Md. 2023. "First Law Optimization and Review of Double and Triple-Effect Parallel Flow Vapor Absorption Refrigeration Systems" Processes 11, no. 8: 2347. https://doi.org/10.3390/pr11082347

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop