Next Article in Journal
A Novel Unmanned Aerial Vehicle Charging Scheme for Wireless Rechargeable Sensor Networks in an Urban Bus System
Previous Article in Journal
Improving the Reverberation Chamber Performance Using a Reconfigurable Source Stirring Antenna Array
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Transient Protection Principle Based on Current Ratio of Two Terminals in Frequency Domain

State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China
*
Author to whom correspondence should be addressed.
Electronics 2022, 11(9), 1463; https://doi.org/10.3390/electronics11091463
Submission received: 3 April 2022 / Revised: 26 April 2022 / Accepted: 30 April 2022 / Published: 3 May 2022
(This article belongs to the Section Circuit and Signal Processing)

Abstract

:
In order to prevent a transmission line boundary having a weak high frequency from impairing single-ended transient-based relay protection, this paper proposes using the coordination of the current frequency domain features of the relay on both sides of the transmission line to achieve whole-line quick-action protection. In the case of an internal fault, since the frequency components of the electrical quantities in the frequency domain on both sides of the protected line are related to the distance from the fault point to two sides of the line, the frequency-domain current spectrum information on both sides of the line is very different and the fluctuation is strong. In the case of an external fault, the transient current at the protection point closer to the fault is transmitted through the entire length of the protected line and reaches the other side away from the fault. Therefore, the fluctuation in the current spectrum in the frequency domain on both sides is quite different. Thus, this paper proposes setting the fault criterion according to the difference in the frequency spectrum fluctuation degree of the frequency-domain current ratio on both sides when internal and external faults occur. After verification using PSCAD simulation, it was found that the protection principle proposed in this article can act quickly and correctly, and identify internal and external faults, under different fault types and fault locations, and is basically not affected by transition resistance.

1. Introduction

The technology and scale of wind power and photovoltaic power generation have achieved significant progress, thus effectively promoting the transformation of the power system into one based on these new forms of energy. Because the new power system is characterized by a high proportion of new energy power sources and power electronic equipment, the electrical characteristics of the power frequency of the system have also changed. At present, the power system is still configured with transmission line protection in a conventional way, and the traditional protection principle has been shown to have problems relating to adaptability [1,2,3]. The relay protection, as the first line of defense, is facing serious challenges [4,5].
The distribution parameters of transmission lines in the actual power system have obvious characteristics, and the fault additional component spectrum generated during the fault often has a large amount of fault information, such as fault location [6], fault type, and fault occurrence time, especially in the high-frequency frequency band. The fault characteristics are more obvious [7], and the protection based on transient quantities is not affected by power frequency phenomena, such as oscillation, CT saturation, and transition resistance. Using high-frequency fault information can quickly detect high-frequency components and achieve high-speed protection [8,9], to avoid the action delay caused by the coordination between the filter and the action time in power frequency protection.
There are three main types of relay protection principles based on fault frequency domain characteristics: the first type focuses on the high-frequency transient line protection principle based on the attenuation effect of fault transient electrical quantities at the line "boundary"; the second type focuses on the transient line protection principle based on the fault natural frequency; and the third category is the transient line protection principle based on fault model identification in the frequency domain.
(1) The principle of high frequency transient line protection based on the attenuation effect of fault transient electrical quantities at the line "boundary". Due to the discontinuous wave impedance caused by the wave traps on both sides of the line and the bus-to-ground capacitance, the attenuation effect generated by the high-frequency component is used to identify internal or external faults. The high-frequency content is higher when an internal fault occurs, and is low when an external fault occurs. The principle and model of this method are relatively simple and easy to implement [10,11,12]. At the same time, the wave trappers and bus-to-ground capacitance at both ends of the line are generally called "line boundaries". The line protection of high frequency transients based on the attenuation effect of transient faults at the line "boundary" is called boundary protection [13,14]. Boundary protection usually does not require line communication and can achieve high-speed action, but the setting of relay protection is relatively difficult.
(2) Transient-based line protection principle considering fault natural frequency. After a fault occurs somewhere on the line, the fault traveling wave will generate a series of harmonics during the propagation from the fault point to the bus. These harmonics are called natural frequencies, among which the component with the lowest frequency and the highest energy are referred to as the natural frequency principal component. Furthermore, there is a certain functional relationship between the natural frequency and the fault distance. Ref. [15] proposed using the spectral correlation of the fault phase current at both ends of the line to identify the internal and external faults, and the spectral energy to determine the faulty phase and the fault type. The traditional impedance criterion is required as an auxiliary criterion in an internal fault in order to ensure the reliability of the protection action. This scheme is not affected by the power frequency phenomenon, does not require communication, and is widely used. The transient line protection principle based on the natural frequency of line faults has strict requirements on the accuracy of the extraction of the main frequency. In addition, its sampling rate is high, implementation is difficulty, and reliability cannot be guaranteed.
(3) Transient line protection principle based on fault model identification in frequency domain. Refs. [16,17,18] proposed a line pilot protection principle based on the comprehensive impedance of fault components, using the ratio of fault voltage and current at both ends of the line as the fault criterion element to identify the fault characteristics. During an external fault, the modulus value of the comprehensive impedance reflecting the capacitive reactance on the transmission line is relatively large, whereas, in an internal fault, the modulus value of the comprehensive impedance reflecting the source impedance and line impedance is relatively small. Thus, internal and external faults can be distinguished according to the magnitude of this modulus value when a fault occurs.
In addition, in Ref. [19], Prof. Suonan at Xi’an Jiaotong University in China and his team proposed a new pilot protection principle for transmission lines based on frequency-domain model recognition theory by adopting the Matrix Pencil algorithm. The internal and external fault-based models were proposed, and the fault recognition was achieved by comparing the internal fault-based model error with the external fault-based model error. In Ref. [20], Prof. Saleh at the University Of New Brunswick presented a review of the time-domain and frequency-domain approaches to detect and identify fault currents, indicating the frequency domain approach has better accuracy and response speed than the time-domain approach, but the response speed may face a lower bound. In Ref. [21], Prof. Jia and his research team at the State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources in NCEPU introduced a modeling method for converter impedance in the frequency domain. The study proposed using frequency-domain information suitable for different types of equipment, and the model based on the frequency domain to analyze the high-frequency characteristics of faults in DC systems was not affected by the converter control strategy. In Ref. [22], Prof. Tzelepis and his team at the University of Strathclyde utilized wavelet transform to detect and discriminate faults, in which the optimum wavelet decomposition level, mother wavelet, and protection threshold were critical to achieve higher performance. In Ref. [23], Prof. Lee at the University of Texas at Arlington proposed a power-spectrum-based hyperbolic S-transform to extract the high-frequency components of the current signals generated by an electric fault, and realized identification of fault classes in power transmission networks. In Ref. [24], Prof. Shu at Kunming University of Science and Technology described the characteristic distribution of the traveling wave by the forward and backward traveling-wave components and realized fault location. In Ref. [25], Prof. Geddada at Nanyang Technological University proposed using the frequency-domain-based short-time Fourier transform to quantitatively analyze high-frequency components in the fault current and to detect faults. In Ref. [26], Prof. Mohsenian at the University of California at Riverside utilized the information in the frequency domain that was obtained during the detection phase to identify the location of faults. The study proved that much lower time resolution in power system measurements is needed, and identified the accuracy and efficiency of the approach.
It can be seen from the above research that an increasing number of scientists are focusing on the frequency domain and the spectrum characteristics of fault information to realize the location of faults. This is because the large scale of electronic equipment, in addition to the new energy resources feeding in to power systems, are resulting in more sophisticated fault characteristics containing multi-frequency components. However, most of the transient-based line protection relying on the frequency domain uses only low-frequency information for identification, which represents a limitation. In addition, the optimum decomposition layers and frequency band in the wavelet transform, which is popularly utilized in transient-based protection strategy, are difficult to define. Thus, the research in this field is still not fully explored. This study utilized frequency-domain information of the double terminals, and identified the optimum decomposition layers and analysis window. As a result, precise internal and external fault identification was realized, thus helping to address the negative effects of protection malfunction, and contributing to the safe and stable operation of new power systems confronted with sophisticated and multiple electrical characteristics.

2. Frequency Spectrum Feature Analysis of Fault Transient Current

2.1. Internal Fault Characteristics Analysis

The fault additional network when an internal fault occurs is as shown in Figure 1.
From the analysis of the frequency components of the wave process of the transmission line, the complex frequency domain expression of the transient current measured at the M and N terminal protection installations can be obtained as follows:
I M ( s ) = U F ( 0 ) ( ω 0 cos φ + s sin φ ) ( s 2 + ω 0 2 ) Z M ( s ) c h γ x + Z C ( s ) s h γ x
I N ( s ) = U F ( 0 ) ( ω 0 cos φ + s sin φ ) ( s 2 + ω 0 2 ) Z N ( s ) c h γ ( l x ) + Z C ( s ) s h γ ( l x )
where UF(0) is the voltage amplitude of the fault point when a fault occurs, ω0 is the power frequency, φ is the voltage initial phase angle when a fault occurs, and chγ and shγ represent hyperbolic functions.
Via Equations (1) and (2), the ratio of the frequency-domain currents at both ends of the line after faults are detected can be described as follows:
I M ( s ) I N ( s ) = Z N ( s ) c h γ ( s ) ( l x ) + Z C ( s ) s h γ ( s ) ( l x ) Z M ( s ) c h γ ( s ) x + Z C ( s ) s h γ ( s ) x
where IM(s) is the basic resonance equation of IM, and its extreme value mainly represents the frequency characteristics of IM; IN(s) is the basic resonance equation of IN, and its extreme value mainly represents the frequency characteristics of IN; chγ and shγ represent hyperbolic functions.
Under normal circumstances, the transmission line only contains power frequency information. When a fault occurs, high-frequency transient information will appear on the line, which destroys the model of the current ratio in the frequency domain on both sides of the line. When there is an internal fault, due to the different distances between the fault point and the protection installations on both sides, the corresponding harmonic frequencies in the transient current spectrum that propagate from the fault point to both sides of the line are different, and are related to the distance from the fault point to the two sides of the line. When an internal fault occurs at a distance of 0.8l from the M side in the line, fault currents on both sides of the line are decomposed by the wavelet packet and in the third frequency band (50–75 kHz) because, through analysis and observation, fault characteristics in this frequency range are the most obvious. After extracting the current information in the corresponding frequencies, phase-mode transformation is performed on the current to better observe its fluctuation situation. Simulation results of the line-mode current spectrum and frequency-domain current ratio are shown in Figure 2.
As shown in Figure 2a,b, due to the impact of multiple frequency components in the transient current spectrum, the current has obvious fluctuations at multiple frequency points because it propagates from the fault point to the installation of protection on both sides of the line through the refraction effect of distributed inductance and capacitance on the line. It can be seen from Figure 2c,d that, when the fault point is not in the middle of the line, the harmonic frequencies in the current spectrum in the frequency domain on both sides of the line are different. The frequency spectrum of the domain current ratio fluctuates at multiple frequencies, but with smaller amplitudes. When the fault occurs in the middle of the line, the fault current spectrum on both sides should be basically the same, and the current ratio in the frequency domain should be roughly 1 and the fluctuation is small. It can be seen from Figure 2 that, when an internal fault occurs at a distance of 0.8l from the M side in the line, the frequency spectrum fluctuation of the frequency-domain current ratio IN/IM is more significant.
When there is a fault in the area, the fault transient current wave is propagated from the fault point to both sides of the line. Due to the refraction and reflection effect of distributed inductance and capacitance from the fault point to the protection installations on both sides of the line, the fluctuation of the fault current spectrum at the protection installations on both sides is different. However, since the fault occurs in the inner area of the protected line, after the fault traveling wave is detected on both sides of the line, the difference in the fault current spectrum measured in the same time window is small. When the fault point is close to one side of the line, more high-frequency components on that side can be detected. However, when a fault occurs at the midpoint of the line, the fault current spectrum on both sides should be basically the same, which shows that the spectrum fluctuations on both sides are also basically the same. Therefore, when the fault point is close to the M side, the high-frequency content in the M-side transient current spectrum is correspondingly more obvious, so the spectral fluctuation characteristics of IM(s)/IN(s) are more significant; when the protection is close to the N side of the line, the high-frequency content in the N-side transient current spectrum is correspondingly more obvious, so the spectral fluctuation characteristics of IN(s)/IM(s) are more significant.

2.2. External Fault Characteristics Analysis

The fault additional network when an external fault occurs is shown in Figure 3.
When an external fault occurs, on the protected line M-N, the transmission line equation can be obtained as follows:
U M ( s ) = U N ( s ) c h γ l Z C ( s ) I N ( s ) s h γ l I M ( s ) = I N ( s ) c h γ l U N ( s ) Z C ( s ) s h γ l
From Figure 3, the relationship between the voltage and the current on the N-side bus can be obtained as:
U N ( s ) = I N ( s ) [ Z M ( s ) + Z C ( s ) ]
Combining Equations (4) and (5), the ratio of the frequency-domain current at both ends of the line can be obtained as:
I M ( s ) I N ( s ) = Z M ( s ) + Z C ( s ) Z C ( s ) s h γ l c h γ l
In the case of an external fault, the transfer function of the frequency-domain current on both sides of the line can be directly obtained from the transmission equation of the line. The frequency-domain current ratio in an external fault is only related to the overall length of the line, so its fluctuation should be relatively regular. Since the transient traveling wave at the fault point is transmitted through the line boundary and enters the protected line during an external fault, and propagates from the side close to the fault through the entire length of the protected line to the other side far from the fault, the spectral fluctuation of the transient current on the near end is weak, whereas that of the transient current on the far end is strong, and their spectral amplitudes vary greatly. When an external fault occurs at a distance of 0.2l from the N side of the line, fault currents on both sides of the protected line are decomposed by the wavelet packet and in the third frequency band (50–75 kHz). The simulation results of the line-mode current spectrum and frequency-domain current ratio are shown in Figure 4. Through comparison of Figure 3 and Figure 4, the difference in the current spectrum between internal and external faults can be determined.
The above analysis and figures indicate the following:
(1) When an internal fault occurs, the frequency spectrum of the current ratio in the frequency domain on both sides of the protected line fluctuates with multiple frequency components. When the fault does not occur at the middle of the line, since the corresponding harmonic frequency in the frequency-domain current spectrum on both sides is different, the spectrum of the frequency-domain current ratio of the line fluctuates at multiple frequency points, but the amplitude is small. When the fault occurs at the middle of the line, the fault current spectrum on both sides should be basically the same, so the frequency domain current ratio should be roughly 1 and the fluctuation is small.
(2) When an external fault occurs, since the fault transient current transmitting into the protected line propagates through the entire length of the protected line, the amplitude of the frequency domain current on both sides is quite different, and the frequency spectrum of the current ratio in the frequency domain should fluctuate regularly and the fluctuation amplitude is large.
(3) When an internal fault occurs, the frequency spectrum fluctuation characteristics of IM(s)/IN(s) are more significant when the fault point is identified to be closer to the M terminal; conversely, when the fault point is closer to the N terminal, the spectrum fluctuation characteristics of IN(s)/IM(s) are more significant; and when the fault point is in the middle of the line, the spectrum fluctuations of IM(s)/IN(s) and IN(s)/IM(s) are basically the same. In the case of an external fault, the frequency domain current of the protection installation nearer the fault point is used as the input, whereas that of the protection on the farther side of the line is used as the output, and the ratio of the corresponding frequency-domain current input to output should fluctuate greatly. Therefore, regardless of the occurrence of internal or external faults, if it is identified that the fault point is closer to one side of the line, the frequency-domain current on that side is taken as the numerator of the ratio of the frequency-domain currents, and correspondingly, the frequency-domain current on the other side is taken as the denominator.
Therefore, fault location can be identified according to the frequency spectrum fluctuation degree of the current ratio in the frequency domain on both sides of the line, so as to form a two-terminal transient-based protection principle.

3. Internal and External Fault Identification Scheme

3.1. Spectrum Fluctuation Identification

Kurtosis is a mathematical statistic that characterizes the distribution characteristics of variables and is very sensitive to the shock component in the signal. It is mainly affected by the shock waveform in the signal and can describe the peak degree of the signal waveform. It is widely used in the failure diagnosis of mechanical equipment. Kurtosis is defined as K, the ratio of the fourth moment to the square of the second moment of the specific signal, which is not affected by the absolute level of the signal, and its mathematical expression is described as follows [27]:
K = E ( x 4 ) E 2 ( x 2 ) = 1 N i = 1 N ( x i x ¯ ) 4 1 N i = 1 N ( x i x ¯ ) 2 2 = N i = 1 N ( x i x ¯ ) 4 i = 1 N ( x i x ¯ ) 2 2
Applying the kurtosis criterion to frequency-domain analysis, kurtosis can be used to analyze non-stationary random signals, reflect the fluctuation and peak degree of frequency-domain signals in different frequency bands through spectral kurtosis, select the optimal number of decomposition layers, and filter out the frequency bands with the most obvious features.
When an internal A-phase grounding fault occurs at a distance of 0.8l from the M side in the line, the phase-mode transformation is performed on the additional fault current on the M side of the line, and spectrum kurtosis analysis is then performed, as shown in Figure 5. In this figure, the yellow part represents the information with the most obvious characteristics, and through which the optimal decomposition layer and analysis window can be determined.
It can be seen from Figure 5 that when the number of decomposition layers is two and the number of optimal kurtosis analysis windows is eight, the signal kurtosis is the largest, which means the fluctuation in the fault current is the most obvious. Therefore, when analyzing the fluctuation in the fault current spectrum, the two-layer wavelet packet decomposition should be selected, and the third frequency band (50–75 kHz) should be selected for spectral feature analysis. The fault line-mode current on the M side is decomposed into two layers of wavelet packets, and then its spectrum is obtained. The upper and lower kurtosis envelope curve spectra U and L are obtained from the current spectrum, and the mean curve M = (U + L)/2. Subtracting the signal from the mean curve yields the fluctuation amplitude–frequency curve of the signal, as shown in Figure 6.
The frequency spectrum fluctuation can be identified by the spectrum fluctuation amplitude–frequency curve of the fault line-mode current after removing the mean curve, and the frequency spectrum fluctuation can be quantified by calculating the spectrum fluctuation variance in Figure 6b.
From the analysis of the characteristics of the transient current spectra of internal and external faults, it can be obtained that the frequency spectrum of the current ratio in the frequency domain on both sides of the line fluctuates at multiple frequency points in an internal fault, but the amplitude is small; the ratio of the current input to output in the frequency domain fluctuates more regularly and with a larger amplitude in external faults. By comparing the fluctuation difference of the current ratio in the frequency domain when the fault occurs inside and outside the line, the fluctuation difference is quantified by the spectrum fluctuation variance, and the new principle of double-terminal transient-based protection is realized.

3.2. Fault Location Criterion

In order to eliminate the three-phase coupling effect of the line, the scheme in this paper uses the line-mode component of the transient current after phase-to-mode transformation for analysis, that is, Im = Ifa − 2Ifb + Ifc, and the sampling frequency is selected to be 200 kHz; thus, the highest observed frequency is 100 kHz.
When t = 0.221 s, internal and external faults are set on the line. The additional components of the fault current at the protection installations on both sides of the line are subjected to phase-mode transformation, and then the modulus current is decomposed by wavelet packets to obtain reconstructed wavelets of different frequency bands. The packet coefficient is used to realize fast fault identification by comparing the spectral fluctuation of the transient line-mode current.
Kurtosis analysis was performed on the currents on both sides of the line, and the optimal number of decomposition layers and the frequency band with the most obvious features were selected according to the kurtosis diagram, as shown in Figure 7. The yellow part represents the current information with the most obvious characteristics.
It can be seen from Figure 7 that the optimal number of decomposition layers for fault current kurtosis analysis is two, regardless of whether it is an internal or external fault. In the protection scheme of this paper, the third frequency band (50–75 kHz) of the two-layer wavelet packet decomposition is uniformly selected as the frequency band for fault feature analysis because of its obvious characteristics.
It can be seen from Equations (3)–(6) that the observation time of the frequency-domain current model on both sides of the line is within a certain time window after the fault traveling wave is detected at the protection installation on the corresponding side. Thus, when analyzing the frequency spectrum fluctuation of the current ratio, the time 5 ms after the fault current is detected by the protection should be selected as the observation time window of the protection criterion.
When an internal fault at a distance of 0.8l from the M side in the line and an external fault at a distance of 0.2l from the N side of the line are set, the fault currents in the 5 ms data window after the faults are detected by the protection on both sides are subjected to phase-mode transformation. After wavelet packet decomposition, the simulation results of the line-mode current spectrum fluctuation curve in the third frequency band (50–75 kHz) and the fluctuation curve of the frequency-domain current ratio are shown in Figure 8. Through Figure 8, the difference in the spectrum current fluctuation can be determined.
It can be seen from Figure 8a,c that, due to the different distances from the fault point to both sides of the line, the frequency spectrum fluctuations on both sides of the line are different. It can be seen from Figure 8b,d that, because the fault current is transmitted into the protected line and propagates from one side to the other side through the full length of the line, the frequency spectrum fluctuations on both sides of the line are different. In the criterion analysis of the current ratio, the current of one side nearer to the fault point is taken as the numerator and the current farther from the fault point is taken as the denominator because, in this way, the characteristic differences are more obvious. According to the selection of the protection criterion components, the fluctuation curve of the current ratio in the fault frequency domain of an internal fault can be obtained from Figure 8g, and that of an external fault can be obtained from Figure 8h. It can be seen from the figure that the frequency spectrum fluctuations of the current ratio in the frequency domain are very different between internal and external faults. The variance in the fluctuation curve of the current ratio can be used to identify the fault location. When an internal fault occurs, the current ratio fluctuates at multiple frequency points, but the fluctuation range is small, which indicates the variance in the corresponding volatility curve is small; when an external fault occurs, the fluctuation in the current ratio is relatively regular and the fluctuation range is large, and the variance in the corresponding volatility curve is large.

3.3. Relay Protection Scheme

Following the above analysis, the variance in the spectrum fluctuation curve of the frequency–domain current ratio in the third frequency band (50–75 kHz) with the most obvious characteristics was selected as the basis for fault identification of internal and external faults, and the corresponding protection criterion was selected according to the moment when the fault is detected on both sides. When the M side detects the fault first, the protection criterion is IM/IN, and when the N side detects the fault first, the protection criterion is IN/IM. When the protection is activated, the spectrum fluctuation variance K3 of the frequency-domain ratio of the line-mode current within 5 ms can be calculated. To be specific, 100 current values on both sides of the line are evenly sampled and calculated 5 ms after the fault occurs, taking the calculated current ratio as x1, x2, …, x100. To facilitate data identification, the calculated value of K3 is amplified by 10 times, which is shown in Formula (8).
K 3 = ( M x 1 ) 2 + ( M x 2 ) 2 + + ( M x 100 ) 2 100 × 10
where M represents the mean of the 100 calculated current ratios.
In the above formula, the variance is selected because it can reflect the fluctuation in the signal.
When K3 exceeds the threshold, it can be identified as an external fault, and when K3 is less than the threshold, it can be identified as an internal fault. The protection criterion expression is shown as follows:
K 3 < K s e t , i n t e r n a l   f a u l t K 3 > K s e t , e x t e r n a l   f a u l t
where protection criterion setting value Kset is set to be 50. In this study, simulations were performed in many conditions, and it was found that setting the threshold at 50 can correctly identify internal and external faults with enough margin.
When the protection detects a fault, it immediately utilizes the fault criteria to identify the fault, and the identification steps are as follows:
(1) After the faults are detected on both sides of the protection, the fault current data within a 5 ms time window after the fault current is sensed by the protection installations are collected, the additional component of the fault current is calculated, and the phase-mode transformation is performed;
(2) Two-layer wavelet packet decomposition is performed on the line-mode components of the additional fault current on both sides;
(3) The wavelet packet reconstruction coefficient of the third frequency band of the line-mode current on both sides is taken for analysis, the protection criterion is selected according to the selection principle of the protection criterion, and the frequency spectrum of the corresponding frequency domain current ratio is obtained;
(4) The upper and lower peak envelope curve and the mean curve for the frequency spectrum of the current ratio in the frequency domain are calculated, and the spectrum fluctuation curve of the de-averaged frequency domain current ratio is obtained;
(5) The variance in the spectrum fluctuation curve of the current ratio in the frequency domain is obtained and compared with the protection criterion threshold. If it is less than the threshold, it is determined to be an internal fault; if it is greater than the threshold, it is determined to be an external fault.

4. Simulation Verification and Analysis of Protection Scheme

In order to verify whether the protection principle proposed in this paper is effective, the 500 kV AC transmission system shown in Figure 9 was built in PSCAD. The protected line M-N was 200 km long and N-B was 100 km long. The bus capacitance to ground was set to 0.1 μF and the protection sampling frequency was 200 kHz. Subsequently, R3 and R4 were set as protection installation on the two terminals of the protected transmission line. In Figure 9, F1 and F2 represent the internal fault and the external fault, respectively. For simulation of this system to verify the correctness of the protection principle, different fault locations, fault types, and transition resistances were set as multiple fault situations.

4.1. Analysis of Different Fault Locations

Internal fault locations were set at 2, 10, 40, 90, 100, 110, 160, 190, and 198 km from the M-side bus in the line, and external faults locations were set at 20, 50, and 80 km from the N-side bus. For an A-phase ground fault that occurs inside or outside the line at t = 0.221 s, the spectrum fluctuation variance in the frequency-domain current ratio calculated by the protection criterion element at different fault locations, and the fault identification results, are shown in Table 1 and Table 2, respectively.
As shown in Table 1 and Table 2, the variance in the spectrum fluctuations in the case of internal faults on the protected line is progressively larger from the central area of the line to the sides of the line. Taking the middle end of the protected line as the dividing line, the protection criterion elements IM/IN and IN/IM are selected according to the sequence of detecting fault currents on both terminals. The fluctuations on both sides of the protected line are symmetrical, but are still much smaller than those in the case of external faults. In an external fault, the closer the fault point to the protection installation, the greater the variance in the spectrum fluctuation of the calculated frequency-domain current ratio. Thus, it can be learned from the above that the protection criterion proposed in this paper can correctly distinguish between internal and external faults occurring at different fault locations.

4.2. Analysis of Different Fault Types

The internal fault was set at 40, 100, and 160 km from the M-side bus in the line. The external fault location was set at 20, 50, and 80 km from the N-side bus outside of the line. Internal or external faults with different fault types occurred at t = 0.221 s. The spectrum fluctuation variance in the frequency domain current ratio calculated by the protection criterion element, and the fault identification results, are shown in Table 3 and Table 4, respectively.
As shown in Table 3 and Table 4, when different types of internal fault occur, the spectral fluctuation variance in the frequency-domain current ratio calculated by the protection criterion element is relatively small, and when a single-phase ground fault occurs, the spectral fluctuation variance is smaller than that of other fault types. When different types of external fault occur, the spectral fluctuation variance is quite different, and the spectral fluctuation variance in a single-phase ground external fault is bigger than that of other fault types. This will help to distinguish between the most common single-phase ground faults that occur inside and outside the protected line. In general, the spectral fluctuation variance in the frequency-domain current ratio in an internal fault is much smaller than that in external faults under any fault types. The protection criterion can correctly and effectively judge different types of internal and external faults.

4.3. Analysis of Different Transition Resistances

The internal fault location was set at 40, 100, and 160 km from the M-side bus in the line. The external fault location was set at 20, 50, and 80 km away from the N-side bus outside of the line. Internal and external faults occur when t = 0.221 s with A-phase ground faults via transition resistances of 0.001, 100, 300, and 500 Ω. The spectrum fluctuation variance in the frequency-domain current ratio calculated by the protection criterion element, and the fault identification results, are shown in Table 5 and Table 6, respectively.
As shown in Table 5 and Table 6, when a A-phase ground fault occurs with different transition resistances, with the increase in transition resistance, the frequency spectrum fluctuation variance in the frequency-domain current ratio calculated by the protection criterion element increases slightly when the internal fault occurs, but the difference is relatively small. When an external ground fault occurs with transition resistance, the frequency spectrum fluctuation variance is significantly increased, which helps to distinguish between internal and external faults. In general, the spectral fluctuation variance in the case of an internal fault is still much smaller than that in an external fault. The protection criterion proposed in this paper can correctly distinguish between internal and external faults, and it can be considered that it is hardly affected by the transition resistance.

5. Conclusions

Based on the analysis of the frequency components of the wave process of the transmission line, in this study, the spectral characteristics of the transient current on both sides of the protected line were analyzed. Through wavelet packet decomposition, the time-domain current measured at the protection installation was converted into the frequency-domain current in different frequency bands. According to the spectral fluctuation difference in the frequency-domain current ratio of the line-mode fault component in the transient state of the internal and external faults, a new protection principle based on the ratio of currents in the frequency domain on both sides was proposed. The main conclusions obtained are as follows:
(1) When there is an internal fault, the frequency spectrum of the current ratio in the frequency domain on both sides of the protected line is impacted by multiple frequency components, causing fluctuations at multiple frequency points, but the amplitude is small. When a fault occurs in the middle of the protected line, since the fault current spectra on both sides should be basically the same, the fluctuation amplitude of the current ratio is the smallest. In the case of an external fault, since the fault transient current transmitting into the protected line spreads through the entire length of the line, the amplitude of the frequency-domain current on both sides is significantly different; thus, the frequency spectrum of the ratio should have a regular fluctuation with relatively large scale.
(2) Using spectral kurtosis to select the optimal number of wavelet packet decomposition layers and the frequency band with the most obvious characteristics, it was found that the optimal number of decomposition layers is two and optimal size of the analysis window is eight. The de-averaged variance in the current ratio fluctuation curve in the frequency domain can effectively identify the spectral fluctuation characteristics of faults, so as to achieve precise identification of internal and external faults. When the variance K3 is larger than 50, an external fault is identified; otherwise, an internal fault is identified.
(3) The protection scheme based on the fluctuation of the current ratio in the frequency domain on both sides of the transmission line is basically not affected by the transition resistance, and can perform well for different fault types and different fault locations, precisely distinguishing internal and external faults.

Author Contributions

Conceptualization, Z.W.; methodology, Z.W.; software, B.Z.; validation, Z.W.; formal analysis, B.Z.; investigation, B.Z.; resources, Z.W.; data curation, L.C.; writing—original draft preparation, B.Z.; writing—review and editing, B.Z.; visualization, L.C.; supervision, Z.W.; project administration, Z.W.; funding acquisition, Z.W. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Telukunta, V.; Pradhan, J.; Agrawal, A.; Singh, M.; Srivani, S.G. Protection challenges under bulk penetration of renewable energy resources in power systems: A review. CSEE J. Power Energy Syst. 2017, 3, 365–379. [Google Scholar] [CrossRef]
  2. Eissa, M. Protection techniques with renewable resources and smart grids—A survey. Renew. Sustain. Energy Rev. 2015, 52, 1645–1667. [Google Scholar] [CrossRef]
  3. Chen, S.; Tai, N.; Fan, C.; Liu, J.; Hong, S. Adaptive distance protection for grounded fault of lines connected with doubly-fed induction generators. IET Gener. Transm. Dis. 2017, 11, 1513–1520. [Google Scholar] [CrossRef]
  4. Chen, G.; Wang, D.; Qiu, Y.; Wang, S.; Qi, X. Challenges and development prospects of relay protection technology. Autom. Electr. Power Syst. 2017, 41, 1–11. [Google Scholar]
  5. Wang, D.; Gao, H.; Li, W.; Liu, Z. Adaptability analysis of directional pilot protection for AC transmission lines connected to LCC-HVDC inverter station. Power Syst. Prot. Control 2018, 46, 33–40. [Google Scholar]
  6. Vazquez, E.; Castruita, J.; Chacon, O.L.; Conde, A. A New Approach Traveling-Wave Distance Protection—Part I: Algorithm. IEEE Trans. Power Deliv. 2007, 22, 795–800. [Google Scholar] [CrossRef]
  7. Lu, Y.; Zhang, B.; Ha, H. Development and prospect of ultra-high speed protection for EHV transmission systems based on fault-generated transients. Autom. Electr. Power Syst. 2001, 25, 56–61. [Google Scholar]
  8. Xia, M.; Huang, Y.; Wang, X. Development and present situation of transient based protections for high voltage power transmission lines. Power Syst. Technol. 2002, 26, 65–69. [Google Scholar]
  9. Liu, H.; Wang, Z.; Xu, Y.; Ma, J. Analysis of transmission process of fault-generated travelling wave along EHV transmission lines and performance of transient current protection. Power Syst. Technol. 2006, 30, 71–75. [Google Scholar]
  10. Bo, Z.Q. A new non-communication protection technique for transmission lines. IEEE Trans. Power Deliv. 1998, 13, 1073–1078. [Google Scholar] [CrossRef]
  11. Duan, J.D.; Zhang, B.H.; Ren, J.F.; Luo, S.; Ha, H.; Zhou, Y. Single-ended transient-based protection for EHV transmission lines basic theory. Proc. CSEE 2007, 27, 37–43. [Google Scholar]
  12. Ha, H.; Zhang, B.; Lv, Z. The spectrum analysis of fault transients for transmission lines part III: Extraction of fault transient spectrum. Relay 2002, 30, 1–4. [Google Scholar]
  13. Ha, H.; Zhang, B.; Lü, Z. The basic theories of boundary protection part I: Fault transient analysis. Relay 2002, 30, 7–14. [Google Scholar]
  14. Ha, H.; Zhang, B.; Lv, Z. The spectrum analysis of fault transients for transmission lines part II: Spectrum of reflection and refraction coefficient. Relay 2002, 30, 1–5. [Google Scholar]
  15. Huang, S.F.; Wang, X.G. Natural frequency characteristic analysis of UHV transmission line and its application in protection. Proc. CSEE 2009, 29, 95–102. [Google Scholar]
  16. Suonan, J.; Liu, K.; Su, X.; Zhang, J.K.; Li, Q.H.; Zhang, Y.N.; Kang, X.N. A novel transmission line pilot protection based on fault component integrated impedance. Proc. CSEE 2008, 28, 54–61. [Google Scholar] [CrossRef]
  17. Suonan, J.; Liu, K.; Song, G. A novel UHV/EHV transmission-line pilot protection based on fault component integrated impedance. IEEE Trans. Power Delivery 2011, 26, 127–134. [Google Scholar] [CrossRef]
  18. Suonan, J.; Deng, X.; Liu, K. Transmission line pilot protection principle based on integrated impedance. IET Gener. Transm. Distrib. 2011, 5, 1003–1010. [Google Scholar] [CrossRef]
  19. Wang, C.; Song, G.; Kang, X.; Suonan, J. Novel Transmission-Line Pilot Protection Based on Frequency-Domain Model Recognition. IEEE Trans. Power Delivery 2015, 30, 1243–1250. [Google Scholar] [CrossRef]
  20. Saleh, S.A.; Valdes, M.E.; Mardegan, C.S.; Alsayid, B. The State-of-the-Art Methods for Digital Detection and Identification of Arcing Current Faults. IEEE Trans. Ind. Appl. 2019, 55, 4536–4550. [Google Scholar] [CrossRef]
  21. Jia, K.; Zhao, Q.; Zhu, Z.; Bi, T. Modeling of DC Distribution System Based on High Frequency Transient Components. IEEE Trans. Smart Grid 2021, 12, 671–679. [Google Scholar] [CrossRef]
  22. Psaras, V.; Tzelepis, D.; Vozikis, D.; Adam, G.P.; Burt, G. Non-Unit Protection for HVDC Grids: An Analytical Approach for Wavelet Transform-Based Schemes. IEEE Trans. Power Delivery 2021, 36, 2634–2645. [Google Scholar] [CrossRef]
  23. Chang, H.-H.; Linh, N.V.; Lee, W.-J. A novel nonintrusive fault identification for power transmission networks using power-spectrum-based hyperbolic s-transform—Part I: Fault classification. IEEE Trans. Ind. Appl. 2018, 54, 5700–5710. [Google Scholar] [CrossRef]
  24. Shu, H.; Liu, X.; Tian, X. Single-ended fault location for hybrid feeders based on characteristic distribution of traveling wave along a line. IEEE Trans. Power Delivery 2021, 36, 339–350. [Google Scholar] [CrossRef]
  25. Yeap, Y.M.; Geddada, N.; Satpathi, K.; Ukil, A. Time-and frequency-domain fault detection in a vsc-interfaced experimental dc test system. IEEE Trans. Ind. Inf. 2018, 14, 4353–4364. [Google Scholar] [CrossRef]
  26. Amini, S.; Pasqualetti, F.; Abbaszadeh, M.; Mohsenian-Rad, H. Hierarchical location identification of destabilizing faults and attacks in power systems: A frequency-domain approach. IEEE Trans. Smart Grid 2019, 10, 2036–2045. [Google Scholar] [CrossRef] [Green Version]
  27. Xu, C.; Luo, X.; Zhang, W.; Lin, T.; Chi, Z.; Chen, Y.; Tan, W.; State Grid Beijing Electric Power Corporation; Zhuhai XJ Electric Co., Ltd. Study on the small-current grounding fault location based on the kurtosis analysis of spectrum sequence. Power Syst. Prot. Control 2018, 46, 52–58. [Google Scholar]
Figure 1. Additional network diagram of internal fault.
Figure 1. Additional network diagram of internal fault.
Electronics 11 01463 g001
Figure 2. Simulation results of the line-mode current spectrum and frequency-domain current ratio under an internal fault: (a) current spectrum on the M side; (b) current spectrum on the N side; (c) frequency-domain current ratio IM/IN; (d) frequency-domain current ratio IN/IM.
Figure 2. Simulation results of the line-mode current spectrum and frequency-domain current ratio under an internal fault: (a) current spectrum on the M side; (b) current spectrum on the N side; (c) frequency-domain current ratio IM/IN; (d) frequency-domain current ratio IN/IM.
Electronics 11 01463 g002
Figure 3. Additional network diagram of an external fault.
Figure 3. Additional network diagram of an external fault.
Electronics 11 01463 g003
Figure 4. Simulation results of the line-mode current spectrum and frequency-domain current ratio under an external fault: (a) current spectrum on the M side; (b) current spectrum on the N side; (c) frequency-domain current ratio IM/IN; (d) frequency-domain current ratio IN/IM.
Figure 4. Simulation results of the line-mode current spectrum and frequency-domain current ratio under an external fault: (a) current spectrum on the M side; (b) current spectrum on the N side; (c) frequency-domain current ratio IM/IN; (d) frequency-domain current ratio IN/IM.
Electronics 11 01463 g004aElectronics 11 01463 g004b
Figure 5. The kurtosis analysis diagram of the line-mode current on the M side: (a) kurtosis spectrum; (b) spectral kurtosis plot under optimal number of decomposition windows.
Figure 5. The kurtosis analysis diagram of the line-mode current on the M side: (a) kurtosis spectrum; (b) spectral kurtosis plot under optimal number of decomposition windows.
Electronics 11 01463 g005
Figure 6. Fluctuation amplitude–frequency curve of fault line-mode current: (a) fault line-mode current peak envelope and mean curve; (b) fluctuation amplitude–frequency curve of the fault line-mode current after removing the mean curve.
Figure 6. Fluctuation amplitude–frequency curve of fault line-mode current: (a) fault line-mode current peak envelope and mean curve; (b) fluctuation amplitude–frequency curve of the fault line-mode current after removing the mean curve.
Electronics 11 01463 g006
Figure 7. Current spectrum kurtosis diagrams on both sides of the line during internal and external faults: (a) current kurtosis diagram on the M side in an internal fault; (b) current kurtosis diagram on the N side in an internal fault; (c) current kurtosis diagram on the M side in and external fault; (d) current kurtosis diagram on the N side in external fault.
Figure 7. Current spectrum kurtosis diagrams on both sides of the line during internal and external faults: (a) current kurtosis diagram on the M side in an internal fault; (b) current kurtosis diagram on the N side in an internal fault; (c) current kurtosis diagram on the M side in and external fault; (d) current kurtosis diagram on the N side in external fault.
Electronics 11 01463 g007
Figure 8. The fluctuation amplitude–frequency curve after removing the mean curve: (a) M-side spectrum current fluctuation curve in an internal fault; (b) M-side spectrum current fluctuation curve in an external fault; (c) N-side spectrum current fluctuation curve in an internal fault; (d) N-side spectrum current fluctuation curve in an external fault; (e) IM/IN current ratio fluctuation curve in an internal fault; (f) IM/IN current ratio fluctuation curve in an external fault; (g) IN/IM current ratio fluctuation curve in an internal fault; (h) IN/IM current ratio fluctuation curve in an external fault.
Figure 8. The fluctuation amplitude–frequency curve after removing the mean curve: (a) M-side spectrum current fluctuation curve in an internal fault; (b) M-side spectrum current fluctuation curve in an external fault; (c) N-side spectrum current fluctuation curve in an internal fault; (d) N-side spectrum current fluctuation curve in an external fault; (e) IM/IN current ratio fluctuation curve in an internal fault; (f) IM/IN current ratio fluctuation curve in an external fault; (g) IN/IM current ratio fluctuation curve in an internal fault; (h) IN/IM current ratio fluctuation curve in an external fault.
Electronics 11 01463 g008
Figure 9. Schematic diagram of a 500 kV AC transmission system.
Figure 9. Schematic diagram of a 500 kV AC transmission system.
Electronics 11 01463 g009
Table 1. Spectrum fluctuation variance in the fault current ratio at different fault locations during the internal A-phase ground fault.
Table 1. Spectrum fluctuation variance in the fault current ratio at different fault locations during the internal A-phase ground fault.
Fault Location/kmProtection Criterion ElementSpectral Fluctuation VarianceIdentification Results
2IM/IN19.9309Internal faults
10IM/IN15.1508
40IM/IN7.9772
90IM/IN5.7403
100IM/IN, IN/IM0.0001
110IN/IM5.7504
160IN/IM7.9880
190IN/IM15.1010
198IN/IM19.8363
Table 2. Spectrum fluctuation variance in fault current ratios at different fault locations during the external A-phase ground faults.
Table 2. Spectrum fluctuation variance in fault current ratios at different fault locations during the external A-phase ground faults.
Fault Location/kmProtection Criterion ElementSpectral Fluctuation VarianceIdentification Results
20IN/IM586.3323External faults
50469.4242
80263.6044
Table 3. Spectrum fluctuation variance in fault current ratios when different types of internal faults occur.
Table 3. Spectrum fluctuation variance in fault current ratios when different types of internal faults occur.
Fault Location/kmFault TypeProtection Criterion ElementSpectral Fluctuation VarianceIdentification Results
40AGIM/IN7.9772 Internal faults
ABG8.1043
AG8.0957
ABC8.0923
100AGIM/IN, IN/IM0.0001Internal faults
ABG0.0001
AB0.0001
ABC0.0001
160AGIN/IM7.9880Internal faults
ABG8.1556
AB8.1373
ABC8.1339
Table 4. Spectrum fluctuation variance in fault current ratios when different types of external faults occur.
Table 4. Spectrum fluctuation variance in fault current ratios when different types of external faults occur.
Fault Location/kmFault TypeProtection Criterion ElementSpectral Fluctuation VarianceIdentification Results
20AGIN/IM586.3323External faults
ABG334.4875
AG327.2228
ABC326.7056
50AGIN/IM469.4242External faults
ABG405.0116
AB403.4514
ABC401.4293
80AGIN/IM263.6044External faults
ABG130.5306
AB138.2270
ABC138.5965
Table 5. Spectrum fluctuation variance in fault current ratio in the case of internal A-phase ground faults with different transition resistances.
Table 5. Spectrum fluctuation variance in fault current ratio in the case of internal A-phase ground faults with different transition resistances.
Fault Location/kmTransition Resistances/ΩProtection Criterion ElementSpectral Fluctuation VarianceIdentification Results
400.001IM/IN7.9772Internal faults
1007.7953
3008.5375
5008.8738
1000.001IM/IN, IN/IM0.0001Internal faults
1000.0001
3000.0001
5000.0001
1600.001IN/IM7.9880Internal faults
1007.8165
3008.5352
5008.6907
Table 6. Spectrum fluctuation variance in fault current ratio in the case of external A-phase ground faults with different transition resistances.
Table 6. Spectrum fluctuation variance in fault current ratio in the case of external A-phase ground faults with different transition resistances.
Fault Location/kmTransition Resistances/ΩProtection Criterion ElementSpectral Fluctuation VarianceIdentification Results
200.01IN/IM586.3323External faults
1002936.3285
3002786.3829
5001758.3178
500.01IN/IM469.4242External faults
100494.1373
300513.4348
500513.5844
800.01IN/IM263.6044External faults
1001044.3562
300280.4352
500124.6260
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Zheng, B.; Chu, L.; Wang, Z. Transient Protection Principle Based on Current Ratio of Two Terminals in Frequency Domain. Electronics 2022, 11, 1463. https://doi.org/10.3390/electronics11091463

AMA Style

Zheng B, Chu L, Wang Z. Transient Protection Principle Based on Current Ratio of Two Terminals in Frequency Domain. Electronics. 2022; 11(9):1463. https://doi.org/10.3390/electronics11091463

Chicago/Turabian Style

Zheng, Bowen, Lu Chu, and Zengping Wang. 2022. "Transient Protection Principle Based on Current Ratio of Two Terminals in Frequency Domain" Electronics 11, no. 9: 1463. https://doi.org/10.3390/electronics11091463

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop