Article

Analysis of the Insulation Characteristics of Hexafluorobutene (C4H2F6) Gas and Mixture with CO2/N2 as an Alternative to SF6 for Medium-Voltage Applications

1
Faculty of Electrical and Electronic Engineering, University Tun Hussein Onn Malaysia, Batu Pahat 86400, Malaysia
2
Architecture and City Design Department, King Fahd University of Petroleum & Minerals, Box #684, Dhahran 31261, KFUPM, Saudi Arabia
3
Advanced High Voltage Engineering Research Center, School of Engineering Cardiff University, Cardiff CF10 3AT, UK
4
Transportation and Traffic Engineering Department, Imam Abdulrahman Bin Faisal University, Dammam 34211, Saudi Arabia
*
Author to whom correspondence should be addressed.
Appl. Sci. 2023, 13(15), 8940; https://doi.org/10.3390/app13158940
Submission received: 4 July 2023 / Revised: 31 July 2023 / Accepted: 2 August 2023 / Published: 3 August 2023
(This article belongs to the Special Issue Advances in Electrical Equipment Insulation for New Power Systems)

Abstract

:
This paper investigates C4H2F6, a promising environmentally friendly insulating gas that possesses high dielectric strength and a low global warming potential. The study focuses on examining the insulation properties of C4H2F6 when combined with CO2/N2, aiming to assess its suitability as a substitute for SF6 in gas-insulated applications. Finite element analyses are performed to evaluate the field utilization factor and electric field distribution in the proposed mixture. The properties of liquefaction temperature were examined in this study to determine the optimal mixing ratio for applications that require a minimum working temperature. Extensive experimental investigations were carried out to assess the dielectric strength characteristics of the gas mixture in both uniform and quasi-uniform electric fields. It was found that pure HFO-1336mzz (E) exhibits a dielectric strength approximately 1.2–1.6 times higher than SF6. Experimental results have revealed that the insulation performance of a 30% HFO-1336mzz (E)/CO2 mixture closely resembles that of SF6, with a matching efficiency of up to 90% in a weakly uniform electric field. This remarkable performance can be attributed to a positive synergistic effect between HFO-1336mzz (E) and CO2, combined with the gas mixture’s excellent self-recoverability property. These experimental findings are further supported by finite element analysis, which confirms the observed results. The 30% HFO-1336mzz (E)/CO2 gas mixture at 0.15–0.20 MPa pressure and constant 0.6 mm air gap reveal superior insulation tolerance and less sensitivity to the electric field, confirming its promising medium-voltage engineering applications. The associated results of this research provide a critical reference for the engineering application of the alternating (AC) and direct current (DC) insulation characteristics of the HFO-1336mzz (E)/CO2 gas mixture.

1. Introduction

Sulfur hexafluoride (SF6) is extensively employed in high-voltage gas-insulated equipment (GIE) due to its high dielectric strength, excellent arc interruption performance, and low boiling point. However, SF6 is a strong greenhouse gas with a global warming potential (GWP) 23,500 times that of CO2 [1]. There has been a 20% rise in the amount of SF6 in the atmosphere over the last five years, and it is estimated that 80% of the SF6 generated globally is utilized in the power sector [2,3]. Reducing SF6 emissions now might add 1.5% to the Paris agreement’s aim of maintaining the global average temperature increase to far below 2 °C [4]. SF6 was one of the six primary greenhouse gases included in the Kyoto Protocol in 1997 [5,6]. This makes it imperative to work on decreasing or capping SF6 use. The pursuit of a gas insulation medium that may substitute SF6 as safely as possible has gained significant attention in recent years. Therefore, the realization of SF6-free practices has now become a crucial task for the green development of power grids.
Many studies have been carried out throughout the years on the insulating capacities of several gases as SF6 substitutes [7,8,9]. No gas or gas mixture has been found to this day which can completely replace SF6. Hence, gases that can replace SF6 must have (1) outstanding physicochemical properties, such as a low liquefaction temperature, low toxicity, good thermal and chemical stability, and non-flammability; (2) exceptional insulation and arc quenching abilities; and (3) excellent environmental characteristics, specifically low GWP and Ozone Depletion Potential (ODP) values [10]. ODP is defined as “Relative amount of degradation caused to the ozone layer compared with trichlorofluoromethane (R-11 or CFC-11) being fixed at an ODP of 1”.
Two types of alternatives to SF6 were investigated: naturally occurring buffers and synthetic gases. Buffer gases include natural gases (CO2, N2, and dry air) [11,12,13], and synthetic gases include gases such as PFCs, CF3I, and c-C4F8 [1417]. The use of buffer gases such as carbon dioxide as a dielectric medium requires large equipment due to momentous expansion in pressure. Moreover, 100% CO2 insulation characteristics are only around 40% of SF6. Although carbon dioxide’s safety and low cost are advantageous factors, implementing it in practical medium-voltage applications would require replacing the existing equipment with bulky construction to sustain high pressure to provide sufficient dielectric strength. Synergistic effects allow for a decrease in GWP proportional to the admixture ratio in SF6-based gas mixtures like SF6/N2 and SF6/CF4 while maintaining usable electric characteristics [12]. Tetrafluoropropene, a novel chemical with four interesting properties, was only discovered recently [13]. It was determined that fluoroketones (C5-FK) [14], fluoronitriles (C4F7N) [15], and trifluoroiodomethane [16] have sufficient electric strength to be employed in electrical equipment under realistic working circumstances. They are usually mixed with low-boiling-point gases, such as carbon dioxide (CO2) or nitrogen (N2), when utilized in HV applications because of their high boiling points. The new alternatives have an electric strength comparable to SF6 and a reduced GWP. Despite the fact that the aforementioned new ecologically friendly insulation gases have been researched and suggested, none of them are a satisfactory substitute because they all have drawbacks. For example, the biological toxicity of C4F7N is still debatable, and its GWP is very high (about 2400). The high liquefaction temperature of C5F10O limits its practical applications since it requires too much buffer gas. Lastly, HFO-1234ze (E) and HFO-1336mzz (Z) were the HFO gases suggested as insulating medium. HFO-1234ze (E) has a lower insulating strength than SF6 and a lower liquefaction temperature (−19.4 °C at 0.1 MPa) [17]. The dielectric strength of HFO-1336mzz (Z) is twice that of SF6, but it has a very high boiling point of 33.4 °C [18].
In this paper, we suggest transhexafluoro-2-butene (HFO-1336mzz (E)/(C4H2F6) as a promising dielectric gas. HFO-1336mzz (E) is a common refrigerant because it has good thermal stability, is colorless, and has no fire or explosion risks. HFO-1336mzz (E) has a very short atmospheric lifespan (days to weeks) and a low GWP of just approximately 18. Since no chlorine nor bromine is present, the ODP value is 0. Because its molecules have such strong electronegative characteristics, they provide a great insulating performance, 1.2 to 1.4 times higher than benchmark SF6. HFO-1336mzz (E) has the drawback of a high liquefaction temperature, about 8 °C, limiting its application as a dielectric gas. To compensate for the drawback of its high boiling point, the proposed gas should be mixed with a buffer gas, such as N2 or CO2, with temperatures of −196 °C and −79 °C, respectively [19].
Related investigations on the insulation capabilities of HFO-1336mzz (E) are currently lacking. Rabie et al. 2015 executed computational screening of several insulating gases, and among them, HFO-1336mzz (E)’s dielectric characteristics were estimated to be almost 1.8 times those of SF6 [20]. Kothe et al. 2020 tested a number of new environmentally beneficial gases. They discovered that the insulating strength of HFO-1336mzz (E) and CO2 or N2 is comparable to that of mixtures of C5F10O/CO2 and C4F7N/CO2 [21]. Its synergistic interactions with various buffer gases and its breakdown characteristics in inhomogeneous electric fields remain unknown. The molecular structure and chemical properties of HFO-1336mzz (E) gas are shown in Figure 1 and Table 1, respectively.

2. Materials and Methods

This research work is divided into two phases, finite element modeling and insulation strength testing. HFO-1336mzz (E) and the mixture’s dielectric breakdown strength were investigated under HVAC and HVDC conditions. The experiments were conducted following the IEC60270 standard, and standard atmospheric conditions were maintained in the lab (temperature t0 = 20 °C, pressure b0 = 0.1013 MPa, absolute humidity h0 = 11 gm/m3) [22]. The TERCO test setup generates HVAC and HVDC test voltages for experiments. The test vessel is modified to meet the technical requirement of changing the electrode’s air gap. For this purpose, a linear actuator is installed at the bottom layer of the test vessel. The test vessel is composed of aluminum, and plexiglass is used as the vessel window. The vessel height is 800 mm, the width is 90 mm, and the thickness of the vessel wall is 5 mm. Hence, based on the dimensions, the total volume of the test gas is approximately 5 L and can bear a pressure of 0.6 MPa. A constant electrode gap distance of 6 mm is maintained throughout the experimental and simulation analysis. Pressure and vacuum gauges are installed to accurately measure the gas pressure inside the vessel. A one-way air valve is installed at the bottom flange to pump gas from the vessel in and out. Prior to conducting the experiments, the test chamber was vacuumed to 0.09 MPa through a vacuum pump and then filled with CO2. This process is repeated 5 times to ensure no impurities are left inside the pressure vessel.
Gas breakdown occurs as the critical field strength is achieved, and the externally applied voltage is recorded as the breakdown voltage. To investigate the basic insulation performance, i.e., the electric strength near its intrinsic strength, weakly non-uniform and uniform fields are used. These field distributions are formed by plane–plane and sphere–plane electrode configurations. The advantages of a sphere–plane arrangement are a simplified alignment, a relatively compact size, and fast conditioning due to the small surface area stressed by the highest field. The sphere–plane arrangement can create field utilization factors representing real GIS and representing real GIS components such as switches. A plane–plane electrode arrangement’s main advantage is the uniformity of field distribution [23].
The electrode configurations are plane–plane and sphere–plane for uniform and slightly uniform electric fields. All the electrodes are cleansed with anhydrous alcohol and dried with cotton to remove the dust. The electrode surfaces are polished with 5000 mesh sandpaper to ensure that the surface roughness value is below 2.5 μm; as a further precaution, 3 aging tests are conducted on the test electrode configuration before every test to remove the protuberances and tiny particles on the electrodes. The electrode schematic diagram can be seen in Figure 2. An AC voltage of known value is applied to the buffer gas CO2 to calibrate and validate the measuring apparatus’s accuracy. The test gas HFO1336-mzz (E) and buffer gases are injected into the pressure vessel following Dalton’s law of partial pressure. A standing time of 24 h is provided to ensure gas mixture uniformity. Considering the insulation medium’s recovery time, the interval between two adjacent breakdowns was set to three minutes. A slow voltage increase rate avoids overestimations of the electric strength due to the statistical time lag but increases the experimental time. Therefore, a fast voltage ramping rate is utilized up to around 80% to 90% of the expected breakdown voltage, and then the voltage is increased in small steps of 0.5 kV/s compared to the initial breakdown value. Under each test condition, at least ten repeated tests were performed. If the initial and consecutive breakdown voltage error is greater than 10%, the test will be repeated, and then the test’s average value is recorded as the breakdown voltage. Moreover, benchmark tests are also conducted using pure SF6 gas.

3. Experimental Setup

The experiment circuit is presented in Figure 3 and Figure 4 for HVAC and HVDC, respectively. IEC60270 [24] is the basis for the experimentation procedure. A control desk (HV 9103) includes a peak, impulse, and DC voltmeter and a variable voltage supply. The control desk operates and controls the HVAC, HVDC, and impulse equipment. The supply voltage to HV9103 is 220–230 V, 50 Hz, and the regulating voltage is 0–220 V AC. During HVAC breakdown, a resistor (HV9121) is attached to safeguard the test transformer (HV 9105), which has an output of 220 V–100 kV in a single stage and 200 kV in two stages. The breakdown voltage is measured in real time by the voltmeter via a measuring capacitor (HV9141), as shown in Figure 3. The HVDC voltage up to 140 kV, 50 mA, and 50 Hz is generated via an experimental setup, as shown in Figure 4. The circuit consists of two HV rectifiers (HV9111) connected with a control desk (HV9103) and a smoothing capacitor (HV9112). A measuring resistor HV9113 measures the DC breakdown voltage. All the equipment can discharge itself except the smoothing capacitor, which is discharged through an external earthing switch.

Finite Element Modeling (FEM)

It is difficult to accurately measure the electric field at every point between the electrodes. Additional challenges should be solved since the electrodes are plunged into pressurized gas in a test chamber. A more practical and economical method of carrying out the measurements is using numerical simulation techniques with computer-aided software. This enables users to skip expensive, intricate, trial-and-error laboratory procedures that are pretty challenging. The electric field utilization factor and field distribution modeling is carried out in this research using the finite element modeling software COMSOL Multiphysics. In FEM software, the geometry of the configuration is constructed, and boundary value conditions are specified [25]. The distribution of the electric field was simulated using the electrostatics module. The analysis necessitates the identification of electrostatic boundary conditions and material properties. An essential element for the simulation is the relative permittivity εr; the εr values of plexiglass and aluminum are 3.4 and 1, respectively, and the gas permittivity value is also selected as 1. The 0 V voltage is at the ground electrode, while the high-voltage electrode is energized with a voltage of 10 V. The bounding box that reflects the real size of the gas chamber is used to symbolize it with dimensions of 140 mm × 80 mm. Similar to the practical experiments, the air gap between electrodes is fixed at 6 mm. The electric field distribution at each point is precisely calculated with the meshing size set to a user-defined extra fine. The design meshing consists of 15,235 domain elements and 384 boundary elements.
The electric field potential for uniform fields configured by plane–plane electrode configurations is shown in Figure 5. It can be seen that the potential is highest at the HV electrode surface and decreases gradually until 0 V at the ground electrode.
When the boundary conditions are satisfied, calculating the electrostatic field requires Gauss’s and Poisson’s equations. The equations are stated as
E = V
V = ρ ε 0
Here E represents the electric field, the applied voltage is represented by V , ρ shows space charge density, and ε 0 represents the dielectric permittivity of free space.
The law of charge conservation must be obeyed by the electric field strength:
. j = 0
j = ρ . v = ρ . μ . E
Here v represents the drift velocity and μ represents the ion mobility across electrode gap distance, by the following equation:
2 V V = 0
The FEA software ascertains the behavior of the electric field. The E m a x and field utilization factor η for each electrode layout were assessed using the breakdown information from the experimental testing. For the sphere–plane and plane–plane configurations, Figure 6 and Figure 7 illustrate that the E m a x occurs in a location of extremely high stress, which measures 1.7475 V/mm on a sphere–plane system and 2.24986 V/mm on a plane–plane system. FEA simulation aims to gather more information about the electric field distribution at every step, which is impossible to observe during practical experiments. As seen in Figure 6 and Figure 7, the sphere–sphere electrode configuration reveals a higher stress point at the center of the electrodes, and the plane–plane electrode configuration shows the highest electric field point at the side edge of the electrode. The field utilization factor η is calculated using Equation (6).
η = E m e a n E m a x
while E m a x represents the maximum electric field and E m e a n can be calculated for each electrode configuration as Equation (7) below:
E m e a n = v d
Here v represents the applied voltage, and d represents the air gap length between the electrodes. To calculate the utilization factor η , a voltage of 10 v is applied to the high-voltage electrode and the ground electrode is assigned 0 volts. The gap distance is maintained at 6 mm for both configurations. The non-uniform electric field contributes to a higher E m a x value, and hence lower breakdown voltages. Theoretically, a higher field utilization factor increases the breakdown voltage value. The simulation results presented in this work have field utilization factors for slightly uniform (sphere–plane) and uniform (plane–plane) configurations, which are 0.74 and 0.95, respectively, proving the electric field uniformity of plane electrodes, as shown in Table 2.
The electrode configuration proposed has a uniform and quasi-uniform electric field; this transition can be analyzed through field inhomogeneity factor α calculation using Equation (8).
α = E m a x E m e a n
The electric field inhomogeneity factor provides a quantitative measure of how uniform the electric field is within a specified region or across specific boundaries. This factor quantifies how much the electric field deviates from uniformity. If α is close to zero, it indicates that the electric field is nearly uniform. Conversely, as α increases, it signifies a more significant deviation from uniformity, indicating a more inhomogeneous electric field.

4. Experimental Results

Experimental results were obtained by varying pressure from 0.05 to 0.30 MPa and increasing the mixing ratio from 10–30% of base gas and 70–90% of buffer gas. The pressure is varied to determine the gas mixture characterization for medium- or high-voltage switchgear. Based on the results, it is evident that the proposed gas mixture can be utilized for a medium-voltage switchgear system, as it shows promising results at pressure 0.20 MPa or below. The mixing values are varied to determine the optimum mixing ratio, which can be employed in practical applications with dielectric strength comparable to the benchmark SF6 gas. The insulation performance reliability of the HFO1336Mzz (E)/CO2 gas mixtures is assessed by comparing with the benchmark SF6. SF6 gas is tested along with all the proposed test gas mixture combinations under the same testing conditions and field configurations. In sphere–plane configuration under AC test voltage of 30%, the base gas mixture at 0.15 MPa shows 1.2 times higher dielectric strength than SF6.
Similarly, the proposed mixture shows 0.9 times dielectric strength for DC voltage compared to SF6. On the other hand, plane–plane configuration under AC voltage shows 1.60 times and under DC voltage shows 1.15 times higher breakdown strength than SF6. The detailed experimental results under HVAC and HVDC are discussed in Section 4.1.

4.1. HVAC Breakdown Characteristics of HFO-1336mzz (E) Mixture with CO2/N2 under Quasi-Uniform Electric Field

The HVAC dielectric properties of the test mixtures are comprehensively investigated in terms of breakdown voltages relative to absolute pressure and mixing ratios. The HVAC breakdown properties of the HFO-1336mzz (E)/CO2 and HFO-1336mzz (E)/N2 mixtures are investigated under uniform and weakly uniform electric field configurations. HFO-1336mzz (E) has a high liquefaction temperature of 7.5 °C, so it needs to be mixed with buffer gases such as CO2 and N2. The buffer gases N2/CO2 are inert in nature; hence, they de-energize free electrons and help reduce the overall greenhouse gas effect. It is evident from Figure 8a that breakdown voltages of the HFO-1336mzz (E)/CO2 gas mixture significantly increase with the increase in applied pressure and mixing ratio. It is because of the significant electro-negativity properties of the proposed gas and the positive synergistic effect between the base gas and buffer gas. Under a quasi-uniform field configuration (sphere–Plane), the breakdown voltages increase nonlinearly with increasing pressure. It is observed that when the HFO-1336mzz (E) mixing ratio is 20% or more, it has a higher breakdown voltage than SF6 at a pressure of less than 0.2 MPa. When the pressure increases from 0.2 MPa, the HFO-1336mzz (E)’s breakdown voltage decreases compared to SF6. At 0.1 MPa and increasing the base gas mixing ratio from 10 to 30%, the proposed gas breakdown potential increases from 10.5 to 22.4 kV. When the HFO-1336mzz (E) mixing ratio is 20%, the breakdown increases from 17.6 kV to 29.7 kV from a pressure of 0.05 to 0.3 MPa. When pressure increases from 0.2 MPa, the proposed gas mixture breakdown voltage is less than SF6, i.e., at 0.3 bar, SF6′s breakdown strength is 1.17 times higher than that of HFO-1336mzz (E)/CO2. In addition, by increasing the gas content of HFO-1336mzz (E) in the gas mixture, the breakdown voltage also increases relatively. When the mixing ratio of HFO-1336mzz (E) is 30%, at 0.15 MPa, the breakdown strength is 1.4 times higher than that of SF6. A similar effect can be seen for HFO-1336mzz (E)/N2 mixtures, in which the highest breakdown strength is achieved when the base gas mixing ratio is the maximum, i.e., 30%. The HFO-1336mzz (E)/N2 mixture’s initial breakdown voltages at lower pressure, i.e., 0.5 and 0.1 MPa, have a 0.67 percent lower breakdown value than the CO2 mixture. HFO-1336mzz (E)/N2 mixtures show relatively nonlinear results as compared to HFO-1336mzz (E)/CO2. However, in both cases, the proposed gas mixtures show superior insulation properties at 0.15–0.20 MPa pressure, as seen in Figure 8.

4.2. HVAC Breakdown Characteristics of HFO-1336mzz (E) Mixture with CO2/N2 under Uniform Electric Field

HFO-1336mzz (E)/CO2 and HFO-1336mzz (E)/N2 mixtures have increased dielectric strength values when pressure and mixing ratio increase. Similarly, the breakdown properties of HFO-1336mzz (E)/CO2 under HVAC test conditions are investigated for uniform field configurations of plane–plane electrodes, as shown in Figure 8b. Linearity in the breakdown voltage curve is observed in uniform field configuration with increasing pressure. It can be noted that the 30% base gas mixture under the uniform electric field shows an approximately 1.04 times higher breakdown voltage than SF6 at a 0.6 mm constant air gap for all applied pressure ranges. The results for the N2 mixture under the same test configuration reveal that the 30% base gas mixture above 0.15 mixture has a higher dielectric breakdown voltage value than SF6. Below 0.15 MPa voltage, all N2 mixtures have lower breakdown values, as can be seen in Figure 9.

4.3. HVDC Breakdown Characteristics of HFO-1336mzz (E) Mixture with CO2/N2 under Quasi-Uniform Electric Field

DC breakdown experiments were performed at 0.05–0.3 MPa to examine the impact of the mixing ratio on the breakdown strength of the HFO-1336mzz (E) mixtures. The findings are displayed in Figure 10. With a rise in HFO-1336mzz (E) gas concentration, the proposed gas mixture’s breakdown voltages grow nonlinearly, showing the proposed gas’s sensitivity to the applied electric field. In sphere–plane electrode configuration, the 30% HFO-1336mzz (E)/CO2 gas mixture shows nearly equivalent dielectric strength to SF6 at 0.2 MPa and HFO-1336mzz (E)/N2 at 0.1 MPa. SF6′s breakdown voltage increases linearly with increasing pressure. Under HVDC applied voltage, it is evident that the 30% HFO-1336mzz (E)/CO2 mixture shows promising results when the pressure applied is below 0.20 MPa. When pressure is increased from 0.2 MPa, the breakdown voltage of SF6 continues to increase, but the gas mixture under test shows a decreasing trend, specifically for the N2 mixture. It reveals the stable insulation properties of SF6 and enhanced dielectric properties of the CO2 mixture at lower pressure. Both of the proposed buffer gas mixtures at a pressure above 0.25 MPa show nonlinearity in breakdown voltage, which is due to the same polarity effect of DC, along with the fact that the electrodes’ surface state and area may be the driving nonlinearity factors at higher pressure values. At pressure values below 0.15 MPa, the values are relatively linear.

4.4. HVDC Breakdown Characteristics of HFO-1336mzz (E) Mixture with CO2/N2 under Uniform Electric Field

Similarly, the HVDC breakdown properties of the proposed mixture are investigated under uniform field configuration. It is evident that the breakdown strength of the test gas increases linearly with an increase in pressure and mixing ratio. Nevertheless, the 30% HFO-1336mzz (E)/CO2 has 1.21 times higher dielectric strength than SF6 at 0.15 MPa under uniform field configuration, as can be seen in Figure 11a. The 30% base gas concentration shows a more promising result in terms of dielectric strength than SF6. The 30% base gas mixture composition can be used for medium-voltage applications. The dielectric characteristics of HFO-1336mzz (E)/N2 for the uniform field configuration can be seen in Figure 11b. SF6 shows a linear increase in breakdown voltage, and nonlinearity can be seen in the proposed gas mixture. The 30% HFO-1336mzz (E)/N2 mixture at lower pressure of less than 0.23 MPa shows lower breakdown strength, but higher than SF6. Above 0.23 MPa, the breakdown voltage increases with respect to SF6. The 30% HFO-1336mzz (E)/N2 mixture at 0.30 MPa pressure reveals 1.06 times higher breakdown voltage value than SF6.

5. Other Characterization of the Dielectric Gas Mixture

5.1. Global Warming Potential of HFO-1336mzz (E)/CO2 Gas Mixture

The global warming potential of HFO-1336mzz (E) is 18, which is considerably less than SF6. The proposed gas mixture has been developed as an alternative to SF6, but the GWP of the mixture needs to be investigated. According to the environmental protection view and ideal gas conditions, the GWP is determined by summing the weight fractions of each component and multiplying that number by their respective GWP, as shown in Equation (9) [24,26]. k represents the mixing ratio of base gas, and the GWP and molar mass of HFO-1336mzz (E) are 18 and 164.5, respectively. Similarly, the GWP and molar mass of CO2 are 1 and 44, respectively. The mixing ratio of the base gas is increased from 1 to 100%, and the GWP value also starts increasing from 1 to 18. It is evident from the results presented in Figure 12 that the proposed mixture has a negligible environmental concern compared to SF6, which has 23,500 GWP.
G W P = k × 164.5 × 18 + ( 1 k ) × 44 × 1 k × 164.5 + ( 1 k ) × 44

5.2. Liquefaction Temperature

The important parameter for a dielectric gas is its liquefaction temperature, which is applicable in practical applications. The liquefaction temperature is the point at which gases melt to a liquid state. At high pressure, the temperature of dielectric gas also increases, transforming the gaseous state to a liquid. The HFO-1336mzz (E) boiling point is comparatively high, at 7.58 °C at 0.1 MPa pressure; hence, it cannot be employed for low-temperature applications. Therefore, it is mixed with buffer gases such as CO2 and N2, having low liquefaction temperatures of −79 °C and −196 °C, respectively, at 0.1 MPa pressure. The HFO-1336mzz (E) and CO2 mixture’s liquefaction temperatures are analyzed. The relationship between the liquefaction temperature at room conditions T b , vapor pressure (P), and liquefaction temperature of the base gas in mixture T is expressed in Equation (10). A and R are gas constants with values of 87 J/mol. K and 8.3 J/mol. K, respectively.
P = e x p A R 1 T b T
Equation (11) can be modified by introducing m , a mixing ratio, by considering ideal gas conditions; the HFO-1336mzz (E) and CO2 mixture’s liquefaction temperature can be calculated using Equation (5) [27].
T m b = T b 1 ln 10 m P A / R
The HFO-1336mzz (E) and CO2 mixture’s liquefaction temperatures with different mixing ratios and pressure ranges, from 0.1 to 0.3 MPa, are depicted in Figure 13. Increasing the pressure and the HFO-1336mzz (E) percentage in the mixture increases the liquefaction temperature. A similar relation is observed by increasing the pressure, which increases the liquefaction temperature. Figure 13 indicates the constraint on the choice of mixing ratio and pressure. If, for instance, a pressure of 0.1 MPa and a critical temperature of −20 °C are required for medium-voltage application, the HFO-1336mzz (E) mixing ratio should not exceed 30%. Similarly, for 0.2 and 0.3 MPa, the HFO-1336mzz (E) should be within 15% and 10%, respectively.

5.3. Synergistic Effect of HFO-1336mzz (E)

The synergistic effect characterizes the gas mixture’s dielectric strength, as mixing two gases results in higher or lower breakdown voltages than in their pure form. To analyze the synergistic effect of the HFO-1336mzz (E)/CO2 gas mixture, a coefficient S is introduced, as can be seen in Equation (12) [28]. In the equation, V b u f f e r , V b a s e , and V m i x show CO2 breakdown voltage, HFO-1336mzz (E), and their mixture, where m denotes the percentage mixture of HFO-1336mzz (E) in the gas mixture.
V m i x = V b u f f e r + m V b a s e V b u f f e r m + 1 m S V b a s e > V b u f f e r
Figure 14 shows the synergistic effect of HFO-1336mzz (E) with CO2 gas. If S = 0, it means there is no synergistic effect, i.e., the breakdown of the mixture is equal to a weighted sum of the component gases and shows a linear effect of V m i x with m . If S > 0 , it means the gas mixture weighted average is greater than the component gases and is known as a negative synergistic effect. If S < 0 , it means the gas mixture weighted sum is less than the component gases and is known as the positive synergistic effect. If 0 < S < 1 , it shows a synergistic effect.
Figure 14 above shows the S value for HFO1336Mzz (E)/CO2 and HFO1336Mzz (E)/N2 for pressure ranges from 0.05 to 0.3 MPa and a mixing ratio ranging from 70 to 90% of base gas proportion in the gas mixture. It is evident from the figure that for all mixture compositions, the S values for HFO1336Mzz (E)/CO2 are lower than HFO1336Mzz (E)/N2. In the case of HFO1336Mzz (E)/CO2, the mixture composition of (90/10%) for all pressure ranges shows the S coefficient value close to zero, indicating a positive synergistic effect. Moreover, the HFO1336Mzz (E)/CO2  S values are 0 to 0.7, while the HFO1336Mzz (E)/N2 values range from 0 to 0.8.
Therefore, even though the two types of buffer gases have almost equivalent dielectric strength, the dielectric breakdown strength of HFO1336Mzz (E)/N2 is inferior to HFO1336Mzz (E)/CO2 mixtures, as validated through synergistic effect analysis.

5.4. Self-Recoverability Test

Self-recoverability of insulation is the ability of insulation to restore itself after breakdown caused by temperature rise and overvoltage. The self-recoverability of gas is tested by analyzing the consecutive AC breakdown voltages at 3 min. A total of 40 breakdown shots were recorded, and it was found that the 70%CO2/30%HFO-1336mzz (E) mixture shows a little deviation from the initial breakdown at around 30 shots. After the 30th breakdown, the voltage shows a decreasing trend, but the percentage difference between the first and last breakdown is still as low as 5%. It is due to the decomposition of the mixture and ionization of gas particles, which are conductive in nature and reduce the breakdown voltages. Another reason might be the conductive carbon deposition on the surface of the electrodes. Hence, the experiment concluded that the 70%CO2/30%HFO-1336mzz (E) mixture could be successfully employed for high-voltage applications at higher pressure. In Figure 15, the self-recoverability of the gas mixture is plotted.

6. Conclusions

This paper has systematically investigated HVAC and HVDC voltage breakdown characteristics of HFO-1336mzz (E) mixed with CO2/N2 as an environmentally friendly alternative for gas-insulated applications. The mixture ratio and gas pressure influence on the insulation characteristics of the proposed gas mixture are investigated under uniform (plane–plane) and quasi-uniform (sphere–plane) electric fields and compared with the hazardous SF6 gas. Finite element analysis is performed on HFO-1336mzz (E)/CO2 to study the electric field distribution of electric potential. The field utilization factor and maximum field intensity point are determined for uniform and weakly non-uniform electric fields. The FEM results reveal a uniform electric field in plane–plane configuration comparable to experimental results. Experimental results show that under quasi-uniform electric fields, the 30% HFO-1336mzz (E) at a pressure below 0.2 MPa has relative HVAC and HVDC dielectric strength equivalent to SF6. Under uniform field configuration at 0.3 MPa, the gas mixture’s AC and DC dielectric strength is comparable to SF6. Furthermore, a synergistic effect of the proposed gas mixture shows favorable results, as synergistic coefficient S values between HFO-1336mzz (E) and CO2 are in the range of 0.05–0.75. The GWP potential of the test mixture for all the mixing ratios is calculated, and it is found that the maximum GWP value is 18, which proves the claim of an eco-friendly alternative to SF6. Additionally, the self-recoverability testing of the 30% HFO-1336mzz (E) + 70% CO2 mixture reveals that after 40 consecutive breakdowns shots, only a 5% minimum difference is noted between the first and last breakdown. The 30% HFO-1336mzz (E)/CO2 gas mixture at 0.15–0.20 MPa pressure and constant 0.6 mm air gap in relevance to practical MV-GIE reveals superior insulation tolerance and less sensitivity to the electric field brings about its potential engineering applications.

Author Contributions

Conceptualization, R.A.R. and R.A.; methodology, R.A.; software, R.A. and A.J.; validation, R.A.; formal analysis, A.S.A., B.A.-R. and A.J.; investigation, R.A. and R.U.; resources, R.U.; data curation, R.A.; writing—original draft preparation, R.A.; writing—review and editing, R.A., A.J. and R.U.; visualization, B.A.-R. and A.S.A.; supervision, R.A.R.; project administration, A.S.A., A.J. and R.U.; funding acquisition, R.A.R., A.S.A. and B.A.-R. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Acknowledgments

This research was supported by The Ministry of Higher Education (MOHE) Malaysia through the Fundamental Research Grant Scheme (FRGS/1/2020/TKO/UTHM/02/6), and we acknowledge the support of King Fahd University of Petroleum & Minerals.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviation

HFOHydrofluoroolefins
ODPOzone Depletion Potential
SF6Sulfur Hexafluoride
HVHigh Voltage
CO2Carbon Dioxide
GWPGlobal Warming Potential
HVACHigh-Voltage Alternating Current
HVDCHigh-Voltage Direct Current
IECInternational Electro Technical Commission
FEMFinite Element Modelling
GNDGround
kVKilovolt

References

  1. Mohamed, R.; Christian, M.F. Assessment of eco-friendly gases for electrical insulation to replace the most potent industrial greenhouse gas SF6. Environ. Sci. Technol. 2018, 52, 369–380. [Google Scholar]
  2. Christophorou, L.G.; Olthoff, J.K.; Brunt, R.J.V. Sulfur hexafluoride and the electric power industry. IEEE Electr. Insul. Mag. 1997, 13, 20–24. [Google Scholar] [CrossRef]
  3. Simmonds, P.G.; Rigby, M.; Manning, A.J.; Park, S.; Stanley, K.M.; McCulloch, A.; Stephan, H.; Prinn, R.G. The increasing atmospheric burden of the greenhouse gas sulfur hexafluoride (SF6). Atmos. Chem. Phys. 2020, 20, 7271–7290. [Google Scholar] [CrossRef]
  4. IPCC. Climate Change 2013: The Physical Science Basis. Working Group I Contribution to the Fifth Assessment Report on Interngovernmental Panel on Climate Change; Cambridge University Press: Cambridge, UK, 2013. [Google Scholar]
  5. U.S. Environmental Protection Agency (USEPA). Global Mitigation of Non-CO2 Greenhouse Gases: 2010–2030; USEPA: Washington, DC, USA, 2013. [Google Scholar]
  6. Breidenich, C.; Magraw, D.; Rowley, A.; Rubin, J.W. The Kyoto protocol to the United Nations framework convention on climate change. Am. J. Int. Law 1998, 92, 315–331. [Google Scholar] [CrossRef]
  7. Beroual, A.; Haddad, A. Recent advances in the quest for a new insulation gas with a low impact on the environment to replace sulfur hexafluoride (SF6) gas in high-voltage power network applications. Energies 2017, 10, 1216. [Google Scholar] [CrossRef] [Green Version]
  8. Khan, B.; Saleem, J.; Khan, F.; Faraz, G.; Ahmad, R.; Ur Rehman, N.; Ahmad, Z. Analysis of the dielectric properties of R410A Gas as an alternative to SF6 for high, & Ahma applications. High Volt. 2019, 4, 41–48. [Google Scholar]
  9. Abd-Rahman, R.; Haddad, A.; Kamarudin, M.S.; Yousof, M.F.M.; Jamail, N.A.M. Dynamic modelling of polluted outdoor insulator under wet weather conditions. In Proceedings of the PECON 2016—2016 IEEE 6th International Conference on Power and Energy, Conference Proceeding, Melaka, Malaysia, 28–29 November 2016; pp. 610–614. [Google Scholar]
  10. Owens, J.G. Greenhouse gas emission reductions through use of a sustainable alternative to SF6. In Proceedings of the 2016 IEEE Electrical Insulation Conference (EIC), Montreal, QC, Canada, 19–22 June 2016; IEEE: New York, NY, USA, 2016; pp. 535–538. [Google Scholar]
  11. Ahmed, R.; Abd Rahman, R.; Kamarudin, M.S.; Yousof, M.F.M.; binti Ahmad, H.; Salem, A.A. Feasibility of Fluoronitrile (C4F7N) as a Substitute to Sulphur Hexafluoride (SF 6) in Gas Insulated Application: A Review. In Proceedings of the 2022 IEEE International Conference on Power and Energy (PECon), Langkawi, Malaysia, 5–6 December 2022; IEEE: New York, NY, USA, 2022; pp. 391–396. [Google Scholar]
  12. Ahmad, R.; Abd Rahman, R.; Salem, A.A.; Jamail, N.A.M.; Ab Rahman, A.; Hamid, H.A. Finite Element Analysis of Electric Field Distribution in C4F7N as an Alternative to SF6 For Electrical Insulation. In Proceedings of the 2021 3rd International Conference on High Voltage Engineering and Power Systems (ICHVEPS), Bandung, Indonesia, 5–6 October 2021; IEEE: New York, NY, USA, 2021; pp. 126–131. [Google Scholar]
  13. Xiao, S.; Tian, S.; Zhang, X.; Cressault, Y.; Tang, J.; Deng, Z.; Li, Y. The influence of O2 on decomposition characteristics of c-C4F8/N2 environmental friendly insulating gas. Processes 2018, 6, 174. [Google Scholar] [CrossRef] [Green Version]
  14. Tan, D.; Zhou, B.; Xue, J.; Cai, F.; Xiao, D. Basic impulse performance of high-pressure CF3IN2 gas mixture and its application for 126 kV GIL. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 1380–1386. [Google Scholar]
  15. Chen, L.; Widger, P.; Kamarudin, M.S.; Griffiths, H.; Haddad, A. CF3I gas mixtures: Breakdown characteristics and potential for electrical insulation. IEEE Trans. Power Deliv. 2016, 32, 1089–1097. [Google Scholar] [CrossRef]
  16. Wang, X.; Wang, Z.; Chen, J.; Shi, X.; Li, X. Surface Flashover Characteristics of Epoxy Resin Composites in SF6/CF4 Gas Mixture with DC Voltage. Energies 2022, 15, 4675. [Google Scholar] [CrossRef]
  17. Koch, M.; Franck, C.M. High voltage insulation properties of HFO1234ze. IEEE Trans. Dielectr. Electr. Insul. 2015, 22, 3260–3268. [Google Scholar] [CrossRef]
  18. Yokomizu, Y.; Sato, M.; Kodama, N.; Edo, T.; Kokura, K. Chemical species produced in arc-quenching gas CO2/O2 mixed with C3H2F4, C4-FN or C5-FK: Prevention of condensed-phase carbon formation and its formulation. J. Phys. D Appl. Phys. 2020, 53, 145202. [Google Scholar] [CrossRef]
  19. Li, Y.; Zhang, X.; Xiao, S.; Chen, Q.; Tang, J.; Chen, D.; Wang, D. Decomposition properties of C4F7N/N2 gas mixture: An environmentally friendly gas to replace SF6. Ind. Eng. Chem. Res. 2018, 57, 5173–5182. [Google Scholar] [CrossRef]
  20. Abd Rahman, R.; Harid, N.; Haddad, A. Stress control on polymeric outdoor insulators. In Proceedings of the 45th International Universities Power Engineering Conference UPEC2010, Cardiff, UK, 31 August–3 September 2010; IEEE: New York, NY, USA, 2010; pp. 1–4. [Google Scholar]
  21. Huo, E.; Liu, C.; Xin, L.; Li, X.; Xu, X.; Li, Q.; Wang, S.; Dang, C. Thermal stability and decomposition mechanism of HFO-1336mzz (Z) as an environmental friendly working fluid: Experimental and theoretical study. Int. J. Energy Res. 2019, 3, 4630–4643. [Google Scholar] [CrossRef]
  22. Rabie, M.; Franck, C.M. Computational screening of new high voltage insulation gases with low global warming potential. IEEE Trans. Dielectr. Electr. Insul. 2015, 22, 296–302. [Google Scholar] [CrossRef] [Green Version]
  23. Kothe, D.C.; Hinrichsen, V.; Ermeler, K.; Kalter, A. Experimental investigation of dielectric properties of alternative insulation gases for medium voltage switchgear. In Proceedings of the VDE High Voltage Technology 2020; ETG-Symposium, Online, 9–11 November 2022; VDE: Berlin, Germany, 2022; pp. 1–6. [Google Scholar]
  24. Zhang, B.; Chen, L.; Li, X.; Guo, Z.; Pu, Y.; Tang, N. Evaluating the dielectric strength of promising SF6 alternatives by DFT calculations and DC breakdown tests. IEEE Trans. Dielectr. Electr. Insul. 2020, 27, 1187–1194. [Google Scholar] [CrossRef]
  25. IEC-60270; High-Voltage Test Techniques: Partial Discharge Measurements. International Electro Technical Commission: Geneva, Switzerland, 2000; pp. 13–31.
  26. D2477-07; Standard Test Method for Dielectric Breakdown Voltage and Dielectric Strength of Insulating Gases at Commercial Power Frequencies. ASTM International: West Conshohocken, PA, USA, 2012.
  27. Kharal, H.S.; Kamran, M.; Ullah, R.; Saleem, M.Z.; Alvi, M.J. Environment-friendly and efficient gaseous insulator as a potential alternative to SF6. Processes 2019, 7, 740. [Google Scholar] [CrossRef] [Green Version]
  28. Salem, A.A.; Abd-Rahman, R.; Kamarudin, M.S.; Ahmed, H.; Jamail, N.A.M.; Othman, N.A.; Yusouf, M.F.M.; Ishak, M.T.; Al-Ameri, S. The effect of insulator geometrical profile on electric field distributions. Indones. J. Electr. Eng. Comput. Sci. 2019, 14, 618–627. [Google Scholar] [CrossRef]
Figure 1. Chemical structure of C4H2F6 or HFO-1336mzz (E).
Figure 1. Chemical structure of C4H2F6 or HFO-1336mzz (E).
Applsci 13 08940 g001
Figure 2. Electrode setup and geometry.
Figure 2. Electrode setup and geometry.
Applsci 13 08940 g002
Figure 3. HVAC test setup.
Figure 3. HVAC test setup.
Applsci 13 08940 g003
Figure 4. HVDC test setup.
Figure 4. HVDC test setup.
Applsci 13 08940 g004
Figure 5. Electric potential simulation of electrodes in a uniform field.
Figure 5. Electric potential simulation of electrodes in a uniform field.
Applsci 13 08940 g005
Figure 6. Electric field intensity of plane–plane electrode configuration (uniform field).
Figure 6. Electric field intensity of plane–plane electrode configuration (uniform field).
Applsci 13 08940 g006
Figure 7. Electric field intensity of sphere–plane electrode configuration (weakly non-uniform field).
Figure 7. Electric field intensity of sphere–plane electrode configuration (weakly non-uniform field).
Applsci 13 08940 g007
Figure 8. Breakdown voltages of (a) HFO-1336mzz (E)/CO2 and (b) HFO-1336mzz (E)N2 at quasi-uniform field.
Figure 8. Breakdown voltages of (a) HFO-1336mzz (E)/CO2 and (b) HFO-1336mzz (E)N2 at quasi-uniform field.
Applsci 13 08940 g008
Figure 9. Breakdown voltages of (a) HFO-1336mzz (E)/CO2 and (b) HFO-1336mzz (E)N2 at uniform field.
Figure 9. Breakdown voltages of (a) HFO-1336mzz (E)/CO2 and (b) HFO-1336mzz (E)N2 at uniform field.
Applsci 13 08940 g009
Figure 10. Breakdown voltages of (a) HFO-1336mzz (E)/CO2 and (b) HFO-1336mzz (E)N2 at quasi-uniform field.
Figure 10. Breakdown voltages of (a) HFO-1336mzz (E)/CO2 and (b) HFO-1336mzz (E)N2 at quasi-uniform field.
Applsci 13 08940 g010
Figure 11. Breakdown voltages of (a) HFO-1336mzz (E)/CO2 and (b) HFO-1336mzz (E)N2 at uniform field.
Figure 11. Breakdown voltages of (a) HFO-1336mzz (E)/CO2 and (b) HFO-1336mzz (E)N2 at uniform field.
Applsci 13 08940 g011
Figure 12. GWP of HFO-1336mzz (E)/CO2 mixture.
Figure 12. GWP of HFO-1336mzz (E)/CO2 mixture.
Applsci 13 08940 g012
Figure 13. Liquefaction temperature of HFO-1336mzz (E)/CO2.
Figure 13. Liquefaction temperature of HFO-1336mzz (E)/CO2.
Applsci 13 08940 g013
Figure 14. Synergistic effect of (a) HFO-1336mzz (E)/CO2 gas mixture and (b) HFO-1336mzz (E)/N2 gas mixture.
Figure 14. Synergistic effect of (a) HFO-1336mzz (E)/CO2 gas mixture and (b) HFO-1336mzz (E)/N2 gas mixture.
Applsci 13 08940 g014
Figure 15. Self-recoverability of HFO-1336mzz (E)/CO2 mixture.
Figure 15. Self-recoverability of HFO-1336mzz (E)/CO2 mixture.
Applsci 13 08940 g015
Table 1. Basic physical and chemical properties of HFO-1336mzz (E), SF6, CO2, and N2.
Table 1. Basic physical and chemical properties of HFO-1336mzz (E), SF6, CO2, and N2.
ParametersSF6HFO-1336mzz (E) CO2N2
Cas no2551-62-466711-86-2124-38-91179900-47-0
Chemical formulaeSF6C4H2F6CO2N2
GWP23,500181–3265–298
ODP0000
Boiling point−63.9 °C7.5 °C−79.0 °C−195.8 °C
Melting point−51 °C−20 °C−78.5 °C−210 °C
Critical temperature45.60 °C137.7 °C31.1 °C−146.9 °C
Critical pressure37.64 bar3.15 bar73.8 bar33.9 bar
Molecular mass (g/mol) 146.05164.544.0114.01
Flammability NoneNoneNonenone
Odor/ColorOdorless/ColorlessOdorless/ColorlessOdorless/ColorlessOdorless/Colorless
StabilityStableStable Stable storage conditionStable storage condition
Solubility in waterTrace0.280 g/L at 25 °CRelatively low solubilityRelatively low solubility
Table 2. Electric field utilization factor calculation.
Table 2. Electric field utilization factor calculation.
Electrode Configuration Electric   Field   Utilization   Factor   η at Constant 6 mm Air Gap Electric   Field   Homogeneity   Factor   α
Sphere–plane0.741.34
Plane–plane0.951.04
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Ahmed, R.; Rahman, R.A.; Aldosary, A.S.; Al-Ramadan, B.; Ullah, R.; Jamal, A. Analysis of the Insulation Characteristics of Hexafluorobutene (C4H2F6) Gas and Mixture with CO2/N2 as an Alternative to SF6 for Medium-Voltage Applications. Appl. Sci. 2023, 13, 8940. https://doi.org/10.3390/app13158940

AMA Style

Ahmed R, Rahman RA, Aldosary AS, Al-Ramadan B, Ullah R, Jamal A. Analysis of the Insulation Characteristics of Hexafluorobutene (C4H2F6) Gas and Mixture with CO2/N2 as an Alternative to SF6 for Medium-Voltage Applications. Applied Sciences. 2023; 13(15):8940. https://doi.org/10.3390/app13158940

Chicago/Turabian Style

Ahmed, Rizwan, Rahisham Abd Rahman, Adel S. Aldosary, Baqer Al-Ramadan, Rahmat Ullah, and Arshad Jamal. 2023. "Analysis of the Insulation Characteristics of Hexafluorobutene (C4H2F6) Gas and Mixture with CO2/N2 as an Alternative to SF6 for Medium-Voltage Applications" Applied Sciences 13, no. 15: 8940. https://doi.org/10.3390/app13158940

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop