Next Article in Journal
Dynamic Modeling for Resilience Measurement: NATO Resilience Decision Support Model
Next Article in Special Issue
Parametric Investigation of the Effects of Localization and Slenderness on the Stress–Strain Response and Confinement Efficiency in FRP-Wrapped Concrete Cylinders
Previous Article in Journal
Method for Volume of Irregular Shape Pellets Estimation Using 2D Imaging Measurement
Previous Article in Special Issue
Region-Based CNN Method with Deformable Modules for Visually Classifying Concrete Cracks
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Numerical Modelling of Thermal Insulation of Reinforced Concrete Ceilings with Complex Cross-Sections

by
Łukasz Drobiec
1,*,
Rafał Wyczółkowski
2 and
Artur Kisiołek
3
1
Department of Building Structures, Silesian University of Technology, ul. Akademicka 5, 44-100 Gliwice, Poland
2
Department of Production Management, Czestochowa University of Technology, Armii Krajowej 19, 42-200 Częstochowa, Poland
3
Institute of Economics, The Great Poland University of Social and Economics in Środa Wlkp., Surzyńskich 2, 63-000 Środa Wlkp, Poland
*
Author to whom correspondence should be addressed.
Appl. Sci. 2020, 10(8), 2642; https://doi.org/10.3390/app10082642
Submission received: 23 March 2020 / Revised: 7 April 2020 / Accepted: 8 April 2020 / Published: 11 April 2020
(This article belongs to the Special Issue Health Structure Monitoring for Concrete Materials, Volume II)

Abstract

:

Featured Application

The paper shows how big differences are obtained between the standard approach to calculating the heat transfer coefficient of ceilings with complex geometries and accurate numerical calculations.

Abstract

The article describes the results of numerical analyses and traditional calculations of the heat transfer coefficient in ceilings with a complex cross-section, and with materials of varying density built-in inside the cross-section. Prefabricated prestressed reinforced concrete, composite reinforced, and ribbed reinforced concrete ceilings were analyzed. Traditional calculations were carried out in accordance with the EN ISO 6946:2017 standard, while the numerical analyses were carried out in a program based on the finite element method (FEM). It has been shown that calculations can be a good alternative to nondestructive testing (NDT) and laboratory tests, whose use in the case of ceilings with different geometries is limited. The differences between the calculations carried out in accordance with EN ISO 6946:2017, and the results of numerical analyses are 12%–39%. The way the air voids are taken into account has an impact on the calculation results. In the traditional method, an equivalent thermal conductivity coefficient was used, while in the numerical analysis, the coefficient was selected from the program’s material database. Since traditional calculations require simplifications, numerical methods should be considered to give more accurate results.

1. Introduction

The erection of a building with reinforced concrete ceilings in accordance with the principles of sustainable development requires an accurate determination of the thermal insulation of the ceiling [1,2,3]. At a certain ceiling thickness, thermal insulation can be improved in two ways. The first way is to use materials with a low thermal conductivity coefficient in the partition. The second way is related to the construction of the partition. The use of insulation materials inside the ceiling, in places where there are free spaces, significantly reduces the intensity of heat flow. However, constructions with complex geometries are then created.
The heat transfer coefficient can be determined by conducting tests (nondestructive, laboratory) or by making calculations. Nondestructive testing methods are currently developing very dynamically [4,5,6,7] based on advanced mathematical models, including artificial intelligence [8,9] and machine learning [10,11,12]. However, conducting such tests usually requires the use of specialized equipment [13,14]. In the case of thermal insulation tests, nondestructive methods offer the possibility of testing homogeneous materials in small areas [15,16]. In practice, therefore, laboratory tests are performed more often. As in the case of nondestructive testing, they will allow testing of thermal insulation of only small elements [17,18,19,20]. For ceilings with complex geometries, both nondestructive testing in small areas and laboratory testing of small samples do not give good results [21,22,23]. Correct results are obtained only when conducting thermal insulation tests on a natural scale, which, however, requires the construction of a full-size model, with walls, ceilings and window and door woodwork [21,22]. A good alternative here is to perform calculations using simple or complex calculation methods [21,23,24]. Recently, programs based on the finite element method (FEM) have been used more and more often to determine the penetration coefficient [25,26,27].
The article compares the values of heat transfer coefficients of ceilings obtained from calculations carried out in accordance with EN ISO 6946:2017 [28] and numerical models. Prefabricated prestressed reinforced concrete, composite reinforced concrete, and ribbed reinforced concrete ceilings with different types of fillings between reinforced concrete beams were analyzed. The analyzed ceilings have complex cross-sections.

2. Analyzed Ceilings

The following ceiling systems were analyzed: a prefabricated prestressed Smart channel ceiling and Teriva Panel, Teriva Base, Teriva Plus and Teriva Termo ribbed ceilings. The Smart ceiling is a 60 cm wide prestressed concrete slab with five 60 × 90 mm air ducts, and reinforcement in the form of six ø 9.3 mm rods in the bottom part and two ø 6.85 mm rods in the top part. The section of the Smart ceiling is shown in Figure 1. The lateral edges of the prefabricated element are shaped so that after filling them with concrete, a permanent connection will occur, which will ensure proper cooperation between the panels when transferring loads. The most important parameters of the ceiling in question are summarized in Table 1.
The Teriva Panel ceiling is a prestressed composite structure with reinforced concrete laid at the construction site. The prefabricated prestressed part consists of a bottom plate 590 mm wide and two ribs. The space between the ribs is filled with foam concrete with a density of 400 kg/m3, and a 4 cm layer of composite concrete is poured into the whole structure at the construction site. The cross-section through the Teriva Panel ceiling is shown in Figure 2, and its basic parameters are given in Table 2.
The Teriva Base ceiling system consists of prefabricated truss beams with a concrete foot, three-chamber filling expanded clay, and concrete hollow bricks and concrete overlay laid at the construction site. The cross-section of this ceiling is shown in Figure 3, and the basic parameters are given in Table 3.
The Teriva Plus system is similar to the Teriva Base ceiling, but their difference lies in the type of filling. In the Teriva Plus case, the filling is expanded clay and concrete five-chamber hollow bricks in the so-called upper shelf as shown in Figure 4, which remains uncovered after pouring concrete into the ceiling. Thanks to this solution, the height of the complete ceiling is equal to the height of the hollow brick itself. The basic parameters of the Teriva Plus ceiling are summarized in Table 4.
The Teriva Termo ceiling is characterized by the use of expanded clay and concrete 10-chamber hollow bricks with shifted vertical walls, as shown in Figure 5. This solution eliminates the occurrence of direct thermal bridges between the upper and lower surfaces of the hollow brick, which in turn should improve the thermal properties of the ceiling. The basic parameters of the Teriva Termo ceiling are summarized in Table 5.

3. Traditional Calculations

The thermal insulation of the discussed ceiling systems was described by means of three parameters: thermal resistance, heat transfer coefficient, and heat transfer resistance. RT thermal resistance is defined as the quotient of the temperature difference and the heat flux density in a steady state, which in the case of a flat homogeneous layer, equals the quotient of the thickness and the thermal conductivity coefficient. The heat transfer coefficient U for a flat partition is defined as the heat flux in a steady state divided by the surface area and by the difference in ambient (fluids) temperatures on both sides of the partition. The heat transfer resistance RU of a flat partition is the sum of its thermal resistance and heat transfer resistance. At the same time, this parameter is the inverse of the heat transfer coefficient.
First, the thermal conductivity resistance was determined. This parameter was calculated in accordance with the principles given in the EN ISO 6946:2017 standard [28]. Since all considered ceilings are partitions consisting of thermally heterogeneous layers, RT resistance was calculated from the formula:
R T = R T + R T 2 ,
where R T —upper limit of thermal resistance: R T —lower limit of thermal resistance.
This approach therefore requires the division of the partition in question into sections and layers, the sections being parallel to the direction of the heat flow and the layers perpendicular. The division of the ceiling into sections concerns the determination of the upper thermal resistance limit. This is done in such a way that the separated sections consist of homogeneous layers. On this basis, the resistance is calculated as a parallel connection of the resistance of individual sections assuming one-dimensional heat flow perpendicular to the surface of the layers:
1 R T = f 1 R T 1 + f 1 R T 1 + + f n R T n ,
where R T i —thermal resistance of individual sections (calculated as the sum of resistance of the individual layers of a given section), f i   —relative surface area of a given section (calculated as the quotient of the surface area of a given section to the surface of the entire partition).
The division of the ceiling into layers is associated with the calculation of the lower limit of thermal resistance. This resistance is calculated as a series connection of resistances of the individual layers:
R T = R T 1 + R T 2 + + R T n ,
where R T i —the equivalent thermal resistance of each heterogeneous layer, calculated as the parallel connection of the resistances of the elements (homogeneous sections) present in this layer. These quantities are calculated according to the formula:
1 R T i = f 1 R T 1 i + f 1 R T 1 i + + f n R T n i ,
The thermal resistance of a homogeneous ceiling element, with the exception of air layers, is described as the relationship
R T i = d i k i ,
where: d i —the dimension of the partition element in the direction of heat flow, k i —thermal conductivity of the material of this element.
Most of the discussed ceilings contain free spaces filled with air in their structure. The thermal resistance of these parts of the ceilings was determined by treating them as unventilated air layers. The value of this parameter depending on the heat flow direction and layer thickness is selected from the table data [22].
After determining thermal resistance, heat transfer resistance was calculated. RU resistance was calculated as a series connection of the ceiling thermal resistance and heat transfer resistance:
R U = R s i + R T + R s e ,
where: R s i ,   R s o —resistance to heat transfer on the internal and external surfaces of the ceiling. The values of these resistances, depending on the type of partition (external or internal) and the direction of the heat flow, are presented in Table 6.
The last of the analyzed parameters, i.e., the heat transfer coefficient U, was calculated as the inverse of the heat transfer resistance:
U = 1 R U ,
The methodology for determining these thermal parameters is presented in detail in one of the ceilings in publication [22].
Performing the relevant calculations, two directions of heat flow (downwards and upwards) were considered for each ceiling system when treating them as internal partitions. The values of thermal conductivity coefficients k adopted for individual materials occurring in the analyzed ceilings are summarized in Table 7.
In the case of the Teriva Panel system, calculations were made for three construction variants differing in the thickness of the concrete overlay layer: Teriva Panel 160 (concrete overlay layer 40 mm), Teriva Panel 180 (concrete overlay layer 60 mm) and Teriva Panel 200 (concrete overlay layer 80 mm). The calculation results were compared in Table 8 and Table 9. Table 8 presents the results obtained for individual Teriva Panel ceiling variants, while Table 9 contains the results obtained for the Smart system and three Teriva systems: Base, Plus and Termo.
Among the calculated parameters, the heat transfer resistance obtained for the heat flow downwards should be considered the most important from a practical point of view. The comparison of the values of this parameter shows that increasing the thickness of the concrete overlay from 40 mm (Teriva Panel 160) to 60 mm (Teriva Panel 180) and 80 mm (Teriva Panel 200) increases the heat transfer resistance of these systems by 3.6% and 7%, respectively.
The lowest value of penetration resistance is found in the Smart ceiling, for which this parameter is 0.459 (m2·K)/W. This result is caused by two factors. First of all, this ceiling has the lowest height (only 15 cm), and as it results from Equation (5), the thermal resistance of the layer is greater the larger its size. The second factor in this respect is the relatively high height of the air ducts, which contributes to the intensification of heat exchange due to convection. In turn, the best insulating properties are characterized by the Teriva Termo ceiling, for which the analyzed parameter is 0.874 (m2·K)/W. This result is due to the ceiling height, which in this case is 30 cm, and the relatively small size of the air chambers within the hollow blocks. The latter factor significantly reduces air convection.
For a more detailed analysis of the results obtained, the percentage excess of heat transfer resistance was determined in relation to the value obtained for the Smart ceiling. This parameter was calculated according to the relationship:
δ R = R x R 0 R 0 · 100 %   ,
where Rx—heat transfer resistance of the analyzed ceiling, R0—heat transfer resistance of the Smart ceiling.
The results of calculations of the parameter δR obtained for both directions of the heat flow are summarized in Table 10. As can be seen, the higher value of the surplus occurs at the upward heat flow. This result should be explained by the relatively large proportion of air convection in free spaces of the Smart panel, which reduces its insulation. In the case of the downward heat flow, the phenomenon of convection in the air chambers does not take place. In this situation, the resistance to heat transfer of this ceiling is much higher.
For the downward flow of heat, the percentage surplus for individual ceilings is between 15% (Teriva Panel 160) and 90% (Teriva Termo). This means that the Teriva Termo ceiling has almost twice the thermal insulation compared to the Smart ceiling. For the upward flow, this parameter in turn varies from 25% to 131%. Larger values in this case are caused by a greater effect of convection on the thermal resistance of the Smart ceiling.
Building partitions, including ceilings, which are elements of the outer casing or elements separating rooms with different microclimatic parameters, must meet specific requirements for thermal insulation. The relevant regulation [12] is required to do so. According to this document, the values of the heat transfer coefficient of walls, ceilings and roofs cannot be higher than the Umax value. For residential, collective housing and public buildings, the requirements for ceilings are as follows:
  • ceilings under unheated attics or over passages when the internal temperature of the rooms is higher than 16 °C Umax = 0.25 W/(m2·K),
  • ceilings under unheated attics or over passages when the internal temperature of the rooms is less than or equal to 16 °C Umax = 0.50 W/(m2·K),
  • ceilings over unheated basements and closed floor spaces Umax = 0.45 W/(m2·K).
As can be see, all analyzed ceilings without an additional insulating layer do not meet the requirements. For this reason, the thickness of the foamed polystyrene layer has to be added to obtain the Umax coefficient values required for the first and third cases. In these calculations, 0.045 W/(m2·K) was adopted as the calculation value of the thermal conductivity coefficient for foamed polystyrene [11]. The obtained results are summarized in Table 11 and Table 12. For Teriva Panel ceilings, the necessary foam thicknesses are approximately: 150 mm—for Umax = 0.25 W/(m2·K), and 75 mm—for Umax = 0.45 W/(m2·K). For other systems, these thicknesses fall within the following ranges:
  • Umax = 0.25 W/(m2·K) − 134.4 ÷ 158.3 mm,
  • Umax = 0.45 W/(m2·K) − 57.9 ÷ 81.7 mm.
In this context, the influence of the heat flow direction is also interesting. For all systems, regardless of the Umax value, the difference between the thickness of the foamed polystyrene between the upward and downward heat flows does not exceed 6 mm. This shows that the direction of heat flow has relatively little effect on the thermal insulation values of ceilings.

4. Numerical Analyzes

In order to determine the heat flux Q, numerical calculations were made in the PSI THERM program based on the finite element method. The same assumptions were made as when calculating in accordance with the guidelines of EN ISO 6946:2017 [28]. The upward flow and the downward flow were modelled. The presence of reinforcement, air voids and materials of different densities and different heat transfer coefficients were taken into account. The heat transfer coefficient in air voids was selected based on the air void database available in the computer program. The value of the heat transfer coefficient of the void is selected depending on its thickness (in the program, the thickness is graded every 5 mm–a range of values for voids with a thickness of 5 mm to 300 mm), depending on the direction of heat flow (horizontally, upwards, downwards) and the type of void (nonventilated or poorly ventilated). Therefore, alternative resistance was used. Ceiling models were divided into finite elements with the dimension of the side equal to 20 mm.
The obtained results are shown in Figure 6, Figure 7, Figure 8, Figure 9, Figure 10, Figure 11 and Figure 12. On the basis of heat flux Q of the obtained numerical models, the heat transfer coefficient U, thermal resistance RT, and thermal resistance of the ceiling RU were calculated. The results of these calculations are summarized in Table 13 and Table 14. Table 13 presents the results obtained for individual variants of the Teriva Panel ceiling, whereas Table 14 contains the results obtained for the Smart system and three Teriva systems: Base, Plus and Termo.
Comparing the results of numerical calculations with the calculations carried out in accordance with EN ISO 6946:2017 [28], it can be stated that the heat transfer coefficients obtained on the basis of numerical calculations are higher than those obtained on the basis of standard calculations. The smallest difference of almost 12% was obtained for the Teriva Panel ceiling with a height of 200 mm. The biggest difference between the results of the calculations occurred in the case of the Smart ceiling, where the numerical simulations showed a U factor 39% higher than in the calculations carried out in accordance with EN ISO 6946:2017 [28]. The percentage differences between the values of the heat transfer coefficient U, calculated in accordance with the standard and obtained from numerical analyses, are given in Table 15.
Numerical calculations have always resulted in higher U values. Greater differences in the results of standard and numerical calculations were observed at downward flow than at upward flow. This is due to different heat transfer resistance values used in traditional and numerical calculations.
When calculating the thermal characteristics of building partitions, the EN ISO 6946:2017 standard is most often used [28]. The heat exchange through ceilings takes place by conduction, convection and radiation. In the case of air-filled spaces in the ceiling, the mathematical description of free convection in free spaces consists in providing a system of equations that includes the equation of continuity, the momentum equation, and the energy conservation equation with boundary conditions. If the spaces have a regular shape, it is possible to replace the complicated description of the phenomenon by assuming that the heat transport in the cavity is one-dimensional heat conduction with a modified air conductivity coefficient. The intensity of air circulation as a result of convection depends on the geometries of the free space (its height and width) and the difference in temperature of the surrounding walls. This phenomenon can be characterized by an equivalent thermal conductivity coefficient, which was adopted for calculations on the basis of nomograms given in the paper [22].
For the numerical calculations of the airspace, the actual geometries of the voids were given. The thermal conductivity coefficient was selected from the program’s material database. A different way of taking convection into account in the ceiling spaces that are filled with air indicated the expected possibility of obtaining various results of numerical simulations and normative calculations with the additional taking account of the equivalent air heat conductivity coefficient. In the case of Teriva Panel ceilings, where there are no air voids, the differences at upward flow of 12%–14.9% are not too great. With a downward flow, the differences are 25.8%–28.2%. For cases of ceilings with air hollow blocks, the results obtained from the numerical calculations differ significantly from the results. With an upward flow, the differences are 19.1%–30.9%, and 31.1%–39.4% with a downward flow. As mentioned above, these differences result from the geometries of the airspace in which convective heat exchange occurs, and from how convection phenomena are taken into account in the calculations.

5. Conclusions

The calculations carried out showed that the finite element method (FEM) can be used to determine the heat transfer coefficient of reinforced concrete ceilings. The differences between the calculations carried out in accordance with EN ISO 6946:2017 [28] are 12%–39%. It should be emphasized that in traditional calculations it is necessary to use simplifications, which especially in the case of complex geometries of ceiling cross-sections, affects the results of calculations. The way of taking into account air voids in both calculation methods has the greatest impact on the calculation results. In the traditional method, an equivalent thermal conductivity coefficient was used, while in the numerical analysis, the coefficient was selected from the program’s material database based on the geometries of the voids. Therefore, it should be concluded that numerical methods give more accurate results.

Author Contributions

Conceptualization, Ł.D., R.W. and A.K.; methodology, R.W.; software, Ł.D.; validation, Ł.D. and R.W.; formal analysis, Ł.D. and R.W.; writing—original draft preparation, Ł.D., R.W. and A.K.; writing—review and editing, Ł.D., R.W. and A.K.; visualization, Ł.D.; supervision, A.K.; funding acquisition, A.K. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Lucero-Álvarez, J.; Rodríguez-Muñoz, N.A.; Martín-Domínguez, I.R. The effects of roof and wall insulation on the energy costs of low income housing in Mexico. Sustainability 2016, 8, 590. [Google Scholar] [CrossRef] [Green Version]
  2. Dixit, A.K.; Roul, M.K.; Panda, B.C. Thermal performance of insulated roof slabs. Recent Adv. Sustain. Concr. Technol. 2018, 12, 165–170. [Google Scholar]
  3. Wang, H.; Chiang, P.C.; Cai, Y.; Li, C.; Wang, X.; Chen, T.L.; Wei, S.; Huang, Q. Application of wall and insulation materials on green building: A review. Sustainability 2018, 10, 3331. [Google Scholar] [CrossRef] [Green Version]
  4. Schabowicz, K. Non-destructive testing of materials in civil engineering. Materials 2019, 12, 3237. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  5. Nowak, R.; Orłowicz, R.; Rutkowski, R. Use of TLS (LiDAR) for building diagnostics with the example of a historic building in Karlino. Buildings 2020, 10, 24. [Google Scholar] [CrossRef] [Green Version]
  6. Grębowski, K.; Rucka, M.; Wilde, K. Non-destructive testing of a sport tribune under synchronized crowd-induced excitation using vibration analysis. Materials 2019, 12, 2148. [Google Scholar] [CrossRef] [Green Version]
  7. Jasiński, R.; Drobiec, Ł.; Mazur, W. Validation of selected non-destructive methods for determining the compressive strength of masonry units made of autoclaved aerated concrete. Materials 2019, 12, 389. [Google Scholar] [CrossRef] [Green Version]
  8. Hoła, J.; Schabowicz, K. New technique of nondestructive assessment of concrete strength using artificial intelligence. NDT E Int. 2005, 38, 251–259. [Google Scholar] [CrossRef]
  9. Schabowicz, K.; Hoła, B. Application of artificial neural networks in predicting earthmoving machinery effectiveness ratios. Arch. Civ. Mech. Eng. 2008, 8, 73–84. [Google Scholar] [CrossRef]
  10. Ziolkowski, P.; Demczynski, S.; Niedostatkiewicz, M. Assessment of failure occurrence rate for concrete machine foundations used in gas and oil industry by machine learning. Appl. Sci. 2019, 9, 3267. [Google Scholar] [CrossRef] [Green Version]
  11. Ziolkowski, P.; Niedostatkiewicz, M. Machine learning techniques in concrete mix design. Materials 2019, 12, 1256. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  12. Giannakis, I.; Giannopoulos, A.; Warren, C. A machine learning scheme for estimating the diameter of reinforcing bars using ground penetrating radar. IEEE Geosci. Remote Sens. Lett. 2020, 99, 1–5. [Google Scholar] [CrossRef] [Green Version]
  13. Drobiec, Ł.; Jasiński, R.; Mazur, W. Accuracy of eddy-current and radar methods used in reinforcement detection. Materials 2019, 12, 1168. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  14. Schabowicz, K. Ultrasonic tomography—The latest nondestructive technique for testing concrete members—Description, test methodology, application example. Arch. Civ. Mech. Eng. 2014, 14, 295–303. [Google Scholar] [CrossRef]
  15. Antczak, E.; Defer, D.; Elaoami, M.; Chauchois, A.; Duthoit, B. Monitoring and thermal characterisation of cement matrix materials using non-destructive testing. NDT E Int. 2007, 40, 428–438. [Google Scholar] [CrossRef]
  16. Balageas, D.; Maldague, X.; Burleigh, D.; Vavilov, V.P.; Oswald-Tranta, B.; Roche, J.M.; Pradere, C.; Carlomagno, G.M. Thermal (IR) and other NDT techniques for improved material inspection. J. Nondestruct. Eval. 2016, 35, 1–17. [Google Scholar] [CrossRef]
  17. Wyczółkowski, R.; Musiał, D. Experimental tests for the occurence of convective heat transfer within the bed of rectangular steel profiles. Arch. Thermodyn. 2012, 33, 89–100. [Google Scholar] [CrossRef]
  18. Wyczółkowski, R.; Benduch, A. The experimental study of the effective thermal conductivity of bundles of rectangular steel sections. Civ. Environ. Eng. Rep. 2014, 14, 119–132. [Google Scholar] [CrossRef] [Green Version]
  19. Bai, G.; Du, N.; Xu, Y.; Qin, C. Study on the thermal properties of hollow shale blocks as self-insulating wall materials. Adv. Mater. Sci. Eng. 2017, 2017, 9432145. [Google Scholar] [CrossRef] [Green Version]
  20. Ma, S.; Bao, P.; Jiang, N. Experimental study of gypsum-concrete dense-column composite boards with external thermal insulation systems. Appl. Sci. 2020, 10, 1976. [Google Scholar] [CrossRef] [Green Version]
  21. Steidl, T.; Krause, P. Moisture transport in cellular concrete walls with the connector for thermal insulation. Period. Polytech. Civ. Eng. 2018, 62, 986–991. [Google Scholar]
  22. Wyczółkowski, R.; Kisiołek, A. Analysis of thermal insulation properties of the Konbet Termo ceiling system. Mat. Bud. 2011, 461, 41–42. (In Polish) [Google Scholar]
  23. Urbán, D.; Roozen, N.B.; Muellner, H.; Zat’ko, P.; Niemczanowski, A.; Rychtáriková, M.; Glorieux, C. Vibrometry assessment of the external thermal composite insulation systems influence on the façade airborne sound insulation. Appl. Sci. 2018, 8, 703. [Google Scholar] [CrossRef] [Green Version]
  24. Nowoświat, A.; Skrzypczyk, J.; Krause, P.; Steidl, T.; Winkler-Skalana, A. Estimation of thermal transmittance based on temperature measurements with the application of perturbation numbers. Heat Mass Transf. 2018, 54, 1477–1489. [Google Scholar]
  25. Babota, F.; Moga, L. Computation and analysis of corrected thermal insulation in a common dwelling building in Romania, in various thermal insulation variants—The slab over the soil. Procedia Manuf. 2018, 22, 352–357. [Google Scholar] [CrossRef]
  26. Ciurej, H.; Piekarczyk, M. Experimental research and integrated FEM modelling for sheet roof covering with thermal insulation. Mech. Mech. Eng. 2010, 14, 183–192. [Google Scholar]
  27. Ascione, F.; Bianco, N.; De Stasio, C.; Mauro, G.M.; Vanoli, G.P. Thermal dynamic insulation: Numerical modeling in a transient regime and application to alternative aviary houses. Energy Procedia 2015, 75, 1711–1721. [Google Scholar] [CrossRef] [Green Version]
  28. ISO. ISO 6946:2017 Building Components and Building Elements. Thermal Resistance and Thermal Transmittance. Calculation Methods; ISO: Geneva, Switzerland, 2017. [Google Scholar]
Figure 1. Cross-section of the prefabricated prestressed Smart ceiling. 1—prefabricated prestressed slab, 2—stressing cables, 3—concrete laid on site.
Figure 1. Cross-section of the prefabricated prestressed Smart ceiling. 1—prefabricated prestressed slab, 2—stressing cables, 3—concrete laid on site.
Applsci 10 02642 g001
Figure 2. Cross-section of the partially prefabricated prestressed composite Teriva Panel ceiling. 1–prefabricated prestressed slab, 2–stressing cables, 3–concrete laid on site, 4–foam concrete.
Figure 2. Cross-section of the partially prefabricated prestressed composite Teriva Panel ceiling. 1–prefabricated prestressed slab, 2–stressing cables, 3–concrete laid on site, 4–foam concrete.
Applsci 10 02642 g002
Figure 3. Cross-section of the Teriva Base thick-ribbed ceiling. 1—prefabricated truss beam, 2—filling expanded clay and concrete hollow brick, 3—concrete laid at the construction site.
Figure 3. Cross-section of the Teriva Base thick-ribbed ceiling. 1—prefabricated truss beam, 2—filling expanded clay and concrete hollow brick, 3—concrete laid at the construction site.
Applsci 10 02642 g003
Figure 4. Cross-section of the Teriva Plus thick-ribbed ceiling. 1—prefabricated truss beam, 2—filling expanded clay and concrete hollow brick, 3—concrete laid at the construction site.
Figure 4. Cross-section of the Teriva Plus thick-ribbed ceiling. 1—prefabricated truss beam, 2—filling expanded clay and concrete hollow brick, 3—concrete laid at the construction site.
Applsci 10 02642 g004
Figure 5. Cross-section of the Teriva Termo thick-ribbed ceiling. 1—prefabricated truss beam, 2—filling expanded clay and concrete hollow brick, 3—concrete laid at the construction site.
Figure 5. Cross-section of the Teriva Termo thick-ribbed ceiling. 1—prefabricated truss beam, 2—filling expanded clay and concrete hollow brick, 3—concrete laid at the construction site.
Applsci 10 02642 g005
Figure 6. Results of numerical calculations of the Smart ceiling: (a) flow upwards, (b) flow downwards.
Figure 6. Results of numerical calculations of the Smart ceiling: (a) flow upwards, (b) flow downwards.
Applsci 10 02642 g006
Figure 7. Results of numerical calculations of the Teriva Panel ceiling with a height of 160 mm: (a) flow upwards, (b) flow downwards.
Figure 7. Results of numerical calculations of the Teriva Panel ceiling with a height of 160 mm: (a) flow upwards, (b) flow downwards.
Applsci 10 02642 g007
Figure 8. Results of numerical calculations of the Teriva Panel ceiling with a height of 180 mm: (a) flow upwards, (b) flow downwards.
Figure 8. Results of numerical calculations of the Teriva Panel ceiling with a height of 180 mm: (a) flow upwards, (b) flow downwards.
Applsci 10 02642 g008
Figure 9. Results of numerical calculations of the Teriva Panel ceiling with a height of 200 mm: (a) flow upwards, (b) flow downwards.
Figure 9. Results of numerical calculations of the Teriva Panel ceiling with a height of 200 mm: (a) flow upwards, (b) flow downwards.
Applsci 10 02642 g009
Figure 10. Results of Teriva Base ceiling calculations: (a) flow upwards, (b) flow downward.
Figure 10. Results of Teriva Base ceiling calculations: (a) flow upwards, (b) flow downward.
Applsci 10 02642 g010
Figure 11. Results of Teriva Plus ceiling calculations: (a) flow upwards, (b) flow downwards.
Figure 11. Results of Teriva Plus ceiling calculations: (a) flow upwards, (b) flow downwards.
Applsci 10 02642 g011
Figure 12. Results of Teriva Termo ceiling calculations: (a) flow upwards, (b) flow downwards.
Figure 12. Results of Teriva Termo ceiling calculations: (a) flow upwards, (b) flow downwards.
Applsci 10 02642 g012
Table 1. Basic parameters of the Smart ceiling.
Table 1. Basic parameters of the Smart ceiling.
ParameterValue
height150 mm
width600 mm
transferred loads depending on the spanfrom 5.0 to 40.0 kN/m2
prefabricated concrete classC40/50
span up to8.1 m
fire resistanceREI 60
weight250 kg/m2
Table 2. Basic parameters of the Teriva Panel ceiling.
Table 2. Basic parameters of the Teriva Panel ceiling.
ParameterValue
height160, 180, 200 mm
width600 mm
transferred loads depending on the spanfrom 2.0 to 34.4 kN/m2
prefabricated concrete classC40/50
span up to7.4 m
fire resistanceREI 30
weight188 kg/m2
Table 3. Basic parameters of the Teriva Base ceiling.
Table 3. Basic parameters of the Teriva Base ceiling.
ParameterValue
height240 mm
rib span600 mm
transferred load depending on the spanfrom 4.0 KN/m2
prefabricated concrete classC20/25
span up to7.2 m
fire resistanceREI 30
weight238 kg/m2
Table 4. Basic parameters of the Teriva Plus ceiling.
Table 4. Basic parameters of the Teriva Plus ceiling.
ParameterValue
height240 mm
rib span600 mm
transferred loads depending on the spanfrom 4.0 kN/m2
prefabricated concrete classC20/25
span up to7.2 m
fire resistanceREI 30
weight257 kg/m2
Table 5. Basic parameters of the Teriva Termo ceiling.
Table 5. Basic parameters of the Teriva Termo ceiling.
ParameterValue
height240 mm
rib span600 mm
transferred loads depending on the spanfrom 4.0 kN/m2
prefabricated concrete classC20/25
span up to7.2 m
fire resistanceREI 30
weight228 kg/m2
Table 6. Heat transfer resistance according to EN ISO 6946 [28] in m2K/W.
Table 6. Heat transfer resistance according to EN ISO 6946 [28] in m2K/W.
Type of SurfaceHeat Flow Direction
UpwardsDownwards
internal0.100.17
external0.040.04
Table 7. Calculation values of conductivity coefficients adopted for individual materials occurring in the analyzed ceilings.
Table 7. Calculation values of conductivity coefficients adopted for individual materials occurring in the analyzed ceilings.
Material Coefficient k, W/(m·K)
concrete1.70
concrete overlay1.00
foam concrete0.14
expanded clay concrete0.90
steel reinforcement58
Table 8. Values of thermal parameters of various Teriva Panel ceiling variants.
Table 8. Values of thermal parameters of various Teriva Panel ceiling variants.
ParameterUnitTeriva Panel 160Teriva Panel 180Teriva Panel 200
resistance RT(m2·K)/W0.1900.2090.227
resistance RU flow upwards(m2·K)/W0.3900.4090.427
resistance RU flow downwards(m2·K)/W0.5300.5490.567
coefficient U flow upwardsW/(m2·K)2.5642.4452.342
coefficient U flow downwardsW/(m2·K)1.8871.8211.764
Table 9. Values of thermal parameters of the Smart and Teriva ceilings: Base, Plus and Termo.
Table 9. Values of thermal parameters of the Smart and Teriva ceilings: Base, Plus and Termo.
ParameterUnitSmartTeriva BaseTeriva PlusTeriva Termo
resistance RT(m2·K)/W0.1190.2800.3700.534
resistance RU flow upwards(m2·K)/W0.3190.4800.5700.734
resistance RU flow downwards(m2·K)/W0.4590.6200.7100.874
coefficient U flow upwardsW/(m2·K)3.2052.0831.7541.362
coefficient U flow downwardsW/(m2·K)2.1791.6131.4081.144
Table 10. Excess percentage heat transfer resistance of individual ceiling systems in relation to the Smart ceiling.
Table 10. Excess percentage heat transfer resistance of individual ceiling systems in relation to the Smart ceiling.
Type of CeilingFlow UpwardsFlow Downwards
%%
Teriva Panel 1602515
Teriva Panel 1803120
Teriva Panel 2003724
Teriva Base 3-chamber5435
Teriva Plus7946
Teriva Termo 10-chamber13190
Table 11. Thicknesses of the polystyrene layer necessary for the analyzed ceilings to obtain the required U values.
Table 11. Thicknesses of the polystyrene layer necessary for the analyzed ceilings to obtain the required U values.
UFlowTeriva Panel 160Teriva Panel 180Teriva Panel 200
0.25 W/(m2·K)upwards 155.2 mm154.4 mm153.6 mm
downwards149.2 mm148.4 mm147.6 mm
0.45 W/(m2·K)upwards78.7 mm77.9 mm77.1 mm
downwards72.7 mm71.9 mm71.1 mm
Table 12. Thicknesses of the polystyrene layer necessary for the analyzed ceilings to obtain the required U values.
Table 12. Thicknesses of the polystyrene layer necessary for the analyzed ceilings to obtain the required U values.
U CoefficientFlowSmartTeriva BaseTeriva PlusTeriva Termo
0.25 W/(m2·K)upwards158.3151.4147.5140.5
downwards152.3145.3141.5134.4
0.45 W/(m2·K)upwards81.774.870.963.9
downwards75.768.864.957.9
Table 13. Values of thermal parameters of various Teriva Panel ceiling variants.
Table 13. Values of thermal parameters of various Teriva Panel ceiling variants.
ParameterUnitTeriva Panel 160Teriva Panel 180Teriva Panel 200
RT flow upwards(m2·K)/W0.1990.2200.241
RT flow downwards(m2·K)/W0.2130.2220.241
RU flow upwards(m2·K)/W0.3390.3600.381
RU flow downwards(m2·K)/W0.4130.4320.451
U flow upwardsW/(m2·K)2.9472.7752.623
U flow downwardsW/(m2·K)2.4202.3172.219
Table 14. Values of thermal parameters of Smart and Teriva ceilings: Base, Plus and Termo.
Table 14. Values of thermal parameters of Smart and Teriva ceilings: Base, Plus and Termo.
ParameterUnitSmartTeriva BaseTeriva PlusTeriva Termo
RT flow upwards(m2·K)/W0.1190.2630.3260.326
RT flow downwards(m2·K)/W0.1190.2630.3250.325
RU flow upwards(m2·K)/W0.2590.4030.4660.561
RU flow downwards(m2·K)/W0.3290.4730.5350.630
U flow upwardsW/(m2·K)3.8592.4802.1461.783
U flow downwardsW/(m2·K)3.0382.1141.8681.588
Table 15. Percentage differences between the results of calculations carried out in accordance with EN ISO 6946:2017 [28], and numerical calculations.
Table 15. Percentage differences between the results of calculations carried out in accordance with EN ISO 6946:2017 [28], and numerical calculations.
CeilingTeriva Panel 160Teriva Panel 180Teriva Panel 200SmartTeriva BaseTeriva PlusTeriva Termo
Flow upwards14.913.512.020.419.122.330.9
Flow downwards28.227.225.839.431.132.738.8

Share and Cite

MDPI and ACS Style

Drobiec, Ł.; Wyczółkowski, R.; Kisiołek, A. Numerical Modelling of Thermal Insulation of Reinforced Concrete Ceilings with Complex Cross-Sections. Appl. Sci. 2020, 10, 2642. https://doi.org/10.3390/app10082642

AMA Style

Drobiec Ł, Wyczółkowski R, Kisiołek A. Numerical Modelling of Thermal Insulation of Reinforced Concrete Ceilings with Complex Cross-Sections. Applied Sciences. 2020; 10(8):2642. https://doi.org/10.3390/app10082642

Chicago/Turabian Style

Drobiec, Łukasz, Rafał Wyczółkowski, and Artur Kisiołek. 2020. "Numerical Modelling of Thermal Insulation of Reinforced Concrete Ceilings with Complex Cross-Sections" Applied Sciences 10, no. 8: 2642. https://doi.org/10.3390/app10082642

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop