Model-Based Control Strategies to Enhance Energy Flexibility in Electrically Heated School Buildings

by
Navid Morovat
1,*,
Andreas K. Athienitis
1,
José Agustín Candanedo
1,2 and
Benoit Delcroix
3
1
Center for Zero-Energy Building Studies, Concordia University, Montreal, QC H3G 1M8, Canada
2
CanmetENERGY, Natural Resources Canada, Varennes, QC J3X 1P7, Canada
3
Laboratoire des Technologies de l’Énergie, Hydro-Québec Research Institute, Shawinigan, QC G9N 0C5, Canada
*
Author to whom correspondence should be addressed.
Buildings 2022, 12(5), 581; https://doi.org/10.3390/buildings12050581
Submission received: 24 March 2022 / Revised: 23 April 2022 / Accepted: 27 April 2022 / Published: 30 April 2022

Abstract

:
This paper presents a general methodology to model and activate the energy flexibility of electrically heated school buildings. The proposed methodology is based on the use of archetypes of resistance–capacitance thermal networks for representative thermal zones calibrated with measured data. Using these models, predictive control strategies are investigated with the aim of reducing peak demand in response to grid requirements and incentives. A key aim is to evaluate the potential of shifting electricity use in different archetype zones from on-peak hours to off-peak grid periods. Key performance indicators are applied to quantify the energy flexibility at the zone level and the school building level. The proposed methodology has been implemented in an electrically heated school building located in Québec, Canada. This school has several features (geothermal heat pumps, hydronic radiant floors, and energy storage) that make it ideal for the purpose of this study. The study shows that with proper control strategies through a rule-based approach with near-optimal setpoint profiles, the building’s average power demand can be reduced by 40% to 65% during on-peak hours compared to a typical profile.

1. Introduction

Electric utilities consider demand-side management (DSM) a key solution to reduce peak power demand. In periods of peak power demand, using DSM is more cost-effective than operating peaking power plants or purchasing power from other jurisdictions [1]. DSM can have an even more significant effect on the grid when integrated with renewable energy sources (RESs). Buildings are important components of smart electricity grids; they can provide flexible services to reduce peak loads and shift demand in accordance with local RES production, such as energy storage in thermal mass and batteries [2,3], charging of electric vehicles [4], and HVAC system adjustments [5]. Ruilova et al. [6] defined energy flexibility in buildings as “the possibility to deviate the electricity consumption of a building from the reference scenario at a specific point in time and during a certain period”. Annex 67 of the IEA Energy in Buildings and Communities Programme (IEA-EBC) defined energy flexible buildings as those with “the ability to manage [their] demand and generation according to local climate conditions, user needs, and grid requirements” [5]. Energy flexibility takes into consideration two-way communications between buildings and the power grid. In this way, buildings are regarded not as consumers but as prosumers [7]. Energy flexibility can be referred to in two ways: thermal energy storage and shifting equipment operation. According to the first approach, the energy consumption of a specific electrical device can be predicted based on the thermal properties of the device or building to minimize electricity consumption. In the second approach, some electrical devices can be controlled to shift the electricity demand to periods with lower electricity prices or greater renewable energy generation [8]. Based on the published literature and presented in IEA-EBC Annex 67, increasing energy flexibility for the design of smart energy systems and buildings is influenced by (1) physical features of the building [2,3], (2) heating, ventilation, and air conditioning (HVAC) systems [5], (3) appropriate control systems and strategies [5], and (4) IEQ requirements [9]. In this context, an effective application of control strategies within HVAC systems is essential for increasing buildings’ efficiency [10,11,12] and energy flexibility [13].
Finck et al. [14] developed a method and tested it under real-life conditions, including the stochastic behavior of occupants and the dynamic behavior of the building and heating system. They used key performance indicators to quantify energy flexibility by considering: (1) energy and power, (2) energy efficiency, and (3) energy costs. They found that this categorization helps to make clear the benefits of using flexibility indicators in real-life applications. Junker et al. [15] presented a methodology for evaluating energy flexibility based on the flexibility function, to describe how a particular smart building or cluster of smart buildings reacts to a penalty signal. Coninck and Helsen [16] developed a methodology to quantify flexibility in buildings based on the cost curve. The methodology returns the amount of energy that can be shifted and the costs of this load shifting. Tauminia et al. [17] proposed a multidisciplinary approach to finding trade-offs between the need to limit environmental impacts and the trend toward higher building energy performance. They found that an oversized photovoltaic (PV) system is not the best solution for load-matching, grid interactions, and environmental impacts in the absence of storage systems. They noted that installing a storage system in conjunction with the appropriate size of a PV system would result in an improved load-matching of the building and reduce grid dependence at low generation times.
Montreal (Québec, Canada) is categorized in climate zone 6 [18], meaning it experiences extreme cold weather during winter. Québec generates most of its electricity (99.8%) from hydroelectric plants, and most commercial buildings rely on electricity as their primary or only energy source [19]. Thus, during cold weather in Québec, the morning peak load (6:00 a.m. to 9:00 a.m.) and evening peak load (4:00 p.m. to 8:00 p.m.) put a strain on the electrical grid [20]. Thus, it is imperative to analyze energy consumption and develop control strategies that effectively reduce and shift peak electricity demand due to heating in buildings. In this context, obtaining a model that provides reliable predictions and can be implemented in real controllers is crucial for optimizing building performance.
The Québec province has over 2600 schools, reaching over 1 million students and almost 100,000 teachers and other staff [21]. Therefore, quantification of energy flexibility in school buildings has a significant role in providing a safe and efficient operation of the future resilient grid. Additionally, indoor environmental quality (IEQ) has a considerable impact on the health and well-being of teachers and students. Thus, simultaneously meeting the need to improve energy flexibility as a grid requirement and the growing demands for environmental performance (especially during/after the COVID pandemic) is of utmost importance to be considered. To achieve these goals, we need to develop models for a school building that provide reliable predictions and can be generalized for widespread deployment in schools.
Although school buildings contribute considerably to the total energy needs, few studies have been focused on school buildings in Canada [22,23]. They examined the energy use intensity (EUI) of 129 elementary and junior high schools in Manitoba, Canada, using data collected from 30 school buildings over ten years. They found that the average EUI at a K-12 school is 127 kWh/m2/year, 264 kWh/m2/year at a junior high school, and 270 kWh/m2/year at an elementary school. They stated that energy consumption might differ between K-12 and elementary and secondary schools due to differences in equipment and activities. Another study by Ouf et al. [23] examined the use of electricity and natural gas in Canadian schools. They divided the schools into three categories based on the year they were built: before 2004, between 2004 and 2013, and after 2013. They found that the electricity EUIs before 2004 was 58 kWh/m2/year, between 2004 and 2013 was 116 kWh/m2/year, and after 2013 was 125 kWh/m2/year. Newly constructed schools are more energy efficient in heating and cooling, but school electricity usage has increased due to the electrification of heating systems and additional teaching equipment.
Building energy performance simulation (e.g., EnergyPlusTM and TRNSYS) is a popular approach to studying school buildings. However, studies based on control-oriented models and measured sensor data of schools are relatively rare. This study investigates measured field data in an archetype electrically heated school building in cold regions. The main objectives of this paper are to: (1) develop a methodology to create data-driven control-oriented models that facilitate developing and assessing the impact of alternative control strategies in the schools; (2) propose different control strategies aimed to enhance the energy flexibility potential of school buildings; and (3) introduce key performance indicators (KPIs) as key parameters to quantify energy flexibility at the zone and building levels while considering IEQ.

2. Methodology

In recent years, international initiatives have recognized the need for a methodology to assess energy flexibility in buildings. This paper outlines the following steps in the method:
  • Identification of the system and load.
  • Characterization of flexibility.
  • Analyzing the impact of scenario modeling on the demand profiles.
  • Proposing key performance indicators to facilitate interaction between building operators, aggregators, and utility companies.
In addition, the method should be scalable and easy to implement [24]. Following these steps, this paper aims to model and enhance the energy flexibility of electrically heated school buildings through a rule-based approach with near-optimal setpoint profiles based on the archetype grey-box models. These archetype models can be adjusted depending on the specific features of the building. This study presents a practical methodology that facilitates the modeling and widespread implementation of appropriate control strategies in school buildings.

2.1. Data-Driven Grey-Box Model

Data-driven grey-box models ensure both physical insight and the reliability of measured data. Literature review indicates that grey-box models are also suitable for demand-side management in smart grids [25,26,27,28]. Gouda and Danaher [25] proposed a second-order model in which each construction element is modeled using three resistances and two capacitances. Candanedo and Dehkordi [26] presented a generalized approach for creating reduced-order control-oriented models. Their methodology can be implemented in building simulation tools to generate simplified models automatically. Bacher and Madsen [27] developed a statistical method for identifying models in building thermal studies. Reynders et al. [28] analyzed two detached single-family houses in Belgium. These two buildings represent two extreme cases of detached single-family houses in Belgium regarding insulation level (high and low insulation levels). They used data obtained from detailed building simulations with the IDEAS library in Modelica software. This study investigated five grey-box model types, ranging from first- to fifth-order models.
In grey-box models, choosing an appropriate level of resolution is essential, as it directly affects the parameter tuning and calculation time. A high-order model containing too many parameters requires information that is not often available with adequate accuracy. An oversimplified model may not be accurate enough to help make decisions. Therefore, obtaining a model that provides reliable predictions and can be implemented in real controllers is crucial for optimal building performance.
This paper investigates the accuracy of data-driven grey-box models for energy demand simulation and energy flexibility analysis. Providing a closer link between smart grids and smart buildings requires appropriate control strategies. Thus, this study presents an application of the developed model for control purposes based on smart grid requirements. The following steps are used to develop grey-box models and quantify energy flexibility:
  • Real building measurement data are collected from the smart meters installed in the archetype zones. Data included variables such as electricity consumption (kW), zone air temperature (°C), weather data, and specific data are related to each zone (e.g., floor heating temperature). All measurements are taken at intervals of 15 min.
  • Numerical models of thermal building control are developed. These models are based on RC model thermal networks.
  • The developed models are calibrated using the collected data. The important parameters are identified using the Sequential Least-Squares Programming (SLSQP) in Python.
  • Appropriate control strategies for zones with the convective system are presented to enhance the energy flexibility available from the building to the grid at specific times, depending on the grid requirement.
  • A building energy flexibility index (BEFI) is applied to quantify dynamic building energy flexibility at the zone and building levels.
  • Predictive control strategies for zones with the convective system and hydronic radiant floor system are presented to use the maximum thermal capacity of the concrete slab, reduce peak load during on-peak hours, and enhance energy flexibility when needed by the grid.

2.2. Governing Equation

A fully explicit finite difference approach is used to solve the energy balance equations at each node in the models. The fully explicit approach assumes that the current temperature of a given node depends only on its temperature and the temperature of the surrounding nodes at a previous time step. By using the heat balance for the control volume, a node’s differential equation can be written as [29]:
T i t + 1 = Δ t C i [ j U i j t ( T j t T i t ) + k U i k t ( T k t T i t ) + Q ˙ i t ] + T i t
  • Uij: Thermal conductance between nodes i and j, W/K;
  • Uik: Thermal conductance between nodes i and k that node k has a known temperature, W/K.
  • T: Temperature at node i, °C.
  • Ci: Thermal capacitance at node i J/K.
  • Q ˙ : Heat source at node i, W.
  • Δt: Time step, s.
The capacitance of the air node contains a factor CT (air thermal capacitance multiplier) that accounts for phenomena such as (energy storage in furniture and objects, the time required for air mixing, delay due to ducting and other factors) that in a low-order model result in capacitance with an observed effective value significantly larger than the one calculated using only the physical properties of the air. The air thermal capacitance multiplier ranges between 6 and 10 [30]. In this paper, we use CT = 8. Equation (1) in matrix form is:
{ T 1 T N } t + 1 = { Δ t C 1 Δ t C N } ( [ j N U 1 j k M U 1 k + C 1 Δ t U 12 U 1 N U N 1 U N 2 j N U N j k M U N k + C N Δ t ] { T 1 T N } t + { Q ˙ 1 + k M ( U 1 k k T k k ) Q ˙ N + k M ( U N k k T k k ) } )
where
  • ⊙: is an elementwise multiplication operator.
  • N: is the number of nodes.
  • M: is the number of nodes with known temperatures.
To assure numerical stability in the solution, the time step must be chosen according to the stability criterion defined in Equation (3):
Δ t m i n ( C i U i )
Using Equation (4), the proportional–integral control (PI controller) calculates the heat produced by the heating system at each time step, and the integral part should be reset periodically.
Q ˙ t + 1 = k p · ( T setpoint t T room . air t ) + k i ( T setpoint t T room . air t ) d t
where
  • kp: proportional gain of the controller, W/K.
  • ki: integral gain of the controller, W/K·s.
Equation (5) illustrates state-space representations of linear differential equation systems. In this equation, (x) is the state vector with n elements, (u) is the input vector with p elements, and (y) represents output vectors with q elements. The vectors are linked by the following matrices: A (n × n), B (n × p), C (q × n), and D (q × p).
x ˙ = A x + B u y = C x + D u
Temperatures of thermal capacitances are generally considered the system’s state in this approach since they have specific physical meaning and are relatively easy to measure [26]. Model identification refers to determining the physical properties of unknown systems based on some experimental or training data. In this paper, the Python function SLSQP is used to minimize the coefficient of variance of the root mean square error (CV-RMSE) as a fit metric. In accordance with ASHRAE Guideline 14, the model should not exceed a CV-RMSE of 30% relative to hourly measured data [31]. By minimizing CV-RMSE, the optimization algorithm determines the equivalent parameters for RC circuits. Equation (6) [31] is used to calculate CV-RMSE, where Ti represents the measurement data, T ^ i represents the simulation results, n corresponds to the total number of observations, and T ¯ represents the average of all measurements.
C V R M S E ( % ) = 100 × [ i = 1 n ( T i T ^ i ) 2 / n ] T ¯
This methodology can be used to create archetype RC thermal networks for representative zones. For example, Figure 1 presents a third-order thermal network RC model (4R3C) for zones with a convective system, which is defined by three state variables.
The inputs to this RC thermal network model are outdoor temperature (Text), solar heat gain (QSG), internal heat gain from occupants and equipment (QIG), and heat delivered by local water–air heat pumps (Qaux), and the output is the indoor air temperature. Montreal weather data are used to determine the outdoor temperature and solar irradiance [32]. Then, the performance of the RC thermal network model is validated with measured data. Table 1 presents an overview of the third-order thermal network parameters.

2.3. Energy Flexibility Quantification

The term “building energy flexibility” refers to “the ability to deviate from the reference scenario at a specified point in time and for a specified period” [6]. Enhancing energy flexibility is essential for balancing supply and demand on the grid and incorporating renewable energy capacity to reduce peak demand at key periods for the grid. Flexibility is also essential for providing contingency reserves for emergencies (e.g., after a power outage) and enabling dynamic electricity trading. Flexible buildings can also meet immediate or short-term grid needs.
Thus, real-time energy flexibility should be predicted and calculated on short notice (e.g., kilowatts available over the next few hours). This paper presents dynamic building energy flexibility indexes (BEFI) to quantify energy flexibility in school buildings and their interaction with the smart grid. We have described the BEFI concept in two previous conference papers on the topic with a preliminary introduction and case studies [33]. By implementing the flexibility strategy and using the reference as-usual profile, Equation (7) calculates the average B E F I ¯ at time t for duration Dt, Equation (8) presents the BEFI as a percentage, and Equation (9) quantifies BEFI% at the building level.
B E F I ¯ ( t , D t ) = t t + D t P ref d t t t + D t P Flex d t D t
B E F I % = P ref P Flex P ref
B E F I b u i l d i n g = 1 n B E F I z o n e
A model can be used to determine the difference in power demand (P, unit: Watt) between the reference case (Pref) and the flexible case (PFlex) to determine the available flexibility. This calculation gives the available flexibility at time t. Every hour, the calculation is repeated to give the available flexibility over the period B E F I ¯ ( t , D t ) .

3. Description of the Case Study: Electrically Heated School Building

The case study school (Figure 2) is an electrically heated building located in Sainte-Marthe-sur-le-Lac (near Montreal, QC, Canada). The total floor area of this two-story school building is 5192 m2 (2596 m2/story). The school includes the following features:
  • In operation since 2017.
  • Hydronic radiant floor systems in several zones (gym and offices).
  • Convective systems in several zones (classrooms, library, kindergarten).
  • A 28-loop geothermal system.
  • An Electrically heated Thermal Energy storage device (ThermElect) with an 80 kW heating capacity. ThermElect converts electrical power into stored heat when the price of electricity is low (or when demand on the grid is low) and provides heat when demand is high.
  • Water–air Heat pumps with a heating capacity of 40 kW at 36 terminals.
  • Water–water heat pump with a capacity of 33 kW.
The building automation system (BAS) and dedicated electrical submeters at this school provide high-quality data with a sampling timestep of fifteen minutes. The thermocouples are T-types with a standard accuracy of 0.2 °C for the temperature range of 0 to 70 °C. The gym and offices have been designed with significant thermal mass, which helps to improve energy flexibility. Table 2 presents some of the key features of the school building:

System Description

Figure 3 illustrates the schematic of the building’s heating system. The system consists of an integrated geothermal system, ThermElect, a water–water heat pump, local water–air HPs, and a hydronic radiant floor system. All heating systems are electrical devices and hence provide a link with the electrical grid. A predictive controller can exploit this link to help balance electricity production and demand, among other potential uses.
The water–water HP has a capacity of 33 kW in two stages (16.5 kW per stage) and a maximum water supply temperature of 48.8 °C. Borehole Thermal Energy Storage (BTES) with 28 loops on the evaporator side of the HP generates low-temperature heat. A thermal energy storage device (ThermElect) pre-heats the water input to local water–air HPs and water–water HP. The supply water temperature of the HP to the zones is controlled through a thermostatic three-way valve with a maximum temperature setting of 48.8 °C. Thermostats regulate the indoor temperature in each zone separately. The hydronic radiant heating and convective systems supply space heating in the offices and the gym.

4. Modeling Results and Discussion

4.1. Archetype Zones with Convective System: Classrooms

Figure 4 shows one of the classrooms in this school. Classrooms are equipped with ground-source water–air heat pumps (1.5–2 tons each) with COP of 3.2 and proportional–integral control (PI) in the local-loop control of room temperature. The classrooms are typically 9.1 m long by 7.2 m wide, with ceiling–floor heights of 3.0 m. Figure 5 shows a schematic of a classroom equipped with a water-to-air HP:
Figure 6 presents the thermal network RC model structures for zones with convective systems. Figure 6a–c shows the first-order model (1R1C), second-order model (3R2C), and third-order model (4R3C), respectively. The inputs for the analyzed models include outdoor temperature (Text), solar heat gain (QSG), internal heat gain (QIG), and heat delivered by water–air heat pumps (Qaux). Montreal weather data are used to determine outdoor temperature and solar radiation. In the measured data, the heat supplied by water–air HP is calculated by multiplying the measured electricity demand by COP of the HP and is used for comparison of models and measurements (shown in Figure 7). The solar heat gains, internal gains, and heating for the third-order model are distributed over the thermal capacitances (Figure 6c). The performance of the simplified RC models from the first-order to the third-order model is validated with measured data, as shown in Figure 7a–c.
As shown in Figure 7a, the first-order model cannot capture the system’s dynamics well. The second-order model has better calibration results than the first-order model, but it still cannot capture details of the thermal dynamics of the system (Figure 7b). The calibration of the third-order model (Figure 7c) shows good accuracy and adequate statistical indices (CV-RMSE of 8% and a maximum difference of 0.4 °C). It should be noted that higher-order models require additional inputs, such as heat flux measurements, to guarantee observability. Since these measurements will not be available in most buildings, higher-order models’ identity cannot be guaranteed [28].

4.1.1. Weather Conditions: Cold Winter Days

Weather data for Montreal’s coldest days (5–8 February 2020) are selected because peak energy demand occurs under these conditions. Figure 8 presents the outdoor temperature and solar flux during these days. The weather data are measured data and were obtained from the hourly Montreal weather file [32].

4.1.2. Available Energy Flexibility in Contingency Event

Contingency reserves are amounts of power that a utility can use in the event of the loss of a generation unit or unexpected load imbalance. To address this need, real-time thermal load flexibility should be predicted ahead of time or calculated continuously and should be available at short notice (e.g., 10 min) over an hour or several hours. This section presents the contingency strategy to quantify the energy flexibility available from the zones with a convective system to the grid at specific times. In this case, a tolerance band setpoint profile is proposed. A flexible approach is proposed within the tolerance limits where the temperature is allowed to deviate from the reference setpoint. For example, during a flexibility event occurring at 2 p.m. for one hour, the temperature is allowed to drop by 2 degrees to provide a “temporary relief” to the heating system (Figure 9a). At this point, the setpoint is lowered two degrees (from 24 to 22 °C). Figure 9b shows the results of available energy flexibility during contingency events.
According to Figure 9b, energy flexibility of around 20 W/m2 can be provided to the grid in the event of loss of a generation unit or other unexpected power outages. The BEFI can be implemented in the BAS with a predictive model controller, which can optimize power flexibility for a known period of high demand. This makes BEFI appropriate for various grid requirements, including contingency reserves and load shifting.

4.2. Archetype Zones with Hydronic Radiant Floor and Convective Heating Systems

Figure 10 presents a schematic of the office zones equipped with local water–air HP and a hydronic radiant floor system on the school’s first floor.
The plan view of the offices and piping of the hydronic radiant floor system is shown in Figure 11. These offices are heated with hydronic radiant and local convective systems. Proportional–integral thermostats control heating systems. The thermocouples in the offices are T-types with a standard accuracy of 0.2 °C for the temperature range of 0 to 70 °C. In addition to air temperatures, floor temperatures are also measured at eight different locations, as shown in Figure 11.
Table 3 presents the radiant hydronic floor area in each zone and the piping length.
A front view of the slab with hydronic radiant piping can be seen in Figure 12. The floor is a concrete slab 15 cm thick insulated at the bottom with total thermal resistance of 5.64 m2 K/W. The pipe is made of cross-linked polyethylene (PEX), has a diameter of 1.25 cm, and is located at the depth of 6 cm. The pipes were kept in place by a wire mesh before casting concrete, and the distance between the pipes was 30.4 cm.
Concrete’s properties are affected by its age, temperature, humidity, and moisture content [34]. Following ASHRAE [35], a normal-density concrete has a conductivity of 1.7 W/(m·K), specific heat of 800 J/(kg·K), and a density of 2200 kg/m3. A water–water HP provides a controlled flow rate of 0.29 L/s with a maximum temperature of 48.8 °C. The HP has a nominal COP of 2.7 under full load conditions at 48.8 °C. Heating power to the hydronic radiant system is calculated by Equation (10):
Q = m ˙ × c p × Δ T
According to the ASHRAE standard 55, the floor temperature must not exceed 29 °C [36]. Thus, a floor surface temperature of 26 °C is considered in this study. Several floor sensors and control valves protect the floor from overheating and enhance thermal comfort. The RC thermal network for the zones with hydronic radiant and convective heating/cooling systems is shown in Figure 13. The inputs are outdoor temperature (Text), solar gain (QSG), internal heat gain (QIG), heat delivered by the hydronic radiant system (qRF), and heat delivered by the convective system (Qaux). These inputs can be:
  • Controllable: such as the heat delivered by the heating systems and the ventilation airflow rate.
  • Uncontrollable: such as the outdoor temperature, solar gains, and internal gains.
The performance of the simplified RC model is validated with measured data, as shown in Figure 14.
Table 4 provides an overview of the thermal network model parameters:

4.2.1. Control Scenarios for Energy Flexibility Activation in Archetype Zones with Hydronic Radiant Floor and Convective Systems

This section investigates the heat supplied to the zones with hydronic radiant and convective systems. It will be possible to develop simple predictive control strategies that use thermal storage potential while also considering peak load and thermal comfort. In the reference case (a business-as-usual case), the hydronic radiant floor temperature setpoint (21.8 °C) is always lower than the air temperature setpoint (23 °C) during the daytime (Figure 15a). As a result, the convective system is the primary heating system, and the floor acts as a heat sink. In this study, alternative control scenarios for a cold winter day are examined and compared to current building operations as a reference case. Assumptions considered in designing control strategies include:
  • To maintain the slab temperature within the comfort range, the slab surface is set to a maximum of 26 °C.
  • The water–water HP can deliver up to 15 kW of heat to the radiant floor heating system, according to the observation from measured data.
  • The operating temperature is considered to be the effective indoor temperature.
  • During unoccupied hours (nighttime), the slab is charged and discharged during occupied hours (daytime).
  • Control Scenario 1 (Reference Case)
The reference case is presented in Figure 15a, which is the current operation of zones with hydronic radiant heating. In this scenario, the convective system is the primary heating system, and the hydronic radiant system is not commonly used. As seen in Figure 16a, in this case, the peak load is 10 kW and occurs during the on-peak hours (6 a.m. to 9 a.m.). Thus, in order to improve the energy flexibility of the building, the following two control scenarios are presented.
2.
Control Scenario 2 (Constant Air Setpoint Temperature)
This control scenario involves preheating the slab from midnight to 8:00 a.m. with a setpoint temperature of 26 °C (Figure 15b). During occupied hours (from 8:00 a.m. to 5:00 p.m.), the slab’s set point temperature is 18 °C, and then it is raised to 22 °C. It is considered that the air setpoint temperature is always constant and equal to 20 °C during occupied and non-occupied hours.
According to Figure 15b, the operative temperature varies between 21 and 24 °C, which is within the thermal comfort range for the occupants. In Figure 16b, the heat delivered to the thermal zones is calculated using Control Scenario 2. In this control scenario, the radiant floor system is the primary heating system, and the heating demand during occupied hours is reduced. It should be noted that in this control scenario, the ventilation system is off, resulting in poor air quality in the offices. Therefore, Control Strategy 3 is presented to address the air quality of the zones during occupied hours.
3.
Control Scenario 3 (Variable Air Setpoint Temperature)
As part of this control scenario, the air setpoint temperature is increased to 23 °C during occupied hours (Figure 15c). As a result, the morning peak load can be reduced, and fresh air can be provided to the zones from 10:00 a.m. to 5:00 p.m. The energy consumption in this flexible scenario is 133.5 kWh, which is less than the reference case (136.6 kWh). The following section will address the slab’s state of charge (SOC) (i.e., thermal storage), as well as the flexibility associated with reducing peak loads and energy consumption over peak periods.

4.2.2. State of Charge (SOC) of the Slab

The thermal inertia in the slab can provide the flexibility to reduce peak loads and shift the heat production of the radiant heating system in time. State of charge (SOC) is a concept that describes how much energy is stored at time t relative to the total capacity, as shown in Equation (11) [37]:
S O C = E t h ( t ) E t h , m i n ( t ) E t h , m a x ( t ) E t h , m i n ( t )
The SOC is the percentage of the stored thermal energy as a function of the minimum and maximum slab surface temperatures, as given by [38].
S O C = T slab ( t ) T th , min ( t ) T th , max ( t ) T th , min ( t )
where Tth,max is the maximum slab surface temperature, set at 26 °C for indoor thermal comfort, and Tth,min is the minimum slab surface temperature, considered equal to the average indoor air temperature.
Figure 17 and Figure 18 illustrate heat storage and SOC of the slab in the reference case (Control Strategy 1) and flexible case (Control Strategy 3). It can be observed that in the reference case, the slab cannot be fully charged. Thus, the thermal energy storage capacity of the slab is not fully utilized; while using a flexible case (Control Strategy 3), the slab is fully charged during unoccupied hours and discharged during on-peak hours. This approach activates the thermal load flexibility of the school and allows the electricity grid to manage electricity demand when needed.

4.2.3. Thermal Load Flexibility in Archetype Zones with Hydronic Radiant System

Equations (7)–(9) calculate BEFI by implementing the flexibility strategy and comparing it with the reference as-usual profile. In Figure 19, a flexibility strategy is applied to zones with hydronic radiant and convective heating systems to calculate the hourly BEFI.
By applying a flexible control strategy, available hourly BEFI provided to the grid during on-peak hours is positive, indicating the power reduction value available compared to the reference case. During nighttime (off-peak hours), the BEFI is negative, showing a higher power demand for charging the slab and preheating the zones. Based on Figure 19, around 60 W/m2 energy flexibility can be provided to the grid in the morning and 45 W/m2 in the evening (on-peak hours).

4.3. Building Level Energy Flexibility

Figure 20 presents energy flexibility at the building level. Zones with radiant floor and convective heating systems can provide around 60 W/m2 energy flexibility. Additionally, classrooms and the library with convective heating systems can provide 20 W/m2 during on-peak hours. In total, by implementing appropriate control strategies, the school building can provide energy flexibility from between 30 W/m2 and 80 W/m2 when needed by the grid.
In this school, the gym and offices’ floor area is 586 m2, and the classrooms’, libraries’, and kindergartens’ floor is 2054 m2. Therefore, the school at the building level has potential flexibility of between 50 and 80 kW, representing 40 to 65% building energy flexibility. This bottom-up approach opens the path towards labeling energy flexibility in school buildings as part of the future smart grid and smart cities.

5. Conclusions

School buildings are an important part of the building stock; they also represent a sizable portion of the total energy use in the building sector. Therefore, quantification of energy flexibility in school buildings has a significant role in providing a safe and efficient operation of the future resilient grid. This paper presented a practical methodology that facilitates the modeling and implementation of appropriate control strategies in school buildings. This paper also presented a methodology for defining and calculating a dynamic energy flexibility index for buildings. The dynamic building energy flexibility index (BEFI) is defined in terms of key performance indicators relative to a reference energy consumption profile at the zone level, building level, and as a percentage. The application of the BEFI was presented for an electrically heated school building in Canada. This study illustrated how low-order lumped parameter thermal network models could be utilized to calculate the BEFI. Furthermore, the activation of energy flexibility through a rule-based approach with near-optimal setpoint profiles is investigated. Results show that applying appropriate control strategies can enhance the school building energy flexibility by 40% to 65% during peak demand periods. In addition to improving energy flexibility in school buildings, these control strategies could reduce the size of HVAC units at the design stage, thereby lowering their operating and initial capital costs.

Author Contributions

Conceptualization, N.M., A.K.A. and J.A.C.; methodology, N.M.; software, N.M.; validation, N.M.; formal analysis, N.M.; investigation, N.M.; resources, A.K.A. and J.A.C.; data curation, N.M.; writing—original draft preparation, N.M.; writing—review and editing, N.M., A.K.A., J.A.C. and B.D.; visualization, N.M.; supervision, A.K.A. and J.A.C.; project administration, A.K.A. and J.A.C.; funding acquisition, A.K.A. and J.A.C. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by NSERC/Hydro-Québec Industrial Research Chair at Concordia University, Grant Number IRCSA 452557.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Acknowledgments

Technical support from Hydro-Québec Research Institute (Laboratoire des Technologies de l’Énergie, Shawinigan, QC, Canada) under the NSERC/Hydro-Québec Industrial Research Chair held by Athienitis is greatly acknowledged. Technical support and data provided by Commission scolaire de la Seigneurie-des-Mille-Îles (CSSMI) are acknowledged with thanks. The authors would like to thank NSERC for funding this project through Candanedo’s Discovery Grant and the NSERC/Hydro-Québec Industrial Research Chair (“Optimized operation and energy efficiency: towards high-performance buildings”) held by Athienitis. The comments of colleagues at CanmetENERGY are gratefully appreciated. The funding contribution of NRCan’s Office of Energy Research and Development through the PERD programs is gratefully acknowledged.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations

BASBuilding automation system
BEFIBuilding energy flexibility index (W)
BTESBorehole thermal energy storage
CThermal capacitance (J/K)
COPCoefficient of performance
CV-RMSECoefficient of variance of the root mean square error
DSMDemand-side management
DtTime (seconds/hours)
EUIEnergy use intensity (kWh/m2/year)
HVACHeating, ventilation, and air conditioning
KPI Key performance indicator
NZEBNet zero energy building
PElectric power (W)
PVPhotovoltaic
QSGSolar gain (W)
QIGInternal heat gain (W)
QauxHeating power (W)
RThermal resistance (K/W)
RESRenewable energy sources
RCResistance–capacitance
SOCState of charge
TTemperature (°C)
ToOutdoor temperature (°C)
TSPSetpoint temperature (°C)
Subscripts
FlexFlexible case
RefReference case
SPSetpoint

References

  1. Davito, B.; Tai, H.; Uhlaner, R. The smart grid and the promise of demand-side management. McKinsey Smart Grid 2010, 3, 8–44. [Google Scholar]
  2. Foteinaki, K.; Li, R.; Heller, A.; Rode, C. Heating system energy flexibility of low-energy residential buildings. Energy Build. 2018, 180, 95–108. [Google Scholar] [CrossRef]
  3. Weiß, T.; Fulterer, A.M.; Knotzer, A. Energy flexibility of domestic thermal loads—A building typology approach of the residential building stock in Austria. Adv. Build. Energy Res. 2019, 13, 122–137. [Google Scholar] [CrossRef]
  4. Afram, A.; Janabi-Sharifi, F. Theory and applications of HVAC control systems–A review of model predictive control (MPC). Build. Environ. 2014, 72, 343–355. [Google Scholar] [CrossRef]
  5. Jensen, S.Ø.; Marszal-Pomianowska, A.; Lollini, R.; Pasut, W.; Knotzer, A.; Engelmann, P.; Stafford, A.; Reynders, G. IEA EBC annex 67 energy flexible buildings. Energy Build. 2017, 155, 25–34. [Google Scholar] [CrossRef] [Green Version]
  6. Torres Ruilova, B. Evaluation of Energy Flexibility of Buildings Using Structural Thermal Mass. Master’s Thesis, Universitat de Barcelona, Barcelona, Spain, 2017. [Google Scholar]
  7. Ilic, D.; Da Silva, P.G.; Karnouskos, S.; Griesemer, M. An energy market for trading electricity in smart grid neighbourhoods. In Proceedings of the 2012 6th IEEE International Conference on Digital Ecosystems and Technologies (DEST), Campione d’Italia, Italy, 18–20 June 2012; pp. 1–6. [Google Scholar]
  8. Lopes, R.A.; Chambel, A.; Neves, J.; Aelenei, D.; Martins, J. A literature review of methodologies used to assess the energy flexibility of buildings. Energy Procedia 2016, 91, 1053–1058. [Google Scholar] [CrossRef] [Green Version]
  9. Reynders, G. Quantifying the Impact of Building Design on the Potential of Structural Storage for Active Demand Response in Residential Buildings. Ph.D. Thesis, KU Leuven, Heverlee, Belgium, 2015. [Google Scholar]
  10. Afroz, Z.; Shafiullah, G.; Urmee, T.; Higgins, G. Modeling techniques used in building HVAC control systems: A review. Renew. Sustain. Energy Rev. 2018, 83, 64–84. [Google Scholar] [CrossRef]
  11. Tabares-Velasco, P.; Christensen, C.; Bianchi, M. Simulated peak reduction and energy savings of residential building envelope with phase change materials. ASHRAE Trans. 2012, 118, 90–97. [Google Scholar]
  12. Morovat, N.; Athienitis, A.K.; Candanedo, J.A.; Dermardiros, V. Simulation and performance analysis of an active PCM-heat exchanger intended for building operation optimization. Energy Build. 2019, 199, 47–61. [Google Scholar] [CrossRef]
  13. Klein, K.; Herkel, S.; Henning, H.-M.; Felsmann, C. Load shifting using the heating and cooling system of an office building: Quantitative potential evaluation for different flexibility and storage options. Appl. Energy 2017, 203, 917–937. [Google Scholar] [CrossRef]
  14. Finck, C.; Li, R.; Zeiler, W. Optimal control of demand flexibility under real-time pricing for heating systems in buildings: A real-life demonstration. Appl. Energy 2020, 263, 114671. [Google Scholar] [CrossRef]
  15. Junker, R.G.; Azar, A.G.; Lopes, R.A.; Lindberg, K.B.; Reynders, G.; Relan, R.; Madsen, H. Characterizing the energy flexibility of buildings and districts. Appl. Energy 2018, 225, 175–182. [Google Scholar] [CrossRef]
  16. De Coninck, R.; Helsen, L. Quantification of flexibility in buildings by cost curves–Methodology and application. Appl. Energy 2016, 162, 653–665. [Google Scholar] [CrossRef]
  17. Tumminia, G.; Sergi, F.; Aloisio, D.; Longo, S.; Cusenza, M.A.; Guarino, F.; Cellura, S.; Ferraro, M. Towards an integrated design of renewable electricity generation and storage systems for NZEB use: A parametric analysis. J. Build. Eng. 2021, 44, 103288. [Google Scholar] [CrossRef]
  18. Ashrae, A.S. Standard 90.1-2016; Energy Standard for Buildings Except Low Rise Residential Buildings. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.: Atlanta, GA, USA, 2016.
  19. Distribution., H.-Q. État D’Avancement 2012 du Plan D’Approvisionnement 2011–2020. 2012. Available online: http://www.regie-energie.qc.ca/audiences/TermElecDistrPlansAppro_Suivis.html (accessed on 12 January 2022).
  20. Hydro-Québec, A.r. Voir Grand Avec Notre Énergie Propre. 2019. Available online: http://www.hydroquebec.com/data/documents-donnees/pdf/rapport-annuel.pdf (accessed on 25 August 2021).
  21. Statistic Canada. Elementary–Secondary Education Survey for Canada, the Provinces and Territories. 2017. Available online: https://www150.statcan.gc.ca/n1/dailyquotidien/171103/dq171103c-eng.htm (accessed on 6 November 2020).
  22. Issa, M.H.; Attalla, M.; Rankin, J.H.; Christian, A.J. Energy consumption in conventional, energy-retrofitted and green LEED Toronto schools. Constr. Manag. Econ. 2011, 29, 383–395. [Google Scholar] [CrossRef]
  23. Ouf, M.; Issa, M.; Merkel, P. Analysis of real-time electricity consumption in Canadian school buildings. Energy Build. 2016, 128, 530–539. [Google Scholar] [CrossRef]
  24. O’Connell, S.; Reynders, G.; Seri, F.; Keane, M. Validation of a Flexibility Assessment Methodology for Demand Response in Buildings. In IOP Conference Series: Earth and Environmental Science; IOP Publishing: Bristol, UK, 2019; p. 012014. [Google Scholar]
  25. Gouda, M.; Danaher, S.; Underwood, C. Building thermal model reduction using nonlinear constrained optimization. Build. Environ. 2002, 37, 1255–1265. [Google Scholar] [CrossRef]
  26. Candanedo, J.A.; Dehkordi, V.R.; Lopez, P. A control-oriented simplified building modelling strategy. In Proceedings of the 13th Conference of International Building Performance Simulation Association, Chambéry, France, 26–28 August 2013. [Google Scholar]
  27. Bacher, P.; Madsen, H. Identifying suitable models for the heat dynamics of buildings. Energy Build. 2011, 43, 1511–1522. [Google Scholar] [CrossRef] [Green Version]
  28. Reynders, G.; Diriken, J.; Saelens, D. Quality of grey-box models and identified parameters as function of the accuracy of input and observation signals. Energy Build. 2014, 82, 263–274. [Google Scholar] [CrossRef]
  29. Athienitis, A.; Santamouris, M. Thermal Analysis and Design of Passive Solar Buildings; Routledge: London, UK, 2002. [Google Scholar]
  30. Hong, T.; Lee, S.H. Integrating physics-based models with sensor data: An inverse modeling approach. Build. Environ. 2019, 154, 23–31. [Google Scholar] [CrossRef] [Green Version]
  31. ASHRAE Guideline. Guideline 14-2002, Measurement of Energy and Demand Saving; American Society of Heating, Ventilating, and Air Conditioning Engineers: Atlanta, GA, USA, 2002. [Google Scholar]
  32. Hydro-Québec. Simulation Énergétique des Bâtiments. Available online: https://www.simeb.ca:8443/index_fr.jsp (accessed on 12 October 2021).
  33. Athienitis, A.K.; Dumont, E.; Morovat, N.; Lavigne, K.; Date, J. Development of a dynamic energy flexibility index for buildings and their interaction with smart grids. In Proceedings of the 2020 Summer Study on Energy Efficiency in Buildings, Virtual, 17–21 August 2020. [Google Scholar]
  34. Marshall, A. The thermal properties of concrete. Build. Sci. 1972, 7, 167–174. [Google Scholar] [CrossRef]
  35. Ashrae, I. 2009 ASHRAE Handbook: Fundamentals; American Society of Heating, Refrigeration and Air-Conditioning Engineers: Atlanta, GA, USA, 2009. [Google Scholar]
  36. ASHRAE 55; Thermal Environmental Conditions for Human Occupancy. American Society of Heating, Refrigeration and Air-Conditioning Engineers: Atlanta, GA, USA, 2017.
  37. Reynders, G.; Lopes, R.A.; Marszal-Pomianowska, A.; Aelenei, D.; Martins, J.; Saelens, D. Energy flexible buildings: An evaluation of definitions and quantification methodologies applied to thermal storage. Energy Build. 2018, 166, 372–390. [Google Scholar] [CrossRef]
  38. Gouvernement du Québec. Plan Directeur en Transition, Innovation et Efficacit Energetiques du Quebec 2018–2023; Gouvernement du Québec: Québec City, QC, Canada, 2018. [Google Scholar]
Figure 1. Thermal network model of the zones with convective system.
Figure 1. Thermal network model of the zones with convective system.
Buildings 12 00581 g001
Figure 2. Electrically heated school building, Horizon-du-Lac (near Montreal, QC, Canada).
Figure 2. Electrically heated school building, Horizon-du-Lac (near Montreal, QC, Canada).
Buildings 12 00581 g002
Figure 3. Process flow diagram (PFD) of the building heating systems.
Figure 3. Process flow diagram (PFD) of the building heating systems.
Buildings 12 00581 g003
Figure 4. Typical classroom with convective heating.
Figure 4. Typical classroom with convective heating.
Buildings 12 00581 g004
Figure 5. Schematic of a classroom with water–air heat pump.
Figure 5. Schematic of a classroom with water–air heat pump.
Buildings 12 00581 g005
Figure 6. RC thermal network model: (a) first-order, (b) second-order, and (c) third-order models.
Figure 6. RC thermal network model: (a) first-order, (b) second-order, and (c) third-order models.
Buildings 12 00581 g006
Figure 7. Calibration of RC thermal network models with measured data: (a) first-order, (b) second-order, and (c) third-order models.
Figure 7. Calibration of RC thermal network models with measured data: (a) first-order, (b) second-order, and (c) third-order models.
Buildings 12 00581 g007
Figure 8. Outdoor temperature and solar flux-Montreal’s coldest days.
Figure 8. Outdoor temperature and solar flux-Montreal’s coldest days.
Buildings 12 00581 g008
Figure 9. (a) Daily setpoint profile with acceptable temperature band and a flexibility event with a duration of 1 h at 2 pm; (b) energy flexibility curve, 1 h event.
Figure 9. (a) Daily setpoint profile with acceptable temperature band and a flexibility event with a duration of 1 h at 2 pm; (b) energy flexibility curve, 1 h event.
Buildings 12 00581 g009
Figure 10. Schematic of the office zone equipped with hydronic radiant floor and convective systems.
Figure 10. Schematic of the office zone equipped with hydronic radiant floor and convective systems.
Buildings 12 00581 g010
Figure 11. Plan view of the offices with hydronic radiant floor system.
Figure 11. Plan view of the offices with hydronic radiant floor system.
Buildings 12 00581 g011
Figure 12. Slab cut with hydronic radiant heating piping.
Figure 12. Slab cut with hydronic radiant heating piping.
Buildings 12 00581 g012
Figure 13. RC thermal network model of the zones with hydronic radiant floor system and convective system.
Figure 13. RC thermal network model of the zones with hydronic radiant floor system and convective system.
Buildings 12 00581 g013
Figure 14. Calibration of RC thermal network model with measured data, zones with hydronic radiant floor system and convective system.
Figure 14. Calibration of RC thermal network model with measured data, zones with hydronic radiant floor system and convective system.
Buildings 12 00581 g014
Figure 15. Temperature profile in different control strategies: (a) Control Strategy 1 (reference case); (b) Control Strategy 2; (c) Control Strategy 3.
Figure 15. Temperature profile in different control strategies: (a) Control Strategy 1 (reference case); (b) Control Strategy 2; (c) Control Strategy 3.
Buildings 12 00581 g015
Figure 16. Heat delivered to the thermal zones in different control strategies: (a) Control Strategy 1 (reference case); (b) Control Strategy 2; (c) Control Strategy 3.
Figure 16. Heat delivered to the thermal zones in different control strategies: (a) Control Strategy 1 (reference case); (b) Control Strategy 2; (c) Control Strategy 3.
Buildings 12 00581 g016
Figure 17. Heat storage and state of charge (SOC) of the slab (reference case).
Figure 17. Heat storage and state of charge (SOC) of the slab (reference case).
Buildings 12 00581 g017
Figure 18. Heat storage and state of charge (SOC) of the slab (flexible case).
Figure 18. Heat storage and state of charge (SOC) of the slab (flexible case).
Buildings 12 00581 g018
Figure 19. Average hourly BEFI (flexible control strategy).
Figure 19. Average hourly BEFI (flexible control strategy).
Buildings 12 00581 g019
Figure 20. Hourly building energy flexibility in school.
Figure 20. Hourly building energy flexibility in school.
Buildings 12 00581 g020
Table 1. Description of RC thermal network model parameters (4R3C).
Table 1. Description of RC thermal network model parameters (4R3C).
ParameterDescriptionParameterDescription
R1, extResistance of Wall1Envelope node
R1,2Resistance between wall and air 2Indoor air temperature node
R2,3Resistance between floor and air3Floor temperature node
R2, extResistance of infiltrationTextOutdoor temperature
C1Capacitance of Envelope QSGSolar heat gain
C2Capacitance of effective air QIGInternal heat gain
C3Capacitance of floorQauxHeating power
Table 2. Key features of the school building.
Table 2. Key features of the school building.
General Information
In operation since2017
SiteSainte-Marthe-sur-le-Lac, Québec, Canada
Latitude 45.5
ASHRAE climate zone6
Heating degree days4495
Net floor area (m2)2596 m2/floor
Number of floors2
Window typeDouble-glazed argon low-e
Mechanical
Space heating/coolingGround-source water–water HP and local water–air HPs
Ventilation systemBalanced mechanical ventilation with DCV, with centralized AHUs with rotary heat recovery. Centralized dedicated outdoor air system (DOAS) modulated based on CO2
Main system, featuresGround-source heat pump (GSHP), energy recovery ventilator (ERV)
DHW sourceElectricity boiler
Electrical
Lighting, typical type, controlsLED-tube luminaires
Table 3. Floor area and piping length of the offices with hydronic radiant system.
Table 3. Floor area and piping length of the offices with hydronic radiant system.
Thermal ZoneArea (m2)Piping Length (m)
Office 164244
Office 21269
Office 32191
Office 427176
Office 51987
Total143667
Table 4. Description of RC thermal network model parameters (7R4C).
Table 4. Description of RC thermal network model parameters (7R4C).
ParameterDescriptionParameterDescription
1Node of envelope R1,extResistance of wall, (K/W)
2Node of indoor air R1,2Resistance between wall and air node, (K/W)
3Node of floor surface R2,3Resistance between floor and air node, (K/W)
4Node of pipe RinfResistance of infiltration, (K/W)
5Node of concrete (top)R3,4Resistance between pipe and floor surface, (K/W)
TextTemperature of outdoor, (°C)R4,5Resistance between concrete and pipe, (K/W)
TgTemperature of ground, (°C)R6,gResistance between ground and concrete, (K/W)
QSGSolar heat gain, (W)C1Capacitance of envelope, (J/K)
QIGInternal heat gain, (W)C2Capacitance of effective Air, (J/K)
QauxHeating power, (W)C4Capacitance of floor (top), (J/K)
QRFHeating of radiant floor, (W)C5Capacitance of floor (below), (J/K)
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Morovat, N.; Athienitis, A.K.; Candanedo, J.A.; Delcroix, B. Model-Based Control Strategies to Enhance Energy Flexibility in Electrically Heated School Buildings. Buildings 2022, 12, 581. https://doi.org/10.3390/buildings12050581

AMA Style

Morovat N, Athienitis AK, Candanedo JA, Delcroix B. Model-Based Control Strategies to Enhance Energy Flexibility in Electrically Heated School Buildings. Buildings. 2022; 12(5):581. https://doi.org/10.3390/buildings12050581

Chicago/Turabian Style

Morovat, Navid, Andreas K. Athienitis, José Agustín Candanedo, and Benoit Delcroix. 2022. "Model-Based Control Strategies to Enhance Energy Flexibility in Electrically Heated School Buildings" Buildings 12, no. 5: 581. https://doi.org/10.3390/buildings12050581

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop