1. Introduction
The framed tube idea is an effective framing system for high-rise buildings. This type of structural system is mainly comprises closely spaced circumferential columns, which are connected by deep spandrel beams. The whole system works as a giant vertical cantilever, and its high efficiency is due to the large distance between windward and leeward columns. Among the most important specifications of tubular systems is their high economic efficiency. A case in point is that the material consumed in this kind of system is reduced by half in comparison with other systems [
1]. In a rigid frame the “strong” bending direction of columns is aligned perpendicular to the face, while this factor is typically aligned along the face of the building in a framed tube system. In a framed tube system, the tube form resists overturning produced by lateral load—a leading cause of compression and tension in columns. Bending in columns and beams or rotation of the beam-column joint in the web section resists the shear force produced by lateral load. Gravity loads are resisted partly by exterior frames and partly by interior columns [
2].
In an ideal tubular structure, circumferential columns and beams are assumed to be completely rigid, so both web and flange panels act separately and bend against lateral loads like a true cantilever. While the above system has a tubular form, it also has a more complicated behavior than a solid tube. To be more specific, the components in a framed tube cannot be completely rigid due to technical and economic constraints [
3]. This will be a leading cause of nonuniform distribution of loads in columns.
Consequently, in a framed-tube structure under lateral load, the stress distribution in the flange wall panels is nonuniform and is nonlinear in the web wall panels. This anomaly which reduces the efficiency of the structures is referred to as “shear lag” [
4]. To obtain a better understanding of this phenomenon, a factor called the shear lag factor is defined. This factor is a ratio of the corner column axial force to the middle column axial force. When the stresses in the corner columns of the flange frame panels exceed those in the middle columns, the shear lag is positive. Nevertheless, in some cases, it is vice-versa where the stress in the middle columns exceeds those in the corner columns, and this is referred to as the negative shear lag.
This paper studied the effect of lateral load type on the shear lag phenomenon in framed-tube reinforced concrete tall buildings with different plan geometries.
2. Review of Literature
With regard to the great importance of framed tube systems in the construction of high-rise buildings, it is no wonder that multifarious research has been carried out on this structural system and its shortcomings in order to make framed tube systems more effective. However, previous studies did not pay enough attention to the subjected load type and its relation to the shear lag factor and the shape of the structures, which play an important role in the amount of this factor.
In 1969, Fazlur Khan proposed a chart named “structural systems for height” which has classified the different types of tubular systems with regard to their efficiency for high-rise buildings of different heights [
5]. In the same year, Chang and Zheng tried to find out more about negative shear lag and its influential factors on a cantilever box girder. In this research, they found that negative shear lag will change with the different boundary conditions of displacement and external force applied to the girder [
6]. In 1988, Shiraishi et al. studied the aerodynamic stability effects on rectangular cylinders by altering their shapes subjected to the lateral loads such as wind and water flow. They cut some squares with different sizes in each edge in a rectangular cross section and observed that it has a controlling effect on the separated shear layer generating from the leading edge. These sections with various sizes of corner-cuts had totally different behaviors against wind force and water flume [
7]. In 1990, Hayashida and Iwasa investigated the effects of the geometry of structures on aerodynamic forces and displacement response for tall buildings. They tested four different plan shapes, with and without corner-cuts in a wind tunnel and identified the aerodynamic damping effects produced by changing some parts of the basic cross section and also the aerodynamic character of basic shapes [
8]. In 1991, Connor and Pouangare presented a simple model for the design of framed tube structures. They modeled the structures as a series of stringers which resisted axial forces without bending rigidity and shear panels which resisted shear forces without bending or axial rigidity. They proposed a model that gives accurate results for the preliminary design and analysis of tubular structures with different geometry and material properties [
9]. Kwan, in 1994, proposed a hand calculation method for approximate analysis in framed tube structures by considering the shear lag factor. This method could be useful for preliminary design and quick evaluation and could provide a better perception of the effect of multifarious parameters on the structure’s behavior [
10]. In 2000, Han et al. investigated the shear lag factor in the web panels of shear-core walls [
11]. Lee et al., in 2002, looked into the behavior of the shear lag of framed tube structures with and without internal tube(s) for the behavioral characteristics of the structures and also the relation between their performance and various structural parameters. They also proposed a simple numerical method for the prediction of the shear lag effect in framed tube structures. It has been found that the stiffness factor has an effective role in producing shear lag in tubular structures [
12]. Haji-Kazemi and Company proposed a new method to analyze shear lag in framed tube structures using an analogy between the shear lag behavior of a cantilever box which represents a uniform framed tube building. This method is able to accurately analyze positive as well as negative shear lag effects in tubular structures accurately [
13]. Furthermore, Moghadasi and Keramati, in 2009, studied the effects of internal tubes in shear lag reduction. They reduced the lateral displacement and shear lag amount in high-rise buildings by adding internal tubes to the framed tube structures [
14].
In 2012, Shin et al. investigated different parameters such as depth and width of beams and columns on the behavior of shear lag in a frame-wall tube building. The results showed that the effect of column depth on the shear lag behavior of framed tube was more outstanding than other parameters [
15]. In 2014, Mazinani et al. compared the shear lag amount of pure tube structural systems with braced tube systems and different types of X-diagonal bracing. It was observed that these braces started from corner-to-corner, increased the stiffness of the structure and consequently reduced the story drift and shear lag factor in the tubular system [
16]. In addition, Nagvekar and Hampali studied the shear lag phenomenon in both the web and wing panel of a hollow structure and measured it in various heights of a structure [
17]. The plan geometry, building’s body form, the ratio of height to width and three-dimensional stiffness for the transfer of wind and seismic loads are the most important structural system properties affect the behavior of tall buildings, as reported by Szolomicki and Golasz-Szolomicka [
18]. Alaghmandan et al. in 2016 inquired about the architectural strategies on wind effects in tall buildings. These tactics included altering the geometry of the whole building scale such as tapering and setbacks, and attenuated the wind effects in some models by architectural strategies [
19]. In 2019, Shi and Zhang proposed a simplified method for calculation of shear lag in diagrid framed tube structures. In their study, the diagrid tube structure is assumed to be equivalent to continuous orthogonal elastic membrane. They tried to solve two key problems of finding the optimized angle of the diagonal column and the shear lag assessment in the preliminary design of the above structures [
20].
In terms of microstructural view of concrete subjected to dynamic loading at high strain rates, Hentz et al. used a 3D discrete element method and verified it [
21]. Furthermore, the evaluation of concrete cracks occurring in complex states of stress was studied by Golewski and Sadowski [
22]. In their study, crack development at shear was investigated through experimental tests using two types of aggregates.
As seen from the review above of previous studies, the possible relation between shear lag and the type of lateral load subjected to these systems is not yet considered.
4. Results and Discussions
In this section, the results obtained from the static and dynamic analyses are discussed, and possible relationships between shear lag and the three different factors are studied in three sections. As was mentioned in the previous sections, the shear lag factor is the ratio of the axial force in a corner column to the middle column axial force in each story. It is worth mentioning that shear lag factors above one are referred to as positive shear lag and below one are referred to as negative. In the first part, the effect of lateral load types on the shear lag of framed tube structures is investigated. For this purpose, three types of lateral load including wind load, static earthquake load and dynamic earthquake load were considered to be subjected to the models. In the second section, the effects of plan geometry on the shear lag of tubular structures were studied and three different plan geometries with different heights were analyzed against different lateral loads. In the last section, the effects of height in framed tube structures on shear lag phenomena were discussed without considering any other factors.
4.1. The Effect of Lateral Load Type on Shear Lag of Framed Tube Structures
There was ample evidence from analysis results, which indicated that wind load could distribute forces among the columns more unequally. In most cases, shear lag phenomenon observed in structures subjected to the wind load were more severe than those for structures subjected to the dynamic or static earthquake load. Wind load in comparison with dynamic earthquake load caused a greater positive shear lag factor in almost all models. The positive Shear Lag factor obtained from the wind load for the 20R model was almost 1.5 times greater than the same factor for the same model against the dynamic earthquake load. Negative shear lag intensity of the 20R model against wind load was 1.22 times more than the same model subjected to the dynamic earthquake load. Although positive shear lag factors calculated from structures subjected to the wind load and dynamic earthquake load for 20T and 20H models were almost equal, negative shear lag factors for these structures subjected to the wind load were 39.08% and 21.18% more than the same models subjected to the dynamic earthquake load. The intensity of positive and negative shear lag factors observed from the 40R model subjected to the wind load was higher than the factors calculated from this model against dynamic earthquake load by 19.59% and 33.85%, respectively. The above percentages for 40T model were 3.3% and 25.71% and, for the 40H model, were 0.0% and 5.59%, respectively. This trend was observed for 60- and 80-story structures as well, and shear lag factors in structures subjected to wind load had greater amounts.
Table 3 shows the percentage differences between shear lag obtained from wind load and dynamic earthquake load. The nature of wind load and its distribution and application on the surface of the structure in comparison with the seismic load applied on the center mas of the rigid diagram floors by ETABS could be the reason for the above differences illustrated in
Table 3.
Moreover, although the dynamic analysis shows a more accurate result in comparison with equal static analysis, the shear lag factors for structures subjected to the static earthquake load were also less than those factors for structures subjected to the wind load in more than 80% of the models.
4.2. The Effect of Geometry of Plan on Shear Lag of Framed Tube Structures
Analysis results indicated that the amount of shear lag in framed tube structures could be highly dependent on the plan geometry of the structure. Shear lag diagrams for three types of 80-story framed tube structures subjected to earthquake loads are shown in
Figure 5 and
Figure 6. Although these diagrams are more similar to a straight line in a particular story, the framed tube structure has less shear lag in that story. Diagrams with a minimum in the middle represent the positive shear lag, and those with a maximum in the middle illustrate negative shear lag.
According to these diagrams, it is observed that hexagon shaped plan structures have a better performance in terms of shear lag in comparison with the other two shapes. This structural behavior is in line with a previous study conducted by Awida, who stated that the octagon shape as a plan geometry can be the best in the structural response against wind load in comparison with other possible plan geometries [
30]. Triangular-shaped structures act much better against lateral loads than rectangular ones which have the most inequality of load distribution in their flange columns. In addition, shear lag factors for every 10 stories in all structures were obtained, and the average of positive and negative shear lag factors for each structure was calculated as shown in
Table 4. This table shows a similar trend in the case of shear lag in all structures. For instance, in terms of positive shear lag of a dynamic earthquake load, the 80H model acted 8.2% better than the 80R model. Moreover, the 80T model had 3.6% less shear lag in comparison with 80R. Furthermore, the negative shear lag factor of the 80H and 80T models—23% and 10.2%, respectively—performed better than the 80R model.
To obtain a better understanding of shear lag fluctuation in the models, shear lag factors for odd stories were investigated, and
Figure 7,
Figure 8 and
Figure 9 shows the shear lag factor diagram for 80-story structures for three types of loads. In regard to these Figures, the shear lag factor diagrams for hexagonal-shaped plan structures in most of the stories are close to one, which means shear lag is at a minimum in these types. The shear lag phenomenon that showed up in rectangular-shaped plan structures was the maximum, especially in the first and last 10 stories. Furthermore, triangular-shaped plan structures exhibited a better behavior, in general, in terms of shear lag in comparison with rectangular ones mostly in the top half of the buildings, but still, shear lag in these structures was far higher than framed tube structures with hexagonal plan shape.
Shear lag factors for static earthquake load are also available in
Table 4. A lower positive shear lag up to 13% in the 80H model in comparison with 80R could be observed, and the 80T model had 5.21% less positive shear lag in comparison with 80R. This amount of reduction in negative shear lag was 21.3% for 80H model and 5.4% for 80T model as compared to the 80R model. This tendency could be observed in all the other models.
In addition to the earthquake load, lateral wind load was also applied to the structures in the static analysis method. The behavior in shear lag reduction in this part of analysis is also like previous sections (See
Table 4). For positive shear lag, 80H and 80T specimens—13% and 6%, respectively—behaved better than the 80R model. Likewise, for negative shear lag, the 80H model responded at 24.7%, and the 80T model responded almost 8.2% better than 80R structures.
It is evident that from
Figure 7, the shear lag effect is more intense in the top half of the structures, and this trend was observed in all other models. The shear lag switch-level from positive to negative in 20-story structures is between the 10th to 15th floors, for 40- story structures is between the 25th to 30th floors, for 60-story structures is between the 35th to 40th floors, and for 80-story structures is between the 45th to 50th floors.
4.3. The Effect of Structural Height on Shear Lag of Framed Tube Structures
Structural height in tubular buildings has a direct effect on shear lag phenomenon. As the height of a framed tube structure increases, the positive shear lag in each story will decrease as well.
Table 5 indicates that 20 story structures had the highest positive shear lag factor in all types of plan geometry. This factor decreased as the number of stories increased almost in all the subsequent models. For example, the positive shear lag factor for 20R model against the dynamic earthquake load was 1.99, and this number was 1.19, 1.09 and 1.09 for 40R, 60R and 80R models, respectively. Furthermore, the average of positive shear lag factors for all models subjected to various lateral loads, without considering their plan geometry, is shown in
Table 5. It is observed that positive shear lag factors in taller structures are fewer than this factor in shorter models and has nothing to do with the factor of geometry. In addition, the average of positive shear lag factors without considering any other factor such as load type and plan geometry was calculated. The positive shear lag factor in 20-story structures was 31.91% fewer than in 40-story structures, 37.02% fewer than in 60-story structures and 37.92% fewer than in 80-story structures. It is concluded that the positive shear lag phenomenon has a negative correlation with the height in framed tube structures subjected to any type of lateral load and with any plan geometry.
4.4. Comparison and Verification of the Results
In this study, a 40-story reinforced concrete framed tube building was chosen to compare the Matrix method [
31] and Haji-Kazemi and Company [
13] analyses results. Beams and columns dimensions in this example are 0.8 × 0.8 m. Each story is 3 m in height, and center to center spacing between columns is 2.5 m. The modulus of elasticity and shear modulus of concrete are 20 and 8.0 GPa, respectively. The external load is 120 kN⁄m and uniformly distributed along the height of the structure.
Figure 10 and
Figure 11 show the axial forces in columns of the web and flange of the structure at the base and 10th floor of the framed tube, respectively.
Due to the symmetry of the structure, only half of the web and flange was considered. These diagrams illustrate that the axial forces in corner columns obtained from the proposed model have 9% and 10% difference in comparison with Haji-Kazemi and Company [
13] and the Matrix method [
31], respectively. In all models and analyses, the shear lag phenomenon was positive at lower heights and negative in the upper stories. Specifically, this anomaly was at a minimum in the middle of each structure.
This factor will decrease gradually in upper stories so that shear lag factor in the middle of the structures decreases to 1 which is considered no shear lag. This trend had no change, and the shear lag factor reduced till the last story. In sharp contrast with lower floors, minimum and negative shear lag factors were obvious in the upper stories. The above results are consistent with the previous studies [
6].
5. Conclusions
This study investigated the effect of lateral load type, plan geometry and height on shear lag behavior of framed tube structures. For this goal, 12 models in four different heights and three different plan geometry against three different load types were considered. From the structural analyses performed, it could be concluded that:
(1) Type of the lateral load could affect the distribution of forces in peripheral columns in tubular structures. Wind load caused a greater amount of positive shear lag in comparison with the dynamic earthquake load and the static earthquake load by 9% and 7.5%, respectively. These numbers for negative shear lag were 14% and 1.5%, respectively. In regard to the importance of wind load in the design of high-rise structures and the severity of shear lag in framed tube structures designed based on it, the above results should be seriously considered by structural designers.
(2) Shear lag phenomenon could be affected significantly by the geometry plan in framed tube structures. Hexagon shaped plan structures had a reasonable behavior against lateral loads. Specifically, the average of positive and negative shear lag factors in the three types of analyses were 28.76%, and 25% less in hexagon shaped plan structures, respectively, in comparison with the control model (rectangular-shaped plan). This superiority may lead the structures towards being more laterally load resistant, of lighter weight and more economical due to its equal load distribution in the whole frame.
(3) Rectangular-shaped plan structures had the most inequality of axial force distribution in the flange frame columns. In the above mentioned structures, the average of positive shear lag rose to near two and even more and the average of negative shear lag fell down to below 0.5 in some cases. These amounts of shear lag are not evident in any other shaped plans.
(4) The structures with triangular-shaped plan had almost the same amount of shear lag with rectangular-shaped plan structures in shorter buildings, but the triangular plan had a better behavior in terms of shear lag than the rectangular plan in taller structures. The triangular performed almost 5% better, in the case of positive, and 8.4% in the case of negative shear lag on average in comparison with the rectangular-shaped plan.
(5) Shear lag of framed tube structures is highly affected by the height of the structure. Column axial forces were distributed more unequally in shorter structures, and taller buildings had smaller amount of shear lag factors. It can be concluded that in taller buildings, the structural behavior of the box-shaped cantilever beam that represents the whole building is more similar to Euler–Bernoulli beam than the shorter building and, as it is known from theory of structures, the effect of shear lag in Euler–Bernoulli cantilever beams (taller buildings) is lower than the shorter ones.