Next Article in Journal
Study of Dynamic Evolution of the Shear Band in Triaxial Soil Samples Using Photogrammetry Technology
Previous Article in Journal
Salinity Stress and the Influence of Bioinoculants on the Morphological and Biochemical Characteristics of Faba Bean (Vicia faba L.)
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Simulation-Based Comparison of PID with Sliding Mode Controller for Matrix-Converter-Based Dynamic Voltage Restorer under Variation of System Parameters to Alleviate the Voltage Sag in Distribution System

by
Abdul Hameed Soomro
1,*,
Abdul Sattar Larik
2,
Mukhtiar Ahmed Mahar
2 and
Anwar Ali Sahito
2
1
Department of Electrical Engineering, Nawabshah Campus, Quaid-e-Awam University of Engineering Science & Technology, Larkano 77150, Pakistan
2
Department of Electrical Engineering, Mehran University of Engineering & Technology, Jamshoro 76090, Pakistan
*
Author to whom correspondence should be addressed.
Sustainability 2022, 14(21), 14661; https://doi.org/10.3390/su142114661
Submission received: 27 September 2022 / Revised: 28 October 2022 / Accepted: 3 November 2022 / Published: 7 November 2022

Abstract

:
A constant power supply is a basic need for each consumer due to the increase in sensitive equipment day by day. As per IEEE standards, a 10% reduction in voltage from the supply voltage is not acceptable and may cause the failure of equipment. Previously, different techniques have been used to alleviate the voltage sag, such as STATCOM, DSTATCOM, SVC, and shunt capacitors, but these devices are connected in parallel, which compensates for the low value of voltage sag, and they have high maintenance costs involved. Compensation for the low and high values of voltage sag is possible through a series-connected device such as a dynamic voltage restorer. In this paper, a matrix converter is presented for DVR to convert AC to AC voltage directly and free from batteries, capacitors, and multiple conversions as needed in a voltage source inverter, resulting in a reduced cost of DVR topology. The DVR is meaningless in the absence of a controller, so it is necessary to select a suitable controller for the satisfactory operation of the DVR under a variation of system parameters. In this paper, the performance of a linear PID controller is analyzed and compared with a nonlinear controller, such as a sliding-mode controller, under variation of power system parameters inorder to select a robust controller that performs satisfactorily for DVR. Earlier trial-and-error methods were used to obtain the parameters of PID gains, but they require a large time to obtain the parameters of the PID gains and there is a chance of inaccuracy. A genetic algorithm was used to obtain the gain parameters, but it has more convergence time and the particle swarm optimization technique has involves less reliability. In this research paper, the sliding surface coefficient parameters such as and Ki for the PI sliding surface of SMC and PID gains are taken through an ant colony algorithm to obtain the robustness of the controllers. The purpose of this paper is to introduce the best DVR topology with reduced cost. MATLAB simulation software was utilized to analyze the performance of the DVR with PID and SMC controllers under different fault conditions and also the THD% of proposed controllers was analyzed through FFT.

1. Introduction

A constant power supply is a basic need for each consumer due to the increase in sensitive equipment day by day [1]. As per IEEE standards, a reduction in voltage from 10%of the supply voltage is not acceptable and may cause the failure of equipment and revenue loss [2]. The researchers present the different types of FACT devices such as SVC, STATCOM, and shunt capacitors for voltage sag alleviation [3], but they are shunt-connected devices, involve high maintenance cost, and also alleviate the low value of the voltage sag, which are the drawbacks of these devices [4]. Active and reactive powers are needed for the alleviation of the low and high value of sag voltage [5], which is only possible through the application of a series-connected device [1]. The dynamic voltage restorer (DVR) is connected in series with the load in order to compensate the voltage sags of small and large value [6]. The researchers present DVR topologies supported with batteries and capacitors for the supply of DC power to the inverter circuit of the DVR [7], but the drawbacks of these topologies is the high cost of maintenance and replacement [8]. In battery-supported DVRs, the multiple conversion of power supply is needed, which increases the complexity of the system [9]. In this paper, a matrix converter is presented which is free from batteries, capacitors, and multiple conversions [10]. It converts AC to AC voltage directly [11], which results in the low cost and less complexity of the DVR topology [12]. The DVR is meaningless in the absence of a controller [4], so it is necessary to select a suitable controller for the satisfactory operation of the DVR under normal conditions as well as for variation of system parameters [7]. In the past, various DVR topologies were presented, such as PID controller with voltage source inverter [13], PID controller with matrix converter [14], and PID controller with PV based voltage source inverter [15],but the control approach of a PID controller is not fit for DVR topologies under variation of power system parameters because the PID controller is a linear controller [14] and the selection of PID controller under fault conditions [14] for DVR topology is questionable. Earlier, a sliding mode controller with a voltage source inverter [7] was presented, but the drawback of such a topology is that it involves high maintenance and replacement cost for the DVR topology due to the utilization of an energy storage device for an inverter circuit [8] to convert DC into AC, and involving multiple conversions [5]. A sliding mode controller with AC chopper [16] was presented to control the dynamics of the DVR, but the drawback is that an AC chopper cannot control the output frequency as a matrix converter [17]. DVR topology with a matrix converter and the control strategy of a sliding mode controller has not been presented [10]. The performance of a DVR topology with a matrix converter and the control strategy of a PID controller is analyzed and compared with a nonlinear controller such as a sliding mode controller under system parameter variations under fault conditions. Different types of techniques were used by researchers [18,19] to obtain the values of the PID gains, and the traditional PID controller is mainly tuned with the Ziegler–Nichols method [20]. In this method, more time is spent to obtain the values of the PID gains and sometimes the generated values give results with large overshoot [21]; therefore, retuning is necessary before applying the control to the device [22]. Pole placement and Cohen–Coon methods can be utilized to obtain the values of PID gains, but they depend on low-order model estimations [23], if a real-coded genetic algorithm is used the convergence time is greater [24], and the PSO technique is less reliable [25,26]. It is necessary to control the operation of DVR to select the optimum values of the sliding surface coefficient parameters such as Kp and Ki for the PI sliding surface of SMC [27] and the tuning parameters for the PID controller. An iterative method, such as the Ant colony algorithm [28], is the best choice [29] in order to save time, reduce insecurity, and provide more reliability [29]. In this paper, the parameters of a PI sliding surface for SMC and PID gains are taken through an ant colony algorithm [30] to obtain the robustness of the controller. The purpose of this paper is to introduce the DVR topology of less cost with a robust controller in order to perform satisfactorily under variation of system parameters. MATLAB simulation software is utilized to analyze the performance of the DVR with PID and SMC controllers under different fault conditions and the THD% of proposed controllers is analyzed through FFT.

2. Dynamic Voltage Restorer

The dynamic voltage restorer is connected in series with the sensitive load in order to inject the required voltage in case of voltage sag [1]. The matrix converter, LC filter, voltage injection transformer, conventional PID controller, and a sliding mode controller are the components of the proposed DVR as shown in Figure 1. The matrix converter converts AC to AC voltage directly [10]. In this paper a three-phase matrix with space vector modulation technique is proposed to control the switching sequence of the matrix converter [31]. A distorted waveform is achieved in the output of matrix converter [32] because semiconductor switches are available in the matrix converter [33]. The problem of distorted waveforms can be avoided by the addition of a filter circuit [34]. The main cause of the addition of the voltage injection transformer is to inject the necessary voltage to the sensitive load in the case of sag voltage [4,12]. The PID and SMC controllers are used to control the dynamics of DVR under nonlinearities.

2.1. Matrix Converter

In this research paper, a three-phase matrix converter device is utilized. It consists of nine bidirectional IGBT switches that are connected in such a way that they form a matrix [17]. It has the capability to convert AC to AC voltage directly and free from an energy storage device, charge up circuit, and multiple conversions [11], which results in reduced cost and less maintenance. Figure 2 shows the direct three-phase matrix switches with common source configurations; in each phase, three switches are connected. The load is connected to check the performance of the converter. Bidirectional switches must be connected in such a way that the input voltage and current are connected with the output voltage and current for the proper commutation sequence [35]. A matrix converter has high-quality input current signals, controllable input power factor, and compact design. DVR topology utilizes the direct matrix converter and obtains the compensation energy from the same power supply for the balanced and unbalanced disturbances [36].

2.2. Park Transformation

Direct-quadrature-zero ( d q o ) transformation is also called Park transformation, which is presented mathematically for the simplicity of controller design and easy analysis of the electrical engineering problems concerned with the three-phase system [37]. In this technique, electrical quantities of three phases are reduced to two-phase electrical quantities. As shown in Figure 3, in the first step, three-phase voltages/currents are given to the a b c / α β block and are in line with the phase lock loop and converted to   α β / d q . The reference and actual values are added and difference is sent to the control circuit, after which the d q components are converted to α β , and finally α β   is converted into abc and the PWM signal is sent to the converter for the operation of the switches [4].

2.3. Voltage Injection Technique

The voltage injection technique is necessary for DVR topology because the value of voltage and phase angle change after the occurrence of voltage sag [5]. A pre-sag voltage injection technique is shown in Figure 4 and proposed in this paper because the phase angle and magnitude remain the same in this technique and the load is free from voltage disturbance [4].
In the pre-sag voltage injection technique, when voltage sag is detected, the DVR will come into its active mode and the needed voltage will be provided to the load [4]. In the case of voltage sag, the phase angle shift δ = 0 and
V I N J = V P r e s a g V P o s t s a g
where
  • V I N J is the injection voltage.
  • V P r e s a g is the pre-sag voltage.
  • V s is the supply voltage.
  • V L is the load voltage.
The needed power is calculated through the Equation (2):
P I N J = 3 V I N J I L + cos θ L + θ I N J

3. Control Circuit for DVR Topology

The control circuit is very essential for the topology of DVR; without the control circuit, the topology of DVR is meaningless [4,17], so proper selection of a controller is necessary for the operation of DVR under balanced and unbalanced conditions. The PID controller is mostly preferred for steady state conditions [21,38] but fails in the case of fault conditions [4]. In a PID controller, the proportional gain helps to reduce the error response, integral gain eliminates the steady state error, and the derivative gain improves the stability of the system [39]. The performance indexes of the PID controller depend on the four parameters such as overshoot, settling time, rise time, and integer absolute error. PI and PID controllers have been used for the topology of the DVR, but they have well known limitations under variations of system parameters and take a long time in settling [4,7,37,39,40]. A sliding mode controller is a non-linear controller with more advantages such as stability under parameter variations, robustness, good dynamic response, and ease of implementation [7,16]. SMC design depends on the switching function and control law [41]. A fast switching response is essential to move the system variables to zero.
The equation for a sliding mode controller is given in Equation (3).
u = s i g n S
S = X ˙ + a . X
where S = 0 and a is the variable
X ˙ = a . X
The sliding phase/surface in which the system slides and makes the system variable to reach at zero S < 0 .   The reachability phase is simple, as it says that any controller that satisfies the condition S S ˙ < 0   will reach the sliding surface and be known as the reachability phase, but due to the inertia of the system, the reachable phase is not equal to zero S > 0   and chatter with back-and-forth motion along the sliding surface, which is known as chattering or oscillations, is shown in Figure 5. The problem of chattering can be avoided by using a hysteresis band [7]. The S ˙ S are opposite to each other with   S = 1   a n d   S ˙ = 1 and δ t is the switching function of the matrix converter, either 1 or −1, as given in Equation (6).
δ t = 1 O N t i m e f o r S < 0 1 O F F t i m e f o r S < 0
when the SMC slides and the system variable reaches zero, then the system will be stable [42].
u f = V d . s i g n S
where u f   is   the   control input to the matrix converter and V d is the DVR voltage.
The sliding surface is calculated through Equation (8),
S t = K p e + K i d i d t e
where e is the error, and K p ,   K i are the PI gains.
State space formulation was utilized in the sliding mode, but now a day’s hysteresis relay is commonly used for the sliding mode because this technique is simple and easy to implement [7]. Therefore, a hysteresis relay sliding mode is selected in this research paper.

4. Ant Colony Algorithm

An ant colony algorithm is an advanced empirical bionic algorithm [42]. In this algorithm, the ants are moving from the nest to the food center and select the smallest path through the sensing of pheromones [30]. As shown in Figure 6a, the ants meet at a point and have no idea how to select the shortest way to reach the food center [43]. There are two tracks, one on the upper side and the other on the lower side, so half the ants move to the upper track and half the ants move to the lower track [42].As shown in Figure 6b,c, assuming that the speed of ants moving is the same, the distance upto the food center is smaller through the upper track and greater through the lower track, and ants select the regular path to accumulate pheromones faster [19]. After a short period of time, it has seen that large quantities of pheromones are accumulated through the upper track and a smaller quantity of pheromones are accumulated through the lower track by the ants [30], as shown in Figure 6d. The large quantity of pheromones help the new ants that want to move towards the food center [29]; in this way all ants will move through the shorter track [42].

4.1. Cost Function

The following three cost functions are suggested for the tuning of the PID controller [44]. The first cost function is given in Equation (9), and through this we can reduce the integrated square error.
f 1   = 0 ( e t d t ) 2
The second cost function is given in Equation (10). In this cost function the rise time, maximum overshoot, steady state error and the settling time are summed up and the sum of these will be utilized to assess the second cost function.
f 2   = 1 C 1   t r t r d + C 2   M p M p d + C 3   t s t d s + C 4 e s s e s s d
The third cost function is given in Equation (11). The design of the PID controller depends on this cost function [42]. The rise time, settling time, overshoot and steady state mainly depend on the selection of the beta, and the value of β is 0.2.
f 3   = 1 1 e β M p + e s s + e β t s t r

4.2. Parameters for ACO

The PID and SMC controllers are designed with ACO technique to choose the better values of the PID gains and sliding surface coefficient parameters such as Kp and Ki for the PI sliding surface of SMC in order to achieve the robustness of the controller and small transient response [30]. In this paper, 50 ants and 50 iterations with 0.8 and 0.2 values of Alpha (α) and Beta (β) are selected with 1000 nodes in an ant colony optimization technique. All the computation was carried out through MATLAB Simulink software.

4.3. Parameters of Controller Gains

Table 1 shows the parameters of controller gains as taken through the ant colony optimization technique.

5. Proposed Power System with Simulation Results

The parameters of Table 2 were utilized in an electrical power distribution system with the proposed DVR, as shown in Figure 7. The performance of DVR under different fault conditions is analyzed with application of the PID and SMC controller through MATLAB Simulation software.

5.1. MATLAB Simulation Results

5.1.1. Case1: Three Phase-to-Ground Fault with PID Controller

In case1, faults occurred in all three phases and voltage was reduced to 70% of the supply voltage. In this case the DVR comes into voltage injection mode and adds the required voltage to the load; the supply voltage is shown in Figure 8a, the load current is shown in Figure 8b, the load voltage is shown in Figure 8c, and the voltage injected by DVR is shown in Figure 8d. It is seen that the output load current and voltage increases beyond normal values and the PID controller settled at time of 0.04 s.

5.1.2. Case2: Double Line-to-Ground Faults with PID Controller

In case 2, phases B and C are under fault and phase A is in healthy condition, then the voltage in phases B and C is reduced to 70% of the supply voltage. In this case, the DVR comes into voltage injection mode and adds the necessary voltage to the load; the supply voltage is shown in Figure 9a, the load current is shown in Figure 9b, load voltage is shown in Figure 9c, and the voltage injected by the DVR is shown in Figure 9d. It is seen that the output load current and voltage increase beyond normal values and the PID controller settled at the time of 0.04 s.

5.1.3. Case3: Three Phase-to-Ground faults with SMC Controller

In case3, faults occur in all three phases and the voltage is reduced to 70% of the supply voltage. In this case the DVR comes into voltage injection mode and adds the required voltage to the load; the supply voltage is shown in Figure 10a, the load current is shown in Figure 10b, the load voltage is shown in Figure 10c, and the voltage injected by the DVR is shown in Figure 10d. It is seen that the output load current and voltage are maintained with normal values and the controller settled at the time from where the fault time started, i.e., 0.02 s.

5.1.4. Case4: Double Line-to -Ground fault with SMC Controller

In case-4, phases B and C are under fault and phase A is in healthy condition, then the voltage in two phases, B and C, is reduced to 70% of the supply voltage. In this case the DVR comes into voltage injection mode and adds the necessary voltage to the load; the supply voltage is shown in Figure 11a, the load current is shown in Figure 11b, the load voltage is shown in Figure 11c, and the voltage injected by the DVR is shown in Figure 11d. It seen that the output load current and voltage are maintained with normal values and the controller settled at the time when the fault started, i.e., 0.02 s.

6. Total Harmonic Distortion (THD%)

THD% analysis at the output of the load voltage is a very important factor for the assessment of power quality in the power distribution system. The allowable value of THD% is 5% as per IEEE standard 519-1992 [7]. The THD% of the proposed system was analyzed through FFT. The total harmonic distortion in the output of load voltage without the proposed topology of the DVR under fault conditions is shown in Figure 12a. In this condition, the THD% is 44.28% of the fundamental frequency. The total harmonic distortion in the output of load voltage is analyzed through FFT with the proposed topology of the DVR with a PID controller is shown in Figure 12b, and which is 12.41% of the fundamental frequency. The total harmonic distortion in the output of the load voltage is analyzed through FFT with the proposed topology of DVR with a SMC controller is shown in Figure 12c and which is 1.99% of the fundamental frequency.

7. Discussion

It is seen from the simulation results of DVR topology with a PID controller that the proposed control approach is not fit for the topology of DVR under fault conditions due to large overshoots in the voltage and current and a settling time that starts at 0.04 s, which may result in equipment failure, stoppage of machines, and revenue loss because most of the equipment is very sensitive and cannot accept the small variation in voltage. The THD% of the PID controller with the proposed DVR is 12.41% of the fundamental frequency, which is not acceptable as per IEEE standards. It is seen in the simulation results of DVR topology with SMC that there is no overshoot in the voltage, and also the THD% is 1.98%, which is within the limit as per IEEE standards. The performance of both controllers is tabulated in Table 3.

8. Conclusions

The DVR topology with direct AC to AC matrix converter and control application of linear controller (PID) and nonlinear controller (SMC) is discussed and the performance of the DVR is analyzed through MATLAB simulation software under different fault conditions, and the THD% is analyzed with FFT. For the robustness of the controllers, the parameters of the PI sliding surface for SMC and PID gains were taken through an ant colony algorithm. It is seen from the simulations and THD% results that the PID controller is not a fit controller for the topology of DVR under system parameters variation due to the large overshoot in current and voltage, as well as the greater time expenditure in settling and the fact that the THD% is not acceptable as per IEEE standards. Therefore, it is seen that the performance of the nonlinear controller (SMC) is satisfactory under parameter variation and the THD% is also within the limit as per IEEE standards. It is concluded that the DVR topology based on a matrix converter and the control approach of a sliding mode controller is the best DVR topology under system parameter variations. This DVR topology has no need for energy storage devices, charge up circuits, and multiple conversions, which results in less cost due to the direct conversion of AC to AC voltage is carried out through the matrix converter.

Author Contributions

Conceptualization, Methodology, and Investigation A.H.S.; Data curation, and Formal analysis A.S.L.; Validation, and supervision M.A.M.; Software, and Writing, review & editing A.A.S. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

All data are contained within the article.

Acknowledgments

The authors would like to thank QUEST, Nawabshah, Pakistan and MUET, Jamshoro, Pakistan for the research facility provided.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Farooqi, A.; Othman, M.M.; Radzi, M.A.M.; Musirin, I.; Noor, S.Z.M.; Abidin, I.Z. Dynamic voltage restorer (DVR) enhancement in power quality mitigation with an adverse impact of unsymmetrical faults. Energy Rep. 2022, 8, 871–882. [Google Scholar] [CrossRef]
  2. Patel, N.; Gandhi, K.; Mahida, D.; Chudasama, P. A review on power quality issues and standards. Int. Res. J. Eng. Technol. 2017, 4, 247–250. [Google Scholar]
  3. Adware, R.; Chandrakar, V. Comprehensive Analysis of STATCOM with SVC for Power Quality Improvement in Multi Machine Power System. In Proceedings of the 2022 2nd International Conference on Power Electronics & IoT Applications in Renewable Energy and Its Control (PARC), Mathura, India, 21–22 January 2022; pp. 1–5. [Google Scholar]
  4. Soomro, A.H.; Larik, A.S.; Mahar, M.A.; Sahito, A.A.; Soomro, A.M.; Kaloi, G.S. Dynamic Voltage Restorer—A comprehensive review. Energy Rep. 2021, 7, 6786–6805. [Google Scholar] [CrossRef]
  5. Tang, L.; Han, Y.; Yang, P.; Wang, C.; Zalhaf, A.S. A review of voltage sag control measures and equipment in power systems. Energy Rep. 2022, 8, 207–216. [Google Scholar] [CrossRef]
  6. Hassanein, W.S.; Ahmed, M.M.; el-Raouf, M.O.a.; Ashmawy, M.G.; Mosaad, M.I. Performance improvement of off-grid hybrid renewable energy system using dynamic voltage restorer. Alex. Eng. J. 2020, 53, 1567–1581. [Google Scholar] [CrossRef]
  7. Zahra, S.T.; Khan, R.U.; Ullah, M.F.; Begum, B.; Anwar, N. Simulation-based analysis of dynamic voltage restorer with sliding mode controller at optimal voltage for power quality enhancement in distribution system. Electr. Eng. Electromech. 2022, 1, 64–69. [Google Scholar] [CrossRef]
  8. Pattanaik, B.; Hussain, S.M.; Karthikeyan, V.; Samuel, G.G. Energy storage system with dynamic voltage restorer integrated for wind energy system. J. Phys. Conf. Ser. 2021, 1964, 042098. [Google Scholar]
  9. Zhan, C.; Ramachandaramurthy, V.K.; Arulampalam, A.; Fitzer, C.; Kromlidis, S.; Bames, M.; Jenkins, N. Two electrical models of the lead–acid battery used in a dynamic voltage restorer. IEE Proc. Gener. Transm. Distrib. 2003, 150, 175–182. [Google Scholar] [CrossRef]
  10. Khanday, S.A.; Sekhar, O.C.; Mir, T.N. Comparative Study of Three Phase AC/AC In-direct Matrix Converters: A Review. In Proceedings of the 2022 International Conference for Advancement in Technology (ICONAT), Goa, India, 21–22 January 2022; pp. 1–6. [Google Scholar]
  11. Diaz, M.; Cardenas, R.; Espinoza, M.; Rojas, F.; Mora, A.; Clare, J.C.; Wheeler, P. An overview of applications of the modular multilevel matrix converter. Energies 2020, 13, 5546. [Google Scholar] [CrossRef]
  12. Lozano, J.M.; Ramirez, J.M.; Correa, R.E. A novel dynamic voltage restorer based on matrix converters. In Proceedings of the 2010 Modern Electric Power Systems, Wroclaw, Poland, 20–22 September 2010; pp. 1–7. [Google Scholar]
  13. Ramasamy, M.; Thangavel, S. Experimental verification of PV based dynamic voltage restorer (PV-DVR) with significant energy conservation. Int. J. Electr. Power Energy Syst. 2013, 49, 296–307. [Google Scholar] [CrossRef]
  14. Rosli, E.; Mustapa, R.; Hidayat, M.; Noor, S.M.; Hamzah, N. Modeling and analysis of applying single phase matrix converter in dynamic voltage restorer. In Proceedings of the 2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO), Langkawi, Malaysia, 3–4 June 2013; pp. 523–528. [Google Scholar]
  15. Yi, T.Q.; Kasilingam, G.; Raguraman, R. Effect of PID power system stabilizer for a synchronous machine in simulink environment. In Proceedings of the IOP Conference Series: Earth and Environmental Science, Putrajaya, Malaysia, 5–6 March 2013; p. 012025. [Google Scholar]
  16. Nasrollahi, R.; Farahani, H.F.; Asadi, M.; Farhadi-Kangarlu, M. Sliding mode control of a dynamic voltage restorer based on PWM AC chopper in three-phase three-wire systems. Int. J. Electr. Power Energy Syst. 2022, 134, 107480. [Google Scholar] [CrossRef]
  17. Zhang, J.; Li, L.; Dorrell, D.G. Control and applications of direct matrix converters: A review. Chin. J. Electr. Eng. 2018, 4, 18–27. [Google Scholar]
  18. Jensi, R.; Jiji, G.W. An enhanced particle swarm optimization with levy flight for global optimization. Appl. Soft Comput. 2016, 43, 248–261. [Google Scholar] [CrossRef]
  19. Duan, H.-b.; Wang, D.-b.; Yu, X.-f. Novel approach to nonlinear PID parameter optimization using ant colony optimization algorithm. J. Bionic Eng. 2006, 3, 73–78. [Google Scholar] [CrossRef]
  20. Hang, C.C.; Åström, K.J.; Ho, W.K. Refinements of the Ziegler–Nichols tuning formula. IIEE Proc. D Control. Theory Appl. 1991, 138, 111–118. [Google Scholar] [CrossRef]
  21. Shah, P.; Agashe, S. Review of fractional PID controller. Mechatronics 2016, 38, 29–41. [Google Scholar] [CrossRef]
  22. Jaleel, J.A.; Thanvy, N. A comparative study between PI, PD, PID and lead-lag controllers for power system stabilizer. In Proceedings of the 2013 International Conference on Circuits, Power and Computing Technologies (ICCPCT), Nagercoil, India, 20–21 March 2013; pp. 456–460. [Google Scholar]
  23. Arunraja, A.; Jayanthy, S. Tuning methods of various controllers. Mater. Today Proc. 2021. [Google Scholar] [CrossRef]
  24. Sundarabalan, C.; Selvi, K. Compensation of voltage disturbances using PEMFC supported Dynamic Voltage Restorer. Int. J. Electr. Power Energy Syst. 2015, 71, 77–92. [Google Scholar] [CrossRef]
  25. Kassarwani, N.; Ohri, J.; Singh, A. Performance analysis of dynamic voltage restorer using improved PSO technique. Int. J. Electron. 2019, 106, 212–236. [Google Scholar] [CrossRef]
  26. Zhou, Y.T.; Nie, J.B.; Han, N.; Chen, C.; Yue, Z.F. Study on PID parameters tuning based on particle swarm optimization. In Advanced Materials Research; Trans Tech Publications Ltd.: Zurich, Switzerland, 2013; pp. 432–438. [Google Scholar]
  27. Soon, C.C.; Ghazali, R.; Jaafar, H.I.; Hussien, S.Y.S. Sliding mode controller design with optimized PID sliding surface using particle swarm algorithm. Procedia Comput. Sci. 2017, 105, 235–239. [Google Scholar] [CrossRef]
  28. Benachaiba, C.; Mazari, B.; Tandjaoui, M.; Haidar, A. Power quality enhancement using DVR based on ant colony controller. In Proceedings of the 2016 57th International Scientific Conference on Power and Electrical Engineering of Riga Technical University (RTUCON), Riga, Latvia, 13–14 October 2016; pp. 1–4. [Google Scholar]
  29. Bristow, D.A.; Tharayil, M.; Alleyne, A.G. A survey of iterative learning control. IEEE Control. Syst. Mag. 2006, 26, 96–114. [Google Scholar]
  30. Dorigo, M.; Birattari, M.; Stutzle, T. Ant colony optimization. IEEE Comput. Intell. Mag. 2006, 1, 28–39. [Google Scholar] [CrossRef]
  31. Omar, R.; Rahim, N. Implementation and control of a dynamic voltage restorer using Space Vector Pulse Width Modulation (SVPWM) for voltage sag mitigation. In Proceedings of the 2009 International Conference for Technical Postgraduates (TECHPOS), Kuala Lumpur, Malaysia, 14–15 December 2009; pp. 1–6. [Google Scholar]
  32. Helle, L.; Larsen, K.B.; Jorgensen, A.H.; Munk-Nielsen, S.; Blaabjerg, F. Evaluation of modulation schemes for three-phase to three-phase matrix converters. IEEE Trans. Ind. Electron. 2004, 51, 158–171. [Google Scholar] [CrossRef]
  33. Casadei, D.; Serra, G.; Tani, A.; Zarri, L. Matrix converter modulation strategies: A new general approach based on space-vector representation of the switch state. IEEE Trans. Ind. Electron. 2002, 49, 370–381. [Google Scholar] [CrossRef]
  34. Li, D.; Wang, T.; Pan, W.; Ding, X.; Gong, J. A comprehensive review of improving power quality using active power filters. Electr. Power Syst. Res. 2021, 199, 107389. [Google Scholar] [CrossRef]
  35. Malekjamshidi, Z.; Jafari, M.; Zhu, J.; Xiao, D. Bidirectional power flow control with stability analysis of the matrix converter for microgrid applications. Int. J. Electr. Power Energy Syst. 2019, 110, 725–736. [Google Scholar] [CrossRef]
  36. Merchan-Villalba, L.R.; Lozano-Garcia, J.M.; Avina-Cervantes, J.G.; Estrada-Garcia, H.J.; Pizano-Martinez, A.; Carreno-Meneses, C.A. Linearly decoupled control of a dynamic voltage restorer without energy storage. Mathematics 2020, 8, 1794. [Google Scholar] [CrossRef]
  37. Faisal, M.; Alam, M.S.; Arafat, M.I.M.; Rahman, M.M.; Mostafa, S.M.G. PI controller and park’s transformation based control of dynamic voltage restorer for voltage sag minimization. In Proceedings of the 2014 9th International Forum on Strategic Technology (IFOST), Cox’s Bazar, Bangladesh, 21–23 October 2014; pp. 276–279. [Google Scholar]
  38. Chauhan, A.; Thakur, P. Power Quality Issues and Their Impact on the Performance of Industrial Machines; Anchor Academic Publishing: Hamburg, Germany, 2016. [Google Scholar]
  39. Singh, S.; Mitra, R. Comparative analysis of robustness of optimally offline tuned PID controller and Fuzzy supervised PID controller. In Proceedings of the 2014 Recent Advances in Engineering and Computational Sciences (RAECS), Chandigarh, India, 6–8 March 2014; pp. 1–6. [Google Scholar]
  40. EAl-Ammar, A.; Ul-Haq, A.; Iqbal, A.; Jalal, M.; Anjum, A. SRF based versatile control technique for DVR to mitigate voltage sag problem in distribution system. Ain Shams Eng. J. 2020, 11, 99–108. [Google Scholar] [CrossRef]
  41. Biricik, S.; Komurcugil, H.; Tuyen, N.D.; Basu, M. Protection of sensitive loads using sliding mode controlled three-phase DVR with adaptive notch filter. IEEE Trans. Ind. Electron. 2018, 66, 5465–5475. [Google Scholar] [CrossRef]
  42. Hsiao, Y.-T.; Chuang, C.-L.; Chien, C.-C. Ant colony optimization for designing of PID controllers. In Proceedings of the 2004 IEEE International Conference on Robotics and Automation (IEEE Cat. No. 04CH37508), New Orleans, LA, USA, 2–4 September 2004; pp. 321–326. [Google Scholar]
  43. Dorigo, M.; Gambardella, L.M. Ant colony system: A cooperative learning approach to the traveling salesman problem. IEEE Trans. Evol. Comput. 1997, 1, 53–66. [Google Scholar] [CrossRef] [Green Version]
  44. Mohamed, A. Optimization Techniques for Tuning the Controller of a Permanent Magnet Brushless Motor. Master’s Thesis, Helwan University, Helwan, Egypt, 2012. [Google Scholar]
Figure 1. Proposed DVR.
Figure 1. Proposed DVR.
Sustainability 14 14661 g001
Figure 2. Direct three-phase matrix converter.
Figure 2. Direct three-phase matrix converter.
Sustainability 14 14661 g002
Figure 3. Coordinated dqo transformation.
Figure 3. Coordinated dqo transformation.
Sustainability 14 14661 g003
Figure 4. Proposed voltage injection technique.
Figure 4. Proposed voltage injection technique.
Sustainability 14 14661 g004
Figure 5. Phase plot of SMC.
Figure 5. Phase plot of SMC.
Sustainability 14 14661 g005
Figure 6. (ad) Movements of ants from nest to food center.
Figure 6. (ad) Movements of ants from nest to food center.
Sustainability 14 14661 g006
Figure 7. Single line diagram of distribution system with proposed DVR.
Figure 7. Single line diagram of distribution system with proposed DVR.
Sustainability 14 14661 g007
Figure 8. (a) Supply voltage during three phase-to-ground-faults with PID controller. (b) Load current during three phase-to-ground-faults with PID controller. (c) Load voltage during three phase-to-ground-faults with PID controller. (d) Voltage injected by DVR during three phase-to-ground-faults with PID controller.
Figure 8. (a) Supply voltage during three phase-to-ground-faults with PID controller. (b) Load current during three phase-to-ground-faults with PID controller. (c) Load voltage during three phase-to-ground-faults with PID controller. (d) Voltage injected by DVR during three phase-to-ground-faults with PID controller.
Sustainability 14 14661 g008
Figure 9. (a) Supply voltage during double line-to-ground faults with PID controller. (b) Load current during double line-to-ground fault with PID controller. (c) Load voltage during double line-to-ground fault with PID controller. (d) Voltage injected by DVR during double line-to-ground fault with PID controller.
Figure 9. (a) Supply voltage during double line-to-ground faults with PID controller. (b) Load current during double line-to-ground fault with PID controller. (c) Load voltage during double line-to-ground fault with PID controller. (d) Voltage injected by DVR during double line-to-ground fault with PID controller.
Sustainability 14 14661 g009
Figure 10. (a) Supply voltage during three phase-to-ground faults with SMC controller. (b) Load current during three phase-to-ground fault with SMC controller. (c) Load voltage during three phase-to-ground fault with SMC controller. (d) Voltage injected by DVR during three phase-to-ground fault with SMC controller.
Figure 10. (a) Supply voltage during three phase-to-ground faults with SMC controller. (b) Load current during three phase-to-ground fault with SMC controller. (c) Load voltage during three phase-to-ground fault with SMC controller. (d) Voltage injected by DVR during three phase-to-ground fault with SMC controller.
Sustainability 14 14661 g010
Figure 11. (a) Supply voltage during double line-to-ground faults with SMC controller. (b) Load current during double line-to-ground fault with SMC controller. (c) Load voltage during double line-to-ground fault with SMC controller. (d) Voltage injected by DVR during double line-to-ground fault with SMC controller.
Figure 11. (a) Supply voltage during double line-to-ground faults with SMC controller. (b) Load current during double line-to-ground fault with SMC controller. (c) Load voltage during double line-to-ground fault with SMC controller. (d) Voltage injected by DVR during double line-to-ground fault with SMC controller.
Sustainability 14 14661 g011
Figure 12. (a) THD% during fault conditions without DVR. (b) THD% with PID controller. (c) THD% with SMC controller.
Figure 12. (a) THD% during fault conditions without DVR. (b) THD% with PID controller. (c) THD% with SMC controller.
Sustainability 14 14661 g012
Table 1. Parameters of controller gains.
Table 1. Parameters of controller gains.
S.NoParameterValue
1Proportional gain6.87688
2Integral gain0.85085
3Derivative gain10
Table 2. Power system and DVR parameters.
Table 2. Power system and DVR parameters.
S.NoParameterValue
1Source voltage11 KV
2Step-down transformer11 KV/400 V
3Resistance of the line0.789
4Inductance of the line15.48 × 10−6
5Load (3-phase)5 KW
6Filter inductance4.5 mH
7Filter capacitance2 µF
Table 3. Performance of Controllers with Proposed DVR Topology.
Table 3. Performance of Controllers with Proposed DVR Topology.
ParametersPID ControllerSMC Controller
Supply voltage327v327v
Sag voltage227v227v
Rise time0.025 s-
Settling time0.04 s0.02 s
Overshoot in voltage173v-
Overshoot in load current5 A-
THD%12.41%1.98%
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Soomro, A.H.; Larik, A.S.; Mahar, M.A.; Sahito, A.A. Simulation-Based Comparison of PID with Sliding Mode Controller for Matrix-Converter-Based Dynamic Voltage Restorer under Variation of System Parameters to Alleviate the Voltage Sag in Distribution System. Sustainability 2022, 14, 14661. https://doi.org/10.3390/su142114661

AMA Style

Soomro AH, Larik AS, Mahar MA, Sahito AA. Simulation-Based Comparison of PID with Sliding Mode Controller for Matrix-Converter-Based Dynamic Voltage Restorer under Variation of System Parameters to Alleviate the Voltage Sag in Distribution System. Sustainability. 2022; 14(21):14661. https://doi.org/10.3390/su142114661

Chicago/Turabian Style

Soomro, Abdul Hameed, Abdul Sattar Larik, Mukhtiar Ahmed Mahar, and Anwar Ali Sahito. 2022. "Simulation-Based Comparison of PID with Sliding Mode Controller for Matrix-Converter-Based Dynamic Voltage Restorer under Variation of System Parameters to Alleviate the Voltage Sag in Distribution System" Sustainability 14, no. 21: 14661. https://doi.org/10.3390/su142114661

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop