Novel High-Step-Up/Step-Down Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems

Department of Electronic Engineering, National Kaohsiung University of Science and Technology, Kaohsiung 82401, Taiwan
Energies 2022, 15(14), 5257; https://doi.org/10.3390/en15145257
Submission received: 1 June 2022 / Revised: 12 July 2022 / Accepted: 18 July 2022 / Published: 20 July 2022
(This article belongs to the Special Issue DC-DC Converters Technologies, Applications and Optimization)

Abstract

:
This paper presents a novel three-port high-step-up/step-down bidirectional DC/DC converter with a coupled inductor for photovoltaic (PV) systems. The proposed converter combines a high-step-up converter, which is used to step-up the PV module to DC bus 200 V, and a battery charge/discharge bidirectional converter to form a three-port bidirectional converter. When sufficient energy is supplied from the PV modules, the converter can step-up the output of the PV modules and provide energy to the DC bus while charging the battery simultaneously. However, when no energy is supplied from the PV modules, the DC bus voltage is provided by the battery. Moreover, the energy stored in the leakage inductor is recycled to the DC-blocking capacitor, and synchronous rectification is conducted in the switch during the step-up mode to reduce switch loss and thereby increase the system’s overall efficiency. Finally, a 500 W three-port bidirectional converter is implemented to verify the feasibility and practicability of the proposed converter. The maximum efficiency of the proposed converter is 95.4%, 94.3%, and 94.7% when operated in the high-step-up mode, battery step-up mode, and step-down mode for the PV modules, respectively.

1. Introduction

In recent years, with the technological advances, the amount of greenhouse gas emission has been continuously increasing, leading to global warming and climate change. Our energy technology industry still relies heavily on fossil fuels and has been unable to handle the current stringent environment [1,2]. Therefore, the use of green energy has become the core economic strategy and is trending at the world politics, because the reduction in greenhouse gas emission and energy conservation are currently the major concerns worldwide.
In general, because of the large difference between the output voltage of green energy and the operating voltage of the DC bus, a high-step-up converter is always required for achieving these requirements. However, a conventional boost converter must operate at an extremely high duty ratio to meet the high-step-up voltage demand; moreover, the maximum step-up ratio is limited by the parasitic elements on the circuit’s components. The existence of the parasitic components [3] and the reverse-recovery time of the diode [4] further reduce the converter’s efficiency. These conditions have limited the use of a conventional boost converter in the field of green energy. Recently, the techniques of the series boost converter, voltage-lift, coupled inductor, and cascade circuit structure have been proposed to achieve a high-step-up ratio [5,6,7,8,9,10,11,12]. When the switch is open, a high current spike flows through the power components; therefore, power components with high current stress are required, thus increasing the costs and conduction energy loss. The conventional flyback converter and forward converter are also suitable for use in high-step-up converters. However, the leakage inductance of the transformer in these converters can cause a high reverse voltage on the switch, and therefore, either a passive snubber circuit or an active clamp is always required to suppress this reverse voltage. A passive snubber circuit uses resistance to deplete the excess energy in the leakage inductor, thereby reducing the circuit efficiency.
An application block diagram of a typical green energy system is shown in Figure 1. While low cost, small circuit size, and high efficiency have been the objectives of R&D, energy storage is also a major research direction in the application of green energy. In a system working on a battery, a high-step-up converter that transfers energy from the battery to the DC bus is necessary due to the large voltage difference between the battery and DC bus. Recently, many studies have investigated bidirectional converters [13,14,15,16,17,18,19,20,21,22], a topology that can operate both step-up and step-down functions, which further reduces the number of components, cost, and size of the system. In a nonisolated bidirectional DC/DC converter with ZVS technology [13], ZVS is achieved using synchronous rectification technology and a clamping circuit, but the converter does not apply galvanic isolation. A switched-quasi-Z-source nonisolated bidirectional DC/DC converter [14] has a wide voltage gain range in step-up and step-down modes. However, all switches of this converter perform hard switching, which causes high switching loss. An isolated bidirectional Cuk topology [15] is suitable for photovoltaic (PV) applications. However, the high-voltage stress and high-current stress across switches can damage the circuit. Furthermore, these nonisolated circuits can be interfered with easily and cannot be used for electricity isolation; these factors considerably limit their usage. The commonly used isolated bidirectional converters include the full-bridge bidirectional converter [17], half-bridge bidirectional converter [19], and bidirectional flyback converter [18]. Both full- and half-bridge bidirectional converters can perform soft-switching by controlling the phase shift, which leads to high efficiency, but their designed transformers face difficulties in achieving LLC resonance. Moreover, the bidirectional flyback converter has the common advantages of few components, low cost, and easy design. When it is switched OFF, the leakage inductance of the transformer leads to resonance with the parasitic capacitor within the switch and causes a voltage spike at the switch; therefore, a switch with high-voltage stress is usually required. These isolated bidirectional converters typically possess a large-sized transformer because of the high turns ratio when operated at a high voltage conversion ratio. Recently, many modified bidirectional converters have been proposed. For example, [21] recycled the energy stored in the leakage inductor of the transformer and performed synchronous rectification, which led to high efficiency while meeting the requirement of electricity isolation. However, in the case of an ideal transformer, this converter topology requires two inductors. Despite having a lower turns ratio, the energy releasing problem for the magnetizing inductor causes low efficiency when operated at high power. In addition, [22] proposed the concept of charging the battery auxiliary power and providing energy for the DC bus during a circuit operating in the step-up mode. The leakage inductance of the coupled inductor can recycle the energy and release it to the circuit of the battery auxiliary power and DC bus on the high-voltage side. However, the control procedure is more complicated and the battery auxiliary power is unable to supply energy to the DC bus.
Although a bidirectional converter combines the functions of step-up and step-down voltages, if it is applied to a PV system, the energy generated from the PV system must pass through two converter stages to charge the battery, thus reducing the overall system efficiency. To solve this problem, the topology of a three-port DC/DC converter has been proposed in the literature [23,24,25,26] for PV systems. When the energy supplied from the PV modules is sufficient, the converter provides energy to the DC bus while charging the battery simultaneously. However, when no energy is supplied from the PV modules, the battery can provide energy to the DC bus. A three-port DC/DC converter can operate in different modes to reduce the system’s cost and size, as proposed in [24,25]. However, they have a larger system size, higher cost, and lower efficiency compared with our proposed converter topology. In general, a three-port DC/DC converter has no function of charging the battery by using the DC bus, which indicates that it lacks the step-down mode, similar to a bidirectional converter. Converters proposed in [27,28,29] have three operating modes, which can also use the DC bus to charge the battery. However, the count of components in [29] is higher than that of the proposed converter and the voltage gain in [28] is lower than that of the proposed converter. As proposed in [30], a three-winding common core coupled inductor was designed and implemented in the converter. If a topology can combine the advantages of bidirectional and three-port converters, the system’s size and cost can be further reduced, and this was the main purpose of the present study.
This paper proposes an isolated three-port bidirectional DC/DC converter, the block diagram of which is shown in Figure 2. When the energy supplied from the PV modules is sufficient, the converter can step-up the output of the PV modules and provide energy to the DC bus while charging the battery. However, when the energy supplied from the PV modules is insufficient, the converter can step-up the output of the battery and provide energy to the DC bus. If there is excess energy in the DC bus, it will be used to charge the battery, which means that this topology can run both high-step-up and high-step-down functions.

2. Circuit Architecture and Operational Principle

This paper proposes a novel three-port high-step-up/step-down bidirectional DC/DC converter with a coupled inductor, as shown in Figure 3. The DC-blocking capacitor Cm at the high-voltage side enables the system to operate in the high-step-down mode by reducing the voltage on the transformer. Moreover, synchronous rectification is performed in the switch during the high-step-up mode to reduce switch loss to increase the system’s overall efficiency. Moreover, the energy stored in the leakage inductor on the transformer’s secondary side can be recycled, which increases the system efficiency. An improved SEPIC is used on the low-voltage side of the PV modules to step-up the output of the PV modules for battery charging and provide energy to the DC bus. The auxiliary inductor Lb,L1 at the battery side can modify the output step-up voltage after it is modified and provide continuous current for charging the battery. Switch S2 and diode D2 prevent the energy generated from the PV system from charging the battery directly and controlling the step-up process for providing energy to the DC bus and charging the battery when the energy supplied from the PV modules is sufficient. The battery output is stepped-up and provides energy to the DC bus in case of a lack of energy supply from the PV modules. If excess energy is present in the DC bus, the energy is used to charge the battery.
The proposed topology can be studied in three working stages. Stage 1 involves stepping-up the output of the PV modules for charging the battery and providing energy to the DC bus when the energy supplied from the PV modules is sufficient. Stage 2 involves stepping-up the battery output to provide energy to the DC bus when the energy supplied from the PV modules is insufficient. Stage 3 involves stepping-down the output of the DC bus and charging the battery when excess energy is present in the DC bus. To simplify the analysis of the proposed topology, the following assumptions were made:
  • All the capacitances are sufficiently large and can be considered as the current sources.
  • Switches and diodes are ideal components.
  • The magnetizing inductances of the transformer are larger than its leakage inductances.
Stage 1: Step-up the PV output for the DC bus and battery charging.
The waveforms of the key components operating in Stage 1 are shown in Figure 4.
  • Mode I [t0 ≤ t < t1].
As shown in Figure 5a, when t = t0, switch S1 and diode D1 turn ON, while switches S2, S4, and diode D2 turn OFF. Furthermore, the parasitic diode of switch S3 is turned ON, and the direction of the current flow is as shown in the figure. In this mode, the PV source stores energy in the input inductor L1 and magnetizing inductor Lm, while the charging inductor Lb releases energy for battery charging. Simultaneously, capacitor C1 and the current induced by the transformer are stored in the voltage-doubling capacitor Cm. During this interval, Vo is provided by the output capacitor Co.
2.
Mode II [t1 ≤ t < t2].
When t = t1, S1 and D1 remain ON, while S2, S4, and D2 remain OFF. In this mode, S3 is turned ON for operating synchronous rectification, and the direction of the current flow is as shown in Figure 5b. Other operations are the same as those in Mode I. Energy is stored in L1 and Lm by the PV source, Lb releases energy for battery charging, Cm is charged by the induced current from the transformer, and Co continues to provide energy to the output Vo.
3.
Mode III [t2 ≤ t < t3].
When t = t2, S1 and D1 still remain ON, while S2, S4, and D2 remain OFF. The parasitic diode on S3 is turned ON, and the direction of current flow is as shown in Figure 5c. The other operations in this mode are the same as those in Mode I.
4.
Mode IV [t3 ≤ t < t4].
When t = t3, S1 is turned OFF; D1 and the parasitic diode on S3 remain ON; S2, S4, and D2 remain OFF. The direction of the current flow in this mode is as shown in Figure 5d. In this mode, the input inductor releases energy for charging the auxiliary inductor Lb. Moreover, the current flowing through the leakage inductor LLk2 charges the parasitic capacitor, Lb releases energy for battery charging, and Co continues to provide energy to the output Vo.
5.
Mode V [t4 ≤ t < t5].
When t = t4, S1, S2, S3, and D2 are OFF, while D1 remains ON. Simultaneously, S4 is turned ON for operating synchronous rectification, and the direction of the current flow is as shown in Figure 5e. In this mode, the energy stored in Lm is transferred to output Vo and charge Co through the transformer’s induction. Meanwhile, Cm releases its stored energy to the output Vo, the input inductor L1 releases energy for charging the auxiliary inductor Lb, and Lb continues to provide energy to the battery.
6.
Mode VI [t5 ≤ t < t6].
When t = t5, S1, S2, S3, and D2 remain OFF, while D1 remains ON. The direction of current flow in this mode is as shown in Figure 5f. Here, the parasitic diode on S4 is turned ON, which indicates that synchronous rectification is stopped. Other operations are the same as those in Mode V.
Stage 2: Battery step-up to DC bus.
In Stage 2, the battery’s output voltage is stepped-up to provide energy to the DC bus. Figure 6 shows the key waveforms of the main components operating in Stage 2.
  • Mode I [t0 ≤ t < t1]
When t = t0, switches S1 and S2 and diode D2 turn ON, while switch S4 and diode D1 turn OFF. The direction of current flow in this mode is as shown in Figure 7a. In addition, the parasitic diode on S3 is ON. In this mode, the battery releases energy to the input inductor L1, capacitor C1, and magnetizing inductor Lm. The induced current from the transformer charges the voltage-doubling capacitor Cm, while the output capacitor Co provides energy to output Vo.
2.
Mode II [t1 ≤ t < t2].
During this interval, S1, S2, and D2 remain ON, while S4 and D1 remain OFF. S3 is turned ON for synchronous rectification when t = t1, and the direction of current flow is as shown in Figure 7b. The other operations are the same as those in Mode I.
3.
Mode III [t2 ≤ t < t3].
When t = t3, S1, S2, and D2 remain ON, while S4 and D1 remain OFF. Simultaneously, synchronous rectification is stopped and the parasitic diode on S3 is turned ON. The direction of current flow is as shown in Figure 7c. The other operations in this mode are the same as those in Mode I, and the battery releases energy for magnetizing inductor, Lm. The induced current from the transformer charges the voltage-doubling capacitor Cm, while the output capacitor Co provides energy to output Vo.
4.
Mode IV [t3 ≤ t < t4].
When t = t4, S1, S2, S3, and D2 remain OFF, while D1 remains ON. Simultaneously, S4 is turned ON to operate synchronous rectification. The direction of current flow in this mode is as shown in Figure 7e. In this mode, the transformer induces energy from Lm to output Vo while simultaneously charging Co. The energy stored in Cm is also released to output Vo. Meanwhile, inductor L1 releases energy for auxiliary inductor Lb charging, and the energy stored in Lm and Lb is recycled back to the battery.
5.
Mode VI [t5 ≤ t < t6].
When t = t5, S1, S2, S3, and D2 remain OFF, while D1 remains ON. The synchronous rectification is stopped because the parasitic diode on S4 is turned ON, and the direction of current flow in this mode is as shown in Figure 7f. Other operations in this mode are the same as those in Mode IV.
Stage 3: DC-bus step-down for battery charging.
When the energy supplied from the PV modules is insufficient, the system steps-down the output voltage of the DC bus for battery charging. The key waveforms of the proposed converter topology in the step-down stage are shown in Figure 8.
  • Mode I [t0 ≤ t < t1].
When t = t0, switch S4 and diode D1 are turned ON, while switches S1, S2, and S3 and diode D2 are turned OFF. Simultaneously, the parasitic diode on switch S1 is turned ON. The direction of current flow in this mode is as shown in Figure 9a. This mode continues the state of Mode VI in Stage 2, where the energy stored in the voltage-doubling capacitor Cm and leakage inductor LLk2 is recycled to output Vo, and the other leakage inductor LLk1 transfers its energy to the input capacitor Ci. Simultaneously, the charging inductor Lb releases energy to charge the battery.
2.
Mode II [t1 ≤ t < t2].
When t = t1, S4 and D1 remain in the ON state, while S1, S2, S3, and D2 remain OFF. The direction of the current flow is shown in Figure 9b. In this mode, the PV source starts to store energy in the magnetizing inductor Lm after the energy stored in Cm and LLk2 is recycled completely. In addition, the induced current from the transformer starts to store energy in Lb while simultaneously charging the battery.
3.
Mode III [t2 ≤ t < t3].
When t = t2, S1, S2, and D2 remain in the OFF state and D1 remains ON. S4 is turned OFF, while the parasitic diode on S3 is turned ON; the direction of current flow is as shown in Figure 9c. In this mode, current flows through the leakage inductor LLk2 and then charges Cm. The induced current from the transformer also stores energy in Lb while simultaneously charging the battery.
4.
Mode IV [t3 ≤ t < t4].
When t = t3, S2, S4, and D2 remain OFF, while D1 remains ON. Simultaneously, both S1 and S3 are turned ON for operating synchronous rectification. The direction of current flow in this mode is as shown in Figure 9d. The energy stored in Lm is induced by the transformer to charge Cm through S3. In addition, Lb starts to release energy through S1 while simultaneously charging the battery.
5.
Mode V [t4 ≤ t < t5]
When t = t4, S2, S4, and D2 remain OFF, while S1, S3, and D1 remain ON, and the direction of current flow is as shown in Figure 9e. In this mode, both S1 and S3 continue to operate synchronous rectification, and the energy stored in Lm is completely released. Simultaneously, Cm starts to transfer energy to Lm and LLk2 while inducing energy to charge Ci. Meanwhile, Lb continues to charge the battery through S1.
6.
Mode VI [t5 ≤ t < t6]
When t = t5, D1 remains ON, while S3, S4, and D2 remain OFF. The direction of current flow is as shown in Figure 9f. The synchronous rectification is stopped as S1 and S4 are turned OFF in this mode and both their parasitic diodes are ON. The current flows through Cm and LLk2, the energy is recycled to output Vo, and the energy stored in Lb is released for battery charging.

3. Steady-State Analysis

This section describes the mathematical derivation of the voltage conversion ratio and the voltage stress of components. First, some assumptions are made to simplify the study and analysis process:
  • All capacitances are sufficiently large and can be considered as the current sources.
  • Switches and diodes are ideal components.
  • The leakage inductances of the transformer are smaller than the magnetizing inductances, and therefore, can be neglected.
  • The system is operating in the continuous conduction mode (CCM).

3.1. Voltage Conversion Ratio

When the energy supplied from the PV modules is sufficient, switch S1 turns on and the voltage difference on the magnetizing inductor is equal to the input voltage supplied from the PV modules. However, when the system lacks the energy supplied from PV modules, switches S1 and S2 turn on and the voltage difference on the magnetizing inductor is equal to the battery voltage. Because the input voltage from the PV modules and battery voltage are almost the same in the three-port converter, both high-step-up processes of the PV modules and battery to the DC bus have the same step-up ratio. To simplify the derivation of the voltage conversion ratio, we first neglect the part of the battery circuit.
  • Step-up voltage conversion ratio, Gstep-up
When switch S1 is turned on:
V Lm = L m d i L d t = V c m n
Δ i L m +   = V i L m D T s
Assuming n = N 2 N 1 , the total turn-on time Ton = DTs; when switch S1 is turned off:
V L = L m d i L d t = V o V c m n
Δ i L = V o V c m n L m ( 1     D )   T s
Total turn-off time, Toff = (1 − D)   T s .
According to the principle of volt–second balance:
Δ i L + = Δ i L
G step-up = V o V i   = n + D 1 D
Assuming that all energy of the magnetizing inductors is transferred to the battery and the maximum current is equal to the stored energy current of the magnetizing inductors, we can design the battery charging current.
i Lb(max) = V i L m D T s = V b L b D T s
2.
Step-down voltage conversion ratio, Gsetp-down.
For deriving the step-down voltage conversion ratio of the DC bus charging battery, switch S2 and diode D2 are first turned off, switch S4 is turned on, and switch S3 is turned off.
V Lm = V o V c m n
Δ i L m   = V o V c m   n L m D T s
Assuming n = N 2 N 1 , the total turn-on time Ton = DTs. When switch S4 is turned off and switch S3 is turned on:
V Lm = V c m n
Δ i L m   = V C m n L m ( 1   D )   T s
Total turn-off time, Toff = (1 − D)   T s .
According to the principle of volt–second balance:
Δ i L + = Δ i L
G step-down = V b V o   = D ( 1 D + n )

3.2. Voltage Stress of Components

Each component’s voltage stress can be derived by analyzing their ON and OFF states. The voltage stress of switch S1 can be determined using the ON state, as shown in Figure 5a.
ViVL1 = 0
With volt–second balance, the voltage stress of switch S1 can be derived as
V S 1 =           1           1 D V i
Because diode D2 is considered ideal, the voltage of switch S2 is equal to the voltage difference between the battery voltage and voltage on the input capacitor:
VS2 = Vb − VCi
During the step-down mode and when switch S4 is turned ON, switch S3 is turned OFF, as shown in Figure 9e, and the voltage difference on the switch is equal to the output voltage:
VS3 = Vo
During the step-down mode and when switch S3 is turned ON, switch S4 is turned OFF, as shown in Figure 9b, and the voltage difference on the switch is equal to the output voltage:
VS4 = Vo
When all the energy stored on Lb is released completely and switch S1 is turned ON, diode D1 is turned OFF and the voltage difference on it is equal to the battery voltage:
VD1 = Vb
Diode D2 has the same voltage stress as that of switch S2.
VD2 = Vb − VCi
During the step-up mode, the voltage stress on input capacitor C1 is expressed as
VC1 = Vin
The voltage stress of the output capacitor Co is equal to Vo:
VCo = Vo
The voltage stress of the voltage-doubling capacitor Cm is equal to
VCm = Vo/2

4. Experimental Results and Analysis

This section presents a comparison between the proposed converter and two different groups of converters. First, we compare the proposed converter with the bidirectional converter presented in [21,22]. As shown in Table 1, the converters proposed in both [21,22] can only be used as traditional bidirectional converters, whereas our three-port bidirectional converter can operate in three different stages and apply different functions. In addition to exhibiting the regular bidirectional step-up/step-down performance, our three-port bidirectional converter can be applied to the PV system. Although [20] described a clamp circuit that can reduce switch voltage stress, more components are required, and the component temperature increase causes the efficiency to decrease rapidly when operating at high wattages. Furthermore, [21] did not use any diode and reported a lower turns ratio of the transformer; it had one more inductor, which led to a larger system size. Furthermore, the efficiency in [21] obviously declined when the system operated at heavy power, and thus, the system can only operate at a maximum power of 200 W. As for [22], although the system could operate at 1 kW, its efficiency did not even reach 90% when operated above 500 W. In addition, switch controlling was very complicated.
Table 2 presents a comparison between the proposed converter and those described in [24,25,28,29,30], all of which are three-port converters. The highest conversion efficiency shown in Table 2 is the calculated efficiency for energy conversion from PV modules to the DC bus, and the proposed converter has an obvious superiority in conversion efficiency. In addition, the proposed converter has a higher step-up ratio with fewer components and at a lower cost. The converter presented in [24] requires two coupled inductors at the output side, which results in an increased size and cost of the system. Furthermore, the power of this converter is only 150W, which will limit its application. Although the cost of the system in [25] is lower than that in [24], the system in [25] does not have an obvious superiority in terms of efficiency and system size. Moreover, it cannot reach a ten-times step-up ratio despite having the same turns ratio of the transformer as that of the transformer with the proposed converter topology. In addition, due to a lack of inductors at the output side, the efficiency of the system decreases when operated at high power. Normally, a three-port converter cannot charge the battery by using the energy from the DC bus, but the proposed converter possesses this function, and so the proposed converter is more suitable for application to PV systems. The count of components is lowest in [28] but the voltage gain is not prominent. Moreover, the converter in [29] is nonisolated, which means that this topology is easily disturbed by noise. In industry, galvanic isolation is necessary because of safety. The number of components is too many to increase the cost, and the efficiency of the proposed converter is better than that of [29]. The performance index of [30] is moderate.
Overall, the number of components of the proposed converter is appropriate, and the voltage gain of the proposed converter is higher. In addition, the proposed converter comes with a great performance of conversion efficiency. However, the conversion efficiency of the proposed converter still has space for improvement, if the power switch has the features of soft-switching.
To verify and demonstrate the operation of the proposed isolated bidirectional three-port DC/DC converter, a 500 W hardware prototype was designed and implemented, and the performance was measured under a full load of 500 W. Figure 10 shows the prototype of the proposed three-port bidirectional DC/DC converter. The measured waveforms of all components successfully evidenced the feasibility and practicability of the proposed converter topology. The corresponding specification and component parameters are summarized in Table 3.
Figure 11 shows the measured efficiency curve of the proposed converter topology operated under three stages. The proposed converter operates under a light load of 50 W and full load of 500 W in the PV step-up stage, with efficiencies of 93.2% and 91.4%, respectively. However, when it operates at approximately 200 W, its highest efficiency reaches 95.4%. Next, for the battery step-up stage, its highest efficiency is 94.3%. Finally, for the step-down stage, the efficiencies for the abovementioned light and full loads are 92.3% and 91.6%, respectively. However, its highest efficiency reaches 94.3% when operated at 250 W.
Figure 12 shows a comparison graph of the measured step-up efficiency between the proposed converter and those described in [20,21,22]. The proposed converter has a higher efficiency than those of the converters proposed in [20,22] but a lower efficiency than that proposed in [21]. However, the proposed converter can operate in three different stages and at high power. Figure 13 shows another comparison graph between the proposed converter and those described in [20,21], and Ref. [22] operated in the step-down mode. The proposed converter has a higher efficiency than the converter proposed in [20] but a lower efficiency than those proposed in [21,22]. However, the proposed converter can operate in three stages and has a low cost.
Figure 14 shows a comparison graph of efficiency between the proposed converter and those proposed in [24,25,28,29] when operated in the PV step-up stage. The proposed converter topology has an obvious superiority over the others.
Figure 15 shows the measured results of the proposed converter under Stage 1. Figure 14a–d show the waveforms of the drive signal Vgs, switch voltage Vds, and switch current is of switches S1, S3, and S4 under a full load of 500 W, whereas the current waveforms of transformers, ipri, isec, and inductors, iLb, iL1, under the same load are shown in Figure 14e,f, respectively.
Figure 16 shows the measured results of the proposed converter under Stage 2. Figure 15a–d show the waveforms of the drive signal Vgs, switch voltage Vds, and switch current is of switches S1, S2, S3, and S4 under a full load of 500 W. Furthermore, Figure 15e,f show the current waveforms of transformers, ipri, isec, and inductors, iLb, iL1, under the full load, respectively.
Figure 17 shows the measured results of the proposed converter under Stage 3. Figure 16a–d show the waveforms of the drive signal Vgs, switch voltage Vds, and switch current is of switches S1, S3, and S4 under a full load of 500 W, whereas the current waveforms of transformers, ipri, isec, and inductors, iLb, iL1, under the same load are shown in Figure 16e,f, respectively.

5. Conclusions

This paper presented a theoretical analysis of the steady state, related considerations, and experimental results of the proposed converter. The proposed novel three-port high-step-up/step-down bidirectional DC/DC converter with a coupled inductor was successfully implemented. The converter possessed the PV step-up mode, battery step-up mode, and DC bus step-down mode to promote the functionality of the circuit. Moreover, an improved SEPIC and a DC-blocking capacitor were employed at the low- and high-voltage side, respectively, to promote the voltage conversion ratio and reduce the voltage of the transformer, which allows a high-step-down performance. In addition, the energy stored in the leakage inductor was recycled, which improved the system’s overall efficiency. Thus, the proposed converter possessed the advantages of high efficiency, high-step-up/down ratio, and lower system size and cost. Finally, a 500 W three-port bidirectional converter was implemented to verify its feasibility and practicability. The highest efficiency of the proposed converter operated under the PV step-up stage was 95.4%, that under the battery step-up stage was 94.3%, and that under the step-down stage was 94.7%. Three-port bidirectional converters can be widely used in smart grid systems, energy storage systems, and electric vehicle power supply systems in the future.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Facing Global Warming—Taiwan’s Response. Response to the Framework Convention on Climate Change News in Taiwan. Available online: http://www.tri.org.tw/unfccc/ (accessed on 12 May 2021).
  2. Ministry of Economic Affairs Bureau of Energy. 2017 Energy and Industrial Technology White Paper. Available online: https://www.moeaboe.gov.tw/ECW/populace/content/ContentDesc.aspx?menu_id=5494 (accessed on 12 May 2021).
  3. Ismail, E.H.; Al-Saffar, M.A.; Sabzali, A.J. High Conversion Ratio DC-DC Converters with Reduced Switch Stress. IEEE Trans. Circuits Syst. I 2008, 55, 2139–2151. [Google Scholar] [CrossRef]
  4. Wuhua, L.; Xiaodong, L.; Deng, Y.; Liu, J.; He, X. A Review of Non-Isolated High Step-Up DC/DC Converter in Renewable Energy Applications. In Proceedings of the Applied Power Electronics Conference and Exposition, 2009, APEC 2009, Washington, DC, USA, 15–19 February 2009; 2009; pp. 364–369. [Google Scholar]
  5. Dimna Denny, C.; Shahin, M. Analysis of bidirectional SEPIC/Zeta converter with coupled inductor. In Proceedings of the 2015 International Conference on Advancements in Power and Energy (TAP Energy), Kollam, India, 24–26 June 2015; pp. 103–108. [Google Scholar]
  6. Zhao, Q.; Lee, F.C. High Performance Coupled-Inductor DC-DC Converters. In Proceedings of the IEEE APEC Conference, Miami Beach, FL, USA, 9–13 February 2003; Volume 1, pp. 109–113. [Google Scholar]
  7. Huber, L.; Jovanovic, M.M. A design approach for server power supplies for networking applications. In Proceedings of the IEEE INTELEC, Phoenix, AZ, USA, 10–14 September 2000; pp. 1163–1169. [Google Scholar]
  8. Feng, X.G.; Liu, J.J.; Lee, F.C. Impedance specifications for stable DC distributed power systems. IEEE Trans. Power Electron. 2002, 17, 157–162. [Google Scholar] [CrossRef]
  9. Wu, T.F.; Yu, T.H. Unified approach to developing single-stage power converters. IEEE Trans. Aerosp. Electron. Syst. 1998, 34, 211–223. [Google Scholar]
  10. Luo, F.L.; Ye, H. Positive output super-Lift converters. IEEE Trans. Power Electron. 2003, 18, 105–113. [Google Scholar]
  11. Zhao, Q.; Tao, F.; Lee, F.C. A Front-end DC/DC Converter for Network Server Applications. In Proceedings of the IEEE PESC Conference, Vancouver, BC, Canada, 17–21 June 2001; Volume 3, pp. 1535–1539. [Google Scholar]
  12. Wai, R.J.; Duan, R.Y. High step-up converter with coupled-inductor. IEEE Trans. Power Electron. 2005, 20, 1025–1035. [Google Scholar] [CrossRef]
  13. Hassan, W.; Soon, J.L.; Lu, D.D.; Xiao, W. A High Conversion Ratio and High-Efficiency Bidirectional DC–DC Converter with Reduced Voltage Stress. IEEE Trans. Power Electron. 2020, 35, 11828–11831. [Google Scholar] [CrossRef]
  14. Zhang, Y.; Liu, Q.; Li, J.; Sumner, M. A Common Ground Switched-Quasi-Z-Source Bidirectional DC–DC Converter with Wide-Voltage-Gain Range for EVs With Hybrid Energy Sources. IEEE Trans. Ind. Electron. 2018, 65, 5189–5191. [Google Scholar] [CrossRef]
  15. Gorji, S.A.; Sahebi, H.G.; Ektesabi, M.; Rad, A.B. Topologies and Control Schemes of Bidirectional DC–DC Power Converters: An Overview. IEEE Access 2019, 7, 118002–118003. [Google Scholar] [CrossRef]
  16. Mukhtar, N.M.; Lu, D.D. A Bidirectional Two-Switch Flyback Converter with Cross-Coupled LCD Snubbers for Minimizing Circulating Current. IEEE Trans. Ind. Electron. 2019, 66, 5948–5957. [Google Scholar] [CrossRef]
  17. Bai, C.; Han, B.; Kwon, B.; Kim, M. Highly Efficient Bidirectional Series-Resonant DC/DC Converter Over Wide Range of Battery Voltages. IEEE Trans. Power Electron. 2020, 35, 3636–3650. [Google Scholar] [CrossRef]
  18. Shi, H.; Sun, K.; Wu, H.; Li, Y. A Unified State-Space Modeling Method for a Phase-Shift Controlled Bidirectional Dual-Active Half-Bridge Converter. IEEE Trans. Power Electron. 2020, 35, 3254–3265. [Google Scholar] [CrossRef]
  19. Haneda, R.; Akagi, H. Design and Performance of the 850-V 100-kW 16-kHz Bidirectional Isolated DC–DC Converter Using SiC-MOSFET/SBD H-Bridge Modules. IEEE Trans. Power Electron. 2020, 35, 10013–10025. [Google Scholar] [CrossRef]
  20. Wu, H.; Sun, K.; Chen, L.; Zhu, L.; Xing, Y. High Step-Up/Step-Down Soft-Switching Bidirectional DC–DC Converter with Coupled-Inductor and Voltage Matching Control for Energy Storage Systems. IEEE Trans. Ind. Electron. 2016, 63, 2892–2903. [Google Scholar] [CrossRef]
  21. Lee, H.-Y.; Liang, T.-J.; Chen, J.-F.; Chen, K.-H. Design and Implementation of a Bidirectional SEPIC-Zeta DC-DC Converter. In Proceedings of the 2014 IEEE International Symposium on Circuits and Systems (ISCAS), Melbourne, Australia, 1–5 June 2015; pp. 101–104. [Google Scholar]
  22. Liang, T.-J.; Lee, J.-H. Novel High-Conversion-Ratio High-Efficiency Isolated Bidirectional DC–DC Converter. IEEE Trans. Ind. Electron. 2015, 62, 4492–4503. [Google Scholar] [CrossRef]
  23. Wai, R.-J.; Liaw, J.-J. High-Efficiency-Isolated Single-Input Multiple-Output Bidirectional Converter. IEEE Trans. Power Electron. 2015, 30, 4914–4930. [Google Scholar] [CrossRef]
  24. Faraji, R.; Farzanehfard, H. Soft-switched nonisolated high step-up three-port DC–DC converter for hybrid energy systems. IEEE Trans. Power Electron. 2018, 33, 10101–10111. [Google Scholar] [CrossRef]
  25. Li, W.; Xu, C.; Luo, H.; Hu, Y.; He, X.; Xia, C. Decoupling-Controlled Triport Composited DC/DC Converter for Multiple Energy Interface. IEEE Trans. Ind. Electron. 2015, 62, 4504–4513. [Google Scholar] [CrossRef]
  26. Hu, Y.; Xiao, W.; Cao, W.; Ji, B.; Morrow, D.J. Three-Port DC–DC Converter for Stand-Alone Photovoltaic Systems. IEEE Trans. Power Electron. 2015, 30, 3068–3076. [Google Scholar] [CrossRef] [Green Version]
  27. Wu, Y.-E. Novel High Efficiency Three-Port Bidirectional Step-up/Step-down DC/DC Converter for Photovoltaic Systems. In Proceedings of the 2020 IEEE 3rd International Conference on Electronics Technology, Chengdu, China, 8–11 May 2020; pp. 289–296. [Google Scholar]
  28. Wu, Y.-E.; Chiu, P.-N. A High-Efficiency Isolated-Type Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems. Energies 2017, 10, 434. [Google Scholar] [CrossRef] [Green Version]
  29. Wu, Y.-E.; Hsiao, S.-L. Novel High-Efficiency Three-Port Bidirectional Step-up/Step-down DC–DC Converter for Photovoltaic Systems. Sustainability 2021, 13, 7913. [Google Scholar] [CrossRef]
  30. Wu, Y.-E.; Hsu, K.-C. Novel Three-Port Bidirectional DC/DC Converter with Three-Winding Coupled Inductor for Photovoltaic System. Energies 2020, 13, 1132. [Google Scholar] [CrossRef] [Green Version]
Figure 1. Application block diagram of green energy system.
Figure 1. Application block diagram of green energy system.
Energies 15 05257 g001
Figure 2. Block diagram of three-port bidirectional converter.
Figure 2. Block diagram of three-port bidirectional converter.
Energies 15 05257 g002
Figure 3. Novel isolated three-port bidirectional DC/DC converter.
Figure 3. Novel isolated three-port bidirectional DC/DC converter.
Energies 15 05257 g003
Figure 4. Key waveforms in Stage 1.
Figure 4. Key waveforms in Stage 1.
Energies 15 05257 g004
Figure 5. Operational diagram of each mode in Stage 1: (a) Mode I, (b) Mode II, (c) Mode III, (d) Mode IV, (e) Mode V, and (f) Mode VI.
Figure 5. Operational diagram of each mode in Stage 1: (a) Mode I, (b) Mode II, (c) Mode III, (d) Mode IV, (e) Mode V, and (f) Mode VI.
Energies 15 05257 g005aEnergies 15 05257 g005b
Figure 6. Key waveforms in Stage 2.
Figure 6. Key waveforms in Stage 2.
Energies 15 05257 g006
Figure 7. Operating diagram of each mode in Stage 2: (a) Mode I, (b) Mode II, (c) Mode III, (d) Mode IV, and (e) Mode V.
Figure 7. Operating diagram of each mode in Stage 2: (a) Mode I, (b) Mode II, (c) Mode III, (d) Mode IV, and (e) Mode V.
Energies 15 05257 g007
Figure 8. Key waveforms in Stage 3.
Figure 8. Key waveforms in Stage 3.
Energies 15 05257 g008
Figure 9. Operating diagram of each mode in Stage 3: (a) Mode I, (b) Mode II, (c) Mode III, (d) Mode IV, (e) Mode V, and (f) Mode VI.
Figure 9. Operating diagram of each mode in Stage 3: (a) Mode I, (b) Mode II, (c) Mode III, (d) Mode IV, (e) Mode V, and (f) Mode VI.
Energies 15 05257 g009
Figure 10. Photographs of the proposed three-port bidirectional DC/DC converter.
Figure 10. Photographs of the proposed three-port bidirectional DC/DC converter.
Energies 15 05257 g010
Figure 11. Efficiency curve of the proposed three-port bidirectional converter.
Figure 11. Efficiency curve of the proposed three-port bidirectional converter.
Energies 15 05257 g011
Figure 12. Comparison graph of the measured efficiency between the proposed converter and previous studies operated in the step-up mode ( Energies 15 05257 i001 proposed paper, Energies 15 05257 i002 [20], Energies 15 05257 i003 [21], Energies 15 05257 i004 [22]).
Figure 12. Comparison graph of the measured efficiency between the proposed converter and previous studies operated in the step-up mode ( Energies 15 05257 i001 proposed paper, Energies 15 05257 i002 [20], Energies 15 05257 i003 [21], Energies 15 05257 i004 [22]).
Energies 15 05257 g012
Figure 13. Comparison graph of the measured efficiency between the proposed converter and previous studies operated in the step-down mode ( Energies 15 05257 i003 proposed paper, Energies 15 05257 i004 [22], Energies 15 05257 i001 [21], Energies 15 05257 i002 [20]).
Figure 13. Comparison graph of the measured efficiency between the proposed converter and previous studies operated in the step-down mode ( Energies 15 05257 i003 proposed paper, Energies 15 05257 i004 [22], Energies 15 05257 i001 [21], Energies 15 05257 i002 [20]).
Energies 15 05257 g013
Figure 14. Comparison graph of the measured efficiency between the proposed three-port converter and previous studies ( Energies 15 05257 i001 proposed paper, Energies 15 05257 i004 [24], Energies 15 05257 i002 [25], Energies 15 05257 i005 [28], Energies 15 05257 i003 [29]).
Figure 14. Comparison graph of the measured efficiency between the proposed three-port converter and previous studies ( Energies 15 05257 i001 proposed paper, Energies 15 05257 i004 [24], Energies 15 05257 i002 [25], Energies 15 05257 i005 [28], Energies 15 05257 i003 [29]).
Energies 15 05257 g014
Figure 15. Measured results under Stage 1 at 500 W: (a,b) switch S1 waveforms, (c,d) switches S3 and S4 waveforms, and (e,f) current waveforms of transformers and inductors, respectively.
Figure 15. Measured results under Stage 1 at 500 W: (a,b) switch S1 waveforms, (c,d) switches S3 and S4 waveforms, and (e,f) current waveforms of transformers and inductors, respectively.
Energies 15 05257 g015
Figure 16. Measured results under Stage 2 at 500 W: (a,b) switch S1 waveforms, (c,d) switches S3 and S4 waveforms, and (e,f) current waveforms of transformers and inductors, respectively.
Figure 16. Measured results under Stage 2 at 500 W: (a,b) switch S1 waveforms, (c,d) switches S3 and S4 waveforms, and (e,f) current waveforms of transformers and inductors, respectively.
Energies 15 05257 g016aEnergies 15 05257 g016b
Figure 17. Measured results under Stage 3 at 500 W: (a,b) switch S1 waveforms, (c,d) switches S3 and S4 waveforms, and (e,f) current waveforms of transformers and inductors, respectively.
Figure 17. Measured results under Stage 3 at 500 W: (a,b) switch S1 waveforms, (c,d) switches S3 and S4 waveforms, and (e,f) current waveforms of transformers and inductors, respectively.
Energies 15 05257 g017
Table 1. Comparison of the proposed converter with other presented bidirectional converters.
Table 1. Comparison of the proposed converter with other presented bidirectional converters.
ReferencesProposed PaperReference [20]Reference [21]Reference [22]
TopologyCoupled inductorCoupled inductorIsolatedIsolated
Input voltage24 V24 V24 V24 V
Output voltage200 V400 V200 V200 V
Output power500 W500 W200 W1 kW
Number of Switch4444
Number of diode2002
Number of Inductor2221
Number of Capacitor3535
Turns ration = 2.5n = 3n = 1.5n = 3
Output terminal2112
Maximum conversion efficiency (Step-up/Step-down)95.4%/94.7%94.3%/92.6%94%/95%94%/95%
CostMediumHighMediumHigh
Converter Operational Mode3222
Table 2. Comparison of the proposed converter with other presented three-port converters.
Table 2. Comparison of the proposed converter with other presented three-port converters.
ReferencesProposed PaperReference [24]Reference [25]Reference [28]Reference [29]Reference [30]
TopologyCoupled
Inductor
Coupled
Inductor
IsolatedIsolatedCoupled
Inductor
Isolated
Input voltage24 V32 V18 V2424–2624–26
Battery voltage24 V48 V12 V242424
Output voltage200 V400 V80 V200 V200 V200 V
Output power500 W150 W200 W500 W500 W500 W
Voltage gain of step-up mode
PV-DC bus
n + D 1 D 1 + N 1 D 1 D n 1 D 2 + n 1 D n 1 D
Voltage gain of step-up mode
Battery-DC bus
n + D 1 D 1 + N 1 D 1 D n 1 D 2 + n 1 D n 1 D
Voltage gain of step-down mode
DC bus-battery
D 1 D + n DD D n D 2 + n 1 D n
Number of Switch444444
Number of Diode252242
Number of Transformer122111
Number of Inductor210121
Number of Capacitor353333
Turns ration = 2.5n = 0.5n = 2n=3n=1n=3
Output terminal222222
Maximum conversion efficiency
(Step-up/Step-down)
95.6%/94.5%94.5%/93.6%91.5%/90.6%94.5%/95.2%94.4%/95.0%95%/94.2%
Converter Mode332333
Table 3. Electrical specifications and component parameters of the proposed converter.
Table 3. Electrical specifications and component parameters of the proposed converter.
Specification
Input DC Voltage Vin24 V
Battery Voltage Vb24 V
Output DC Voltage Vo200 V
Maximum output power Po500 W
Switching frequency fs50 kHz
Coupled inductors turns ratioN1:N2 = 1:2.5
ComponentModelSpecification
S1, S2IRFP4321150 V/78 A
S3, S4IRFP4868300 V/70 A
D1, D2MBR40200200 V/40 A
CiElectrolytic Capacitor100 uF/100 V
C1Electrolytic Capacitor220 uF/100 V
CoElectrolytic Capacitor470 uF/450 V
CmMPP Film Capacitor4.7 uF/250 V
LbMPP Ring core85 uH
L1MPP Ring core56 uH
LmMPP EE core260 uH
LKLeakage inductance0.5 uH
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Wu, Y.-E. Novel High-Step-Up/Step-Down Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems. Energies 2022, 15, 5257. https://doi.org/10.3390/en15145257

AMA Style

Wu Y-E. Novel High-Step-Up/Step-Down Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems. Energies. 2022; 15(14):5257. https://doi.org/10.3390/en15145257

Chicago/Turabian Style

Wu, Yu-En. 2022. "Novel High-Step-Up/Step-Down Three-Port Bidirectional DC/DC Converter for Photovoltaic Systems" Energies 15, no. 14: 5257. https://doi.org/10.3390/en15145257