Review on Detection and Analysis of Partial Discharge along Power Cables

1
State Grid Jibei Electric Power Company Limited, Beijing 100054, China
2
State Grid Jibei Electric Power Company Limited Smart Distribution Network Center, Qinghuangdao 066199, China
3
State Grid Qinhuangdao Electric Power Supply Company, Qinghuangdao 066099, China
4
School of Electrical and Electronic Engineering, North China Electric Power University, Baoding 071003, China
*
Author to whom correspondence should be addressed.
Energies 2021, 14(22), 7692; https://doi.org/10.3390/en14227692
Submission received: 27 October 2021 / Revised: 11 November 2021 / Accepted: 14 November 2021 / Published: 17 November 2021

Abstract

:
Partial discharge (PD) detection and analysis plays a crucial role for acceptance testing and condition monitoring of power cables. Various aspects are related to PD in power cables from theory to practice. This paper first summarizes the PD mechanism and models used for PD analysis in power cables. Afterwards, PD detection is addressed in the aspects of off-line test, on-line test, and sensors. PD analysis is discussed in detail. Specifically, related quantities and algorithms for PD analysis are outlined. PD characteristics with affecting factors, e.g., dielectric type, load, and applied voltage are discussed. Experience on PD development trend with measurements in field is analyzed. Based on the comprehensive review, challenges of PD detection and analysis along a power cable are proposed.

1. Introduction

Partial discharge (PD) is a breakdown that occurs in part of the insulating material caused by overhigh electric field. It is widely used in power equipment testing and diagnostics since it is a widely accepted indicator for defects.
The research on measurement and location of partial discharge phenomena started from the early 1940s [1]. A large amount of work has been undertaken regarding PD from modeling to measurement since then. The International Electrotechnical Commission (IEC) adopted the nomenclature “partial discharges” in 1967, which helps to formulate the relevant research [2].
PD can happen wherever there is an insulation defect, from gas insulated to oil insulated to solid insulated equipment. Different equipment with various structures and insulation materials may show different PD characteristics. Reviews of PD for different power equipment exist, e.g., for transformers [3,4] and gas insulated switchgear [5].
Power cables refer to medium voltage and high voltage power cables with the related accessories. They are essential components in power systems. PD detection and analysis plays a vital role for power cable diagnostics. Though reviews about PD are available in the literature, this paper focuses on PD detection and analysis in power cables, which has not been reported in depth previously [6,7]. A large amount theoretical and practical work has been performed for PDs in power cables. From the theoretical point of view, different models with various emphases are proposed to reveal the PD phenomenon. Artificial defects can be created in a laboratory to generate PDs for model validation [8]. In practice, off-line tests for PDs are commonly employed and on-line monitoring is developing fast due to its in-time characteristics. However, interpreting the practical measurement results on defects of cables in service is much more complicated. With development of new application scenarios, e.g., DC cables, more research on cable PD detection and analysis is needed. This paper tries to cover both theoretical and practical aspects of PDs along cables by giving a comprehensive review on the present literature. The paper is organized as follows: partial discharge phenomenon, models, typical location, and propagation along power cables are reviewed in Section 2. Detection is discussed in Section 3. Afterwards, the PD analysis is summarized in Section 4. Section 5 proposes the challenges and Section 6 is the conclusion.

2. Partial Discharge Model

There is no clear distinction between PD models for power cables and other power equipment. Still, details need to be noted and clarified for PD in power cables, e.g., typical PD location. A different feature of PD in cables compared with other equipment is that the cable’s coaxial structure forms a natural propagation channel for electromagnetic waves and since PD is typically a narrow pulse containing high frequency components, it can be regarded as an electromagnetic wave. Thus, PDs originating in the cable can travel within the transmission line. Given the determined cable system as a travelling path, it allows to quantify the PD magnitude in terms of pC and therefore comparing PD magnitudes obtained from different cable systems is possible. This section briefly reviews aspects of the partial discharge phenomenon and model.

2.1. Partial Discharge Phenomenon

Two conditions must be fulfilled for partial discharge occurrence. (1) An initial electron must exist for ionization avalanche. (2) The electric field in the specific spot must be higher than the inception field [9]. The emission of initiatory electrons from the cathode is a stochastic process [10,11]. Thus, after the ignition voltage has been reached, an avalanche will start after a time delay τs. In practice, τs can be expected to be in the order of milliseconds, several orders of magnitude larger than the formation time of an electron avalanche [11,12,13]. In the literature, different discharge mechanisms were described with different nomenclature [11], from “Townsend-like” [14], “streamer-like” [14] to “glow” [15] “pseudo-glow” [15] and “swarming micro partial discharge” [16]. Reference [17] gives an overview of different definitions, in which the author claimed that explanations of all different PD phenomena should be studied in terms of Townsend and/or streamer discharge. Townsend discharge has the large pulse width and short height while streamer discharge has a fast rise time and short tail. Figure 1 shows a typical comparison between these two kinds of discharge. A criterion to distinguish such phenomena is proposed by different researchers, e.g., Penning claimed a streamer when the number of electrons per avalanche is between 108 and 109 [18]. Raether regarded pulse risetime less than 3 ns as an indicator for streamer [19].

2.2. Partial Discharge Model

Partial discharge can be subdivided into corona discharge, surface discharge, and internal discharge [21]. Corona discharge is a discharge caused by the air ionization near the high voltage electrode [22]. It is argued that corona discharges are not directly related with cables but may originate from the cable terminal connections such as switchgear [23]. Surface discharge occurs along the surface of a dielectric material and quite often at the interface between two materials. Power cables, especially cable joints are made of several layers of solid dielectric materials. Thus, surface discharge is one of the main reasons for cable failure [24]. Internal discharge happens within dielectrics with low strength. Crack, contamination, air void, and trees, etc., can cause internal partial discharge.
Various models have been developed for PDs with different study intentions. More literature focuses on the internal PD compared with surface or corona discharge [25], especially discharge in void. For internal PD, a widely used model is the three-capacitance model or abc-model proposed by Whitehead in 1951 [26]. Since then, capacitor model is commonly used to represent the partial discharge process [27,28,29]. Development on the capacitor model was continued by later researchers. For example, integral equations and Monte Carlo simulation are integrated into the abc-model to represent the PD statistical distribution [30,31]. However, there are arguments about the model [32,33,34], which claims that the capacitive network model is not capable of representing the partial discharge physics. One solid reason is that the potential along the cavity surface is not equal when a PD happens [34,35]. Instead, induced charge theory is used to model the partial discharge phenomenon [36,37,38,39]. The induced charge is defined as the difference between the charge on the electrode with and without a discharge event [32]. Rather than circuit based as the capacitor model, this model is field based and analytical solutions can be derived with defined defect geometries in the cable [25]. The main equation is shown in (1), where ρ is volume charge density and σ is surface charge density. λ is a function satisfying the Laplace equation.
Q = λ ρ d V λ ρ d s
However, it is unrealistic for the model to consider a uniform surface charge distribution on the cavity surface. The particle in cell (PIC) method is also used for internal PD simulation [40]. This method was initially accepted as a simulation tool for plasma in the late 1950s. The method follows the trajectories of charged particles and computes the electromagnetic or electrostatic field in a mesh [41]. Macro-quantities such as current density are derived from the velocity and position of these particles [42,43]. Fluid model is another modeling approach for internal PD. This model utilizes drift-diffusion equations to simulate the generation, movement, and dissipation of the charged species (electron, positive and negative ions). Furthermore, Poisson’s equation is needed to determine the distribution of the electric field in the void [44]. Moreover, finite element analysis (FEA) can be used for PD simulation. The advantage of using the FEA method is that field distribution can be obtained, from which an insight of pre-discharge condition can be observed. FEA models can be categorized into electric current model and electrostatic model. In the electric current model, the gas dielectric breakdown within the cavity is simulated by increasing the gas conductivity [25]. In the electrostatic FEA model, a PD event is simulated by increasing the charge density along the void surface until the field across the void becomes lower than the extinction field [45]. Multiphysics can also be added to the model, e.g., the electric field distribution and the temperature. However, long time consumption is the disadvantage of the FEA method [46]. As for surface and corona discharge, similar approaches exist. RC network is used for modeling corona and surface discharge from the equivalent electric circuit point of view, corresponding to the abc-model for internal discharge [47,48]. Particle in cell (PIC) model, fluid model, and FEA based models are also used for corona and surface discharges. The advantages and disadvantages for each model are summarized in Table 1.
The chosen modeling approach mainly depends on the researcher’s objective. For instance, efficient simulation for macroscopic parameters, e.g., repetition rate, without representing the PD physical process can be achieved by the abc-model. While, research on microscopic processes incorporating charged particles can refer to the fluid model. It should be noted that there is no perfect model yet and great potential exists to improve the modeling approach and this is discussed further in Section 5.

2.3. Partial Discharge Location and Propagation

PD often occurs in accessories of power cables, e.g., joints and termination [24]. Due to more complex structure and material design, the electrical field can be considerably higher to trigger PD to occur. A stress-relief cone with a specially designed shape and dielectric material is designed to reduce the electric stress in the accessories. A typical cable joint design is shown in Figure 2. Moreover, improper handling during installation can create defects leading to PD also. It has been reported that for the high voltage corrugated aluminum sheath cables, discharge is observed between the sheath and water blocking layer, whose mechanism is still under investigation [57,58]. Figure 3 shows these typical phenomena.
As long as PD occurs in power cables, it will propagate along the cable, which shall be considered as a transmission line. Lumped parameters model [60], Bergeron model [61], and frequency dependent model [62] are the three mainly used models to describe the cable’s transmission line behavior. The lumped parameter model can only be used when the cable length is short enough that the propagation time of PD along the cable can be ignored. When the cable is sufficiently long, the distributed parameter model shall be used. The Bergeron model can reveal the time delay along the cable caused by PD propagation. However, it considers the line losses by lumped resistance at cable ends. The frequency dependent model is the most accurate one to model a transmission line in which the distributed parameters vary with frequency. For a single-core cable, there is one propagation path for the PD between the conductor and the earth shield. For multi-core cables, the propagation modes become complex and mathematical treatment can be utilized to decouple these channels. For instance, phase to phase and the shield to phase channel can be accessed for the three-core cables [63]. For PDs in the power cable, the propagation effect is vital since it affects the senor location, detection accuracy, etc.

3. Partial Discharge Detection

A power cable normally has to experience several tests from manufacturing to service, such as type test for the qualification, sample test and routine test in the production period, and after lay test. There are different standards existing to regulate these tests from IEC standards, European standards to IEEE standards. The most applied international standards can be categorized according to nominal voltage:
  • 1 and 3 kV, IEC 60502-1,
  • 6–30 kV, IEC 60502-2/4 and VDE 278,
  • 30–150 kV, IEC 60840,
  • 150–500 kV, IEC 62067.
Although the contents differ from different standards, a partial discharge test exists in all standards above 3 kV and it plays a crucial role in the cable tests.
Partial discharge is such a complex phenomenon that it is extremely difficult to reproduce the PD detection measurement. A specimen tested in rapid succession often exhibits variation in the detected discharge amplitudes at the inception voltage. Additionally, the inception and extinction voltage for discharge slightly differ for every applied voltage excursion [64]. The reasons may be in part due to changes in the cavity configuration, e.g., wax formation within the voids in the oil-impregnated insulation cable, statistical variations in the discharge process, vapor pressure, and gas composition changes within the cavities. The nature of the cavity wall may change due to pitting and erosion as well as the deposition of compounds on the walls [64,65,66]. Despite the difficulties, PD is still employed as a parameter for condition measurement [67,68,69]. Compared with oil/paper insulated cables, polymeric cables are strongly susceptible to degradation induced by PD. Thus, the polymeric cables are required to be free of PD at operating voltage with a detection sensitivity of 5 pC [70].
Partial discharge in the solid insulation is a transient process and it can reach several hundred MHz [71], even up to 1 GHz [70,72]. The measured charge is so-called apparent charge [27]. Both inductive and capacitive sensors can be applied for PD detection, which will be discussed in detail below.

3.1. Off-Line Test

There are on-line PD tests and off-line PD tests for power cables. The partial discharge test circuit was reviewed in [15]. For the off-line test, several options are available with the difference of how to energize the cable. Since the power source can be the bottleneck for the off-line test and the off-load cable can be considered as a capacitor, it is crucial to decrease the demanded capacitive power from the source to energize the cable and hence to reduce the cost and weight of the test equipment. Three types of tests are generally adopted for the off-line test, namely the alternating current (AC) voltage test, very low frequency (VLF, for instance 0.1 Hz) test, and damped AC (DAC) test. The methods are listed in Table 2 [73]. To ensure well comparable test results, the PD measuring circuit is specified in Standard IEC 60270. The PD measuring circuit commonly used is shown in Figure 4, where U is the high-voltage supply, Zmi is the input impedance of measurement system, CC is the connecting cable, Ca is the test object, Ck is the coupling capacitor, CD is the coupling device, MI is the measurement instrument, and Z is the filter.
The AC voltage test: the resonant test system normally connects an inductor in series with the tested cable to form a series resonant circuit [73,74,75,76,77]. The frequency can be adjusted to fulfill the resonant condition, as schematically shown in Figure 5 [78]. The system consists of a three-phase source, the frequency converter (normal topology is converter and inverter), exciting transformer, the series resonant reactor, the capacitive divider, and the cable under test. The frequency converter has three-phase input while one-phase output to reduce the demanded supply capacity. The exciter transformer can be excited with variable voltage and frequency. The exciter transformer energizes the series resonant reactor and the cable capacitance. With this method, frequency is normally between 20 and 300 Hz. Otherwise, the inductor value can be tuned to form a resonant circuit with the cable around 50 Hz. The frequency tuned method is preferred since it can bring the specific weight of the testing device down to 1 kg/kVA [79]. Care must be taken for PD measurement since power transistors switching may generate noise.
VLF: the schematic circuit for the VLF test is show in Figure 6 [80]. Since the power P demanded to energize the cable is proportional to the test frequency f as
P = 2 π f C U ²
where C is the cable capacitance, VLF can reduce the test power significantly. The voltage levels for installation and acceptance test are based on the most used worldwide practices from 2U0 to 3U0, where U0 is the rated rms phase to ground voltage [81]. The VLF voltage can be sinusoidal, cosine-rectangle, or trapezoidal [82]. The test voltage and test duration are the main test parameters [83]. For DAC, the applied voltage has the oscillation frequency from several tens Hz to several hundred Hz [84].
Damped AC test: two commercially available systems are used for the oscillating voltage waveform procedure [83]: (1) oscillating waveform test system (OWTS) [85]; (2) complex discharge analysis (CDA) [86]. The principle of OWTS test is shown in Figure 7 [59]. The cable is charged with a DC power supply over several seconds to the rated voltage, after which a specially designed solid-state switch connects an air-core inductor to the cable in a closure time of <1 µs. The circuit will be resonant at the frequency dependent on the fixed air-core inductor and the tested cable capacitance. The inductor is designed to have a low loss factor and the resonant frequency is from 50 Hz to 1 kHz. The CDA system has quite a similar idea compared with OWTS. The charging time for the cable system is in the order of 10 s to keep a low power demand. The tail time should be chosen around 10 milli-seconds, which corresponds to half of a power frequency cycle. Consequently, the PD detection must be performed during the tail time of the transient voltage [86].
The question for these methods is whether they can represent the condition under power frequency energizing? Three parameters can be investigated: the PD inception voltage (PDIV), the PD magnitude, and the PD patterns [87]. However, existing investigations are often based on various defects without statistical validation, often leading to contradictory results [88]. Dutch experience [89] used the VLF from 1U0 to 2U0 depending on the circumstances. Reference [90] stated that VLF will fasten the increase of electric tree compared with 50 Hz AC while it is less stressful if there is no defect. References [59,91] showed that oscillating voltages lead to higher ignition voltages for the electrical trees and water trees (about 1.7–2.5 times higher of inception voltage than 50 Hz). While, for 0.1 Hz sinusoidal voltage, the tree ignition voltage is about 1.6–2 times higher than the value under 50 Hz. Reference [85] claimed that the OWTS method gives the PD magnitudes and inception voltage in the same range as 50 Hz AC energizing based on measurement of 6 kV plastic insulated cable accessories for different defects. However, higher PDIV of OWTS on cable samples is reported by [87]. The test on cavity in XLPE showed that the use of OWTS voltage seems to provide PD inception voltage values well above (up to 200%) those measured at 50 Hz [92]. The DAC method was compared with 50 Hz and similar PD behavior has been observed based on the XLPE cable test [93]. The CDA system manufacturer has proposed recommendations for its usage [94]. In [95], PD of cavities in cast polyester was performed and it was found that the PD inception voltage is not dependent on the applied voltage frequency-shape. However, in [96,97], the authors claimed that 25–30% difference exists when testing PDIV and PDEV (partial discharge extinction voltage) at different frequencies for PE material. In general, both PDIV and PDEV for internal and surface PDs have a non-monotone behavior from 0.01 to 1000 Hz. In [98], it was described that the PDIV at 50 Hz is about 80% of 0.1 Hz measurement based on XLPE cable test. A test on XLPE material showed that although differences are limited, PDIV seems to be lower when testing with a lower frequency rather than a higher one [88]. Field experiences (paper, EPR, and XLPE cable) [99] showed that neither 0.1 Hz nor DAC can always give close inception PD voltage compared with 50 Hz and the maximum difference is about 200%. The PD tests mentioned above are summarized in Table 3.
To summarize, there are three main off-line PD testing methods as in Table 2. The applied voltage shapes differ from each other. Yet, the PD measurement is similar by recording at the energizing side. PD location can be derived based on the time domain reflectometry. Though they are accepted as an effective tool to diagnose cables with the measured PD result, it is still not completely clear how to correlate their measured result with each other or with the cable performance under 50 Hz AC.

3.2. On-Line Test

On-line PD measurement is usually more costly. Thus, it is mainly for assets with high importance such as high voltage cable accessories [67,100]. Reference [101] described an on-line system for medium voltage cable. It is not unusual that cable defects generate PDs over a long period without failure. On-line tests offer the opportunity to collect all PD measurement data. Such data must be analyzed in a statistical way. Data such as discharge number, intensity, density, and pattern need to be recorded per PD location [102]. Field tests also show that different off-line methods may give different PD locations. This fact reflects the nature of the insulating medium and highlights that a clear identification of defective points can be obtained if one considers not only the PD level associated with the defect but also other diagnostic indicators such as the repetition of the PD activity in the specific location [99]. With the continuous monitoring ability under the rated working condition, the on-line partial discharge condition assessment of high voltage and medium voltage cables is becoming more widespread in power electric systems [103]. It is worth noting that more benefits can be obtained if the PD location can be pinpointed by an on-line testing system for cables. Due to the higher attenuation and complicated cross-bonding paths for PD, PD location for medium voltage cables over length is more feasible and PD on-line monitoring for high voltage cables is mainly focusing on accessories. The general approach to locate PD online is to install the time-synchronized sensors at both ends of the cable section to be monitored and the location of PD can be determined by the arrival time difference at the two installed sensors [104].

3.3. Sensors

The discharge is accompanied by (1) a current caused by charge displacement; (2) radiation emitted by excited particles falling back to a lower energy state; (3) ultra-sonic sound; (4) heat generated by particle impact; (5) chemical reactions [11]. Thus, the detection can be divided as electrical discharge detection and nonelectrical discharge detection. The nonelectrical phenomena are chemical reaction, gas pressure, heat, sound, and light, from which the last two are of practical importance [105]. Photography and acoustic emission (AE) sensors can be used for detection. Dissolved gas analysis (DGA) is related to the chemical transformation. While for the electrical discharge detection, inductive and capacitive sensors are used. Refs. [106,107,108] summarized inductive coupling (a sensor that picks up the magnetic field of PD), galvanic coupling (PD signal is measured as the voltage drop across an impedance inserted into the current path), and capacitive coupling (a sensor that picks up the electric field of PD); directional coupler is also introduced as an integrated sensor in the cable joint with both capacitive and inductive coupling. When the sensor is considered by frequency range, then there are AE sensors covering the frequency in 20–500 kHz; high frequency current transformer (HFCT) with the frequency range of 30 kHz–300 MHz; very high frequency (VHF) methods which measure frequency range of 30–300 MHz; ultra-high frequency (UHF) method with window type sensor measuring frequency range from 300 to 3000 MHz [109]. Typical sensors used for PD detection along power cables are summarized in Table 4 with advantages and disadvantages. Their locations with respect to the cable system are indicated in Figure 8. The inductive sensors need a current path for PD while the coupling capacitor has issues for installation since, for example, it needs to interrupt the cable shield. AE and UHF sensors are non-contact sensors. However, the attenuation needs to be considered. An ultraviolet imager is easy to use but it can detect only corona discharge at cable termination. New progress has been made by researchers to develop novel sensors for convenient and accurate measurements in field, e.g., the spherical electromagnetic sensor [110], which is not included in Table 4.

4. Partial Discharge Analysis

4.1. Quantities and Algorithms for Analysis

Standard quantities are used for PD analysis: inception voltage, extinction voltage; maximum and minimum PD amplitude in mV or pC. For AC test, the time and phase information of applied voltage are utilized, such as inception and extinction phase of the applied voltage (the phase interval defined as difference of the two), mean number of discharges per cycle of the applied voltage, mean integrated charge quantity, or mean integrated signal height per cycle of the test voltage [118]. Phase-resolved PD (PRPD) and phase resolved pulse sequence (PRPS) are two typical patterns to analyze PD as shown in Figure 9. The PRPD patterns show phase, pulse count, and charge magnitude information and PRPS includes PD intensity, time of occurrence, and PD phase. Another alternative approach is to consider the dynamic between consecutive PD pulses proposed by Hoof and Patsch with the name of “Pulse Sequence Analysis” (PSA) [119]. A PSA pattern is usually constructed with the instantaneous voltage differences/time difference between consecutive pulses, as shown in Figure 10. Compared to AC, the major issue for PD measurements under DC is the absence of phase information. If there is ripple in the applied DC voltage, it can be utilized to help PD analysis as a phase reference, similarly to AC [120]. For DC without noticeable ripple, one can observe only a series of impulses. Many algorithms and techniques are used for PD extraction and interpretation [121,122].
Denoising, pattern recognition, arrival time estimation, and PD location are the main areas where algorithms are crucial for analysis. Considering the noise reduction, there are mainly three types of noises in PD detection: white noise, sinusoidal noise, and pulse interference. Wavelet analysis, empirical mode decomposition (EMD), and mathematical morphology methods are generally used to treat white noise and the filtering technique is used to remove sinusoidal noise [123]. Denoising algorithms that are effective also for pulse interference are not trivial. Yet, researchers proposed methods that are valid in their test, such as k-means clustering and recursive continuous s-shaped algorithm [124,125]. Pattern recognition is usually to classify different PD types, e.g., PD from different defects in cable joints. Fuzzy logic [126], support vector machine, genetic algorithm, and neural network [127] are used for this purpose. New methods are being continuously proposed such as rough set theory [128], deep learning, and texture feature-based algorithms [129,130]. PD arrival time estimation is vital for its location along cables. The available methods include the trigger level based method, signal energy based method, Akaike information criterion (AIC) method, Gabor centroid method, phase-based method [131], and multiple signal classification algorithm [132]. Each method may have different performance under various noise conditions or PD shapes. The PD location algorithm is essentially used to determine the time difference between the detected PD and its reference. Thus, by application of arrival time estimation on the individual pulses, the location can be derived. Moreover, methods based on the relation between the studied pulses were researched to locate PD, such as the correlation algorithm [133] and phase difference method [134]. It can be foreseen that with the rapid development of information computer technology and its application in various industries, PD analysis can be improved dramatically in the future.

4.2. PD Characteristics for Different Cables

There are basically two kinds of cable structure: laminar dielectric structure (with multiple layers of paper impregnated with a dielectric fluid) and solid dielectric structure (a metallic conductor covered with a semiconducting screen over which a solid dielectric insulation is extruded) [136]. Reference [137] claimed that the PDs between paper layers are mainly the Townsend discharge; and when a metal becomes one of the electrodes, streamers can be developed from some of the Townsend discharges. If a deep cavity experiences high enough over-voltage between two ionizing events, the streamer releases more energy at one time and it is more harmful to the paper insulated cable. For solid dielectric material, a void is usually created to study the partial discharge [11,37,138,139,140]. Reference [141] stated that for the situation of a flat cavity, the aging process is generally agreed on as follows. (1) The dissociation products of air due to PD increases the conductivity of the cavity surface. (2) The surface roughness increases caused by charge carrier attack and deposition from by-products. (3) PD activities produce localized solid by-products, i.e., crystals. (4) Such solid by-products further increase the field to intensify the PD, initiating the tree growth. (5) Finally, a breakdown may happen due to the tree growth. If fillers are present in the dielectric, the insulation between filler particles is normally most severely degraded. For flat cavities in polyethylene, the author in [11] discovered a featured pulse shape relating to each aging step. At the beginning, streamer-like narrow pulses with high magnitude show in the cavity. Afterwards, a conductive surface appears across the cavity, and the PD develops into Townsend-like, which is wide with low amplitude. When crystal by-products appear, the PD evolves to pulse with small amplitude and intermediate width.

4.3. PD with Temperature and Load

For some insulation defects, the operating condition of the cable will influence the PD testing [142]. The test result in [142] showed for voids in paper insulated cable, the PD decreased obviously if the cable load increased. Additionally, the PD magnitude and the number of PD sites vary as the cable load changes. While for cavities and electrical treeing in XLPE cable, PD was found not to be significantly influenced by the cable loading conditions. However, it is not the case for interfacial defects. Both the PD magnitude and the number of PD sites are a function of the cable temperature. PD tends to increase as the cable load increases. A recent test shows that with the temperature increase, PDIV may decrease slightly for XLPE and EPR [143].

4.4. PD under AC and DC

With the increasing application of HVDC projects and emergence of distributed DC systems, PD behavior under DC is starting to draw people’s attention. Electric field distribution under AC depends on the material’s permittivity while the electric field in DC cables is dependent on conductivity, which in turn relates to the electric field and temperature. The complicated charge injection conduction mechanisms can be modeled by a bipolar charge transport model at the interface between electrode and dielectric [144]. PD in AC cables has been extensively studied while much less is available for DC cables. Experiments show that the PD repetition rate under DC is much lower than that under AC. An analytical model for this explanation can be found in [145,146] based on the abc-model while a qualitative description is available in [143]. Research also confirmed that the PDIV in DC can be much higher than in AC for the same defect at room temperature. However, the PDIV in DC can become lower than that in AC for higher temperature, at least for the typical XLPE materials used from cables [143,147]. The reason is that temperature rise can increase the dielectric conductivity significantly [143]. Regarding the PD magnitude, its value under AC is higher than under DC. The reason is considered to be the statistical time delay for the firing electron [143,145]. Taking the PD in cavity as an example, the PD will occur after a statistical time delay when the electric field exceeds the PDIV. Under AC voltage, the delay may wait for a further increased voltage, leading to a larger PD. While under DC voltage, a constant residual field can be assumed after PD. Thus, it is plausible to get a smaller mean PD magnitude at DC energization. Voltage polarity inversion can lead to PD and cause premature insulation breakdown. It can be dangerous for cable life when operation transient occurs a few times per day. Faster DC voltage rise rate leads to higher PD cumulative damage [148].

4.5. Experience on PD Development

Study [143] shows that actual failed cables have experienced a drop in PD intensity before complete failure. The reason behind this could be that the internal arcing had carbonized the dielectric to such a degree that the resistive component is low enough to prevent a voltage build-up across the void. This low resistive component would also increase current flow, leading to additional heating and resultant insulation damage. Yet, this phenomenon has not been verified completely by cable partial discharge observation. To observe the trend of partial discharge is of vital importance for condition monitoring [149]. Reference [150] showed a 2-year experience on MV paper insulated cable with an off-line VLF PD test method, in which it was claimed that the high and concentrated discharges are often located to places at or adjacent to joints. Different phases often show similar PD behavior. Repeated measurement sometimes showed confusing results: PD magnitude and location may change. Ninety percent of PDs are with the magnitude of 5000 pC which is regarded as a “normal” level, however, cable may fail even with PD between 1000 and 4000 pC. Some cable may even fail without PD behavior. Though some literature is published [140,151,152], it is important to further study the cable aging mechanisms with PD. Reference [153] shared an experience with on-line PD monitoring for paper insulated cable: 12 cable sections out of 17 showed clear rising levels of PD activity within 5–150 days before failure. Although the activity rate appeared to fluctuate periodically through the day, there is no direct relation with the load profile (this non-direct relationship is also mentioned in [154]). Occasionally, the activity rate first climbed up and then decreased prior to the failure with or without PD magnitude increase. When part of the circuit is switched off and the other parts re-energized, a significant step down change in discharge activity can be observed. Furthermore, when the circuit is re-energized after repairs, a rise in discharge activity for a few days can be often observed due to the reason that the internal pressures in the cable recover. This indicates that the off-line and off-load PD test performed when the circuit has been de-energized for some time may not be comparable with its on-line conditions. Reference [155] compared on-line PD measurement with HFCT and offline test with OWTS; results showed 75% agreement. Reference [156] stated that online PD measurement could be used as a pre-selecting method for off-line diagnostics. Reference [157] reviewed six cases with on-line PD monitoring systems and it stated that the number of discharges per second, and PD density change significantly depending on the type of developing fault. Some defects deteriorate slowly, with a high PD frequency and intensity. Yet there are also weak spots that result suddenly into failure. Most weak spots discharge at a low level first and then high frequency, high intensity discharges develop. In general conclusion, it takes years (on average) for a weak spot in PILC to develop into a fault while for XLPE cable, this can be a couple of days to months (on average) [104].

5. Challenge and Discussion

PD modeling still needs improvement. On one hand, a balanced model between efficiency and physical accuracy needs to be developed. On the other hand, PD nature is not completely revealed by the available models. Plasma dynamics and plasma chemistry started to draw researcher’s attention to better understand PD’s mechanism [44,158] since these models focus more on PD internal physical process rather than the macroparameter from the outside. Only full PD mechanism interpretation can help explain phenomenon. However, the mechanism interpretation calls for new measurement methods, especially on the microscale. It is desired to obtain the relevant quantities relating to the PD process, such as electric field and gas pressure variation at the PD spot.
Correlation between PD tests on samples in the laboratory and PD measurements in the field should be strengthened. Denoising needs to be improved from both sensor and algorithm aspects. Precise diagnostics based on PD are still challenging since the correlation between PD and aging till failure is not clear.
PDs in new scenarios need to be studied further. Compared with AC, PD under DC awaits to be further explored. PD for different cable insulation materials under extreme conditions need to be studied further accompanying its application, e.g., superconducting cable, PD of cable in extreme cold environments, PD of cable in vacuum pressure [159,160].
Facing so many aspects, it is vital to be clear about the objective in practice. For instance, cable circuit connections and long-distance propagation may make characteristics of different types of PDs no longer detectable. Thus, to find and locate PDs for power cables would be of more significance than to distinguish their type.

6. Conclusions

The paper reviewed the mechanism and test aspects of PDs along power cables. PD phenomena can be categorized into Townsend or streamer. Various PD models were introduced from a capacitor model to analytical model to FEA based ones with their pros and cons. Specific model can be chosen to use according to the study purpose. Off-line and on-line PD measurement systems were summarized. For off-line tests, alternating current voltage with resonant test system, damped alternating current, and very low frequencies down to 0.01 Hz method are widely used. On-line systems are getting more popular now. Sensors (mainly capacitive and inductive for electrical character of PD measurement) used for PD measurement were also discussed. For PD interpretation, evaluation parameters, affecting factors for PD behavior, and the trend of observation were discussed. Although PD is a topic with a long history, there are still many challenges to be solved.

Author Contributions

Conceptualization, X.Z., B.P., S.L., Y.L. (Yaxin Liu) and Y.L. (Yifan Liu); methodology, P.X.; software, Y.L. (Yan Li); validation, Y.L. (Yan Li), Y.L. (Yifan Liu) and L.Q.; formal analysis, Y.L. (Yan Li); investigation, Y.L. (Yan Li); resources, Y.L. (Yan Li); data curation, Y.L. (Yan Li); writing original draft preparation, Y.L. (Yan Li); writing—review and editing, Y.L. (Yan Li); visualization, Y.L. (Yan Li); supervision, Q.X.; project administration, X.Z.; funding acquisition, X.Z. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Fundamental Research Funds for the Central Universities under Grant 2018MS081.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Nattrass, D.A. Partial discharge. XVII. The early history of partial discharge research. IEEE Electr. Insul. Mag. 1993, 9, 27–31. [Google Scholar] [CrossRef]
  2. Kind, D.; Konig, D. AC breakdown of epoxy resins by partial discharges in voids. IEEE Trans. Electr. Insul. 1968, ei-3, 40–46. [Google Scholar] [CrossRef]
  3. Hussain, M.R.; Refaat, S.S.; Abu-Rub, H. Overview and partial discharge analysis of power transformers: A literature review. IEEE Access 2021, 9, 64587–64605. [Google Scholar] [CrossRef]
  4. Chen, Z. Review of direction of arrival estimation algorithms for partial discharge localization in transformers. IET Sci. Meas. Technol. 2019, 13, 529–535. [Google Scholar] [CrossRef]
  5. Metwally, L. Status review on partial discharge measurement techniques in gas-insulated switchgear/lines. Electr. Power Syst. Res. 2004, 69, 25–36. [Google Scholar] [CrossRef]
  6. Chen, G.; Pan, C.; Tang, J. Numerical modeling of partial discharges in a solid dielectric-bounded cavity: A review. IEEE Trans. Dielectr. Electr. Insul. 2019, 26, 981–1000. [Google Scholar]
  7. Refaat, S.S.; Shams, M.A. A review of partial discharge detection, diagnosis techniques in high voltage power cables. In Proceedings of the 2018 IEEE 12th International Conference on Compatibility, Power Electronics and Power Engineering, Doha, Qatar, 10–12 April 2018; IEEE: Piscataway, NJ, USA, 2018. [Google Scholar]
  8. Seo, I.J.; Khan, U.A.; Hwang, J.S.; Lee, J.G.; Koo, J.Y. Identification of insulation defects based on chaotic analysis of partial discharge in HVDC superconducting cable. IEEE Trans. Appl. Supercond. 2015, 25, 1–5. [Google Scholar] [CrossRef]
  9. Fruth, B. Partial discharge mechanisms in solid insulation systems. In Proceedings of the 4th International Conference on Conduction and Breakdown in Solid Dielectrics, Sestri Levante, Italy, 22–25 June 1992; IEEE: Piscataway, NJ, USA, 1992. [Google Scholar]
  10. Christophorou, L.G.; Pinnaduwage, L.A. Basic physics of gaseous dielectrics. IEEE Trans. Electr. Insul. 1990, 25, 55–74. [Google Scholar] [CrossRef]
  11. Morshuis, P. Partial Discharge Mechanisms: Mechanisms Leading to Breakdown, Analyzed by Fast Electrical and Optical Measurements. Ph.D. Thesis, Delft University of Technology, Delft, The Netherlands, 1993. [Google Scholar]
  12. Miyoshi, Y. Electrical breakdown of gases: Edited by J.M. Meek and J.D. Craggs, Wiley, New York, 1978, 878 pages. J. Electrost. 1979, 6, 385391. [Google Scholar] [CrossRef]
  13. Dissado, L.A.; Fothergill, J.C. Electrical degradation and breakdown in polymers. In IEE Materials and Devices Series; IET Digital Library: London, UK, 1992; pp. 287–355. [Google Scholar]
  14. Devins, J.C. The 1984 J.B. whitehead memorial lecture the physics of partial discharges in solid dielectrics. IEEE Trans. Electr. Insul. 1984, EI-19, 475–495. [Google Scholar] [CrossRef]
  15. Bartnikas, R. A commentary on partial discharge measurement and detection. IEEE Trans. Electr. Insul. 1987, EI-22, 629–653. [Google Scholar] [CrossRef]
  16. Tanaka, T. Internal partial discharge and material degradation. IEEE Trans. Electr. Insul. 1986, EI-21, 899–905. [Google Scholar] [CrossRef]
  17. Danikas, M.G. The definitions used for partial discharge phenomena. IEEE Trans. Electr. Insul. 1993, 28, 1075–1081. [Google Scholar] [CrossRef]
  18. Penning, M.F. Electrical discharges in gases. Am. J. Phys. 1958, 26, 651. [Google Scholar] [CrossRef]
  19. Raether, H. Electron Avalanches and Breakdown in Gases; Butterworths: Washington, WA, USA, 1964; pp. 73–191. [Google Scholar]
  20. Fromm, U.; Kreuger, F.H. Statistical behaviour of internal partial discharges at DC voltage. Jpn. J. Appl. Physics Pt Regul. Pap. Short Notes 1994, 33, 6708–6715. [Google Scholar] [CrossRef]
  21. Majidi, M.; Fadali, M.S.; Etezadi-Amoli, M.; Oskuoee, M. Partial discharge pattern recognition via sparse representation and ANN. IEEE Trans. Dielectr. Electr. Insul. 2015, 22, 1061–1070. [Google Scholar] [CrossRef]
  22. Shafiq, M.; Hussain, G.A.; Kütt, L.; Lehtonen, M. Effect of geometrical parameters on high frequency performance of Rogowski coil for partial discharge measurements. Measurement 2014, 49, 126–137. [Google Scholar] [CrossRef]
  23. IEEE. IEEE Guide for Partial Discharge Testing of Shielded Power Cable Systems in a Field Environment; IEEE: Piscataway, NJ, USA, 2007; Std 400.3-2006; pp. 1–44. [Google Scholar]
  24. Luo, J.H.; Shi, J.K.; Cao, J.; Yuan, J. Study on surface discharge of composite dielectric in XLPE power cable joints. In Proceedings of the Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, Cincinnati, OH, USA, 18 October 2001. [Google Scholar]
  25. Albarracin, R.; Rodriguez-Serna, J.M.; Masud, A.A. Finite-element-analysis models for numerical simulation of partial discharges in spherical cavities within solid dielectrics: A review and a novel method. High Volt. 2020, 5, 556–568. [Google Scholar]
  26. Eyring; Henry. Dielectric breakdown of solids (Whitehead, S.). J. Chem. Educ. 1952, 29, 108. [Google Scholar] [CrossRef]
  27. Kuffel, E.; Kuffel, J.; Zaengl, W.S. High Voltage Engineering Fundamentals; Pergamon Press: Oxford, UK, 1984; pp. 367–394. [Google Scholar]
  28. Achillides, Z.; Georghiou, G.E.; Kyriakides, E. Partial discharges and associated transients: The induced charge concept versus capacitive modeling. IEEE Trans. Dielectr. Electr. Insul. 2008, 15, 1507–1516. [Google Scholar] [CrossRef]
  29. Shi, C.; Czaszejko, T. Partial discharge test circuit as a spark-gap transmitter. IEEE Electr. Insul. Mag. 2011, 27, 36–44. [Google Scholar]
  30. Hikita, M.; Yamada, K.; Nakamura, A.; Mizutani, T.; Oohasi, A.; Ieda, M. Measurements of partial discharges by computer and analysis of partial discharge distribution by the Monte Carlo method. IEEE Trans. Electr. Insul. 1990, 25, 453–468. [Google Scholar] [CrossRef]
  31. Uehara, H.; Okamoto, T. Modeling and analysis of partial discharge phenomena using integral equations. IEEE Trans. Dielectr. Electr. Insul. 2020, 27, 1915–1923. [Google Scholar] [CrossRef]
  32. Crichton, G.C.; Karlsson, P.W.; Pedersen, A. Partial discharges in ellipsoidal and spheroidal voids. IEEE Trans. Electr. Insul. 1989, 24, 335–342. [Google Scholar] [CrossRef] [Green Version]
  33. Pedersen, A.; Crichton, G.C.; Mcallister, I.W. The theory and measurement of partial discharge transients. IEEE Trans. Electr. Insul. 1991, 26, 487–497. [Google Scholar] [CrossRef] [Green Version]
  34. Mcallister, I.W. Electric field theory and the fallacy of void capacitance. IEEE Trans. Electr. Insul. 1991, 26, 458–459. [Google Scholar] [CrossRef] [Green Version]
  35. Danikas, M.G.; McAllister, I.W.; Crichton, G.C.; Pedersen, A. Discussion: Partial discharges in ellipsoidal and spheroidal voids. IEEE Trans. Electr. Insul. 1991, 26, 537–539. [Google Scholar] [CrossRef]
  36. Pedersen, A.; Crichton, C.; McAllister, W.I. Partial discharge detection: Theoretical and practical aspects. Sci. Meas. Technol. IEE Proc. 1995, 142, 29–36. [Google Scholar] [CrossRef]
  37. Danikas, M.G. Discharge studies in solid insulation voids. In Proceedings of the Conference on Electrical Insulation & Dielectric Phenomena, Pocono Manor, PA, USA, 28–31 October 1990; IEEE: Piscataway, NJ, USA, 1990. [Google Scholar]
  38. Kolev, N.P.; Gadjeva, E.D.; Danikas, M.G.; Gourov, N.R. An approach to develop a partial discharge investigation. In Proceedings of the Electrical Insulation Conference and Electrical Manufacturing and Coil Winding Conference, Cincinnati, OH, USA, 28 October 1999. [Google Scholar]
  39. Boggs, S.A. Partial discharge III. Cavity-induced PD in solid dielectrics. IEEE Electr. Insul. Mag. 1990, 6, 11–16. [Google Scholar] [CrossRef]
  40. Deshpande, A.S.; Saxena, A.; Umbarkar, S.B.; Mangalvedekar, H.A.; Kazi, F.S.; Singh, N.M.; Cheeran, A.N. Electrodynamic analysis and characterisation of void discharge using particle in cell code. In Proceedings of the 2013 19th IEEE Pulsed Power Conference, San Francisco, CA, USA, 16–21 June 2013. [Google Scholar]
  41. Dawson, J.M. Particle simulation of plasmas. Rev. Mod. Phys. 1983, 55, 403. [Google Scholar] [CrossRef]
  42. Tskhakaya, D.; Matyash, K.; Schneider, R.; Taccogna, F. The particle-in-cell method. Contrib. Plasma Phys. 2008, 47, 563–594. [Google Scholar] [CrossRef]
  43. Wu, F.F.; Liao, R.J.; Wang, K.; Yang, L.J.; Grzybowski, S. Numerical simulation of the characteristics of heavy particles in bar-plate dc positive corona discharge based on a hybrid model. IEEE Trans. Plasma Sci. 2014, 42, 868–878. [Google Scholar] [CrossRef]
  44. Algwari, Q.T.; Saleh, D.N. Numerical modeling of partial discharge in a void cavity within high-voltage cable insulation. IEEE Trans. Plasma Sci. 2021, 49, 1536–1542. [Google Scholar] [CrossRef]
  45. Illias, H.A.; Tunio, M.A.; Bakar, A.A.; Mokhlis, H.; Chen, G. Partial discharge behaviours within a void-dielectric system under square waveform applied voltage stress. IET Sci. Meas. Technol. 2014, 8, 81–88. [Google Scholar] [CrossRef]
  46. Illias, H.A.; Chen, G.; Lewin, P.L. Comparison between three-capacitance, analytical-based and finite element analysis partial discharge models in condition monitoring. IEEE Trans. Dielectr. Electr. Insul. 2017, 24, 99–109. [Google Scholar] [CrossRef]
  47. Au, M.; Agba, B.L.; Gagnon, F. A model of electromagnetic interferences induced by corona discharges for wireless channels in substation environments. IEEE Trans. Electromagn. Compat. 2015, 57, 1–10. [Google Scholar] [CrossRef]
  48. Kogan, V.; Dawson, F.; Gao, G.; Nindra, B. Surface corona suppression in high voltage stator winding end turns. In Proceedings of the Electrical Electronics Insulation Conference, Electrical Manufacturing & Coil Winding Conference, Rosemont, IL, USA, 18–21 September 1995; IEEE: Piscataway, NJ, USA, 1995. [Google Scholar]
  49. Borghei, M.; Ghassemi, M.; Rodríguez-Serna, J.M.; Albarracín-Sánchez, R. A finite element analysis and an improved induced charge concept for partial discharge modeling. IEEE Trans. Power Deliv. 2020, 36, 2570–2581. [Google Scholar] [CrossRef]
  50. Li, Y.; Huang, H.Y.; Hu, Y.; Zhang, W.D. Microscopic simulation and characteristics analysis of surface discharge based on PIC-MCC method. In Proceedings of the 2018 Condition Monitoring and Diagnosis, Perth, WA, Australia, 23–26 September 2018. [Google Scholar]
  51. Zhu, T.; Wang, S.; Guo, Z.; Wang, S.; Zhang, N. Study on the corona discharge ionized field of UHVdc based on particle-in-cell iterative method. IEEE Trans. Magn. 2019, 55, 1–4. [Google Scholar] [CrossRef]
  52. Li, X.; Sun, A.; Teunissen, J. A Computational study of negative surface discharges: Characteristics of surface streamers and surface charges. IEEE Trans. Dielectr. Electr. Insul. 2020, 27, 1178–1186. [Google Scholar] [CrossRef]
  53. Pan, C.; Meng, Y.P.; Wu, K.; Han, Z.H.; Qin, K.; Cheng, Y.H. Simulation of partial discharge sequences using fluid equations. J. Phys. d-Appl. Phys. 2011, 44, 1417–1425. [Google Scholar] [CrossRef]
  54. Pan, C.; Tang, J.; Zeng, F.P. Numerical Modeling of Partial Discharge Development Process. In Plasma Science and Technology—Basic Fundamentals and Modern Applications; Jelassi, H., Benredjem, D., Eds.; IntechOpen: London, UK, 2018; pp. 110–127. [Google Scholar]
  55. Lee, S.H.; Lee, S.Y.; Chung, Y.K.; Park, I.H. Finite-element analysis of corona discharge onset in air with artificial diffusion scheme and under fowler–nordheim electron emission. IEEE Trans. Magn. 2007, 43, 1453–1456. [Google Scholar] [CrossRef]
  56. Bouazabia, S.; Hadjout, L.; Boulahbal, M. Modelling of a surface discharge in a concentric circle system under alternating voltage. In Proceedings of the Electrical Insulation Conference, Montreal, QC, Canada, 31 May–3 June 2009; IEEE: Piscataway, NJ, USA, 2009. [Google Scholar]
  57. Cao, J.P.; Wang, S.H.; Li, N.Y.; Huang, B.; Zhu, Y.Z.; Chen, J.; Liu, Y.; Wang, X.; Lian, R. Analysis on buffer layer discharges below the corrugated aluminum sheath of XLPE cables and comparison with other metal sheath structures. In Proceedings of the 2019 IEEE 3rd International Conference on Circuits, Systems and Devices, Chengdu, China, 23–25 August 2019. [Google Scholar]
  58. Du, B.X.; Du, X.Y.; Kong, X.X.; Li, J.; Li, Z.J.; Li, X. An investigation on discharge fault in buffer layer of 220kV XLPE AC cable. IET Sci. Meas. Technol. 2021, 15, 508–516. [Google Scholar] [CrossRef]
  59. Petzold, F.; Beigert, M. Experiences of PD diagnosis on mv cables using oscillating voltages (owts). In Proceedings of the 2005 IEEE/PES Transmission and Distribution Conference and Exhibition: Asia and Pacific, Dalian, China, 18 August 2005; pp. 1–7. [Google Scholar]
  60. Mami, M.S.; Kksal, M. Remark on the lumped parameter modeling of transmission lines. Electr. Mach. Power Syst. 2000, 28, 565–575. [Google Scholar]
  61. Suyaroj, N.; Premrudeepreechacharn, S.; Watson, N.R. Transient state estimation with the Bergeron transmission line model. Turk. J. Electr. Eng. Comput. Sci. 2017, 25, 806–819. [Google Scholar] [CrossRef]
  62. Abdullah, H.; Uwe, S. A full frequency-dependent cable model for the calculation of fast transients. Energies 2017, 10, 1158. [Google Scholar]
  63. Wagenaars, P.; Wouters, P.; van der Wielen, P.C.J.M.; Steennis, E.F. Measurement of transmission line parameters of three-core power cables with common earth screen. IET Sci. Meas. Technol. 2010, 4, 146–155. [Google Scholar] [CrossRef] [Green Version]
  64. Bartnikas, R.; Novak, J.P. On the spark to pseudoglow and glow transition mechanism and discharge detectability. IEEE Trans. Electr. Insul. 1992, 27, 3–14. [Google Scholar] [CrossRef]
  65. Gamez-Garcia, M.; Bartnikas, R.; Wertheimer, M.R. Synthesis Reactions Involving XLPE Subjected to partial Discharges. IEEE Trans. Electr. Insul. 2007, EI-22, 199–205. [Google Scholar]
  66. Gamez-Garcia, M.; Bartnikas, R. Modification of XLPE exposed to partial discharges at elevated temperature. IEEE Trans. Electr. Insul. 1990, 25, 688–692. [Google Scholar] [CrossRef]
  67. Wu, R.N.; Chang, C.K. The use of partial discharges as an online monitoring system for underground cable joints. IEEE Trans. Power Deliv. 2011, 26, 1585–1591. [Google Scholar] [CrossRef]
  68. Wester, F.J.; Gulski, E.; Smit, J.J. Condition based maintenance of MV power cable systems on the basis of advanced PD diagnostics. In Proceedings of the 16th International Conference and Exhibition on Electricity Distribution, 2001. Part 1: Contributions, Amsterdam, The Netherlands, 18–21 June 2001; IET: London, UK, 2001. [Google Scholar]
  69. Gargari, S.M.; Wouters, P.; Wielen, P.; Steennis, E.F. Statistical analysis of partial discharge patterns and knowledge extraction in MV cable systems. In Proceedings of the 10th International Conference on Probablistic Methods Applied to Power Systems, Rincon, PR, USA, 25–29 May 2008. [Google Scholar]
  70. Bartnikas, R. Partial discharges. Their mechanism, detection and measurement. IEEE Trans. Dielectr. Electr. Insul. 2002, 9, 763–808. [Google Scholar] [CrossRef]
  71. Stone, G.C.; Boggs, S.A. Propagation of partial discharge pulses in shielded power cable. In Proceedings of the Conference on Electrical Insulation & Dielectric Phenomena—Annual Report 1982, Amherst, MA, USA, 17–21 October 1982. [Google Scholar]
  72. Blackburn, T.R.; Liu, Z.; Phung, B.T.; Morrow, R. Investigation of partial discharge mechanisms in a void under AC electric stress. In Proceedings of the 1999 Eleventh International Symposium on High Voltage Engineering, London, UK, 27–23 August 1999; IET: London, UK, 2001. [Google Scholar]
  73. Gulski, E.; Cichecki, P.; Wester, F.; Smit, J.J.; Bodega, R.; Hermans, T.J.W.H.; Seitz, P.P.; Quak, B.; Vries, F.D. On-site testing and PD diagnosis of high voltage power cables. IEEE Trans. Dielectr. Electr. Insul. 2008, 15, 1691–1700. [Google Scholar] [CrossRef]
  74. Mashikian, M.S.; Szarkowski, A. Medium voltage cable defects revealed by off-line partial discharge testing at power frequency. IEEE Electr. Insul. Mag. 2006, 22, 24–32. [Google Scholar] [CrossRef]
  75. Mashikian, M.S. Preventive maintenance testing of shielded power cable systems. IEEE Trans. Ind. Appl. 2002, 38, 736–743. [Google Scholar] [CrossRef]
  76. Kreutzer, M.; Schlapp, H.; Waeben, P.M. On site MV-cable testing with AC-voltages. In Proceedings of the 12th International Conference on Electricity Distribution, Birmingham, UK, 17–21 May 1993; IET: London, UK, 2001. [Google Scholar]
  77. Montanari, G.C.; Cavallini, A.; Puletti, F. A new approach to partial discharge testing of HV cable systems. IEEE Electr. Insul. Mag. 2006, 22, 14–23. [Google Scholar] [CrossRef]
  78. Ota, H.; Ichihara, M.; Miyamoto, N.; Kitai, S.; Maruyama, Y.; Fukasawa, M.; Takenhana, H. Application of advanced after-laying test to long-distance 275 KV XLPE cable lines. IEEE Trans. Power Deliv. 1995, 10, 567–579. [Google Scholar] [CrossRef]
  79. Gerlach, H.G. Resonant power supply kit system for high voltage testing. Power Eng. Rev. IEEE 1991, 11, 35. [Google Scholar] [CrossRef]
  80. Pultrum, E.; Boone, W.; Steennis, E.F. Dutch distribution cable performance. In Proceedings of the IEE Colloquium on MV Paper Cables: Asset or Liability, Capenhurst, UK, 21 April 1998; IET: London, UK, 2001. [Google Scholar]
  81. IEEE. IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF); IEEE: Piscataway, NJ, USA, 2004; Std 400.2-2004; pp. 1–60. [Google Scholar]
  82. Wang, X.; Taylor, N.; Edin, H. Enhanced distinction of surface and cavity discharges by trapezoid-based arbitrary voltage waveforms. IEEE Trans. Dielectr. Electr. Insul. 2016, 23, 435–443. [Google Scholar] [CrossRef]
  83. Oyegoke, B.; Hyvonen, P.; Aro, M.; Gao, N. Selectivity of damped ac (dac) and vlf voltages in after-laying tests of extruded mv cable systems. IEEE Trans. Dielectr. Electr. Insul. 2003, 10, 874–882. [Google Scholar] [CrossRef]
  84. Niasar, M.G.; Wang, X.; Kiiza, R.C. Review of partial discharge activity considering very-low frequency and damped applied voltage. Energies 2021, 14, 440. [Google Scholar] [CrossRef]
  85. Gulski, E.; Smit, J.J.; Seitz, P.N.; Smit, J.C.; Turner, M. On-site PD diagnostics of power cables using oscillating wave test system. In Proceedings of the 1999 Eleventh International Symposium on High Voltage Engineering, London, UK, 23–27 August 1999; IET: London, UK, 1999. [Google Scholar]
  86. Lemke, E.; Schmiegel, P.; Elze, H.; Russwurm, D. Procedure for evaluation of dielectric properties based on complex discharge analyzing (CDA). In Proceedings of the Conference Record of the 1996 IEEE International Symposium on Electrical Insulation, Montreal, QC, Canada, 16–19 June 1996. [Google Scholar]
  87. Gulski, E.; Smit, J.; Seitz, P.; Smit, J.C. Pd measurements on-site using oscillating wave test system. In Proceedings of the Conference Record of the 1998 IEEE International Symposium on Electrical Insulation, Arlington, VA, USA, 7–10 June 1998. [Google Scholar]
  88. Cavallini, A.; Krotov, V.; Montanari, G.C.; Morshuis, P.H.F.; Mariut, L.E. The role of supply frequency in the evaluation of partial discharge inception voltage in XLPE-embedded cavities. In Proceedings of the 2012 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, Montreal, QC, Canada, 14–17 October 2012. [Google Scholar]
  89. Pultrum, E.; Hetzel, E. Dutch experience with VLF partial discharge detection. In Proceedings of the IEE Colloquium on MV Paper Cables: Asset or Liability? (Digest No. 1998/290), Capenhurst, UK, 21 April 1998; IET: London, UK, 1998. [Google Scholar]
  90. Mohaupt, P.; Baur, M.; Schlick, T. Vlf testing and diagnosis on medium voltage power cables. In Proceedings of the 2003 IEEE 10th International Conference on Transmission and Distribution Construction, Operation and Live-Line Maintenance, Orlando, FL, USA, 6–10 April 2003. [Google Scholar]
  91. Kalkner, W.; Bach, R. Comparative study on alternative test voltages for layed medium voltage cables. In Proceedings of the International Symposium on High Voltage Engineering, Dresden, Germany, 26–30 August 1991. [Google Scholar]
  92. Cavallini, A.; Montanari, G.C.; Mariut, L.E. The influence of test voltage waveforms on partial discharge activity in XLPE. In Proceedings of the 2012 IEEE International Symposium on Electrical Insulation, San Juan, PR, USA, 10–13 June 2012. [Google Scholar]
  93. Cichecki, P.; Gulski, E.; Smit, J.J.; Hermans, T.; Bodega, R.; Seitz, P.P. Conventional and unconventional partial discharges detection in power cables using different AC voltages. In Proceedings of the 2009 IEEE Electrical Insulation Conference, Montreal, QC, Canada, 31 May–3 June 2009. [Google Scholar]
  94. Brettschneider, S.; Lemke, E.; Hinkle, J.L.; Schneider, M. Recent field experience in PD assessment of power cables using oscillating voltage waveforms. In Proceedings of the Conference Record of the 2002 IEEE International Symposium on Electrical Insulation, Boston, MA, USA, 7–10 April 2002. [Google Scholar]
  95. Bodega, R.; Morshuis, P.H.F.; Lazzaroni, M.; Wester, F.J. Pd recurrence in cavities at different energizing methods. IEEE Trans. Instrum. Meas. 2004, 53, 251–258. [Google Scholar] [CrossRef]
  96. Cavallini, A.; Montanari, G. Effect of supply voltage frequency on testing of insulation system. IEEE Trans. Dielectr. Electr. Insul. 2006, 13, 111–121. [Google Scholar] [CrossRef]
  97. Hauschild, W.; Cavallini, A.; Montanari, G. Effect of supply voltage frequency on testing of insulation system. IEEE Trans. Dielectr. Electr. Insul. 2006, 13, 1189–1191. [Google Scholar] [CrossRef]
  98. Sumereder, C. A comparison of partial discharge detection with 50 Hz and 0.1 Hz at XLPE Cables. In Proceedings of the 2012 IEEE International Symposium on Electrical Insulation, San Juan, PR, USA, 10–13 June 2012. [Google Scholar]
  99. Colloca, V.; Fara, A.; Nigris, M.D.; Rizzi, G. Comparison among different diagnostic systems for medium voltage cable lines. In Proceedings of the 16th International Conference and Exhibition on Electricity Distribution, 2001. Part 1: Contributions. CIRED, Amsterdam, The Netherlands, 18–21 June 2001; IET: London, UK, 2001. [Google Scholar]
  100. Ekberg, M.; Gustafsson, A.; Leijon, M.; Bengtsson, T.; Eriksson, T.; Tornkvist, C.; Johansson, K.; Li, M. Recent results in hv measurement techniques. IEEE Trans. Dielectr. Electr. Insul. 1995, 2, 906–914. [Google Scholar] [CrossRef]
  101. Van der Wielen, P.C.J.M.; Steennis, E.F. Risk-controlled application of current MV cable feeders in the future by intelligent continuous diagnostics. In Proceedings of the 2011 IEEE Power and Energy Society General Meeting, Detroit, MI, USA, 24–28 July 2011. [Google Scholar]
  102. Steenis, E.F.; Ross, R.; Schaik, N.V.; Boone, W.; Aartrijk, D.M.V. Partial discharge diagnostics of long and branched medium-voltage cables. ICSD’01. In Proceedings of the 2001 IEEE 7th International Conference on Solid Dielectrics, Eindhoven, The Netherlands, 25–29 June 2001. [Google Scholar]
  103. Renforth, L.; Seltzer-Grant, M.; Mackinlay, R.; Goodfellow, S.; Clark, D.; Shuttleworth, R. Experiences from over 15 years of on-line partial discharge (OLPD) testing of in-service MV and HV cables, switchgear, transformers and rotating machines. In Proceedings of the IX Latin American Robotics Symposium and IEEE Colombian Conference on Automatic Control, Bogota, Colombia, 1–4 October 2011. [Google Scholar]
  104. Steennis, F.; Wagenaars, P.; Wielen, P.; Wouters, P.; Li, Y.; Broersma, T.; Bleeker, P. Guarding MV cables on-line: With travelling wave based temperature monitoring, fault location, PD location and PD related remaining life aspects. IEEE Trans. Dielectr. Electr. Insul. 2016, 23, 1562–1569. [Google Scholar] [CrossRef] [Green Version]
  105. Kreuger, F. Partial Discharge Detection in High-Voltage Equipment; Butterworths: Oxford, UK, 1989; pp. 29–72. [Google Scholar]
  106. Pommerenke, D.; Strehl, T.; Heinrich, R.; Kalkner, W.; Schmidt, F.; Weissenberg, W. Discrimination between internal PD and other pulses using directional coupling sensors on hv cable systems. IEEE Trans. Dielectr. Electr. Insul. 1999, 6, 814–824. [Google Scholar] [CrossRef]
  107. Morin, R.; Bartnikas, R.; Lessard, G. In-service location of partial discharge sites in polymeric distribution cables using capacitive and inductive probes. In Proceedings of the 1999 IEEE Transmission and Distribution Conference, New Orleans, LA, USA, 11–16 April 1999. [Google Scholar]
  108. Schwarz, R.; Judendorfer, T.; Muhr, M. Review of partial discharge monitoring techniques used in high voltage equipment. In Proceedings of the 2008 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, Quebec, QC, Canada, 26–29 October 2008. [Google Scholar]
  109. Cheng, C.; Fan, C.L.; Hsiao, H.C.; Wang, W.M. On-site partial discharge measurement of underground cable system. In Proceedings of the 2011 7th Asia-Pacific International Conference on Lightning, Chengdu, China, 1–4 November 2011. [Google Scholar]
  110. Romano, P.; Imburgia, A.; Ala, G. Partial discharge detection using a spherical electromagnetic sensor. Sensors 2019, 19, 1014. [Google Scholar] [CrossRef] [Green Version]
  111. Si, W.; Fu, C.; Yuan, P. An integrated sensor with AE and UHF methods for partial discharges detection in transformers based on oil valve. IEEE Sens. Lett. 2019, 3, 1–3. [Google Scholar] [CrossRef]
  112. Zachariades, C.; Shuttleworth, R.; Giussani, R.; MacKinlay, R. Optimization of a high-frequency current transformer sensor for partial discharge detection using finite-element analysis. IEEE Sens. J. 2016, 16, 7526–7533. [Google Scholar] [CrossRef] [Green Version]
  113. Abdullah, A.Z.; Rohani, M.N.K.H.; Isa, M.; Hamid, H.; Arshad, S.N.M.; Othman, M. Real on-site partial discharge measurement technique in medium voltage power cable. In Proceedings of the 2018 IEEE 7th International Conference on Power and Energy (PECon), Kuala Lumpur, Malaysia, 3–4 December 2018. [Google Scholar]
  114. Pavan Kumar, C.L.G.; Abdul Khalid, N.H.; Ahmad, M.H.; Nawawi, Z.; Sidik, M.A.B.; Jambak, M.I.; Kurnia, R.F.; Waldi, E.P. Development and validation of rogowski coil with commercial high frequency current transformer for partial discharge detection. In Proceedings of the 2018 International Conference on Electrical Engineering and Computer Science (ICECOS), Pangkal, Indonesia, 2–4 October 2018. [Google Scholar]
  115. Rodrigo, A.; Llovera, P.; Fuster, V.; Quijano, A. High performance broadband capacitive coupler for partial discharge cable tests. IEEE Trans. Dielectr. Electr. Insul. 2013, 20, 479–487. [Google Scholar] [CrossRef]
  116. Technical paper A Guide for Partial Discharge Measurements on medium voltage (MV) and High Voltage (HV) Apparatus Part 1—Introduction. Available online: https://www.omicronenergy.com/download/file/fb29b0a044fcf4cb50e54e8a7a97d04e/ (accessed on 16 November 2021).
  117. Lemke, E.; Strehl, T.; Markalous, S.; Weissenberg, W. Ultra-wide-band PD diagnostics of power cable terminations in service. IEEE Trans. Dielectr. Electr. Insul. 2008, 15, 1570–1575. [Google Scholar] [CrossRef]
  118. Cavallini, A.; Conti, M.; Contin, A.; Montanari, G.C. Advanced PD inference in on-field measurements. ii. Identification of defects in solid insulation systems. IEEE Trans. Dielectr. Electr. Insul. 2003, 10, 528–538. [Google Scholar] [CrossRef]
  119. Hoof, M.; Patsch, R. Voltage-difference analysis, a tool for partial discharge source identification. In Proceedings of the Conference Record of the 1996 IEEE International Symposium on Electrical Insulation, Montreal, QC, Canada, 16–19 June 1996. [Google Scholar]
  120. Dezenzo, T.; Betz, T.; Schwarzbacher, A. The different stages of PRPD pattern for negative point to plane corona driven by a DC voltage containing a ripple. IEEE Trans. Dielectr. Electr. Insul. 2017, 24, 47–53. [Google Scholar] [CrossRef]
  121. Herold, C.; Leibfried, T. Advanced signal processing and modeling for partial discharge diagnosis on mixed power cable systems. IEEE Trans. Dielectr. Electr. Insul. 2013, 20, 791–800. [Google Scholar] [CrossRef]
  122. Sahoo, N.C.; Salama, M.; Bartnikas, R. Trends in partial discharge pattern classification: A survey. IEEE Trans. Dielectr. Electr. Insul. 2005, 12, 248–264. [Google Scholar] [CrossRef]
  123. Ashtiani, M.B.; Shahrtash, S.M. Partial discharge de-noising employing adaptive singular value decomposition. IEEE Trans. Dielectr. Electr. Insul. 2014, 21, 775–782. [Google Scholar] [CrossRef]
  124. Lin, Y. Using K-means clustering and parameter weighting for partial-discharge noise suppression. IEEE Trans. Power Deliv. 2011, 26, 2380–2390. [Google Scholar] [CrossRef]
  125. Lu, L.; Zhou, K.; Zhu, G.Y.; Chen, B.D.; Yana, X.M. Partial discharge signal denoising with recursive continuous S-shaped algorithm in cables. IEEE Trans. Dielectr. Electr. Insul. 2021, 28, 1802–1809. [Google Scholar] [CrossRef]
  126. Salama, M.; Bartnikas, R. Fuzzy logic applied to PD pattern classification. IEEE Trans. Dielectr. Electr. Insul. 2000, 7, 118–123. [Google Scholar] [CrossRef]
  127. Rosle, N.; Muhamad, N.A.; Rohani, M.N.K.H.; Jamil, M.K.M. Partial Discharges Classification Methods in XLPE Cable: A Review. IEEE Access 2021, 9, 133258–133273. [Google Scholar] [CrossRef]
  128. Peng, X.S.; Wen, J.Y.; Li, Z.H.; Yang, G.Y.; Zhou, C.K.; Reid, A.; Hepburn, D.M.; Judd, M.D.; Siew, W.H. Rough set theory applied to pattern recognition of Partial Discharge in noise affected cable data. IEEE Trans. Dielectr. Electr. Insul. 2017, 24, 147–156. [Google Scholar] [CrossRef] [Green Version]
  129. Peng, X.S.; Yang, F.; Wang, G.J.; Wu, Y.J.; Li, L.; Li, Z.H.; Bhatti, A.A.; Zhou, C.K.; Hepburn, D.M.; Reid, A.J.; et al. A convolutional neural network-based deep learning methodology for recognition of partial discharge patterns from high-voltage cables. IEEE Trans. Power Deliv. 2019, 34, 1460–1469. [Google Scholar] [CrossRef]
  130. Kim, J.; Kim, K.I. Partial discharge online detection for long-term operational sustainability of on-site low voltage distribution network using CNN transfer learning. Sustainability 2021, 13, 4692. [Google Scholar] [CrossRef]
  131. Wagenaars, P.; Wouters, P.; Wielen, P.C.J.M.V.D.; Steennis, E.F. Accurate estimation of the time-of-arrival of partial discharge pulses in cable systems in service. IEEE Trans. Dielectr. Electr. Insul. 2008, 15, 1190–1199. [Google Scholar] [CrossRef]
  132. Kim, Y.H.; Youn, Y.W.; Yi, S.H.; Hwang, D.H.; Sun, J.H.; Lee, J.H. High-resolution partial discharge location estimation in power cables. IEEE Trans. Dielectr. Electr. Insul. 2014, 21, 758–765. [Google Scholar] [CrossRef]
  133. Steiner, J.P.; Reynolds, P.H. Estimating the location of partial discharges in cables. IEEE Trans. Electr. Insul. 1992, 27, 44–59. [Google Scholar] [CrossRef]
  134. Lan, S.; Hu, Y.Q.; Kuo, C.C. Partial discharge location of power cables based on an improved phase difference method. IEEE Trans. Dielectr. Electr. Insul. 2019, 26, 1612–1619. [Google Scholar] [CrossRef]
  135. Raymond, W.J.K.; Illias, H.A.; Abu Bakar, A.H. High noise tolerance feature extraction for partial discharge classification in XLPE cable joints. IEEE Trans. Dielectr. Electr. Insul. 2017, 24, 66–74. [Google Scholar] [CrossRef]
  136. Chan, J.C.; Duffy, P.; Hiivala, L.J.; Wasik, J. Partial discharge. VIII. PD testing of solid dielectric cable. IEEE Electr. Insul. Mag. 1991, 7, 9–16. [Google Scholar] [CrossRef]
  137. Robinson, G. Ageing characteristics of paper-insulated power cables. Power Eng. J. 1990, 4, 95–100. [Google Scholar] [CrossRef]
  138. Megahed, I. The discharge-repetition rate in cavities in epoxy resin, polyethylene, and mica under alternating voltage conditions. IEEE Trans. Electr. Insul. 1975, 10, 69–74. [Google Scholar] [CrossRef]
  139. Gutfleisch, F.; Niemeyer, L. Measurement and simulation of PD in epoxy voids. IEEE Trans. Dielectr. Electr. Insul. 1995, 2, 729–743. [Google Scholar] [CrossRef]
  140. Illias, H.; Chen, G.; Lewin, P. Partial discharge behavior within a spherical cavity in a solid dielectric material as a function of frequency and amplitude of the applied voltage. IEEE Trans. Dielectr. Electr. Insul. 2011, 18, 432–443. [Google Scholar] [CrossRef]
  141. Morshuis, P.H.F. Degradation of solid dielectrics due to internal partial discharge: Some thoughts on progress made and where to go now. IEEE Trans. Dielectr. Electr. Insul. 2005, 12, 905–913. [Google Scholar] [CrossRef]
  142. Ahmed, N.; Srinivas, N. Can the operating conditions of the cable system effect the data of the field PD testing? In Proceedings of the 2001 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, Kitchener, ON, Canada, 14–17 October 2001. [Google Scholar]
  143. Feng, X.Y.; Xiong, Q.; Gattozzi, A.L.; Hebner, R.E. Partial discharge experimental study for medium voltage DC cables. IEEE Trans. Power Deliv. 2020, 36, 99. [Google Scholar] [CrossRef]
  144. Zhan, Y.; Chen, G.; Hao, M.; Pu, L.; Zhao, X.F.; Sun, H.F.; Wang, S.; Guo, A.X.; Liu, J. Comparison of two models on simulating electric field in HVDC cable insulation. IEEE Trans. Dielectr. Electr. Insul. 2019, 26, 1107–1115. [Google Scholar] [CrossRef]
  145. Seri, P.; Naderiallaf, H.; Montanari, G.C. Modelling of supply voltage frequency effect on partial discharge repetition rate and charge amplitude from AC to DC at room temperature. IEEE Trans. Dielectr. Electr. Insul. 2020, 27, 764–772. [Google Scholar] [CrossRef]
  146. Morshuis, P.; Smit, J.J. Partial discharges at DC voltage: Their mechanism, detection and analysis. IEEE Trans. Dielectr. Electr. Insul. 2005, 12, 328–340. [Google Scholar] [CrossRef] [Green Version]
  147. Montanari, G.C.; Hebner, R.; Seri, P.; Naderiallaf, H. Partial Discharge Inception Voltage and Magnitude in Polymeric Cables under AC and DC Voltage Supply; Jicable: Varsailles, France, 2019. [Google Scholar]
  148. Montanari, G.C.; Seri, P.; Bononi, S.F.; Albertini, M. Partial discharge behavior and accelerated aging upon repetitive DC cable energization and voltage supply polarity inversion. IEEE Trans. Power Deliv. 2020, 36, 99. [Google Scholar] [CrossRef]
  149. Tokunaga, S.; Tsurusaki, T.; Arief, Y.Z.; Ohtsuka, S.; Mizuno, T.; Hikita, M. Partial discharge characteristics till breakdown for XLPE cable joint with an artificial defect. In Proceedings of the 7th International Conference on Properties and Applications of Dielectric Materials, Nagoya, Japan, 1–5 June 2003. [Google Scholar]
  150. Olsson, L.; Bengtsson, G. PD-mapping of paper insulated MV cables in Gothenburg. In Proceedings of the 14th International Conference and Exhibition on Electricity Distribution. Part 1. Contributions, Birmingham, UK, 2–5 June 1997; IET: London, UK, 1997. [Google Scholar]
  151. Densley, J. Ageing mechanisms and diagnostics for power cables—An overview. IEEE Electr. Insul. Mag. 2001, 17, 14–22. [Google Scholar] [CrossRef]
  152. Mladenovic, I.; Weindl, C. Artificial aging and diagnostic measurements on medium-voltage, paper-insulated, lead-covered cables. IEEE Electr. Insul. Mag. 2012, 28, 20–26. [Google Scholar] [CrossRef]
  153. Walton, C.M. Detecting and locating MV failure before it occurs. Experience with live line partial discharge detection on underground paper insulated 11 kV cables in London. In Proceedings of the 16th International Conference and Exhibition on Electricity Distribution, 2001. Part 1: Contributions. CIRED, Amsterdam, The Netherlands, 18–21 June 2001; IET: London, UK, 2001. [Google Scholar]
  154. Alsharif, M.; Wallace, P.A.; Hepburn, D.M.; Zhou, C.K. Partial discharge resulting from internal degradation in underground MV cables: Modelling and analysis. In Proceedings of the 2009 44th International Universities Power Engineering Conference (UPEC), Glasgow, UK, 1–4 September 2009. [Google Scholar]
  155. Wester, F.; Gulski, E.; Smit, J.; Groot, E. Aspect of on-line and offline PD diagnosis of distribution power cables. In Proceedings of the Conference Record of the 2002 IEEE International Symposium on Electrical Insulation, Boston, MA, USA, 7–10 April 2002. [Google Scholar]
  156. Smit, J. Insulation condition estimation of distribution power cables by on-line and off-line diagnostics. In Proceedings of the 2001 International Symposium on Electrical Insulating Materials, Himeji, Japan, 22–22 November 2001. [Google Scholar]
  157. Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Partial discharge trends in medium voltage cables measured while in-service with PDOL. In Proceedings of the IEEE PES T&D 2010, New Orleans, LA, USA, 19–22 April 2010. [Google Scholar]
  158. Callender, G. Critical analysis of partial discharge dynamics in air filled spherical voids. J. Phys. 2018, 51, 125601. [Google Scholar] [CrossRef] [Green Version]
  159. Oh, D.; Kim, H.; Lee, B. Novel diagnostic method of DC void discharge in high temperature superconducting cable based on pulse sequence analysis. IEEE Trans. Appl. Supercond. 2020, 30, 1–5. [Google Scholar] [CrossRef]
  160. Zhou, L.J.; Bai, L.L.; Zhang, J.K.; Cao, W.D.; Xiang, E.X. Measurement and diagnosis of PD characteristics of industrial cable terminations in extreme cold environment. IEEE Trans. Instrum. Meas. 2021, 70, 1–11. [Google Scholar] [CrossRef]
Figure 1. (a) Townsend type partial discharge.Reprinted from Ref [20]. (b) streamer type partial discharge. Reprinted from Ref [20].
Figure 1. (a) Townsend type partial discharge.Reprinted from Ref [20]. (b) streamer type partial discharge. Reprinted from Ref [20].
Energies 14 07692 g001
Figure 2. Illustration of cable joint design for electric stress control.
Figure 2. Illustration of cable joint design for electric stress control.
Energies 14 07692 g002
Figure 3. (a) Discharge at the distribution cable joint. Reprinted from Ref [59]. (b) discharge at the buffer layer under corrugated aluminum sheath.
Figure 3. (a) Discharge at the distribution cable joint. Reprinted from Ref [59]. (b) discharge at the buffer layer under corrugated aluminum sheath.
Energies 14 07692 g003
Figure 4. Schematic of the partial discharge test circuit.
Figure 4. Schematic of the partial discharge test circuit.
Energies 14 07692 g004
Figure 5. Resonant testing system schematic diagram.
Figure 5. Resonant testing system schematic diagram.
Energies 14 07692 g005
Figure 6. VLF testing system schematic diagram.
Figure 6. VLF testing system schematic diagram.
Energies 14 07692 g006
Figure 7. OWTS testing system schematic diagram.
Figure 7. OWTS testing system schematic diagram.
Energies 14 07692 g007
Figure 8. Illustration of sensor locations.
Figure 8. Illustration of sensor locations.
Energies 14 07692 g008
Figure 9. (a) Typical example of PRPS. Reprinted from Ref [111]. (b) typical example of PRPD. Reprinted from Ref [135].
Figure 9. (a) Typical example of PRPS. Reprinted from Ref [111]. (b) typical example of PRPD. Reprinted from Ref [135].
Energies 14 07692 g009
Figure 10. PSA construction for PD. Reprinted from Ref [119].
Figure 10. PSA construction for PD. Reprinted from Ref [119].
Energies 14 07692 g010
Table 1. PD models summary with advantages and disadvantages.
Table 1. PD models summary with advantages and disadvantages.
ModelPD TypeAdvantages and Disadvantages
abc-modelInternal PD+ Easy to understand and implement.
− Cannot represent the physics behind the discharge.
Induced chargeInternal PD+ Analytical solutions can be derived.
− The model is developed with the following restrictions: uniform electric field inside the void. The electric field in the bulk of the solid dielectric remains the same during a PD event [49].
RC networkCorona [47] and surface PD [48]+ Simple implementation.
− Circuit model cannot completely reveal the physical process.
Particle in cell (PIC) Surface PD [50], corona PD [51], and internal PD [40]+ Clear physical interpretation and easy implementation.
− The method requires a large amount of computation resources and converges slowly [43].
Fluid model Surface PD [52], corona PD [43], and internal PD [53]+ Microscopic physical processes of a PD can be obtained.
− The stochastic characters are not taken into account [54]. Large computation consumption. Impractical in ageing and multiple PD analysis where simulations for a large number of power frequency AC cycles are required [25].
Finite element analysis Corona PD [55], surface PD [56], and internal PD+ Electric field in geometry can be derived without restrictions on the geometry or uniformity of electric field distribution. Non-linear or anisotropic media could be considered [25].
− Time consuming and there is lack of reliable knowledge on input parameters.
Table 2. Different off-line PD tests.
Table 2. Different off-line PD tests.
SystemSourceMain Parameters
AC voltage testAlternating current voltage with resonant test systemTest voltage and test frequency
VLF testVery low frequencies down to 0.01 HzTest voltage and test duration
Damped AC testDamped alternating current at frequencies between 20 and 500 HzTest voltage, frequency, and damping
Table 3. Off-line PD measurement results.
Table 3. Off-line PD measurement results.
Test ObjectResult
6 kV plastic insulated cable accessories with realistic internal defects: bad contact between semiconducting layer and the stress cone, bad adjustment of the stress cone and internal cavities [85]50 Hz AC power frequency and oscillating wave voltages of 1066 Hz gave PDIV and PD magnitude in the same range without a consistent difference.
10 kV cable sample [87]Higher PDIV for OWTS than 50 Hz.
Dielectric cavities embedded in an XLPE sandwich [88]PDIV values with OWTS significantly exceeded those obtained with sinusoidal voltage waveforms. PDIV with 0.1 Hz was on average lower than those obtained for higher frequencies.
Electrical treeing on an XLPE cable sample [90]A widespread electrical tree for 50 Hz while a straight channel with VLF. Tree growth rate for VLF was faster. Number of PD per second for VLF was much lower.
Needle and water tree damage [91]Oscillating voltages lead to higher electrical tree inception voltage than 50 and 0.1 Hz while 0.1 Hz tests indicate higher tree ignition voltage than 50 Hz.
Three layers of polyethylene [92]0.1 Hz VLF with sinusoidal waveform, 50 Hz AC and OWTS using frequencies of 200, 500, and 1000 Hz were performed. PDIV increased slightly with frequency and PDIV for OWTS was in general much higher than the ones derived with sinusoidal waveforms.
Full size test setup of 100 m 150 kV XLPE cable with defect created in cable joint [93]Continuous 50 Hz AC voltage and Damped AC voltage (60 Hz, 400 Hz) were applied, and similar PD characteristics was observed.
A spherical air-filled cavity between two brass electrodes cast in polyester resin [95]DAC, VLF, and 50 (60) Hz test were performed. PDIV is not dependent on the voltage frequency shape. The PD level measured at frequencies above 200 Hz was slightly lower than that with the 50 Hz AC energizing; both the PD magnitude and the PD pattern demonstrated that the PD process at VLF frequencies can be either very close to that at 50 Hz or quite different. The main reason is supposed to be that the deposited charge decay time can vary over several orders of magnitude depending on the condition of the cavity surface.
Spherical electrode on a 1 mm thick LDPE disc placed on a grounded plane electrode activating surface discharges on the LDPE disc. Three 1 mm thick PE foils, the layer in the middle had a punched hole [97]25–30% differences can be observed when testing PDIV and PDEV at different frequencies. In general, both PDIV and PDEV had a non-monotone behavior from 0.01 to 1000 Hz for internal and surface PD activities.
Two XLPE cables consisting of 168 and 233 m were connected by a defective cable joint. Artificial defects were made to generate internal and surface PD [98]PDIV at 50 Hz is about 80% of 0.1 Hz measurement.
Five cables made of paper, EPR, and XLPE with terminations having artificial defects in laboratory and 18 field cable circuits (paper and EPR) [99]For the laboratory test, 0.1 Hz VLF gave higher PDIV result than 50 Hz AC, however, it is not always the case in the field. Neither 0.1 Hz nor DAC can always give close inception PD voltage compared with 50 Hz and the maximum difference is about 200%.
Table 4. PD sensors with advantages and disadvantages.
Table 4. PD sensors with advantages and disadvantages.
Sensor TypeAdvantagesDisadvantages
AE sensorImmune to electromagnetic noiseHigh attenuation [111]
HFCTNon-intruding installation, wide bandwidth [112]Material saturation caused by large current at power frequency
Current loop is needed
Rogowski coilLight weight, low cost compared with HFCT [113]Narrow frequency band [114]
Current loop is needed
Coupling capacitorHigh sensitivity, possible to be integrated in cable [115]The size and cost of a coupling capacitor can become problematic for onsite measurement [116]
Installing can be an issue, safety risk due to galvanic contact needs to be considered
UHFGood anti-disturbance performance [111]Strong attenuation, cannot be calibrated [117]
Cable shielding effect
Ultraviolet imagerEasy to useCan only detect corona discharge at cable termination
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Zhang, X.; Pang, B.; Liu, Y.; Liu, S.; Xu, P.; Li, Y.; Liu, Y.; Qi, L.; Xie, Q. Review on Detection and Analysis of Partial Discharge along Power Cables. Energies 2021, 14, 7692. https://doi.org/10.3390/en14227692

AMA Style

Zhang X, Pang B, Liu Y, Liu S, Xu P, Li Y, Liu Y, Qi L, Xie Q. Review on Detection and Analysis of Partial Discharge along Power Cables. Energies. 2021; 14(22):7692. https://doi.org/10.3390/en14227692

Chicago/Turabian Style

Zhang, Xiaohua, Bo Pang, Yaxin Liu, Shaoyu Liu, Peng Xu, Yan Li, Yifan Liu, Leijie Qi, and Qing Xie. 2021. "Review on Detection and Analysis of Partial Discharge along Power Cables" Energies 14, no. 22: 7692. https://doi.org/10.3390/en14227692

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop