A Robust Vector Current Controller with Negative-Sequence Current Capability for Grid-Connected Inverters

by
Houshang Karimi
1,*,
Aboutaleb Haddadi
2,
Masoud Karimi-Ghartemani
3 and
Mahdieh Sadabadi
4
1
Department of Electrical Engineering, Ploytechnique Montreal, Montreal, QC H3T 1J4, Canada
2
Electric Power Research Institute (EPRI), Palo Alto, CA 94304, USA
3
Department of Electrical and Computer Engineering, Mississippi State University, Starkville, MS 39762, USA
4
Department of Automatic Control and Systems Engineering, University of Sheffield, Sheffield S1 3JD, UK
*
Author to whom correspondence should be addressed.
Energies 2021, 14(15), 4549; https://doi.org/10.3390/en14154549
Submission received: 14 June 2021 / Revised: 14 July 2021 / Accepted: 22 July 2021 / Published: 27 July 2021
(This article belongs to the Topic Power System Modeling and Control)

Abstract

:
This paper presents a vector current controller (in the synchronous reference, or the dq, frame) with negative-sequence current injection capability for three-phase grid-connected converters. This capability is desired for the operation of the converter during unbalanced conditions and also for a certain type of islanding detection. The proposed controller first determines the double-frequency current references and then uses a sixth-order two-input two-output proportional-integral-resonance (PIR) structure, which is optimally designed. Compared with the existing similar approaches, the proposed controller has a simpler structure and more robust performance, e.g., against system parameter uncertainties and weak grid conditions. The proposed controller is developed for converters with both the L-type and L C L -type filters. For the L C L -type converter, a suboptimal partial state feedback control is also proposed to achieve robust stability and active damping of resonance poles without requiring additional sensors. Detailed experimental results are presented to illustrate the properties and performances of the proposed controller.

1. Introduction

Grid-connected converters exchange positive-sequence balanced current with the grid during normal operation. However, they may be required to exchange a negative-sequence current component in some conditions. For example, during an asymmetrical grid fault, when the grid is unbalanced [1,2,3,4,5,6] or when they are equipped with an active islanding detection mechanism, which is based on injection of a small negative-sequence current [7,8].
The common control approach is the vector current control (VCC) technique in the synchronous reference (or dq) frame where the current references become constant [9]. To maintain this desired feature of the VCC approach, i.e., having constant references, while injecting a negative-sequence current, two separate control channel are put together for each sequence component. In this approach, multiple filters must be inserted into this structure to block the double-frequency oscillations. Despite some solutions to simplify the controller, e.g., [10], this approach still has an increased order and structural complexity of the controller [7,11,12,13]. One more important concern with this approach is the impact of those controller dynamics in aggravating the system oscillations under weak grid conditions [14,15,16]. Moreover, such approaches are not directly applicable to the inverters with L C L -type filters due to the complex coupling of the two axes in these filters. For this reason, almost all controllers for implementing fault ride-through are structured in a stationary (or natural time) domain with extensive current reference calculations and multiple resonance controllers [1,5,17,18,19]. In [20], the controller gains in a stationary frame for an L C L -type filter are designed using a linear matrix inequality (LMI) approach.
In [21], this problem is addressed for an inverter with an L C L filter where the controller and also a state observer are optimally designed. Resonant (or internal model based) controllers are used for perfect tracking. However, two different control channels are still used for the dq axes. In [22,23], the real power oscillations are removed by injecting an unbalanced current. However, only an L-type filter is considered. Separate control channels are used, and the design of current controllers are not discussed in [23].
Robust sliding mode control (SMC) for grid-connected voltage source converters (VSCs) operating under unbalanced grid conditions has been proposed in [24]. Although the proposed method does not require a phase-locked loop (PLL), it employs an observer to estimate positive- and negative-sequence components of the grid voltage. Moreover, the SMC technique suffers from the chattering phenomenon, which degrades controller performance and its accuracy [25]. In [26], an enhanced three-stage passivity-based controller for L C L -type VSCs connected to a weak and unbalanced grid is proposed. This method is structurally complex and assumes to have access to all current and voltage signals.
This paper proposes a new controller for a VSC based distributed energy resource (DER) unit with negative-sequence current injection capability. The application of islanding detection is considered for the study presented in this paper. The proposed controller finely determines the reference currents and then uses a multivariable proportional-integrating-resonance (PIR) function. This obviates the need for several notch filters used in existing methods, e.g., in [7,27,28], which significantly reduces the controller’s order. The reduced order of the proposed controller together with its optimal design lead to a high level of robustness against weak grid conditions and system uncertainties as demonstrated in this paper. The proposed controller is applied to both L-type and L C L -type filters without requiring additional sensors or observers. The L C L -type filters are increasingly used due to their lower cost and volume, which leads to higher power density as well as higher efficiency for high power applications.
The effectiveness of the proposed control scheme is validated using experimental tests under IEEE1547 anti-islanding test conditions, unbalanced load, weak grid conditions, and uncertainties in the output filter parameters. All the developments and testing are performed for two cases of inverters with L-type and L C L -type output filters. Performances of the proposed method and conventional method are compared against uncertainties in system parameters and against weak grid conditions. It is shown that substantial performance improvement is achieved.
The main contributions of the paper are (1) proposing a structurally simple and robust current controller for the VSCs with negative-sequence current injection capability; (2) proposing a systematic and step-by-step control design algorithm applicable to both L-filter and L C L -filter interfaced VSCs; (3) developing an active islanding detection algorithm based on negative-sequence current injection for L-type as well as L C L -type VSCs; (4) presenting several simulation and experimental scenarios to verify the performance of the proposed control systems and islanding detection algorithm.

2. Test Setup

Figure 1 shows a schematic diagram of the test system consisting of a DER unit and a local parallel R L C load connected to the grid through switch S. The grid has been represented by an ideal voltage source behind an impedance whose per-phase resistance and inductance have been denoted by R s and L s . The power circuit of the DER unit comprises a conditioned prime energy source that is modeled by a dc voltage source, a VSC, and a three-phase output filter, which could be an L-type or L C L -type filter. A step-up transformer connects the DER unit to the point of common coupling (PCC). The R L C load is tuned at the resonance frequency of 60 ± 0.1 Hz to behave as a pure resistance, R, which is adjusted to absorb the nominal power of the DER unit at the nominal PCC voltage.

3. Overview of a Conventional Islanding Detection Method

In [7], an islanding detection method is presented where the VSC injects a small amount of negative-sequence current during normal operation. Its block diagram structure is shown in Figure 2. Its current controller consists of two channels: one channel regulates the positive-sequence component of the DER terminal current and thereby the output real and reactive powers of the unit; the other channel controls the amplitude of negative-sequence current for the purpose of islanding detection. The current control task is performed in a rotating d q frame whose angle is that of the PCC voltage obtained from a PLL. A unified three-phase signal processor (UTSP) whose input is the PCC voltage is used for precise detection of negative-sequence voltage after islanding occurs.
Each control channel includes four second-order notch filters and two PI controllers. Furthermore, its PLL uses a loop filter of order 4, H ( s ) , as shown in Figure 2, in order to block the double-frequency ripples. Its UTSP is a system of order 7. The total order of the controller of [7] amounts to 30, which indicates a rather complicated structure. In addition to the implementation burden, such a complex structure causes the inverter responses to deviate from the designed characteristics when uncertain and weak grid conditions and disturbances are present, as shown in this paper.

4. Proposed Controller

As shown in Appendix B, to inject a negative-sequence current with magnitude I n , the d q components of the current must have a double-frequency component with the same magnitude and with a 90 ° phase shift. Therefore, the reference values for the currents in d q frame are
i t d * ( t ) = I t d 0 * + I n * cos ( 2 ω 0 t ) i t q * ( t ) = I t q 0 * I n * sin ( 2 ω 0 t )
where ω 0 is the nominal angular frequency.

4.1. Proposed Control Structure

The proposed control scheme directly operates on the basis of (1) and consists of an output controller and a state feedback controller, as shown in Figure 3. The output controller is a sixth-order linear time-invariant (LTI) system with two inputs and six outputs and is properly constructed (using a PIR function) so that the precise tracking of stepwise commands and double-frequency sinusoidal signals are guaranteed. Such a controller also ensures the complete rejection of dc and double-frequency disturbances. Therefore, the matrices, A c and B c , implement the characteristic polynomial of p ( s ) = s ( s 2 + 4 ω 0 2 ) in a 2I6O controllable system [29]. In other words,
A c = blkdiag { A c 1 , A c 2 } , B c = blkdiag { B c 1 , B c 2 }
where blkdiag stands for “block diagonal”, and A c i and B c i are in the controllable canonical form as
A c i = 0 1 0 0 0 1 0 4 ω 0 2 0 , B c i = 0 0 1 , i = 1 , 2
The gains of the output controller, i.e., K c , are multiplied with the controller state variables in a coupled manner (Figure 3). The subscript c is used for the state variables of the output controller and p for those of the plant.

4.2. Mathematical Modeling

4.2.1. L-Type Filter

Assume the L-type filter is used with inductance L f and parasitic resistance R f . Moreover, let us consider the phase-angle of the PCC voltage, θ ( t ) , as the reference phase-angle for the Park transformation. We then apply the KVL to the ac side to obtain v t , d q = R f i t , d q + L f ( d i t , d q d t + j ω i t , d q ) + v s , d q , in which ω = θ ˙ . Defining the state, input, output, and disturbance vectors as
x p T = [ x 1 x 2 ] = [ i t d i t q ] , y T = [ y 1 y 2 ] = [ i t d i t q ] u T = [ u 1 u 2 ] = [ v t d v t q ] , w T = [ w 1 w 2 ] = [ v s d v s q ] ,
leads to an LTI model described by
x ˙ p ( t ) = A p x p + B p u + E w , y = C p x p
A p = R f L f ω ω R f L f , B p = 1 L f I 2 , C p = I 2 , E = 1 L f I 2
where I 2 is the 2 × 2 identity matrix.
The state-space model of the output controller is given by
x ˙ c = A c x c + B c e = A c x c B c C p x p + B c y r e f
where e = y r e f y = y r e f C p x p is used. Augmenting the controller and plant state-space models and defining the unified state vector x as x = [ x c T x p T ] T lead to
x ˙ ( t ) = A x + B u + B r e f y r e f + E ¯ w , y = C x ,
A = A c B c C p 0 A p , B = 0 B p , B r e f = B c 0 , E ¯ = 0 E ,
and C = [ 0 C p ] . The control law in the form of a full state feedback may be written as
u = K c x c K p x p = K x , K = [ K c K p ] .

4.2.2. L C L -Type Filter

Consider an L C L filter with the converter side impedance L c s + R c , capacitance C f , and the grid side impedance L g s + R g . This will increase the number of plant state variables to 6, and x p may be defined as x p T = [ i t d i t q v c d v c q i g d i g q ] . The plant state-space model is described by Equation (5), where the matrices are defined as
A p = R c L c ω 1 L c 0 0 0 ω R c L c 0 1 L c 0 0 1 C f 0 0 ω 1 C f 0 0 1 C f ω 0 0 1 C f 0 0 1 L g 0 R g L g ω 0 0 0 1 L g ω R g L g B p T = 1 L c [ I 2 0 ] , C p = [ I 2 0 ] , E T = 1 L g [ 0 I 2 ]
where 0 is the zero matrix of proper dimensions [30]. The augmented system equations and the state feedback law remain the same as Equations (8), (9), and (10), respectively.

4.3. Optimal Controller Design

The disturbances and set-points can be expressed in terms of the linear combination of dc and double-frequency sinusoidal signals, i.e., span { 1 , cos ( 2 ω t ) , sin ( 2 ω t ) } . Therefore, applying the linear transformation defined by p ( D ) = D ( D 2 + 4 ω 2 ) (where D is the time derivative operator) will vanish them, i.e., [ d d t ( d 2 d t 2 + 4 ω 2 ) ] [ c 1 + c 2 sin ( 2 ω t ) + c 3 cos ( 2 ω t ) ] = 0 , for all constants c 1 , c 2 , c 3 . Now, we apply p ( D ) to both sides of equations (8) and (10) to obtain
z ˙ ( t ) = A z + B v , v s . = K z
with z = p ( D ) x = p ( D ) x c x p = z c z p , and v s . = p ( D ) u . It can readily be observed that z c = [ e 1 e ˙ 1 e ¨ 1 e 2 e ˙ 2 e ¨ 2 ] T where e 1 = i t d , r e f i t d , e 2 = i t q , r e f i t q .
The linear quadratic regulator (LQR) technique is applied to Equation (12) to minimize
J = 0 ( q 1 e 1 2 + q 2 e ˙ 1 2 + q 3 e ¨ 1 2 + q 4 e 2 2 + q 5 e ˙ 2 2 + q 6 e ¨ 2 2 + q 7 z p 1 2 + q 8 z p 2 2 + r 1 v 1 2 + r 2 v 2 2 ) d t .
The cost function (Equation (13)) penalizes the tracking errors as well as their first- and second-order time-derivatives. All components of the cost function converge to zero if the closed-loop system is asymptotically stable.
For the L C L -type filter, the cost function is extended to
J = 0 ( q 1 e 1 2 + q 2 e ˙ 1 2 + q 3 e ¨ 1 2 + q 4 e 2 2 + q 5 e ˙ 2 2 + q 6 e ¨ 2 2 + q 7 z p 1 2 + q 8 z p 2 2 + q 9 z p 3 2 + q 10 z p 4 2 + q 11 z p 5 2 + q 12 z p 6 2 + r 1 v 1 2 + r 2 v 2 2 ) d t .
A step-by-step algorithm for designing the state feedback gains is proposed as follows.
Design Algorithm for L-Type Filter:
Step 1. 
Initialize the parameters of the cost function to r 1 = r 2 = 1 and q 1 = q 4 = ϵ , where 0 < ϵ 1 is a real number, and the remainder of q i ’s are zero.
Step 2. 
Increase q 1 and calculate K using the MATLAB command lqr. Plot the trajectory of closed-loop poles, i.e., eigenvalues of A c l = A B K . Increase q 1 until the low-frequency dominant poles obtain sufficient distance from the imaginary axis. Freeze q 1 and proceed to Step 3.
Step 3. 
Repeat Step 2 for q 4 . This will shift the low-frequency poles of the second channel to the left.
Step 4. 
Repeat Step 2 consecutively for q 2 , q 5 , q 3 , and q 6 . Notice that q 2 and q 3 are the coefficients of the e ˙ 1 and e ¨ 1 , and this means that they can introduce more damping to the high-frequency poles (at double-frequency). The same is true for q 5 and q 6 of the second control channel.
Step 5. 
Final fine-tuning may be carried out by increasing q 7 and q 8 until the closed-loop poles are located at desirable places.
Design Algorithm for L C L -Type Filter:
Step 1–4. 
Same as for the L-type filter.
Step 5. 
Increase q 7 , q 8 , and q 9 , consecutively, to introduce sufficient damping to the resonance poles of the L C L
Step 6. 
Final fine-tuning may be carried out by increasing q 10 to q 12 until the closed-loop poles are located at desirable places.
Remark on distance of poles: The distance of the closed-loop poles from the imaginary axis determines the speed of responses. This distance should be sufficient to produce fast responses that ensure current limiting is achieved when grid voltage transient faults occur. However, on the other side, the distance is limited by the measurement noise sensitivity and also the switching frequency constraints, i.e., the common rule that several switching cycles must be included within the time constant of the system responses.
Design Example for L-Type Filter:
Figure 4 shows the loci of the closed-loop system poles obtained by executing the proposed design algorithm. The numerical values of the system parameters are given in Table A1. In this figure, first, q 1 varies from 10 14 to 10 18 . The loci of the poles versus the variations of q 1 are shown in blue. Then, q 4 varies from 10 14 to 10 18 , and the movement of the poles is shown in red. Subsequently, q 2 and q 5 vary between 10 10 to 10 12.5 , consecutively. Finally, q 3 and q 6 are varied between 10 4 to 10 6.5 . These introduce adequate damping to the double-frequency poles of the controller. At this location, the closed-loop system poles are at 458 ± j 345 , 364 ± j 125 , 346 ± j 987 , and 243 ± j 831 , which indicates fast and damped responses. The controller gains are
K = [ 9.7 × 10 8 3.2 × 10 5 4976 2.6 × 10 8 9.3 × 10 4 1395 2.6 × 10 8 9.3 × 10 5 1395 9.7 × 10 8 3.2 × 10 5 4976 K c | 7 0 0 7 K p ] .
Design Example for L C L -Type Filter:
Figure 5 shows the loci of the poles of the closed-loop system when the proposed design algorithm is executed for the L C L -type filter. First, q 1 and q 4 are consecutively increased from 10 15 to 10 18 . Subsequently, q 2 and q 5 are varied between 10 9 to 10 12.5 . Then, q 3 and q 6 are varied between 10 3 and 10 6.5 . These introduce adequate damping to the double-frequency poles of the controller. Finally, q 7 and q 8 are varied between 10 2 and 10 1 ; q 9 and q 10 are increased from 10 3 to 10 1 . This will introduce sufficient damping to the resonance poles. At this location, the closed-loop poles are at 414 ± j 361 , 395 ± j 4966 , 395 ± j 4212 , 248 ± j 66 , 236 ± j 862 , and 143 ± j 780 , which indicates fast and damped responses. The controller gains are
K = [ 9.3 × 10 8 6.7 × 10 5 4.8 × 10 3 3.8 × 10 8 2.2 × 10 5 1.7 × 10 3 3.8 × 10 8 2.2 × 10 5 1.7 × 10 3 9.3 × 10 8 6.7 × 10 5 4.8 × 10 3 K c | 8.95 0 0.14 0.02 1.44 0.14 0 8.95 0.02 0.14 0.14 1.44 K p ] .
Design for L C L -Type Filter without Additional Sensors:
The L C L -type filter requires six additional number of sensors compared with the L-type filter. The proposed optimal controller design, however, proved to be working without using the new state variables of the L C L -type filter in the feedback loop. Figure 6 shows the closed-loop eigenvalues of the system when the gains of the additional signals are forced to zero. It is observed that this does not introduce instability or noticeable performance degradation, compared to when all the variables are used in the feedback, i.e., Figure 5. The closed-loop poles are at 478 ± j 4152 , 440 ± j 4912 , 277 ± j 379 , 240 ± 140 , 237 ± j 927 , and 136 ± j 796 , which indicates fast and damped responses. The controller gains are
K = [ 9.4 × 10 8 6.6 × 10 5 4.8 × 10 3 3.5 × 10 8 2.1 × 10 5 1.6 × 10 3 3.5 × 10 8 2.1 × 10 5 1.6 × 10 3 9.4 × 10 8 6.6 × 10 5 4.8 × 10 3 K c | 8.84 0 0 0 0 0 0 8.84 0 0 0 0 K p ] .

4.4. Detection of Sequences

A modified version of the unified three-phase signal processor (UTSP) of [7] is used in this paper. This was recently proposed in [22]. It is capable of robustly and accurately measuring the negative-sequence voltage. The operation of this processor is conveniently controlled by two gains: μ 1 and μ 2 . The setting of these two gains are μ 1 = 2 3 ( 2 ζ 1 ω ) , μ 2 = 2 3 μ 1 2 4 ζ 2 2 , where ζ 1 and ζ 2 are two damping ratios. The first damping ratio specifies the filtering strength, while the second damping ratio determines the bandwidth of the frequency estimation loop.

5. Robust Stability Analysis

It is shown that multivariable quadratic designs have the property of a large gain margin and good phase margin for each control channel. Similar results are derived for nonlinear perturbations in the feedback loop [31,32]. However, in this section, a robust stability analysis for the closed-loop system with respect to uncertainties in the system parameters is carried out. The state-space A-matrix of the closed-loop system is A c l = A B K , where the state feedback gain K is designed in Section 4.3. To incorporate the parameter uncertainties, an approach is to employ a matrix set, referred to as the polytopic uncertain matrix, as described in [33]
A c l ( λ ) = i = 1 q λ i A c l i ,
where A c l i , i = 1 , , q , are known vertices of the polytope; q is the number of vertices; λ = λ 1 λ q T belongs to a standard unit simplex defined by
Λ = λ : λ i R , λ i 0 , i = 1 q λ i = 1 .
Theorem 1.
The closed-loop state matrix in Equation (15) is stable for all λ Λ if there exist symmetric positive-definite matrices P i 0 ( i = 1 , , q ) , S 1 , and S 2 such that
0 P i P i 0 + S 1 S 2 I A c l i + S 1 S 2 I A c l i T 0 ,
for i = 1 , , q .
Proof. 
See Theorem 2.4 in [34]. □
The conditions given in Equation (17) are in terms of LMIs in unknown variables P i , S 1 , and S 2 . The LMIs can be solved using YALMIP [35] as an interface and MOSEK [36] as a semidefinite programming (SDP) solver.

5.1. Robust Stability Analysis for L-Type Filter

To analyze the robust stability of the closed-loop system with respect to the uncertainty in the VSC and grid inductances, i.e., L f and L s , which are connected in series, it is assumed that L f + L s L min L max . In this case, the polytope in Equation (15) has q = 2 vertices:
A c l 1 = A ( L max ) B ( L max ) K , A c l 2 = A ( L min ) B ( L min ) K ,
where A ( L max ) , B ( L max ) , and ( A ( L min ) , B ( L min ) ) are obtained from Equation (9) by substituting the maximum and minimum values of L f + L s , respectively. The values of L min and L max are initially chosen close to the nominal value of L f . Subject to the feasibility of the LMI conditions in Equation (17), the uncertainty interval L min L max is iteratively stretched such that the largest possible uncertainty interval is found. Following this procedure, the uncertainty interval L f + L s 1 35 -mH is obtained. As a result, the LMI conditions in equation (17) guarantees that the closed-loop system is robustly stable for all values of L f + L s in the given interval.

5.2. Robust Stability Analysis for L C L -Type Filter

For the case of the L C L -type filter, the robust stability of the closed-loop system is analyzed for the uncertainties in the L C L filter parameters L c , L g , C f , and the grid inductance L s . In this case, the polytope in Equation (15) has q = 2 3 vertices A c l i , i = 1 , , q , obtained by substituting the maximum and minimum values of L c , L g + L s , and C f in the plant model (Equation (11)) and the resultant matrices in Equation (9). Following the stretching procedure proposed for the case of the L-type filter, the robust stability of the closed-loop system for all values of L c , L g + L s , and C f in the intervals L c 1 17.5 -mH, L g + L s 2.5 15 -mH, and C f 10 22 - μ F is guaranteed.

6. Performance Evaluation

An experimental test setup has been developed, as shown in Figure 7, with the parameters of Table A1. This realizes the test system of Figure 1 and is a hardware-in-the-loop (HIL) configuration consisting of: (1) a 20-kVA two-level SemikronSKHI61 inverter; (2) a pulse width modulation (PWM) signal generator; (3) either an L-type filter realized by a 5-mH, 25-A inductor or an L C L -type filter realized by two 5-mH, 25-A inductors and a 19- μ F capacitor; (4) a 20-kVA, 50:120 V step-up transformer; (5) a dc voltage source implemented using a full-bridge diode rectifier fed by a 24.2-kVA, 50-A autotransformer with a variable output voltage of 0–280 V, a 450-V dc capacitor on the dc side of the diode rectifier, and a 1:1 isolating transformer interfacing the ac side of the diode rectifier to the grid; (6) a circuit breaker (CB) representing the islanding switch; and (7) an R L C load connected to the low-voltage side of the step-up transformer. The DER controller is implemented on an OP5600 real-time digital simulator. The simulator and the hardware interact through: (i) an OP8660 HIL Controller and Data Acquisition Interface that measures v s a b c , V d c , and i t a b c signals and supplies them to the OP5600 simulator; and (ii) three output channels of the OP5600 simulator that supply the reference signals v t a b c * to the PWM signal generator device. The amplitude of the injected negative-sequence current has been fixed at 4%, and the detection threshold is set at 2%. All signals are saved using OP5600 scopes as data files and then re-plotted in MATLAB.

6.1. L-Type Filter

6.1.1. Performance under the IEEE1547 Test Conditions

This standard requires the DER unit to detect the island within 2 s of its formation. At t = 1 s, an intentional islanding event is produced by manually opening the circuit breaker CB. Figure 8 presents the results. The DER detects this increase in V n and successfully declares an islanding condition within about 6 ms. Figure 8c shows the injected double-frequency perturbations in I t d and I t q . Figure 8e,g show that V p and f have the same steady-state value before and after the islanding event since the DER powers match those of the load in steady-state.

6.1.2. Effect of Load (L) Imbalance

In this case, the inductance of phase ‘a’ of the load has been reduced by 50%. Figure 9 shows that the proposed control scheme maintains stability and detects the island in about 4 ms. Contained oscillations in V n are due to the resonance between the perturbed L and C. This mismatch also causes the frequency to deviate from its nominal value following the islanding.

6.1.3. Performance under Weak Grid Conditions

The PCC short-circuit ratio (SCR) is weakened by adding a 5-mH series inductor between the PCC and the low-voltage terminals of the step-up transformer. Before adding this inductor, the PCC SCR is about 10, and the added 5-mH inductor reduces the SCR to about 1.8, thus creating a weak grid condition. Figure 10 illustrates the stable performance of the control and the successful detection of the island within about 2 ms.

6.1.4. Effect of Filter Parameter Uncertainty

The inductance of the output filter has been increased by 100% by adding another 5-mH inductor to it. Figure 11 illustrates the stable performance of the controller and the successful detection of the island in about 7 ms despite this considerable uncertainty.

6.2. L C L -Type Filter

6.2.1. IEEE1547 Test Conditions

Figure 12 illustrates the successful detection of the islanding event in about 5 ms.

6.2.2. Load (L) Imbalance

Figure 13 shows the successful detection of the islanding event in about 4 ms.

6.2.3. Weak Grid Conditions

Figure 14 shows that the controller has a stable performance, and the islanding detection is successful under weak grid conditions. The pre-islanding negative-sequence voltage component at PCC appears but does not cause an erroneous islanding detection.

6.2.4. Filter Parameter Uncertainty

The grid-side inductance of the L C L filter has been increased by 100% by adding a 5-mH inductor in the series with L g . Figure 15 shows the results illustrating the stable performance of the controller and the successful detection of the island in about 4 ms.

6.3. Comparison with Conventional Controller

The conventional controller is designed according to the guidelines of [7]. The parameters of the system and controller are given in Table I and Appendix A of [7]. At t = 1 s, a step jump from 0.66 pu (2300 A) to 1 pu (3460 A) in the positive-sequence real current is applied to both systems. The following four scenarios are simulated in the MATLAB/Simscape environment using the realistic switching model of the VSC. In each scenario, the real and reactive currents, and the error of the current signals for both conventional and proposed systems are shown.

6.3.1. Case I: Base Conditions

In this case, no uncertainty is considered, and the grid is stiff (SCR = 20). Figure 16 shows that both methods have similar transient responses, while the proposed one shows better decoupling of the real and reactive currents.

6.3.2. Case II: Uncertain Conditions

An uncertainty of 30% is introduced in the inverter filter inductance. Figure 17 shows that this uncertainty has slowed down the conventional method’s response, while the proposed method is unaffected.

6.3.3. Case III: Weak Grid Conditions

A weak grid condition that reduces the SCR from 20 to 2 is introduced in the system. Figure 18 shows that this weak grid condition has caused a further increase in the response transient time and the level of oscillations in the conventional method, while the proposed method is unaffected.

6.3.4. Case IV: Uncertain and Weak Grid Conditions

A 50% uncertainty in the filter inductance is combined with the weak grid condition (SCR = 2). Figure 19 shows that the responses of the conventional system have become very sluggish, and the coupling between the real and reactive current loops has increased, whereas the proposed method is still unaffected.
Further simulations demonstrate that the proposed method is strongly robust against the inverter filter uncertainties and weak grid conditions. For example, with an uncertainty of 250% in the inverter filter combined with an extremely weak grid (SCR = 1), the proposed method still provides good performance, while the conventional system shows poor performance and even becomes unstable when the uncertainty in the L-filter exceeds 100% and the grid SCR is below two. This concludes that due to the inclusion of multiple additional filters in the conventional controller, interfering dynamics are produced, which compromise its robust performance and stability under uncertain and/or weak grid conditions. Moreover, the proposed method is computationally more efficient than the conventional method. For example, when running the simulation in the Matlab/Simulink at the same conditions, the conventional method takes about twice more time than the proposed method.

7. Conclusions

This paper presented a new controller for a grid-connected converter unit with negative-sequence current capability. The main advantage of the proposed control scheme with respect to the similar existing one is the simultaneous control of the negative-sequence perturbation and positive-sequence current by means of a single unified controller. This feature greatly simplifies the controller. This simplified structure, together with the optimal design of the proposed control scheme, provides a high level of robustness against variation of grid stiffness and filter parameter uncertainties. The proposed controller is also applicable to both L- and L C L -type output filters.

Author Contributions

Conceptualization, H.K. and M.K.-G.; Modeling and simulation, H.K. and A.H.; Experimental results, A.H., M.K.-G., and H.K.; Formal analysis, H.K., M.K.-G., M.S.; Stability analysis, M.S.; Investigation, H.K., A.H., and M.K.-G.; Writing–original draft preparation, A.H. and M.K.-G.; Writing–review and editing, M.K.-G., A.H., and H.K.; Supervision, H.K and M.K.-G. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Conflicts of Interest

The authors declare no conflict of interest.

Appendix A. Test System Parameters

Table A1 presents the parameters of the test system.
Table A1. Parameters of the experimental setup of Figure 7.
Table A1. Parameters of the experimental setup of Figure 7.
DER Unit
ParameterValueRatingManufacturer
Inverter power rating 20 kVASemikron
Switching frequency10 kHz
L f , R f 5 mH ,60 m Ω 25 AHammond
L c , R c 5 mH ,60 m Ω 25 AHammond
L g , R g 5 mH ,60 m Ω 25 AHammond
C f 19 μ F240 VLab-Volt
Load
R , L , C 8 Ω , 92.6 mH, 76 μ F500 W, 25 A, 240 VHammond, Lab-Volt
Grid and DC Source
Voltage, Freq86 V (rms-LL), 60 Hz12 kVA
DC Source280 V24 kW
Controller
OP5600Real-time Simulator OPAL-RT Technologies
OP8660HIL Controller OPAL-RT Technologies
UTSP
ζ 1 , ζ 2 0.4, 1.5

Appendix B. Representation of Unbalanced Signals in the dq-frame

Consider an unbalanced three-phase signal, x a b c ( t ) , as
x a b c ( t ) = x a ( t ) x b ( t ) x c ( t ) = A p cos ( ω t + δ p ) A p cos ( ω t + δ p 120 ) A p cos ( ω t + δ p + 120 ) + A n cos ( ω t + δ n ) A n cos ( ω t + δ n + 120 ) A n cos ( ω t + δ n 120 ) + A z cos ( ω t + δ z ) A z cos ( ω t + δ z ) A z cos ( ω t + δ z )
where A p , A n , and A z are, respectively, the magnitudes of positive-, negative-, and zero-sequence, and δ p , δ n , and δ z are the corresponding phase-angles. Applying the Park transformation with angle θ to the three-phase signal x a b c ( t ) yields x d ( t ) = A p cos ( ω t θ + δ p ) + A n cos ( ω t + θ + δ n ) , x q ( t ) = A p sin ( ω t θ + δ p ) A n sin ( ω t + θ + δ n ) , x 0 ( t ) = A z cos ( ω t + δ z ) . When ω t θ = θ 0 , with θ 0 being a constant, the representation of the positive-sequence component of x a b c ( t ) in the d q -frame will be constant components, while its negative-sequence component will oscillate at the double-frequency 2 ω . Now, consider x d ( t ) = A + C cos ( 2 ω t + δ d ) , x q ( t ) = B + D cos ( 2 ω t + δ q ) , and x 0 ( t ) = 0 , where ω is the angular frequency, and the parameters A , B , C , D , δ d , and δ q are some constant real numbers ( C 0 , D 0 ). Using the reference phase-angle θ ( t ) = ω t and applying Park inverse transformation to x d q 0 ( t ) results in
x a ( t ) = A a cos ( ω t + δ a ) + 1 2 C cos ( 3 ω t + δ d ) 1 2 D sin ( 3 ω t + δ q ) x b ( t ) = A b cos ( ω t + δ b ) + 1 2 C cos ( 3 ω t + δ d 120 ) 1 2 D sin ( 3 ω t + δ q 120 ) x c ( t ) = A c cos ( ω t + δ c ) + 1 2 C cos ( 3 ω t + δ d + 120 ) 1 2 D sin ( 3 ω t + δ q + 120 )
Thus, the conditions that eliminate the third harmonic are C = D and δ q = δ d + 90 .

References

  1. Camacho, A.; Castilla, M.; Miret, J.; Borrell, A.; de Vicuña, L.G. Active and reactive power strategies with peak current limitation for distributed generation inverters during unbalanced grid faults. IEEE Trans. Ind. Electron. 2014, 62, 1515–1525. [Google Scholar] [CrossRef] [Green Version]
  2. Nian, H.; Shen, Y.; Yang, H.; Quan, Y. Flexible grid connection technique of voltage-source inverter under unbalanced grid conditions based on direct power control. IEEE Trans. Ind. Appl. 2015, 51, 4041–4050. [Google Scholar] [CrossRef]
  3. Nejabatkhah, F.; Li, Y.W.; Wu, B. Control strategies of three-phase distributed generation inverters for grid unbalanced voltage compensation. IEEE Trans. Power Electron. 2015, 31, 5228–5241. [Google Scholar]
  4. Guo, X.; Liu, W.; Lu, Z. Flexible power regulation and current-limited control of the grid-connected inverter under unbalanced grid voltage faults. IEEE Trans. Ind. Electron. 2017, 64, 7425–7432. [Google Scholar] [CrossRef]
  5. Castilla, M.; Miret, J.; Camacho, A.; de Vicuña, L.G.; Matas, J. Modeling and design of voltage support control schemes for three-phase inverters operating under unbalanced grid conditions. IEEE Trans. Power Electron. 2014, 29, 6139–6150. [Google Scholar] [CrossRef]
  6. Rodriguez, P.; Timbus, A.V.; Teodorescu, R.; Liserre, M.; Blaabjerg, F. Flexible active power control of distributed power generation systems during grid faults. IEEE Trans. Ind. Electron. 2007, 54, 2583–2592. [Google Scholar] [CrossRef]
  7. Karimi, H.; Yazdani, A.; Iravani, R. Negative-sequence current injection for fast islanding detection of a distributed resource unit. IEEE Trans. Power Electron. 2008, 23, 298–307. [Google Scholar] [CrossRef]
  8. Dhar, S.; Dash, P.K. Performance analysis of a new fast negative sequence power injection oriented islanding detection technique for photovoltaic photovoltaic based voltage source converter based micro grid operation. IET Gener. Transm. Distrib. 2015, 9, 2079–2090. [Google Scholar] [CrossRef]
  9. Blaabjerg, F.; Teodorescu, R.; Liserre, M.; Timbus, A.V. Overview of control and grid synchronization for distributed power generation systems. IEEE Trans. Ind. Electron. 2006, 53, 1398–1409. [Google Scholar] [CrossRef] [Green Version]
  10. Du, X.; Gu, S.; Wang, G.; Tai, H.M.; Ji, Y. Simple current control method for three-phase VSC under unbalanced grid condition. IET Power Electron. 2018, 11, 1161–1168. [Google Scholar] [CrossRef]
  11. Shin, D.; Lee, K.J.; Lee, J.P.; Yoo, D.W.; Kim, H.J. Implementation of fault ride-through techniques of grid-connected inverter for distributed energy resources with adaptive low-pass notch PLL. IEEE Trans. Power Electron. 2014, 30, 2859–2871. [Google Scholar] [CrossRef]
  12. Mahamedi, B.; Eskandari, M.; Fletcher, J.E.; Zhu, J. Sequence-Based Control Strategy With Current Limiting for the Fault Ride-Through of Inverter-Interfaced Distributed Generators. IEEE Trans. Sustain. Energy 2018, 11, 165–174. [Google Scholar] [CrossRef]
  13. Zhao, X.; Guerrero, J.M.; Savaghebi, M.; Vasquez, J.C.; Wu, X.; Sun, K. Low-voltage ride-through operation of power converters in grid-interactive microgrids by using negative-sequence droop control. IEEE Trans. Power Electron. 2016, 32, 3128–3142. [Google Scholar] [CrossRef] [Green Version]
  14. Liserre, M.; Teodorescu, R.; Blaabjerg, F. Stability of photovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values. IEEE Trans. Power Electron. 2006, 21, 263–272. [Google Scholar] [CrossRef]
  15. Midtsund, T.; Suul, J.; Undeland, T. Evaluation of current controller performance and stability for voltage source converters connected to a weak grid. In Proceedings of the 2nd International Symposium on Power Electronics for Distributed Generation Systems, Hefei, China, 16–18 June 2010; pp. 382–388. [Google Scholar]
  16. Silwal, S.; Taghizadeh, S.; Karimi-Ghartemani, M.; Hossain, M.J.; Davari, M. An enhanced control system for single-phase inverters interfaced with weak and distorted grids. IEEE Trans. Power Electron. 2019, 34, 12538–12551. [Google Scholar] [CrossRef]
  17. Liu, W.; Blaabjerg, F.; Zhou, D.; Chou, S.F. Modified Instantaneous Power Control with Phase Compensation and Current-limited Function under Unbalanced Grid Faults. IEEE J. Emerg. Sel. Top. Power Electron. 2021, 9, 2896–2906. [Google Scholar] [CrossRef]
  18. Wu, W.; Liu, J.; Li, Y.; Blaabjerg, F. Individual Channel Design-Based Precise Analysis and Design for Three-Phase Grid-Tied Inverter with LCL-Filter under Unbalanced Grid Impedance. IEEE Trans. Power Electron. 2020, 35, 5381–5396. [Google Scholar] [CrossRef]
  19. Afshari, E.; Moradi, G.R.; Rahimi, R.; Farhangi, B.; Yang, Y.; Blaabjerg, F.; Farhangi, S. Control strategy for three-phase grid-connected PV inverters enabling current limitation under unbalanced faults. IEEE Trans. Ind. Electron. 2017, 64, 8908–8918. [Google Scholar] [CrossRef] [Green Version]
  20. Maccari, L.A.; Massing, J.R.; Schuch, L.; Rech, C.; Pinheiro, H.; Oliveira, R.C.; Montagner, V.F. LMI-based control for grid-connected converters with LCL filters under uncertain parameters. IEEE Trans. Power Electron. 2013, 29, 3776–3785. [Google Scholar] [CrossRef]
  21. Lai, N.B.; Kim, K.H. Robust control scheme for three-phase grid-connected inverters with LCL-filter under unbalanced and distorted grid conditions. IEEE Trans. Energy Convers. 2017, 33, 506–515. [Google Scholar] [CrossRef]
  22. Karimi, H.; Karimi-Ghartemani, M.; Sheshyekani, K. Robust control of three-phase voltage source converters under unbalanced grid conditions. IEEE Trans. Power Electron. 2019, 34, 11278–11289. [Google Scholar] [CrossRef]
  23. Zarei, S.F.; Mokhtari, H.; Ghasemi, M.A.; Peyghami, S.; Davari, P.; Blaabjerg, F. Control of grid-following inverters under unbalanced grid conditions. IEEE Trans. Energy Convers. 2019, 35, 184–192. [Google Scholar] [CrossRef]
  24. Yin, Y.; Vazquez, S.; Marquez Alcaide, A.; Liu, J.; Leon, J.I.; Wu, L.; Franquelo, L.G. Observer-Based Sliding Mode Control for Grid-Connected Power Converters under Unbalanced Grid Conditions. IEEE Trans. Ind. Electron. 2021, 1. [Google Scholar] [CrossRef]
  25. Khalil, H.K. Nonlinear Systems, 3rd ed.; Prentice-Hall: Upper Saddle River, NJ, USA, 2002. [Google Scholar]
  26. Li, J.; Zhang, Y.; Zhao, Y.; Ren, L.; Wang, J.; Liu, Y. An Improved Three-Stages Cascading Passivity-Based Control of Grid-Connected LCL Converter in Unbalanced Weak Grid Condition. IEEE Access 2021, 9, 89497–89506. [Google Scholar] [CrossRef]
  27. Graungaard Taul, M.; Wang, X.; Davari, P.; Blaabjerg, F. Current Reference Generation Based on Next-Generation Grid Code Requirements of Grid-Tied Converters During Asymmetrical Faults. IEEE J. Emerg. Sel. Top. Power Electron. 2020, 8, 3784–3797. [Google Scholar] [CrossRef] [Green Version]
  28. Guan, L.; Yao, J.; Liu, R.; Sun, P.; Gou, S. Small-Signal Stability Analysis and Enhanced Control Strategy for VSC System during Weak-Grid Asymmetric Faults. IEEE Trans. Sustain. Energy 2021, 1. [Google Scholar] [CrossRef]
  29. Davison, E.; Ferguson, I. The design of controllers for the multivariable robust servomechanism problem using parameter optimization methods. IEEE Trans. Autom. Control. 1981, 26, 93–110. [Google Scholar] [CrossRef]
  30. Sadabadi, M.S.; Haddadi, A.; Karimi, H.; Karimi, A. A Robust Active Damping Control Strategy for an LCL-Based Grid-Connected DG Unit. IEEE Trans. Ind. Electron. 2017, 64, 8055–8065. [Google Scholar] [CrossRef]
  31. Safonov, M.; Athans, M. Gain and phase margin for multiloop LQG regulators. IEEE Trans. Autom. Control. 1977, 22, 173–179. [Google Scholar] [CrossRef]
  32. Lin, F. Robust Control Design: An Optimal Control Approach; John Wiley & Sons: Chichester, UK, 2007. [Google Scholar]
  33. Sadabadi, M.S.; Peaucelle, D. From static output feedback to structured robust static output feedback: A survey. Annu. Rev. Control 2016, 42, 11–26. [Google Scholar] [CrossRef] [Green Version]
  34. Ebihara, Y.; Peaucelle, D.; Arzelier, D. S-Variable Approach to LMI-Based Robust Control, 1st ed.; Springer: London, UK, 2015. [Google Scholar]
  35. Lofberg, J. YALMIP: A toolbox for modeling and optimization in MATLAB. In Proceedings of the 2004 IEEE International Conference on Robotics and Automation (IEEE Cat. No.04CH37508), Taipei, Taiwan, 2–4 September 2004; pp. 284–289. [Google Scholar] [CrossRef]
  36. MOSEK ApS. The MOSEK Optimization Toolbox for MATLAB Manual. Version 9.0.; 2019. [Google Scholar]
Figure 1. A schematic diagram of the test system.
Figure 1. A schematic diagram of the test system.
Energies 14 04549 g001
Figure 2. A schematic diagram of the conventional controller of [7].
Figure 2. A schematic diagram of the conventional controller of [7].
Energies 14 04549 g002
Figure 3. The structure of the proposed control scheme.
Figure 3. The structure of the proposed control scheme.
Energies 14 04549 g003
Figure 4. Loci of the closed-loop system poles for the L-type filter.
Figure 4. Loci of the closed-loop system poles for the L-type filter.
Energies 14 04549 g004
Figure 5. Loci of the closed-loop system poles for the L C L -type filter.
Figure 5. Loci of the closed-loop system poles for the L C L -type filter.
Energies 14 04549 g005
Figure 6. Loci of the closed-loop system poles for the L C L -type filter without additional sensors.
Figure 6. Loci of the closed-loop system poles for the L C L -type filter without additional sensors.
Energies 14 04549 g006
Figure 7. Experimental setup: (top) a block diagram of the circuit, and (bottom) the laboratory setup.
Figure 7. Experimental setup: (top) a block diagram of the circuit, and (bottom) the laboratory setup.
Energies 14 04549 g007
Figure 8. L-type filter case: Performance of the proposed controller under the IEEE1547 anti-islanding test: (a) three-phase PCC voltages; (b) three-phase inverter terminal currents; (c) d- and q-axis components of the inverter terminal current; (d) fundamental frequency power components of the DER unit; (e,f) amplitudes of positive- and negative-sequence PCC voltage, respectively; (g) frequency; and (h) ID signal.
Figure 8. L-type filter case: Performance of the proposed controller under the IEEE1547 anti-islanding test: (a) three-phase PCC voltages; (b) three-phase inverter terminal currents; (c) d- and q-axis components of the inverter terminal current; (d) fundamental frequency power components of the DER unit; (e,f) amplitudes of positive- and negative-sequence PCC voltage, respectively; (g) frequency; and (h) ID signal.
Energies 14 04549 g008
Figure 9. L-type filter case: Performance under load (L) imbalance: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Figure 9. L-type filter case: Performance under load (L) imbalance: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Energies 14 04549 g009
Figure 10. L-type filter case: Performance under weak grid condition with SCR = 1.8: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Figure 10. L-type filter case: Performance under weak grid condition with SCR = 1.8: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Energies 14 04549 g010
Figure 11. L-type filter case: Performance under 100% increase in filter inductance: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Figure 11. L-type filter case: Performance under 100% increase in filter inductance: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Energies 14 04549 g011
Figure 12. L C L -type filter case. Performance of the proposed controller under the IEEE1547 anti-islanding test: (a) three-phase PCC voltages; (b) three-phase inverter terminal currents; (c) d- and q-axis components of inverter terminal current; (d) fundamental frequency power components of the DER unit; (e,f) amplitude of positive- and negative-sequence voltages at PCC, respectively; (g) frequency; and (h) ID signal.
Figure 12. L C L -type filter case. Performance of the proposed controller under the IEEE1547 anti-islanding test: (a) three-phase PCC voltages; (b) three-phase inverter terminal currents; (c) d- and q-axis components of inverter terminal current; (d) fundamental frequency power components of the DER unit; (e,f) amplitude of positive- and negative-sequence voltages at PCC, respectively; (g) frequency; and (h) ID signal.
Energies 14 04549 g012
Figure 13. L C L -type filter case. Performance under load (L) imbalance: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Figure 13. L C L -type filter case. Performance under load (L) imbalance: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Energies 14 04549 g013
Figure 14. L C L -type filter case. Performance under weak grid condition with SCR = 1.8: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Figure 14. L C L -type filter case. Performance under weak grid condition with SCR = 1.8: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Energies 14 04549 g014
Figure 15. L C L -type filter case: Performance under 100% increase in L g : (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Figure 15. L C L -type filter case: Performance under 100% increase in L g : (a,b) estimated magnitudes of positive- and negative-sequence PCC voltage, respectively; (c) estimated frequency; and (d) ID signal.
Energies 14 04549 g015
Figure 16. Comparison of the results for Case I: d q components of the inverter currents ( I t , d q ) and error signals ( e t , d q ): (a,b) conventional method, and (c,d) proposed method.
Figure 16. Comparison of the results for Case I: d q components of the inverter currents ( I t , d q ) and error signals ( e t , d q ): (a,b) conventional method, and (c,d) proposed method.
Energies 14 04549 g016
Figure 17. Comparison of the results for Case II: d q components of the inverter currents ( I t , d q ) and error signals ( e t , d q ): (a,b) conventional method, and (c,d) proposed method.
Figure 17. Comparison of the results for Case II: d q components of the inverter currents ( I t , d q ) and error signals ( e t , d q ): (a,b) conventional method, and (c,d) proposed method.
Energies 14 04549 g017
Figure 18. Comparison of the results for Case III: d q components of the inverter currents ( I t , d q ) and error signals ( e t , d q ): (a,b) conventional method, and (c,d) proposed method.
Figure 18. Comparison of the results for Case III: d q components of the inverter currents ( I t , d q ) and error signals ( e t , d q ): (a,b) conventional method, and (c,d) proposed method.
Energies 14 04549 g018
Figure 19. Comparison of the results for Case IV: d q components of the inverter currents ( I t , d q ) and error signals ( e t , d q ): (a,b) conventional method, and (c,d) proposed method.
Figure 19. Comparison of the results for Case IV: d q components of the inverter currents ( I t , d q ) and error signals ( e t , d q ): (a,b) conventional method, and (c,d) proposed method.
Energies 14 04549 g019
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Karimi, H.; Haddadi, A.; Karimi-Ghartemani, M.; Sadabadi, M. A Robust Vector Current Controller with Negative-Sequence Current Capability for Grid-Connected Inverters. Energies 2021, 14, 4549. https://doi.org/10.3390/en14154549

AMA Style

Karimi H, Haddadi A, Karimi-Ghartemani M, Sadabadi M. A Robust Vector Current Controller with Negative-Sequence Current Capability for Grid-Connected Inverters. Energies. 2021; 14(15):4549. https://doi.org/10.3390/en14154549

Chicago/Turabian Style

Karimi, Houshang, Aboutaleb Haddadi, Masoud Karimi-Ghartemani, and Mahdieh Sadabadi. 2021. "A Robust Vector Current Controller with Negative-Sequence Current Capability for Grid-Connected Inverters" Energies 14, no. 15: 4549. https://doi.org/10.3390/en14154549

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop