Thermal Analysis of the Medium Voltage Cable

by
Tomasz Szczegielniak
*,
Dariusz Kusiak
and
Paweł Jabłoński
Department of Automation, Electrical Engineering and Optoelectronics, Faculty of Electrical Engineering, Czestochowa University of Technology, Armii Krajowej 17, 42-200 Czestochowa, Poland
*
Author to whom correspondence should be addressed.
Energies 2021, 14(14), 4164; https://doi.org/10.3390/en14144164
Submission received: 15 June 2021 / Revised: 7 July 2021 / Accepted: 8 July 2021 / Published: 9 July 2021
(This article belongs to the Section J: Thermal Management)

Abstract

:
The use of high voltage power cables in distribution and transmission networks is still increasing. As a result, the research on the electrical performance of cable lines is still up to date. In the paper, an analytical method of determining the power losses and the temperature distribution in the medium voltage cable was proposed. The main feature of the method is direct including the skin and proximity effects. Then the Joule law is used to express the power losses in the conductor and screen, and the Fourier-Kirchhoff equation is applied to find out the temperature distribution in the cable. The research was focused on a cable with isolated screen and return current in the screen taken into account. The proposed method was tested by using the commercial COMSOL software(5.6/COMSOL AB, Stockholm, Sweden) as well as by carrying out laboratory measurements. Furthermore, the results obtained via the proposed method were compared with those given in literature. The differences between the temperature values calculated by the analytical method, numerical computations and obtained experimentally do not exceed 10%. The proposed analytical method is suitable in prediction the temperature of the power cables with good accuracy.

Graphical Abstract

1. Introduction

An increasing demand for electric energy, among others due to growth in population density, results in wide usage of power cables [1,2,3,4,5]. In such places as city centers, the installation of overhead lines not always is desirable or even possible; therefore, underground cables for the electric energy transmission are used. The first underground cable line was installed in the United Kingdom in 1890. Over 100 years experience in electric power infrastructure make high voltage cables a good solution for using in underground high-power transmission system [6,7,8,9,10,11]. Compared with overhead transmission lines, power cable lines are safer and more reliable. On the other hand, malfunctions of cable lines are harder to detect and their maintenance or repair is time-consuming and more expensive. Increasing requirements for reliability in power transmission are the challenges in optimizing the design of the power cable lines [12,13,14,15,16].
The crucial factors defining the cable ampacity, i.e., the largest current passing safely in the cable, are the conductor cross-sectional area, its electrical conductivity and the operating temperature. In case of DC cables, the bigger the cross-sectional area and conductivity the higher the ampacity. For AC cables, this rule applies for small enough cross-sections, because the current density distribution across the cable is not uniform due to electromagnetic induction (skin and proximity effects). The passage of current generates heat in the conductor, which rises the temperature and affects the insulating layers of the cable. If the insulation temperature exceeds the permissible one for a longer time, the insulation material (usually polyethylene) can be melted leading to permanent damage of the cable [17,18,19,20,21,22,23,24].
A typical power cable includes of a copper or aluminum conductor and a number of auxiliary layers that perform insulating, shielding and protective functions. The structure of the medium voltage cable is presented in Figure 1. There are two types of losses generated in a cable: current-dependent losses and voltage-dependent losses. Current-dependent losses refer to the heat generated in conductor and screen. In turn the voltage-dependent losses refer to the heat generated in insulation layers. The heat generated by the above-mentioned losses tends to increase the temperatures of the associated and surrounding cable parts.
Heating of cable lines was a subject of several dozen papers in recent years. The thermal properties of high and medium voltage cables have been studied both analytically [7,8] as well as numerically [3,6,15,19]. Numerical methods such as finite elements or finite differences have been applied in thermal analysis of power cables. Several papers concern power cables buried in the ground or placed in tunnels [2,6,10]. In the calculations reported in literature, the power losses generated in cable conductor are calculated using Joule’s law for cable conductor AC resistance, without taking into account skin and proximity effects [2]. The skin effect and proximity effects cause non-uniform distribution of the current density in the conductor and the screen. As a result, the effective cross-section of the current path decreases, and the cable resistance increases. Consequently, the power losses and temperature in conductor increases, too. Thus, in the precise thermal analysis of the power cables the skin and proximity effects should be taken into account. Usually, these effects are taken into account through introducing specific coefficients into the computational model. This is the easiest way to include the above-mentioned effects in thermal considerations, and is widely used [3,6,8]. In contrast, the method proposed in this paper is based on the use of analytical solutions of the current densities in a cylindrical conductor and in tubular screen. Even though the current densities are expressed by Bessel functions, it is possible to calculate the integrals of these functions and thus determine the power losses in the cable parts. It is therefore possible to determine the volume heat sources and the temperature distribution in the cable.
The novelty of the paper is the development of an analytical method for determining power losses and temperature of a power cable, taking into account skin and proximity effects. In addition, this paper presents the analytical method of cable temperature determination with simultaneous taking into account of the return current in the screen and losses in insulation layers. The proposed method can be used therefore to determine the cable temperature in non-nominal and short-circuit conditions. Moreover, an additional advantage of the presented method is the determination of the temperature distribution along the radius of the cable. Therefore, the proposed method can be used for cable structure optimization.
The outline of the method is as follows: first we determine the current-dependent losses which are generated in the braided conductor and wire screen. In the calculations we assume that the braided conductor is a cylindrical conductor and the wire screen is a tubular conductor. Power losses generated in these parts are functions of load current and they are determined from Joule’s law with the skin and proximity effects taken into account. Next, from the Fourier-Kirchhoff equation the distribution of the temperature in the cable is determined. Two configurations are considered: cable with isolated screen and cable with return current in the screen. The proposed analytical method is validated through finite element method and laboratory measurements. Moreover, in Section 5 the results of calculations taking into account the voltage-dependent losses are presented.

2. Power Losses and Temperature in the Cable with Isolated Screen

Let us consider the power losses in the medium voltage cable of cross-section presented in the Figure 2. Assuming the braided conductor is a cylindrical conductor with outer radius R1 one obtains the current density in the following form [25]:
J _ ( r ) = Γ _   I _ 2   π   R 1   I 0 ( Γ _ r ) I 1 ( Γ _ R 1 )
where I means complex rms (root mean square) value of current, I 0 ( Γ _ r ) , I 1 ( Γ _ R 1 ) are the modified Bessel functions of the first kind of order 0 and 1 [26], respectively, Γ _ = j ω μ 0 γ is the complex propagation constant, ω is the angular frequency, μ 0 = 4 π   10 7   H m - 1 is the magnetic permeability of the vacuum, and γ is the electrical conductivity of the conductor.
In turn, assuming the screen is a tubular conductor with the internal and external radii R2 and R3, respectively, the following equation for eddy current density inside the screen is obtained:
J _ e 0 ( r ) = 1 z J _ e 0 ( r ) = Γ _ e   I _ 2   π   R 2 j _ e 0 ( r ) = 1 z J e 0 ( r )   exp [ j φ J   e 0 ( r ) ]
where:
j _ e 0 ( r ) = b _ 0   I 0 ( Γ _ e   r ) + c _ 0   K 0 ( Γ _ e   r ) d _ 0
In addition:
d _ 0 = I 1 ( Γ _ e R 3 )   K 1 ( Γ _ e R 2 ) I 1 ( Γ _ e R 2 )   K 1 ( Γ _ e R 3 )
b _ 0 = β e   K 1 ( Γ _ e R 2 ) K 1 ( Γ _ e R 3 )
c _ 0 = β e   I 1 ( Γ _ e R 2 ) I 1 ( Γ _ e R 3 )
β e = R 2 R 3 (   0 β e 1 )
In the above equations Γ _ e = j   ω   μ γ e = ω   μ   γ e   exp [ j π 4 ] is the complex propagation constant for the screen, whereas γ e is the electrical conductivity of the screen.
Power losses in the conductor and screen can be calculated from the Joule law, i.e., [27]:
P = V 1 γ J _ ( r ) J _ * ( r )   d V
Power losses in the conductor of the medium voltage cable presented in the Figure 2 are as follows:
P = I 2 Γ _   l 4 π   R 1   γ I 0 ( Γ _   R 1 )   I 1 * ( Γ _   R 1 ) j   I 0 * ( Γ _   R 1 )   I 1 ( Γ _   R 1 ) I 1 ( Γ _   R 1 )   I 1 * ( Γ _   R 1 )
where l is the length of the cable. In turn, power losses in the screen are equal to:
P e 0 = Γ _ e *   l   I 2 4   π   γ e   β e 2   R 3 a _ 0 d _ 0   d _ 0 *
where:
a _ 0 = b _ 0   b _ 0 * { I 0 * ( Γ _ e R 3 ) I 1 ( Γ _ e R 3 ) + j   I 0 ( Γ _ e R 3 ) I 1 * ( Γ _ e R 3 ) β e [ I 0 * ( Γ _ e R 2 ) I 1 ( Γ _ e R 2 ) + j   I 0 ( Γ _ e R 2 ) I 1 * ( Γ _ e R 2 ) ] } c _ 0   c _ 0 * { K 0 * ( Γ _ e R 3 ) K 1 ( Γ _ e R 3 ) + j   K 0 ( Γ _ e R 3 ) K 1 * ( Γ _ e R 3 ) β e [ K 0 * ( Γ _ e R 2 ) K 1 ( Γ _ e R 2 ) + j   K 0 ( Γ _ e R 2 ) K 1 * ( Γ _ e R 2 ) ] } c _ 0   b _ 0 * { I 0 * ( Γ _ e R 3 ) K 1 ( Γ _ e R 3 ) j   K 0 ( Γ _ e R 3 ) I 1 * ( Γ _ e R 3 ) β e [ I 0 * ( Γ _ e R 2 ) K 1 ( Γ _ e R 2 ) j   K 0 ( Γ _ e R 2 ) I 1 * ( Γ _ e R 2 ) ] } + b _ 0   c _ 0 * { I 1 ( Γ _ e R 3 ) K 0 * ( Γ _ e R 3 ) j   I 0 ( Γ _ e R 3 ) K 1 * ( Γ _ e R 3 ) β e [ I 1 ( Γ _ e R 2 ) K 0 * ( Γ _ e R 2 ) j   I 0 ( Γ _ e R 2 ) K 1 * ( Γ _ e R 2 ) ] }
b _ 0 * = β e   K 1 * ( Γ _ e R 2 ) K 1 * ( Γ _ e R 3 )
c _ 0 * = β e   I 1 * ( Γ _ e R 2 ) I 1 * ( Γ _ e R 3 )
d _ 0 * = I 1 * ( Γ _ e R 3 ) K 1 * ( Γ _ e R 2 ) I 1 * ( Γ _ e R 2 ) K 1 * ( Γ _ e R 3 )
On the basis of the determined power losses, it is possible to determine the volumetric heat sources in the conductor and the screen. The volumetric heat source in the conductor equals:
q V = P V = I 2 Γ _   4 π 2   R 1 3   γ I 0 ( Γ _   R 1 )   I 1 * ( Γ _   R 1 ) j   I 0 * ( Γ _   R 1 )   I 1 ( Γ _   R 1 ) I 1 ( Γ _   R 1 )   I 1 * ( Γ _   R 1 )
whereas in the screen it is:
q V e = P e 0 V e
where power Pe0 is expressed by Equation (10), and the volume of the screen is:
V e = π ( R 3 2 R 2 2 ) l
In the next step the temperature is determined. Assuming the cable length, l, is much larger than its transverse dimensions (Figure 3), then in steady state the temperature in the conductor (0 < r < R1) fulfills the following equation [28]:
d 2 T d r 2 + 1 r d T d r = q V λ I
In the insulation layers (R1 < r < R2) and (R3 < r < R4) the temperature is described by the equation as follows:
d 2 T d r 2 + 1 r d T d r = 0
In turn, in the screen (R2 < r < R3) the temperature satisfies the following equation:
d 2 T d r 2 + 1 r d T d r = q V e λ I I I
The general solutions of the above equations can be expressed as follows:
T I ( r ) = A ln r q V r 2 4 λ I + B
T I I ( r ) = C ln r + D
T I I I ( r ) = E ln r q V e r 2 4 λ I I I + F
T I V ( r ) = G ln r + H
where A, B, …, H are constants that can be determined from interface and boundary conditions. In the considered case they yield:
d T I d r | r = 0 = 0
T I ( R 1 ) = T I I ( R 1 )
λ I ( d T I d r ) r = R 1 = λ I I ( d T I I d r ) r = R 1
T I I ( R 2 ) = T I I I ( R 2 )
λ I I ( d T I I d r ) r = R 2 = λ I I I ( d T I I I d r ) r = R 2
T I I I ( R 3 ) = T I V ( R 3 )
λ I I I ( d T I I I d r ) r = R 3 = λ I V ( d T I V d r ) r = R 3
λ I V ( d T I V d r ) r = R 4 = α ( T I V T o )
where To is the ambient temperature of the space around the cable, α is the heat transfer coefficient between the cable and the surrounding space, and λi is the thermal conductivity of the i-th region. Using conditions (25)–(32) in Equations (21)–(24) leads to the following results:
A = 0
B = q V 4 λ I R 1 2 + C ln R 1 + D
C = q V 2 λ I I R 1 2
D = q V e 4 λ I I I R 2 2 + E ln R 2 C ln R 2 + F
E = q V 2 λ I I I R 1 2 + q V e 2 λ I I I R 2 2
F = q V e 4 λ I I I R 3 2 E ln R 3 + G ln R 3 + H
G = q V e 2 λ I V R 3 2 q V 2 λ I V R 1 2 + q V e 2 λ I V R 2 2
H = T 0 λ I V α G R 4 G ln R 4
Thus, the temperature of the external surface of the cable (r = R4) will be given by the equation:
T ( r = R 4 ) = T O λ I V α 1 R 4 [ q V e 2 λ I V R 3 2 q V 2 λ I V R 1 2 + q V e 2 λ I V R 2 2 ]
The above presented model allows for determining the operation temperature of the medium voltage cable. Since the material properties such as electrical and thermal conductivity change with temperature, nonlinear thermal analysis should be performed. For the considered range of temperature, the electrical conductivity can be assumed as follows [6]:
γ = γ 20 1 + k ( T 20 )
where: γ 20 is an electrical conductivity at 20 °C, k is the temperature coefficient for electrical resistivity. In turn, the thermal conductivity of individual layers of the cable should be determined iteratively using physical tables.

3. Power Losses in the Cable with Return Current in the Screen

Now let us consider the power losses in the medium voltage cable with return current in the screen—see Figure 4.
In the case of cable shown in Figure 4, the current density in the screen equals [25]:
J _ e ( r ) = J _ e 0 ( r ) + J _ ew ( r )
where current density J _ e 0 ( r ) takes into account the internal proximity effect and is given by Equation (2), whereas current density J _ ew ( r ) can be expressed as follows:
J _ ew ( r ) = Γ _ e   I _ 2   π   R 3   j _ ew ( r ) = J ew ( r )   exp [ j   φ J   ew ( r ) ]
where:
j _ ew ( r ) = K 1 ( Γ _ e R 2 )   I 0 ( Γ _ e r ) + I 1 ( Γ _ e R 2 )   K 0 ( Γ _ e r ) d _ 0
In addition:
d _ 0 = I 1 ( Γ _ e R 3 )   K 1 ( Γ _ e R 2 ) I 1 ( Γ _ e R 2 )   K 1 ( Γ _ e R 3 )
The power losses in the conductor of the cable with the return current in the screen are expressed by Equation (9). In turn, the power losses in the screen can be calculated from the equation:
P e = P e 0 + P ew
where P e 0 is given by Equation (10) and power P e w can be expressed as follows:
P e w = Γ _ l   I 2 4   π   γ   R 3 a _ e b _ e b _ e *
where:
a _ e = K 1 ( Γ _ R 2 ) K 1 * ( Γ _ R 2 ) [ I 0 ( Γ _ R 3 ) I 1 * ( Γ _ R 3 ) j   I 1 ( Γ _ R 3 ) I 0 * ( Γ _ R 3 ) ] I 1 ( Γ _ R 2 ) I 1 * ( Γ _ R 2 ) [ K 0 ( Γ _ R 3 ) K 1 * ( Γ _ R 3 ) j   K 1 ( Γ _ R 3 ) K 0 * ( Γ _ R 3 ) ] + I 1 ( Γ _ R 2 ) K 1 * ( Γ _ R 2 ) [ K 0 ( Γ _ R 3 ) I 1 * ( Γ _ R 3 ) + j   K 1 ( Γ _ R 3 ) I 0 * ( Γ _ R 3 ) ] K 1 ( Γ _ R 2 )   I 1 * ( Γ _ R 2 )   [ I 0 ( Γ _ R 3 )   K 1 * ( Γ _ R 3 ) + j   I 1 ( Γ _ R 3 )   K 0 * ( Γ _ R 3 ) ]
In addition:
b _ e = I 1 ( Γ _   R 3 )   K 1 ( Γ _   R 2 ) I 1 ( Γ _   R 2 )   K 1 ( Γ _   R 3 )
b _ e * = I 1 * ( Γ _   R 3 )   K 1 * ( Γ _   R 2 ) I 1 * ( Γ _   R 2 )   K 1 * ( Γ _   R 3 )

4. Numerical Example

Based on presented model, the temperature distribution in an XRUHAKXS 1 × 120/50 12/20 kV cable [29] was calculated. Table 1 lists the materials and thermal properties of the individual cable layers shown in Figure 3. Current in the aluminum conductor was I _ = 200 A. The frequency was 50 Hz. The ambient temperature was To = 20 °C. The heat transfer coefficient was assumed to be α = 5. The electric conductivity was γ = 35 MS·m−1 for the aluminum conductor and γ = 56 MS·m−1 for the copper screen.
Apart from analytical calculations with use of the proposed method, also numerical simulations with use of finite elements were performed with the aid of the commercial COMSOL software. The Electromagnetic Heating interface and two modules: Magnetic Fields and Heat Transfer in Solids were used. In the computations the radiation and natural convection were taken into account. The natural convection was considered by applying the Heat Transfer in Fluid condition in the external region and setting the Velocity field option at 0.01 m/s along the y axis. The radiation was considered by setting the boundary condition called Diffuse Surface on the external surface of cable and by introducing the emissivity coefficient ε = 0.5. The mesh was set as: Physics-controlled mesh. The complete mesh consisted of 9974 domain elements and 304 boundary elements. Figure 5 and Figure 6 show the temperature distribution in the considered cable with isolated screen, whereas Figure 7 and Figure 8 present the temperature distribution in the cable with return current in the screen.
The plots presented in Figure 5, Figure 6, Figure 7 and Figure 8 indicate the temperature in the aluminum conductor and copper screen is nearly constant. The constancy of the temperature distribution is due to the very good thermal conductivity of the material (aluminum or copper) from which the conductor and screen is made. It means that in the steady state the temperature distribution inside conductor and screen is constant despite non-uniform distribution of the current density and power losses. This is a valuable remark that can inspire engineers involved in the analysis, design and testing of power cables, because it is possible to determine the conductor temperature versus the load current.
The calculations of the temperature of the aluminum conductor and copper screen depending on the load current value were also performed. The dependence of the conductor temperature on the current value is shown in Figure 9. In turn, the dependence of the screen temperature on the current value is shown in Figure 10. The calculations presented in Figure 9 and Figure 10 were made for the XRUHAKXS 1 × 120/50 12/20 kV cable with isolated screen.
To verify the proposed analytical method as well as the COMSOL computations, suitable measurements were also carried out. The laboratory setup used in the temperature measurements of the XRUHAKXS 1 × 120/50 12/20 kV cable is shown in Figure 11. A current of 200 A was excited in the cable by an AC current source. In order to avoid additional heating of the XRUHAKXS cable (disturbing the measurements), the connection between the generator and the tested cable was made using two copper cables with a cross-section of 120 mm2 each. The ambient temperature was To = 20 °C. Temperature measurements were made with a 9-channel temperature recorder and by TP-202J-1b-200-2.0 thermocouples. The temperature recorder was connected to a computer via a USB connector, which allowed for saving the measurement results (Figure 12). Three temperature sensors (J type) were placed in the phase conductor, another three sensors in the screen, next two on the surface of the cable and one sensor measured the ambient temperature. The temperature sensors were installed in properly drilled holes in the middle of the cable length (Figure 13). The sensors were connected to the temperature recorder. Ambient temperature was measured by a probe immersed in oil to eliminate possible short-term sudden changes in the ambient temperature. The measurements were carried out for 5 h until reaching steady state. The results of the measurements and calculations are shown in Table 2.
The results presented in Table 2 indicate the proposed method can be used to determine the temperature of medium voltage cable conductive layers with good accuracy. The differences between the temperature values calculated by analytical method and the measured ones do not exceed 10%. It is noticeable that the measured values are slightly smaller than the computed ones. These differences are most likely due to the thermal conditions in the laboratory.

5. Power Losses in the Insulation Layers

In the cable temperature calculations, the dielectric losses in the insulation material should be taken into account, because the heat is generated not only as a result of active power losses in the conductor and cable screen, but also as a result of dielectric losses. The dielectric losses in the insulation material can be expressed as follows [23]:
W d = 2 π f C U 2 tan δ
where f means frequency, U is an operating voltage, C is a capacitance of the insulation layer, tan δ is a loss tangent. The loss tangent equals:
tan δ = γ ω ε
where ω is the angular frequency, γ is for the electrical conductivity of the insulation and ε is its electrical permittivity.
In the case of medium voltage cable (Figure 3), the capacitances of the insulating layers are as follows [25]:
C I I = 2 π ε I I l ln R 2 R 1
In addition:
C I V = 2 π ε I V l ln R 4 R 3
Taking into account the dielectric losses results in appearing the source term in Equation (19) so that it takes the following form:
d 2 T d r 2 + 1 r d T d r = q i λ i
where i denotes the layer number. The general solutions of Equations (18), (56) and (20) become now:
T I ( r ) = A ln r q I r 2 4 λ I + B
T I I ( r ) = C ln r q I I r 2 4 λ I I + D
T I I I ( r ) = E ln r q I I I r 2 4 λ I I I + F
T I V ( r ) = G ln r q I V r 2 4 λ I V + H
Applying the interface and boundary conditions (25)–(32) leads to the following results:
A = 0
B = C ln R 1 + D + R 1 2 4 ( q I λ I q I I λ I I )
C = R 1 2 2 λ I I ( q I I q I )
D = ( E C ) ln R 2 + F + R 2 2 4 ( q I I λ I I q I I I λ I I I )
E = R 2 2 2 λ I I I ( q I I I q I I ) + R 1 2 2 λ I I I ( q I I q I )
F = ( G E ) ln R 3 + H + R 3 2 4 ( q I I I λ I I I q I V λ I V )
G = R 3 2 2 λ I V ( q I V q I I I ) + R 2 2 2 λ I V ( q I I I q I I ) + R 1 2 2 λ I V ( q I I q I )
H = T 0 λ I V α G R 4 G ln R 4 + q I V R 4 2 4 λ I V + q I V R 4 2 α λ I V
Exemplary temperature calculations taking into account dielectric losses were made for an XRUHAKXS 1 × 120/50 12/20 kV cable, assuming the geometrical and physical parameters as in Section 4 and: U = 12 kV, εo = 8.85·10−12 F/m, εII = εII = 2.25, γII = γIV = 10−12 S/m. This gave CII = 0.185 nF, CIV = 0.682 nF, qII = 3.83 W/m3 and qIV = 0 W/m3. The temperature distribution along the cable radius is shown in the Figure 14.
Comparing Figure 14 with Figure 5, it can be noticed that they are nearly the same, and this is due to the fact that the dielectric losses are much less than in the aluminum conductor. Thus, in the thermal analysis of the medium voltage cable the dielectric losses can be omitted because the temperature of the cable is determined by the power losses in the conductor.

6. Results Discussion

For a broader analysis, the results obtained via the analytical method proposed in the paper were compared with the simulation results with those for two types of XLPE cables given in [15] and [30]. Table 3 shows the materials and thermal properties of the individual XLPE-0 cable layers described in [15]. The current in the copper conductor was I _ = 1244   A . The frequency was 50 Hz. The ambient temperature was To = 17.7 °C. The electric conductivity was γ = 55 MS·m−1 for the copper conductor, and γ = 35 MS·m−1 for the aluminum screen. The cable conductor temperature calculation results are shown in Table 4.
In addition, the calculations of the temperature of a 110 kV XLPE cable from [30] were performed. The thermal and geometrical parameters of the cable layers are presented in Table 5. The current in the copper conductor was I _ = 850   A . The ambient temperature was assumed to be To = 40 °C. The results of the cable conductor temperature calculation are presented in Table 6.
Based on the results presented in Table 4 and Table 6, it can be concluded that the analytical method proposed in this paper can be successfully used to determine the temperature of power cables. The differences between the results presented in [15,30] and the values obtained with the use of the proposed approach do not exceed a few percent. The analysis of Table 2, Table 4 and Table 6 confirm that the method presented in this paper is fairly accurate.

7. Conclusions

In the paper an analytical approach to the determination of the operation temperature of the medium voltage cable has been presented. The proposed method of determining the temperature allows for the derivation of not very complicated relationships that may be inspiring for engineers dealing with the analysis, design and testing of power cables. The most important advantage of the proposed method is its transparency and short calculation time. In the presented analytical model, the skin and proximity effects were considered. The results obtained via the proposed analytical method were compared with those by the finite element method, laboratory measurements and the results of simulations reported in other scientific paper. The differences between the temperature values calculated with use of the analytical method, computed by COMSOL and measured do not exceed 10% and the differences between the simulation results presented in [15] and those obtained with the use of the proposed analytical method do not exceed several percent. Thus, on the basis of the performed validation, it can be concluded that the analytical method proposed in the paper is fairly accurate.
The determination of the operation temperature of many power devices is made by numerical methods. However, they do not allow for generalization of the results and derivation of useful dependencies aiding the design of specific elements of power system. Analytical methods can be used for simple elements. Power cables are not complicated devices, so the analytical method to analyze them can be used. The adoption of certain simplifying assumptions allows for finding general relationships between the physical parameters and the operating temperature of the power cables. However, it should be emphasized that each extension of assumptions (e.g., taking into account nonlinearities) leads to significant difficulties in finding the analytical solution. In addition, an important problem is the knowledge of heat transfer coefficients. Attempts to determine analytically the value of the heat transfer coefficients usually lead to complex mathematical models even for not complicated devices. Therefore, the heat transfer coefficients are usually determined by semi-empirical methods based on the theory of similarity. No matter of the method used, the significance of the heat transfer coefficients in thermal calculations seems high.
In further research the proposed method will be developed and extended to more complex cable systems. Attempts will be made to determine the temperature of cables buried in the ground, placed in tunnels ect.

Author Contributions

Conceptualization, T.S.; methodology and validation, T.S., P.J. and D.K.; writing—original draft preparation, T.S.; writing—review and editing, D.K. and P.J.; measurements, T.S., D.K.; supervision, P.J. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding. The APC was funded by Czestochowa University of Technology.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Orton, H. History of Underground Power Cables. Electr. Insul. Mag. 2013, 29, 52–57. [Google Scholar] [CrossRef]
  2. Metwally, I.; Al-Badi, A.; Al Farsi, A. Factors influencing ampacity and temperature of underground power cables. Electr. Eng. 2013, 95, 383–392. [Google Scholar] [CrossRef]
  3. Ocłoń, P.; Bittelli, M.; Cisek, P.; Kroener, E.; Pilarczyk, M.; Taler, D.; Rao, R.V.; Vallati, A. The performance analysis of a new thermal backfill material for underground power cable system. Appl. Therm. Eng. 2016, 108, 233–250. [Google Scholar] [CrossRef]
  4. Sarajcev, I.; Majstrovic, M.; Medic, I. Calculation of Losses in Electric Power Cables as the Base for Cable Temperature Analysis. In WIT Transactions on Engineering Sciences; WIT Press: Southampton, UK, 2020; Volume 27, pp. 529–537. [Google Scholar]
  5. Goga, V.; Paulech, J.; Vary, M. Cooling of Electrical Cu Conductor with PVC Insulation—Analytical, Numerical and Fluid Flow Solution. J. Electr. Eng. 2013, 64, 92–99. [Google Scholar] [CrossRef] [Green Version]
  6. Ocłoń, P.; Taler, D.; Cisek, P. Fem-Based Thermal Analysis of Underground Power Cables Located in Backfills Made of Different Materials. Strength Mater. 2015, 47, 770–780. [Google Scholar]
  7. Benato, R.; Forzan, M.; Marelli, M.; Orini, A.; Zaccone, E. Harmonic Behaviour of HVDC Cables. In Proceedings of the IEEE PES T&D, New Orleans, LA, USA, 19–22 April 2010; pp. 1–9. [Google Scholar]
  8. Rozegnał, B.; Albrechtowicz, P.; Mamcarz, D.; Rerak, M.; Skaza, M. The Power Losses in Cable Lines Supplying Nonlinear Loads. Energies 2021, 14, 1374. [Google Scholar] [CrossRef]
  9. Wang, P.; Liu, G.; Ma, H. Investigation of the Ampacity of a Prefabricated Straight-Through Joint of High Voltage Cable. Energies 2017, 10, 2050–2067. [Google Scholar] [CrossRef] [Green Version]
  10. Wang, Y.; Chen, R.; Li, J.; Grzybowski, S.; Jiang, T. Analysis of Influential Factors on the Underground Cable Ampacity. In Proceedings of the IEEE Conference on Electrical Insulation Conference, Annapolis, MD, USA, 5–8 June 2011; pp. 430–433. [Google Scholar]
  11. Diego, J.; Belana, J.; Orrit, J.; CaAdas, J.; Mudarra, M.; Frutos, F.; Acedo, M. Annealing effect on the conductivity of xlpe insulation in power cable. IEEE Trans. Dielectr. Electr. Insul. 2011, 18, 1554–1561. [Google Scholar] [CrossRef] [Green Version]
  12. Liu, X.; Yu, Q.; Liu, M.; Li, Y.; Zhong, L.; Fu, M. DC electrical breakdown dependence on the radial position of specimens within HVDC XLPE cable insulation. IEEE Trans. Dielectr. Electr. Insul. 2017, 24, 1476–1486. [Google Scholar] [CrossRef]
  13. Hoerauf, R. Ampacity application considerations for underground cables. IEEE Trans. Ind. Appl. 2016, 52, 4638–4645. [Google Scholar] [CrossRef]
  14. Demoulias, C.; Labridis, D.P.; Dokopoulos, P.S.; Gouramanis, K. Ampacity of Low-Voltage Power Cables Under Nonsinusoidal Currents. IEEE Trans. Power Deliv. 2007, 22, 584–594. [Google Scholar] [CrossRef]
  15. WenWei, Z.; YiFeng, Z.; ZhuoZhan, H.; XiangBing, W.; YanFeng, W.; Gang, L.; Yue, X.; NingXi, Z. Thermal Effect of Different Laying Modes on Cross-Linked Polyethylene (XLPE) Insulation and a New Estimation on Cable Ampacity. Energies 2019, 12, 2994. [Google Scholar]
  16. Faruk, A.; Yunus, B. Thermal modelling and analysis of high-voltage insulated power cables under transient loads. Comput. Appl. Eng. Educ. 2013, 21, 516–529. [Google Scholar]
  17. Olsen, R.S.; Holboll, J.; Gudmundsdóttir, U.S. Dynamic Temperature Estimation and Real Time Emergency Rating of Transmission Cables. In Proceedings of the IEEE Power and Energy Society General Meeting, San Diego, CA, USA, 1–8 July 2012; pp. 1–8. [Google Scholar]
  18. Gołębiowski, J.; Zaręba, M. The simplified method for transient thermal field analysis in apolymeric DC cable. Electr. Eng. 2011, 93, 209–216. [Google Scholar] [CrossRef] [Green Version]
  19. Xiao-Kai, M.; Zhi-Qiang, W.; Guo-Feng, L. Dynamic Analysis of Core Temperature of Low-Voltage Power Cable Based on Thermal Conductivity. Can. J. Electr. Comput. Eng. 2016, 39, 59–65. [Google Scholar]
  20. Więcek, B.; De Mey, G.; Chatziathanasiou, V.; Papagiannakis, A.; Theodosoglou, I. Harmonic analysis of dynamic thermal problems in high voltage overhead transmission lines and buried cables. Electr. Power Energy Syst. 2014, 58, 199–205. [Google Scholar] [CrossRef]
  21. Topolski, Ł.; Warecki, J.; Hanzelka, Z. Methods for determining power losses in cable lines with non-linear load. Przeglad Elektrotechniczny 2018, 9, 85–90. [Google Scholar] [CrossRef]
  22. Shchebeniuk, L.A.; Antonets, T.Y. Investigation of losses in insulation of high-voltage cables with XLPE insulation. Electr. Eng. Electromechanics 2016, 58–62. [Google Scholar] [CrossRef] [Green Version]
  23. Domke, K.; Grzybowski, A.; Nadolny, Z.; Rakowska, A.; Siodła, K. Determination of the inner conductor temperature of high voltage power cable. Przegląd Elektrotechniczny 2010, 202–204. [Google Scholar]
  24. Kocot, H.; Kubek, P. The analysis of radial temperature gradient in bare stranded conductors. Przegląd Elektrotechniczny 2017, 132–135. [Google Scholar]
  25. Piątek, Z. Modeling of Lines, Cables and High Current Busducts; Wydawnictwo Politechniki Częstochowskiej: Czestochowa, Poland, 2007. (In Polish) [Google Scholar]
  26. McLachlan, N.W. Bessel Functions for Engineering; PWN: Warsaw, Poland, 1964. [Google Scholar]
  27. Griffiths, D.J. Fundamentals of Electrodynamics; WN PWN: Warsaw, Poland, 2001. (In Polish) [Google Scholar]
  28. Wiśniewski, S.; Wiśniewski, T.S. Heat Exchange; WNT: Warsaw, Poland, 2000. (In Polish) [Google Scholar]
  29. TELE-FONIKA Company: High. Voltage Cables, 1st ed.; TELE-FONIKA Company: Cracow, Poland, 2012. (In Polish) [Google Scholar]
  30. Chen, Y.; Duan, P.; Cheng, P.; Yang, F.; Yang, Y. Numerical Calculation of Ampacity of Cable Laying in the Ventilation Tunnel Based on Coupled Fields as well as the analysis on relevant factors. In Proceeding of the 11th World Congress on Intelligent Control and Automation, Shenyang, China, 29 June–4 July 2014; pp. 3534–3538. [Google Scholar]
Figure 1. The medium voltage cable cross section: 1—braided conductor, 2, 4—semi-conductive layer, 3—XLPE insulation, 5, 7—semi-conductive swelling tape, 6—wire screen, 8—aluminum laminated sheath, 9—PE oversheath.
Figure 1. The medium voltage cable cross section: 1—braided conductor, 2, 4—semi-conductive layer, 3—XLPE insulation, 5, 7—semi-conductive swelling tape, 6—wire screen, 8—aluminum laminated sheath, 9—PE oversheath.
Energies 14 04164 g001
Figure 2. Simplified model of the medium voltage cable with isolated screen.
Figure 2. Simplified model of the medium voltage cable with isolated screen.
Energies 14 04164 g002
Figure 3. Thermal model of the medium voltage cable (λ means thermal conductivity, α is a heat transfer coefficient).
Figure 3. Thermal model of the medium voltage cable (λ means thermal conductivity, α is a heat transfer coefficient).
Energies 14 04164 g003
Figure 4. The simplified model of medium voltage cable with return current in the screen.
Figure 4. The simplified model of medium voltage cable with return current in the screen.
Energies 14 04164 g004
Figure 5. Temperature distribution in the XRUHAKXS 1x120/50 12/20kV cable—analytical method.
Figure 5. Temperature distribution in the XRUHAKXS 1x120/50 12/20kV cable—analytical method.
Energies 14 04164 g005
Figure 6. Temperature distribution in the XRUHAKXS 1 × 120/50 12/20 kV cable—Comsol computation.
Figure 6. Temperature distribution in the XRUHAKXS 1 × 120/50 12/20 kV cable—Comsol computation.
Energies 14 04164 g006
Figure 7. Temperature distribution in the XRUHAKXS 1 × 120/50 12/20 kV cable with return current in the screen—analytical method.
Figure 7. Temperature distribution in the XRUHAKXS 1 × 120/50 12/20 kV cable with return current in the screen—analytical method.
Energies 14 04164 g007
Figure 8. Temperature distribution in the XRUHAKXS 1 × 120/50 12/20 kV cable with return current in the screen—Comsol computation.
Figure 8. Temperature distribution in the XRUHAKXS 1 × 120/50 12/20 kV cable with return current in the screen—Comsol computation.
Energies 14 04164 g008
Figure 9. The dependence of the conductor temperature on the current value.
Figure 9. The dependence of the conductor temperature on the current value.
Energies 14 04164 g009
Figure 10. The dependence of the screen temperature on the current value.
Figure 10. The dependence of the screen temperature on the current value.
Energies 14 04164 g010
Figure 11. Laboratory stand for temperature measurements in power cables: 1—supply, 2—temperature recorder, 3—XRUHAKXS 1 × 120/50 12/20 kV cable, 4—temperature sensors, 5—supply cables.
Figure 11. Laboratory stand for temperature measurements in power cables: 1—supply, 2—temperature recorder, 3—XRUHAKXS 1 × 120/50 12/20 kV cable, 4—temperature sensors, 5—supply cables.
Energies 14 04164 g011
Figure 12. Schematic of the temperature sensors.
Figure 12. Schematic of the temperature sensors.
Energies 14 04164 g012
Figure 13. Temperature sensors installed in XRUHAKXS cable.
Figure 13. Temperature sensors installed in XRUHAKXS cable.
Energies 14 04164 g013
Figure 14. Temperature distribution in the XRUHAKXS 1x120/50 12/20kV cable—dielectric losses were taken into account.
Figure 14. Temperature distribution in the XRUHAKXS 1x120/50 12/20kV cable—dielectric losses were taken into account.
Energies 14 04164 g014
Table 1. Thermal properties and thicknesses of XRUHAKXS 1 × 120/50 12/20 kV cable.
Table 1. Thermal properties and thicknesses of XRUHAKXS 1 × 120/50 12/20 kV cable.
Layer NoCable LayerRadiusThermal Conductivity
W/(mK)
IAluminum ConductorR1 = 6.2 mm280
IIXLPE InsulationR2 = 12.2 mm0.4
IIICopper ScreenR3 = 14.9 mm400
IVPE OversheathR4 = 17.9 mm0.42
Table 2. Temperature in XRUHAKXS 1 × 120/50 12/20 kV cable [°C].
Table 2. Temperature in XRUHAKXS 1 × 120/50 12/20 kV cable [°C].
MethodConductorScreen
Analytical computations40.137.4
COMSOL computations40.238.8
Measurements38.837.6
Table 3. Thermal properties and geometrical parameters of XLPE-0 cable.
Table 3. Thermal properties and geometrical parameters of XLPE-0 cable.
Layer No.Cable LayerRadiusThermal Conductivity
W/(mK)
ICopper ConductorR1 = 13.3 mm400
IIXLPE InsulationR2 = 82 mm0.31
IIIAluminum ScreenR3 = 86 mm280
IVPVC OversheathR4 = 92 mm0.42
Table 4. Conductor temperature of XLPE-0 cable [°C].
Table 4. Conductor temperature of XLPE-0 cable [°C].
MethodConductor Temperature
Analytical computations90.7
Method presented in paper [15]89.6
Table 5. Thermal properties and geometrical parameters of 110 kV XLPE cable.
Table 5. Thermal properties and geometrical parameters of 110 kV XLPE cable.
Layer No.Cable LayerRadiusThermal Conductivity
W/(mK)
ICopper ConductorR1 = 17 mm400
IIXLPE InsulationR2 = 37 mm0.2875
IIICopper ScreenR3 = 39 mm280
IVXLPE InsulationR4 = 44 mm0.2875
Table 6. Conductor temperature of 110 kV XLPE cable [°C].
Table 6. Conductor temperature of 110 kV XLPE cable [°C].
MethodConductor Temperature
Analytical computations64.29
Method presented in paper [30]66.27
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Szczegielniak, T.; Kusiak, D.; Jabłoński, P. Thermal Analysis of the Medium Voltage Cable. Energies 2021, 14, 4164. https://doi.org/10.3390/en14144164

AMA Style

Szczegielniak T, Kusiak D, Jabłoński P. Thermal Analysis of the Medium Voltage Cable. Energies. 2021; 14(14):4164. https://doi.org/10.3390/en14144164

Chicago/Turabian Style

Szczegielniak, Tomasz, Dariusz Kusiak, and Paweł Jabłoński. 2021. "Thermal Analysis of the Medium Voltage Cable" Energies 14, no. 14: 4164. https://doi.org/10.3390/en14144164