Development and Experimental Validation of TRNSYS Simulation Model for Heat Wheel Operated in Air Handling Unit

Department of Building Service Engineering and Process Engineering, Faculty of Mechanical Engineering, Budapest University of Technology and Economics, Muegyetem rkp. 3-9., H-1111 Budapest, Hungary
*
Author to whom correspondence should be addressed.
Energies 2020, 13(18), 4957; https://doi.org/10.3390/en13184957
Submission received: 6 August 2020 / Revised: 16 September 2020 / Accepted: 16 September 2020 / Published: 22 September 2020
(This article belongs to the Section G: Energy and Buildings)

Abstract

:
Reducing energy usage to save the environment is one of the main goals for the future. The energy losses in ventilation have a huge impact on energy consumption in buildings. In this work, the energy performance of a heat recovery wheel system equipped in an air handling unit was tested year-round, and the results compared with the simulation output for the system using TRNSYS software. The selected conditioned space was the staff offices of an H&M fashion shop, located in Eger, Hungary. Temperature, relative humidity, and air velocity sensors were placed at the wheel inlet and outlet sections to record data and determine the annual energy saving. The results revealed a good agreement between the measured and simulated results.

1. Introduction

Recently, concerns about building thermal load are receiving more attention as buildings are the most important energy consumers in most countries. Heat recovery is an approach for HVAC (Heating, Ventilation and Air Conditioning), which protects the environment and lowers the energy used in buildings. It improves energy efficiency and reduces energy consumption as the energy loss from ventilation reaches up to 50% of the total energy losses in buildings [1].
Various researchers carried out an energy-saving calculation using simulation. Often, the conventional approach cannot be performed under different ambient conditions. Energy-saving was investigated by several researchers, under different climate conditions [2,3]. Jani et al. [4] developed a TRNSYS (Transient System Simulation Tool) model to simulate a desiccant dehumidifier. Experimental measurements were obtained and compared to the simulation results. The simulated results showed that the system coefficient of performance had a critical influence when the regeneration temperature and relative humidity varied.
Improvement of the energy performance of a building using a heat pump was investigated by Wallin et al. [5]. The heat pump system was simulated using TRNSYS. They found that there is the potential to increase the heat exchange rate of the air-handling unit by coupling a heat pump to the system.
Zendehboudi et al. [6] determined the performance of a simple desiccant evaporative cooling cycle in four cities in Iran. The coefficient of performance (COP) was calculated in each case and the results were compared. They found that the city with the highest humidity levels had the best potential for the cooling system with the use of a desiccant wheel.
Based on the investigated literature, most of the case studies focused on the energy recovery system used in the ventilation system. Some of the research concentrated on an alternative hygroscopic material for desiccant wheels to find the most energy-saving solution by using different composite materials [7]. Other studies focused on the energy performance of a building using TRNSYS simulation software to calculate the payback period when an energy recovery system was implemented [8]. Additionally, another study were performed on a run-around membrane energy exchanger (RAMEE) using simulation computed programs for various climates to estimate the reduced annual energy consumption and greenhouse gas emissions [9].
Different weather conditions, such as dry-bulb temperature, relative humidity, or airspeed, were used in the previous studies, and the effect of these parameters on the heating and cooling demands was investigated.
In this work, a complete system of an existing air handling unit (AHU) with an air-to-air rotary heat wheel was modeled for simulation using TRNSYS 18 [10]. The investigated running ventilation system was designed by the HVAC design engineer to supply fresh air and to provide the proper indoor air quality in the conditioned space, located in Eger, Hungary. The heating and cooling demands are covered by an independent system, the investigated ventilation system, which includes indoor air units connected to additional outdoor units and does not affect the ventilation energy consumption and was not investigated by our research work and investigations. The functioning hours of this retail location were between 7:00 a.m. and 8:00 p.m. A direct expansion coil integrated into the AHU was connected to a variable refrigerant volume (VRV) outdoor unit. The main objective and the novelty of this study was the development of a simulation model that was suitable for determining the energy consumption of ventilation systems and detailed investigation of the annual energy performance of the heat wheel with high accuracy. Temperature, humidity, and air velocity sensors were placed in selected sections in the air handling elements that significantly influence the heating and cooling processes. The data measured from these sensors were recorded remotely using a monitoring system by a building management system (BMS) software. Simulated results were validated with the experimental data. The effects of ambient parameters, such as regeneration temperature, dry bulb temperature, and relative humidity (RH), on energy performance was studied. The electrical energy consumption was calculated to obtain the energy-saving impact of the heat wheel on the VRV electric energy consumption.

2. Description of the Investigated AHU

The main air handling components of the investigated system were an air-to-air rotary heat wheel that recovered the sensible heat, a mixing box, supply fan, exhaust fan, and direct expansion cooling/heating (DX) coil connected to a variable refrigerant volume (VRV) outdoor unit. Figure 1 shows the elements of the investigated AHU (Air Handling Unit) and describes the components.
The detailed configuration for the AHU following the path of the arrow around Figure 1 is as follows: the damper supply section, filter section, empty section, reciprocator heat wheel supply, mixing box supply, dx-coil, fan supply, filter supply, hole supply, hole return, filter return, and fan return.
The air damper was fully opened; the heat wheel rotation was operating at a constant speed throughout the experiment. The mixing box was fully closed so the supply air did not mix with the exhaust air.
The measurements were conducted from April 2019 to March 2020. The measurements were recorded on an hourly basis. The working hours of the retail shop were 7:00 a.m. to 8:00 p.m. throughout the year.
Figure 2 shows the air handling processes in the investigated AHU. The outside air passes through the air-to-air heat recovery wheel to recover the heat energy (state 1 to state 2) from the exhaust air inlet and it is further heated/cooled by a DX coil (state 2 to state 3) to the required supply air conditions at state 3. The air from the conditioned space enters the exhaust fan section and passes to the rotary heat wheel from the exhaust side, the supply air as upstream is passed through the rotary heat wheel, and it is cooled/heated from state 4 to state 5. On the regeneration side, the regeneration air is extracted (state 5 to state 6) into the ambient environment. The specification and the technical data of the AHU and the heat wheel, given by the producer, are provided in Table 1. The technical data for the supply and return fan are presented in Table 2. The technical specifications of the installed sensors and instrument are presented in Table 3.
Experimental tests were conducted by measuring the temperature, relative humidity, mass flow rate across the AHU, process, and regeneration air stream flow rate simultaneously using sensors. A digital sensor was used for precise measurement of the temperature and relative humidity at different states in AHU. The regeneration airflow rate at different sections in the AHU was also measured with the digital sensors. A digital temperature controller in a conditioned space controls the temperature depending on the changes in room temperature. The computer software by the manufacturer for monitoring and recording was used to observe and record all the data obtained by the sensors in the AHU. Since this research focused on the annual heat recovering by the heat wheel, the mixing box between the inlet and outlet sections of the AHU was set to be closed during the investigations. Figure 3 shows a screenshot of the investigated AHU in the building management system (BMS) program. The recorded data were evaluated. Energetic investigations were performed on the performance of AHU using the measurements. To achieve this, the mathematical approaches described in Section 3 were implemented.

3. Description of the Used Mathematical Model

In this study, the performance of the air handling unit was investigated by calculating the cooling/heating capacity of the direct expansion coil, electrical power input of the VRV, coefficient of performance (COP), and the effectiveness of the heat recovery wheel. The cooling/heating capacity ( Q ˙ c ) of the system is expressed in Equation (1) [11]:
Q ˙ c = m a ˙ ( h 3 h 2 )
where m a ˙ is the mass flow rate of air leaving the coil (kg/s), which is calculated by the multiplication of the average measured velocity of the air (m/s) and the area of the cross-section of air duct (0.74 m2), and the density of the air ( ρ a i r ) , which is around 1.2 kg/m3. h2 and h3 are the enthalpies of the air in states 2 and 3, respectively (Figure 2).
The power consumption of the VRV system E c o m p [12] is calculated using Equation (2):
E t = E c o m p
where E c o m p is the power consumption of the compressor, which is measured by using an energy meter.
Q ˙ r   is the regeneration heat supplied by the energy wheel [11], which is calculated by:
Q ˙ r = m r ˙ ( h 1 h 2 )
where m r ˙ is the mass flow rate of regeneration air and h1 and h2 are the enthalpies in states 1 and 2, respectively.
The coefficient of performance (COP) of the system is calculated [13] using the Equation (4):
C O P = Q ˙ c E t
The sensible effectiveness of heat recovery wheel (HRW) is determined by Equation (5) [14]:
ε = V ˙ s ( T 1 T 2 ) V ˙ m i n ( T 1 T 4 )
where T1 is the outdoor air temperature at the supply inlet of the heat wheel, T2 is the air temperature in the supply outlet of the heat wheel, and T4 is the air temperature in the exhaust inlet of the heat wheel.   V ˙ s is the volume flow rate of the supply air (m3/h) and V ˙ m i n is the smaller volume flow rate (supply or exhaust air) (m3/h).
The sensible heat transfer is determined by Equation (6) [15]:
Q ˙ s = V ˙ m i n · ρ a i r · C p · ( T 1 T 4 ) .

4. Description of the Developed TRNSYS Simulation Model

Figure 4 shows the TRNSYS model of the AHU system. The components used in the model were selected from the TRNSYS TESS library. The system was modeled and simulated using TRNSYS to compare the performance of the simulated and the measured data throughout the year.
Type 9e (data reader) was used to read the ambient parameters for the measured outdoor dry bulb temperature and relative humidity. These parameters were read from an external file that contained the measured outdoor ambient parameters. The same type was used to read the return ambient parameters and the volume flow rate from the indoor space. The actual measurements from the outdoor and the return from the space were used to perform an accurate validation of the TRNSYS model.
The rotary heat wheel was modeled as type 760 as it represents sensible air-to-air heat recovery with controlled outlet conditions, DX coil was modeled as type 136, type 65c, and type 46a used as an output plotter and printer. Type 111b represented the supply and return air fans. The cooling and heating process signals were monitored using type 165 from the TESS library. Type 14 (time-dependent function) was used as a schedule for the running system to work during the working hours (7:00 a.m. to 8:00 p.m.).

5. Model Validation

The new TRNSYS model was validated by comparing this model with the actual data [16]. Measured weather parameters were used as input data for the simulation models. Then a comparison was conducted between the simulated and measured values to determine the accuracy of the developed TRNSYS model. As hourly data analysis was used, the criteria of normalized mean bias error (NMBE) and coefficient of variation of the root mean square error (CVRMSE) were 10% and 30%, respectively. NMBE and CVRMSE are calculated by Equations (6) and (7), respectively, where y i is the measured value, y ^ i is the predicted or simulated value, y ¯ is the mean of the y i values, and N is the total number of measured points [17].
N M B E = 1 N i N ( y i y ^ i ) y ¯ · 100    
C V ( R M S E ) = 1 N i N ( y i y ^ i ) 2 y ¯ .100    

6. Results and Discussion

The measured and simulated ambient temperature from the TRNSYS model during winter and summer are presented in this section. The functioning hours of the AHU were between 7:00 a.m. and 8:00 p.m., which means the unit was turned off after 8:00 p.m.
Figure 5 shows a graph representing the fresh outlet from the heat wheel and exhaust inlet between the simulated and measured temperature the summer period (cooling) Figure 6 represents the fresh outlet from the heat wheel and exhaust inlet between the simulated and measured temperature in the winter period (heating).
On the heat wheel recovery sides, the monitored fresh air outlet from the heat wheel during summer was slightly higher than the simulation results, which would lead to higher energy consumption in the DX coil. During winter, it had lower values, which would lead to more energy from the VRF outdoor unit being consumed.
In the exhaust inlet section of the heat wheel, temperatures with a slight difference in the measured values temperature were observed during both winter and summer months.
In the following equations, the supply and exhaust air volume flow rate (during summer and winter) will be calculated.
For summer, the fresh air volume flow supply was measured by a sensor located at state 1. The mathematical approach to calculate the air volume flow rate is:
  V ˙ s = A · ω a v g   ·   3600
where V ˙ s is the volume flow rate of the supply air (m3/h), A is the area of cross-section of air duct (0.74 m2), and ω a v g is the average velocity of the supply fresh air in summer (0.411 m/s).
  V ˙ s s = 1095   ( m 3 / h )
The exhaust fresh air volume flow was measured by a sensor located at state 5. The average velocity of the exhaust fresh air in summer was 0.339 m/s.
  V ˙ e s = 901.5   ( m 3 / h )
For winter, the average velocity of the supply fresh air was 0.362 m/s.
  V ˙ s w = 963   ( m 3 / h )
The average velocity of the exhaust fresh air in winter was 0.268 m/s.
  V ˙ e w = 714.3   ( m 3 / h )
The reason for some differences in the higher supply airflow is that exhaust airflow is only an operational set since there are many doors and windows in the building that have leakages, so some of the supply air leaves the conditioned spaces as it is injected by the diffusers. The simulation volume flow rate values were taken from the monitored values as these values were inputs in the TRNSYS simulation.
Figure 7 and Figure 8 represent the VRV power (in kW) for summer and winter, respectively.
Figure 7 and Figure 8 show that the monitored VRV power in summer was higher than the simulated results. This could be due to the high monitored ambient temperatures during June. The results of the VRV power in winter showed values between the measured and simulated results.
Figure 9 and Figure 10 show the sensible effectiveness values (ɛs) of the heat wheel as a function of fresh air inlet temperature in winter (heating) and summer (cooling), respectively.
Figure 10 shows that the measured effectiveness in winter varied with an average of 74.1%. The simulation had an almost constant trend throughout the month, with an average value of around 73.9%. Figure 9 shows that the measured effectiveness of the HWR in summer had relatively higher values than the simulated results. The maximum value reported was around 97.6%, with an average effectiveness of around 80.2%. The simulation results showed more stable values of effectiveness than the measured values as a function of outdoor air temperature.
The difference in effectiveness between the measured and simulated values occurred due to the heat wheel in the simulation that takes the value of effectiveness as an input value. That is why it showed almost constant value throughout the month. The effectiveness value for the heat wheel was calculated according to Equation (5) depending on the measured temperatures recorded.
Figure 11 shows the sensible heat transfer (kWh) by the heat wheel. It represents the heat transfer rate for the whole year by heat wheel.
The calculated sensible heat transfer by the measured parameters of the heat wheel was relatively higher than the simulation results for many reasons, such as the higher calculated effectiveness from the measured ambient parameters and the higher difference between the supply inlet and the exhaust inlet temperature in the measured values.
Figure 12 shows the accumulated electrical energy consumption in kWh for the VRF outdoor unit throughout the year in the winter season (heating) and summer season (cooling).
Figure 12 shows good agreement between the measured and simulated results in hourly energy use. The simulated energy uses in heating and cooling mode were all within the range of ±10% (Table 4). This is within the acceptable criteria range, with the model considered calibrated if the absolute value of NMBE was less than 10%. The CVRMSE values for heating and cooling mode were 19% and 24%, respectively, which are considered acceptable as the criterion for CVRMSE is less than 30% based on ASHREA Guideline 14-2014 [18]. Table 4. Shows the calibration results of the simulation model.

7. Conclusions

The simulated results of the AHU air-conditioning system emphasize the good performance of the system. The main findings of this research study are summarized as follows:
(1)
The analysis of the supply air condition (fresh air inlet) of the heat wheel showed that the system can save energy in different weather conditions and it is more useful than the conventional air conditioning systems.
(2)
The change in the fresh inlet temperature air has a major influence on the system performance. The performance of the AHU air-conditioning system can be further enhanced by equipping a sorption wheel for the supply of regeneration energy to maximize the energy savings by transfer of the humidity air from the extract air.
(3)
The sensible effectiveness values of the heat wheel measured were higher than the simulated data in summer, whereas it was lower in winter.
(4)
The simulation value of sensible effectiveness showed a constant trend that was close to the given effectiveness values in the technical data sheet of the producer (74.9%).
(5)
The NMBE and CVRMSE used to validate the model showed that the TRNSYS model has an acceptable range as the criteria for NMBE and CVRMSE are less than 10% and 30%, respectively. The developed TRNSYS model can be useful for predicting the performance of such extreme conditions.
Altogether, the heat wheel was found to be reliable in performance, environmentally friendly, and has a notable energy-saving impact on the electrical consumption. The developed TRNSYS model can be used to simulate the performance heat wheel under different operating conditions.

Author Contributions

M.K. provided funding for the research, developed the measurement system, and conducted the field study for the topic. The simulation model was developed and validated using the measured results by L.A.-H. and supervised by M.K. The text was written by L.A.-H. and amended by M.K. All authors have read and agreed to the published version of the manuscript.

Funding

The sensors, instruments, and transducers were financially supported and installed, as well as BMS software for data recording was constructed for this research work, by the national Intherm Ltd. This research project was financially supported by the National Research, Development and Innovation Office from NRDI Fund (grant number: NKFIH PD_18 127907) and János Bolyai Research Scholarship of the Hungarian Academy of Sciences, Budapest, Hungary. The research reported in this paper and carried out at the Budapest University of Technology and Economics was supported by the TKP2020, National Challenges Program of the National Research Development and Innovation Office (BME NC TKP2020), as well as by the Higher Education Excellence Program of the Ministry of Human Capacities in the frame of Artificial Intelligence research area of Budapest University of Technology and Economics (BME FIKP-MI). The authors acknowledge the Hungary Government for their financial support as the Stipendium Hungaricum Scholarship.

Acknowledgments

The author wishes to thank Árpád Nagy and Gyula Szabó from the Intherm Ltd. group, as well as Balázs Zuggó and Noémi Bálint from the Daikin Hungary Ltd. group for providing the research background with their professional, technical, and practical knowledge for this research.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

Abbreviations
hEnthalpy (kJ/kg)
m ˙ Air mass flow rate (kg/h)
RHRelative Humidity (%)
QHeat Capacity (kW)
E t Power Consumption (kW)
TTemperature (°C)
V ˙ Air volume flow rate (m3/h)
VRVVariable Refrigerant Flow
AHUAir Handling Unit
HWRHeat Wheel Recovery
COPCoefficient of Performance
Greek Letters
εeffectiveness
τtime (h)
ρ a i r Density of the air (kg/m3)
C p Specific heat capacity (kJ/kg °C)
Subscripts
EiExhaust air inlet
oOutdoor
SiSupply air inlet
SoSupply air outlet
sssupply air in summer
esexhaust air in summer
swsupply air in winter
ewexhaust air in winter
sSensible

References

  1. Kassai, M.; Al-Hyari, L. Experimental investigation on operation parameters of 3Å molecular sieve desiccant coated total energy recovery wheel for maximum effectiveness. Therm. Sci. 2020, 24, 2113–2124. [Google Scholar] [CrossRef] [Green Version]
  2. Wan, K.K.W.; Li, D.H.W.; Liu, D.; Lam, J.C. Future trends of building heating and cooling loads and energy consumption in different climates. Build. Environ. 2011, 46, 223–234. [Google Scholar] [CrossRef]
  3. Ahmed, K.; Carlier, M.; Feldmann, C.; Kurnitski, J. A New Method for Contrasting Energy Performance and Near-Zero Energy Building Requirements in Different Climates and Countries. Energies 2018, 11, 1334. [Google Scholar] [CrossRef] [Green Version]
  4. Jani, D.B.; Mishra, M.; Sahoo, P.K. Performance studies of hybrid solid desiccant - vapor compression air-conditioning system for hot and humid climates. Energy Build. 2015, 102, 284–292. [Google Scholar] [CrossRef]
  5. Jörgen, W.; Joachim, C. Improving heat recovery using retrofitted heat pump in air handling unit with energy wheel. Appl. Therm. Eng. 2014, 64, 823–829. [Google Scholar]
  6. Zendehboudi, A.; Hashemi, R. A Study on the Performance of a Solar Desiccant Cooling System by TRNSYS in Warm and Humid Climatic Zone of IRAN. Int. J. Adv. Sci. Technol. 2014, 69, 13–18. [Google Scholar] [CrossRef]
  7. Bareschino, P.; Pepe, F.; Roselli, C.; Sasso, M.; Tariello, F. Desiccant-based air handling unit alternatively equipped with three hygroscopic materials and driven by solar energy. Energies 2019, 12, 1543. [Google Scholar] [CrossRef] [Green Version]
  8. Rasouli, M.; Simonson, C.J.; Besant, R.W. Applicability and optimum control strategy of energy recovery ventilators in different climatic conditions. Energy and Buildings. 2010, 42, 1376–1385. [Google Scholar] [CrossRef]
  9. Rasouli, M.; Akbari, S.; Simonson, C.J.; Besant, R.W. Energetic, economic and environmental analysis of a health-care facility HVAC system equipped with a run-around membrane energy exchanger. Energy Build. 2014, 69, 112–121. [Google Scholar] [CrossRef]
  10. TRNSYS. Trnsys 17—Input—Output—Parameter Reference, A Transient System Simulation Program User’s Manual. Solar Energy Laboratory, University of Wisconsin, Madison, 2011. Available online: http://web.mit.edu/parmstr/Public/TRNSYS/04-MathematicalReference.pdf (accessed on 18 September 2020).
  11. Speerforck, A.; Schmitz, G. Experimental investigation of a ground-coupled desiccant assisted air conditioning system. Appl. Energy 2016, 181, 575–585. [Google Scholar] [CrossRef] [Green Version]
  12. Jani, D.B.; Mishra, M.; Sahoo, P.K. Performance analysis of a solid desiccant assisted hybrid space cooling system using TRNSYS. J. Build. Eng. 2018, 19, 26–35. [Google Scholar] [CrossRef]
  13. De Antonellis, S.; Intini, M.; Joppolo, C.M.; Leone, C. Design Optimization of Heat Wheels for Energy Recovery in HVAC Systems. Energies 2014, 7, 7348–7367. [Google Scholar] [CrossRef] [Green Version]
  14. Kassai, M. Energy Performance Investigation of a Direct Expansion Ventilation Cooling System with a Heat Wheel. Energies 2019, 12, 4267. [Google Scholar] [CrossRef] [Green Version]
  15. ASHRAE Standard. Standard 84-1991, Method of Testing Air-to-Air Heat Exchangers; American Society of Heating, Refrigerating and Air Conditioning, Engineers Inc.: Atlanta, GA, USA, 1991. [Google Scholar]
  16. Hong, T.; Sun, K.; Zhang, R.; Hinokuma, R.; Kasahara, S.; Yura, Y. Development and validation of a new variable refrigerant flow system model in EnergyPlus. Energy Build. 2016, 117, 399–411. [Google Scholar] [CrossRef] [Green Version]
  17. Granderson, J.; Touzani, S.; Custodio, C.; Sohn, M.; Fernandes, S. Assessment of Automated Measurement and Verification (M&V) Methods; Building Technology and Urban Systems Division, Lawrence Berkeley National Laboratory: Berkeley, CA, USA, 2015. [Google Scholar]
  18. American Society of Heating, Ventilating, and Air Conditioning Engineers (ASHRAE). Guideline 14-2014, Measurement of Energy and Demand Savings; Technical Report; American Society of Heating, Ventilating, and Air Conditioning Engineers: Atlanta, GA, USA, 2014. [Google Scholar]
Figure 1. The schematic arrangement of components of AHU with the heat wheel. 1: Air-to-air rotary heat wheel; 2: Mixing box; 3: Direct expansion cooling/heating (DX) coil; 4: Supply fan; 5: Exhaust fan.
Figure 1. The schematic arrangement of components of AHU with the heat wheel. 1: Air-to-air rotary heat wheel; 2: Mixing box; 3: Direct expansion cooling/heating (DX) coil; 4: Supply fan; 5: Exhaust fan.
Energies 13 04957 g001
Figure 2. The schematic arrangement of components of AHU with the heat wheel.
Figure 2. The schematic arrangement of components of AHU with the heat wheel.
Energies 13 04957 g002
Figure 3. The AHU schematic in the building management system (BMS).
Figure 3. The AHU schematic in the building management system (BMS).
Energies 13 04957 g003
Figure 4. TRNSYS simulation model.
Figure 4. TRNSYS simulation model.
Energies 13 04957 g004
Figure 5. The fresh outlet and exhaust inlet around the heat during summer.
Figure 5. The fresh outlet and exhaust inlet around the heat during summer.
Energies 13 04957 g005
Figure 6. The fresh outlet and exhaust inlet around the heat during winter.
Figure 6. The fresh outlet and exhaust inlet around the heat during winter.
Energies 13 04957 g006
Figure 7. The measured and simulated power consumption in summer.
Figure 7. The measured and simulated power consumption in summer.
Energies 13 04957 g007
Figure 8. The measured and simulated power consumption in winter.
Figure 8. The measured and simulated power consumption in winter.
Energies 13 04957 g008
Figure 9. The measured and simulated sensible effectiveness values in summer.
Figure 9. The measured and simulated sensible effectiveness values in summer.
Energies 13 04957 g009
Figure 10. The measured and simulated sensible effectiveness values in winter.
Figure 10. The measured and simulated sensible effectiveness values in winter.
Energies 13 04957 g010
Figure 11. The measured and simulated sensible heat transfer (kWh).
Figure 11. The measured and simulated sensible heat transfer (kWh).
Energies 13 04957 g011
Figure 12. The measured and simulated electrical energy consumption in winter and summer (heating and cooling).
Figure 12. The measured and simulated electrical energy consumption in winter and summer (heating and cooling).
Energies 13 04957 g012
Table 1. Specification and technical data for AHU and energy wheel.
Table 1. Specification and technical data for AHU and energy wheel.
ParameterValueUnit
Length Overall2897mm
InsulationFoam-
Duct Supply (Width × Height)1370 × 540mm
Total heating capacity12.3kW
Total cooling capacity10.9kW
COP (Coefficient of Performance)5.56-
EER (Energy Efficiency Ratio)3.99-
Evaporating Temperature6°C
Heat Wheel TypeSensible%
Heat Wheel Effectiveness74.9%
Heat Wheel Pressure drop80Pa
Heat Wheel Power12kW
Table 2. Technical data for the supply and return fan.
Table 2. Technical data for the supply and return fan.
DeviceParameterValueUnit
Supply FanTypeCentrifugal Fan-
Total Static Pressure619Pa
Flow Design2250m3/h
Rated Power0.7kW
Return FanTypeCentrifugal Fan-
Total Static Pressure473pa
Flow Design1850m3/h
Rated Power0.49kW
Table 3. Specifications of the sensors and instruments.
Table 3. Specifications of the sensors and instruments.
DeviceWorking RangeAccuracy
Temperature Sensor−40 to 150 °C±0.4 °C
Humidity Sensor10–90%±3%
Air velocity Sensor2–20 m/s±0.2 m/s
Electricity energy meter5–100 A±1%
Table 4. Calibration results of the simulation model.
Table 4. Calibration results of the simulation model.
Total Energy ConsumptionNMBE (%)CVRMSE (%)
Heating Measured Total (kWh)63425.5%19%
Heating Simulation Total (kWh)6753
Cooling Measured Total (kWh)20347%24%
Cooling Simulation Total (kWh)1864

Share and Cite

MDPI and ACS Style

Al-Hyari, L.; Kassai, M. Development and Experimental Validation of TRNSYS Simulation Model for Heat Wheel Operated in Air Handling Unit. Energies 2020, 13, 4957. https://doi.org/10.3390/en13184957

AMA Style

Al-Hyari L, Kassai M. Development and Experimental Validation of TRNSYS Simulation Model for Heat Wheel Operated in Air Handling Unit. Energies. 2020; 13(18):4957. https://doi.org/10.3390/en13184957

Chicago/Turabian Style

Al-Hyari, Laith, and Miklos Kassai. 2020. "Development and Experimental Validation of TRNSYS Simulation Model for Heat Wheel Operated in Air Handling Unit" Energies 13, no. 18: 4957. https://doi.org/10.3390/en13184957

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.