Next Article in Journal
Mitigating Capacity Decay by Adding Carbohydrate in the Negative Electrolyte of Vanadium Redox Flow Battery
Previous Article in Journal
Which Factors Determine CO2 Emissions in China? Trade Openness, Financial Development, Coal Consumption, Economic Growth or Urbanization: Quantile Granger Causality Test
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Optimal Placement of Capacitors in Radial Distribution Grids via Enhanced Modified Particle Swarm Optimization

by
Muhammad Junaid Tahir
1,2,
Muhammad Babar Rasheed
3 and
Mohd Khairil Rahmat
1,*
1
Renewable Energy Research Labortary (RENERAL) Electrical Engineering Section, British Malaysian Institute, Universiti Kuala Lumpur, Gombak 53100, Selangor, Malaysia
2
Electrical Technology Section, The University of Lahore, Lahore 53700, Pakistan
3
Escuela Politécnica Superior, ISG, Universidad de Alcalá, 28800 Alcalá de Henares, Spain
*
Author to whom correspondence should be addressed.
Energies 2022, 15(7), 2452; https://doi.org/10.3390/en15072452
Submission received: 8 December 2021 / Revised: 28 December 2021 / Accepted: 17 January 2022 / Published: 27 March 2022
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
This paper presents the integration of shunt capacitors in the radial distribution grids (RDG) with constant and time-varying load consideration for the reduction of power losses and total annual cost, which turns to enhance the voltage profile and annual net savings. To gather the stated goals, three objective functions are formulated with system constraints. To solve this identified problem, a novel optimization technique based on the modification of particle swarm optimization is proposed. The solution methodology is divided into two phases. In phase one, potential candidate buses are nominated using the loss sensitivity factor method and in phase two the proposed technique first selects the optimal buses for the capacitor placement among the potential buses then it decides the optimal sizing of the capacitors as well. To demonstrate the performance in terms of efficiency and strength, the proposed technique is tested on IEEE 15, 33, and 69 bus system for the optimal placement and sizing of capacitors (OPSC) problem. The results are achieved in terms of annual net savings for 15 bus (47.66 % c a s e 1 , 32.76 % c a s e 2 , 26.46 % c a s e 3 ) , 33 bus (33.09% c a s e 1 , 27.06 % c a s e 2 , 24.15 % c a s e 3 ), and 69 bus (34.51% c a s e 1 , 29.43 % c a s e 2 , 25.83 % c a s e 3 ) which are comparable to other state of the art methods, and it also indicates the success of the proposed technique.

1. Introduction

Power demand is increasing globally with time, so it is required to control the power flow efficiently. With the increase of the power demand, power losses are also increased due to which RDG operates at a low power factor and faces low voltage. These power losses can be minimized using conventional methods. Capacitor placement is one of the methods used to minimize the power losses of the system at the distribution level. Capacitor injects leading current in the system, which opposes the lagging current of the system. As a result, system power losses are minimized along with the improvement of voltage profile, power factor, and system stability [1]. This leads to a significant enhancement of annual net savings and total annual cost reduction. Thus, optimal placement and sizing of capacitors (OPSC) have a dynamic role in the RDG.
The complexity of the OPSC problem depends upon the size of the power system. To solve this problem the possible number of solutions depends upon the ( i d x , c q ) n combinations whereas “n” is the length of “idx” and “idx” is the index of the potential candidate buses with “cq” capacitors. Several heuristic approaches have been recommended to resolve the OPSC problem in the literature as it is time-consuming to evaluate the set of solutions. A comprehensive review of reported literature, concentrating on numerous heuristic methods demonstrated in the recent years presented in [2] to discuss the OPSC problem. Various heuristic techniques are applied in the last few years such as fuzzy genetic algorithm [3], grey wolf optimization [4], particle swarm optimization [5], ant lion optimization [6], dolphin algorithm [7], salp swarm algorithm [8], two-stage method [9], Fuzzy-DE and Fuzzy-MAPSO [10], fire fly algorithm [11], crow search algorithm [12], whale optimization algorithm [13], the locust search algorithm [14], vortex search algorithm [15], to resolve OPSC related problem.
Similarly, different analytical methods i-e, loss sensitivity factor (LSF), voltage stability index (VSI), and power loss index (PLI) reported in the literature are used to nominate the potential candidate buses for the optimal capacitor placement and their combination with different optimization techniques are considered to decide the sizing of capacitors in the RDG. In this sequence, several traditional mathematical methods and their combinational schemes with optimization techniques are practiced in the last few years as in [16] LSF and artificial bee colony is presented, LSF and mine blast algorithm in [17], LSF and salp swarm algorithm [18], LSF and Flower pollination algorithm used in [19], LSF and discrete particle swarm optimization [20], VSI and genetic algorithm [21,22] offered VSI and shark smell optimization algorithm. LSF and VSI along with cuckoo search algorithm [23], VSI and LSF combined with bacterial foraging optimization algorithm in [24], LSF and VSI with hybrid algorithm [25]. PLI and crow search algorithm [26], PLI and Improved harmony algorithm in [27] to obtain the solution for OPSC problem.
In many cases, the recently referenced algorithms radiate an impression of being convincing, yet they may not guarantee to show up at ideal cost regard and are challenging to get away from the local minima. Yet PSO algorithm is very much popular among the other algorithms for solving complex optimization problems due to its better exploration and exploitation process. This enhances its ability to handle nonlinear optimization problems effectively. It is also observed in the prior mentioned work that traditional cost functions were used as an objective function for the OPSC problem and most of the researchers used just single or maximum of two cost functions to evaluate the performance of the proposed algorithm for the OPSC problem. But in this paper, three different cost functions, i.e., C o s t T I F L , C o s t T D F L and C o s t T D V L (see Equations 11–13) are formulated to resolve the OPSC problem. Besides, a modernistic predominant method reliant upon modification of particle swarm optimization (MPSO) is proposed to unwind the OPSC issue. The alteration is finished by presenting an original inertia term in the velocity equation ( 2 w w 2 × v i D k ) which improves the capacity of the algorithm to discover the optimal solutions by staying away from the redundancy of particle velocity in each iteration. This approach helps to improve the findings of local best for each particle and global best at the end of each iteration. So as a result, the proposed algorithm has achieved better efficiency and strength. In, addition a simple recursive load flow algorithm is developed to perform the power flow, and the LSF method is used to nominate potential candidate buses for the capacitor placement. Then LSF method is integrated with the MPSO technique for the OPSC to achieve, maximization of annual net savings, reduction of total annual cost, and active power losses. To highlight the performance, the proposed technique is tested on three IEEE bus systems for the OPSC problem. Additionally, a comprehensive analysis is also demonstrated by considering the fixed and switched capacitors with constant and time-varying load for each stated IEEE bus system. The findings indicate that the proposed technique competitively address the OPSC problem in term of efficiency and strength.
Precisely, the following are the vital contributions of this research work:
  • Review of analytical, heuristic and their combinational methods reported in the literature for tackling optimal placement and sizing of the capacitor problem.
  • A novel modified evolutionary algorithm is executed for reactive power planning in a radial distribution system.
  • Analytical and heuristic combinational algorithms are applied on three IEEE distribution systems.
  • Three objectives for intensification of annual net savings are achieved while considering system constraints.
The rest of this paper is ordered as follows: in Section 2, we demonstrated three mathematical formulations of the OPSC problem (power flow, objective function, system constraints). Then loss sensitivity factor method, fixed and switched capacitors, proposed (MPSO) technique step by step approach are expressed in Section 3 (Methodology); our experimental setup with the effective outcome results presented in Section 4. Lastly, the paper concludes in Section 5.

2. OPSC Problem Formulation

The key precedence of employing capacitors in the RDG is minimization of power losses, improvement of voltage profile, power factor, and system stability. So, better results can be achieved if the sizing and location of the capacitors are pointed accurately. In this paper, minimization of total annual cost is the main focus while considering the system constraints. Several researchers used just single or, maximum, two cost functions to evaluate the performance of their proposed algorithm for the OPSC problem. However, in this research work, three different cost functions are formulated and an innovative MPSO technique is deployed to solve these cost functions.

2.1. Power Flow Formulation

Before formulating the cost function it is necessary to understand the power flow of a radial type distribution system while minimizing the power losses by placing the capacitors optimally. The flow of active and reactive power in each branch of the system illustrated in Figure 1 is determined using (1) and (2), respectively, [28]:
P p = P e f f / q + P l o s s / k
Q p = Q ( e f f / q ) + Q ( l o s s / k )
Current is an important factor, to find out active and reactive power losses of the system. So, the current flow in each branch of the power system is evaluated using (3).
I k = P p j Q p U p < δ p
I k = U p δ p U q δ q R k + j X k
Similarly, using the conventional method, active and reactive power losses in each branch expressed in (5) and (6).
P l o s s / k = I k 2 × R k
Q l o s s / k = I k 2 × X k
P l o s s / k = P e f f / q 2 + Q e f f / q 2 U q 2 × R k
Q l o s s / k = P e f f / q 2 + Q e f f / q 2 U q 2 × Q k
By summing up, all the branch losses the resultant can be stated as total active and reactive power losses that occurred in the system are demonstrated in (9) and (10).
T o t a l P l o s s = q = 2 N b k = 1 N b 1 P e f f / q 2 Q e f f / q 2 U q 2 × R k
T o t a l Q l o s s = q = 2 N b k = 1 N b 1 P e f f / q 2 Q e f f / q 2 U q 2 × Q k
where N b refers to the total number of buses and N b 1 are the total branches integer.

2.2. Objective Function

Several kinds of cost functions are reported in the literature to evaluate the performance of the algorithms. In this paper, three kinds of cost functions are considered based on total power loss cost and its combination with capacitor cost. Capacitor cost can be categorized as: fixed capacitor cost, variable capacitor cost, and capacitor installation cost. The total annual cost of the RDG reported in [17] is considered as first objective function, which is gathered by optimal placement and sizing of the capacitors and its relation is formulated as follows:
m i n ( C o s t T I F L ) c a s e 1 = K p × T o t a l P l o s s / c p + q = 1 n K c × Q q c
where F L is the fix load, T I is time independent, K p is the cost of power losses in $/kWh, T o t a l P l o s s / c p are the power losses with capacitor placement, K c is the cost in $/kVAr of Q q c capacitor rating in (11). For details refer to Table 1 and Table A1 (Appendix A). In case-1 cost function is independent of time and it is minimized while considering fix load.
The second objective function considered in this paper, suggested recently in [14]. It is worthy to be mention that this objective function also considers capacitor installation cost to find out annual net savings of the RDG. The second objective function is stated in (12):
m i n ( C o s t T D F L ) c a s e 2 = K p × T × T o t a l P l o s s / c p + K i c × N q + q = 1 n K c × Q q c
where F L is the fix load, T D is time dependent, K p is the cost of power losses in $/kWh, T is total annual operation time in hours, T o t a l P l o s s / c p are the power losses with capacitor placement, K i c is the installation cost of N q number of capacitors, K c are the capacitor cost in $/kVAr of Q q c capacitor rating in (12). For details refer to Table 1. In case-2 cost function is dependent on time and it is also minimized while considering fix load. The cost function reported in [29] is considered as third objective function considered in this paper and it is expressed as:
m i n ( C o s t T D V L ) c a s e 3 = K p × T × T o t a l P l o s s / c p + K i c × N q + q = 1 n K c f i x e d × Q q c f i x e d + q = 1 n K c s w i t c h e d × Q q c s w i t c h e d
where V L is the variable load, T D is time dependent, K p is the cost of power losses in USD/kWh,T is total annual operation time in hours, T o t a l P l o s s / c p are the power losses with capacitor placement, K i c is the installation cost of N q number of capacitors, K c f i x e d and K c s w i t c h e d are the fixed and switched capacitor cost in USD/kVAr of Q q c capacitor rating in (13). For details refer to Table 1. It is entrusting to see that this objective function considers the fixed and switched capacitors ratings along with capacitor installation cost to find out annual net savings of the RDG. In case-3 the cost function is also dependent on time and it is minimized while considering time-varying load.

2.3. System Constraints

While achieving the objective functions following constraints are needed to be considered:

2.3.1. Voltage Limitation

While performing the capacitor placement it is necessary to consider the upper and lower voltage constraints i-e, U i m a x =1.05 and U i m i n =0.95.
U i m i n U i U i m a x

2.3.2. Reactive Injection Limitation

It is necessary to control reactive power injection within the constraints while doing capacitor placement.
Q c j m i n Q c j Q c j m a x
where Q c j m i n is the lower constraint and Q c j m a x is the upper constraint and Q c j is the rating of the capacitor which is placed at bus j. Here Q c j m i n =50 kVAr and Q c j m a x = 3000 kVAr are considered as constraints.

2.3.3. Maximum Reactive Power Limitation

The total compensated capacitor rating needed to be monitor so that it does not go beyond the total reactive power of the load at each bus.
i = 1 n Q c ( i ) j = 1 n Q L ( j )
Here i = 1 n Q c ( i ) is the sum of total compensated power of capacitors and j = 1 n Q L ( j ) is the sum of the total reactive power demand of the loads.

3. Methodology

To find the initial losses of the network it is necessary to perform load flow analysis. Through which power system current state can be expressed, in terms of the voltage level at each bus, the overall power factor of the system and power losses in each branch. Several methods are reported in the literature to perform load flow analysis of the system. In this paper, the method reported in [28], is adapted to perform load flow analysis of the system, to find the state of the network before and after optimal capacitor placement. Equations (9) and (10) are used to find the total active and reactive power losses of the system before and after capacitor placement.

3.1. Loss Sensitivity Factor

To minimize the power losses in the system, after performing load flow and evaluating the system initial conditions, it is necessary to nominate the candidate busses for the capacitor placement. In this paper, the loss sensitivity factor method [30] is adopted, for the nomination of busses to optimally place the capacitors. The loss sensitivity factor method helps to predict the candidate buses, which have more capability to reduce the power losses of the system.
P l o s s / k Q e f f / q = Q e f f / q P e f f / q 2 + Q e f f / q 2 U q 2 × R k
To nominate the candidate buses four simple steps are involved in this method.

3.1.1. Power Loss Indexing

In step one loss sensitivity index (LSI) is achieved for all busses by using (18), which is the resultant derivative of (7).
L S F = 2 × Q e f f / q U q 2 × R k

3.1.2. LSF Ranking

The resultant LSF of each bus placed in descending order in step 2 and its position index also stored.

3.1.3. Operating Voltage Normalization

In step three operating voltage of all busses which are obtained from the load flow method without OPSC, converted to a normalized voltage using (19).
U n o r m ( i ) = U i 0.95

3.1.4. Selection of Candidate Buses

The last step is very crucial and important because it is compulsory to make sure that the resultant normalized bus voltage, indexing order is the same as the LSF bus indexing order. In the last, only those buses are selected as candidate buses, which are having normalized voltage less than 1.01p.u, whether the power system is large or small.

3.2. Fixed and Switched Capacitors

In the RDG power demand varies with the time as load varies and this may cause enhancement of power losses and instability in the system. To minimize these losses and stabilize the RDG fixed and switched capacitors are used. The capacitors which are permanently installed are called fixed capacitors and with the load demand which can be switched ON/OFF are known as switched capacitors. In this paper, optimal placement and sizing of the fixed and switched capacitors with respect to load variation is also considered to enhance the annual net saving and reduce the total annual cost, power losses. For this purpose, three levels of load are considered with a specific duration of time (see Table 2).

3.3. Novel Modified Particle Swarm Optimization

In 1995, Dr. Kennedy and Dr. Ebenhart [31] introduced the standard particle swarm optimization, which is a smart stochastic technique. This algorithm starts with the initialization of particles positions X i = ( x i 1 , x i 2 , , x i D ) and their velocities “ V i = ( v i 1 , v i 2 , , v i D ) ” in “D” dimensional search space along with inertia weight coefficient, acceleration constants, random variables, personal best of each particle, “ P b e s t i = ( p b i 1 , p b i 2 , , p b i D ) ” and global best among all particles, “ G b e s t i = ( p g i 1 , p g i 2 , , p g i D ) ”.
w = w m a x w m a x w m i n i t e r m a x × i t e r
where “w” is inertia, w m a x = 0.9 , w m i n = 0.4 , i t e r m a x ” is the maximum number of iterations and “iter” is the k t h iteration number. In this research, we have proposed an unusual modified inertia term to find the new velocity of each particle and it is formulated as:
v i D k + 1 = 2 w w 2 × v i D k Novel Inertia Term + c 1 × r 1 × p b e s t i D k x i D k Congnative Term + c 2 × r 2 × g b e s t i D k x i D k Social Term
x i D k + 1 = x i D k + v i D k + 1
Here it is fascinating to see the trait of new velocity using modified inertia term in Figure 2, i.e., resultant vector is ( 2 w w 2 ) × v i D k . Essentially, this unique inertia term assists with moderating the dull qualities for the v i D k + 1 which goes to expand the quantity of opportunities for every particle to improve individual best in every iteration. This upgrades the presentation of the proposed strategy as far as effectiveness and strength. During every iteration velocity and position of every particle is revived utilizing (21) and (22) and gbest and pbest values are taken care of, while getting the best outcomes algorithm stops.
v i D k + 1 = rand × v i D k + 1 if v i D k + 1 = v i D k v i D k + 1 otherwise
Normally (23) is used in standard PSO and other modified PSO methods reported in the literature to settle the repetitive elements for new velocity. Our proposed technique mitigates this repetitive issue; it can be seen in Figure 3, that each value of “w” either positive or negative outcomes for unfamiliar inertia term ( 2 w w 2 ) is different. So there is no need to use (23) in our technique. For more accurate results, each particle velocity is restricted between the maximum and minimum values [ v m a x , v m i n ] using (24).
v i D k + 1 = v m a x = c a p m a x v m i n = c a p m i n
where c a p m a x is 3000kVAr and c a p m i n is 50 kVAr.
v i D k + 1 = v m a x i f v i D k + 1 > v m a x v i D k + 1 i f v i D k + 1 v m a x v m i n i f v i D k + 1 < v m i n
While updating the velocity for kth iteration, particle velocity is lemmatized by (23), and resultant velocity gathered in the form of (25).
Figure 3. Novel inertia term response.
Figure 3. Novel inertia term response.
Energies 15 02452 g003

4. Execution of MPSO for OPSC

To understand the performance of the proposed MPSO algorithm for the OPSC problem, the pseudocode is stated below.
Step 1
Perform load flow to evaluate the initial state of the RDG in terms of power losses, total annual cost, minimum voltage.
Step 2
Use loss sensitivity method to highlight the potential buses for the optimal capacitor placement.
Step 3
Initialize random set of solutions; particle velocity, particle position, cognitive, social components, and random variables.
Step 4
Set maximum iteration limit.
Step 5
Check whether generated solution is satisfying the constraints; install capacitors on optimal buses while satisfying the (14)–(16).
Step 6
Evaluate the fitness of the solution in each iteration for (11)–(13); total annual cost.
Step 7
Generate new set of solutions using (21) and (22); update particle velocity and particle position.
Step 8
Stop the algorithm and display the result when it reached to maximum iteration or optimal solution is achieved; power losses reduction, total annual cost reduction, improvement of voltage profile, enhancement of annual net saving.

5. Results and Discussion

To show the effectiveness of the proposed algorithm for the OPSC problem, the approach was tested on IEEE 15, 33, and 69 bus RDG and the outcomes were compared with the reported results in the recent literature. A novel inertia term was added in the standard PSO algorithm. This approach helps to get away from local minima by mitigating the repetition of velocity for each particle through this possibility to get optimal result is increased. This ability enables our algorithm to perform better as compared to conventional PSO and other algorithms. All results were tabulated for the stated objective functions i-e case-1, case-2 and case-3. To show the efficiency and strength of the proposed modernistic MPSO; the technique has been executed 20 times on MaTLAB® 2015b with intel® Core™ i3-2370M CPU @ 2.4GHz and 4GB RAM, for each execution number of iteration (k) is taken as 1000 with 20 number of particles (N).

5.1. Statistical Analysis

To demonstrate the efficiency of the proposed algorithm, the statistical breakdown for the stated objective functions (11)–(13) is given in Table 3 in terms of best (maximum), worst (minimum), average (mean), and standard deviation values. While convergence curves in Figure 4, Figure 5, Figure 6, Figure 7, Figure 8 and Figure 9 reflect the strength of the proposed unusual MPSO technique. Here it is necessary to mention that CPU time represents the total time to compute: load flow with and without capacitor, LSF method, number of iterations of MPSO to reach optimal solution. Furthermore, comparative results are explained in the below subsections.
Figure 4. Flow chart of MPSO for solving OPSC problem.
Figure 4. Flow chart of MPSO for solving OPSC problem.
Energies 15 02452 g004

5.2. IEEE 15 Bus RDG

In this study, initially, IEEE 15 bus system is taken to test the proposed unique technique. System data are taken from [32], it has 15 buses, 14 branches (see Figure 5a) and it works at 11kV, 100MVA base value, with 1226kW active load, and 1251kVAr reactive load. While examining the system for case-1 and case-2 (without capacitor placement) active power loss is 61.7926kW, the minimum system voltage is 0.9445p.u. at bus 13, power loss cost, and the total annual cost is 10381$ and 32478$ with zero net savings (see Table 4 and Table 5). Candidate buses are nominated using the LSF method, and potential buses are ranked in descending order, as shown in Figure A2 (Appendix A). Comparative results are presented to show the effectiveness of the proposed technique with other reported techniques; MAPSO, TSM, dPSO, DE, IHA, FPA.
Our proposed unfamiliar technique suggested 510, 345, and 325kVAr rating at bus 4, 7 and 11 (case-1) and bus 4, 6 with 670 and 400kVAr (case-2) for the OPSC problem. The suggested sizing results in the power losses reduction up to 51.16%, 48.81% with 47.66%, 32.76% net saving (see Figure 6) with an enhanced minimum voltage of 0.9690, 0.9630 p.u. (observe Figure 5b). It is observed that a remarkable enhancement in annual net saving is achieved after OPSC using MPSO.
Figure 5. (a) IEEE 15 bus system. (b) Voltage profile.
Figure 5. (a) IEEE 15 bus system. (b) Voltage profile.
Energies 15 02452 g005
Moreover, our proposed technique is tested for different loading conditions; off-peak, mid-peak, and peak load (case-3) for 15 bus system. Initially, (without capacitor placement) system faces 14.698, 61.7926, and 168.877kW power losses with 0.9730, 0.9445 and 0.9081 p.u. minimum voltage at bus 13, power loss cost, and the total annual cost is 1764$ and 19502$ 15199$ with zero net savings (see Table 6). Our proposed innovative technique suggested bus 4,6 for the optimal placement of capacitor with 0, 1000, and 200kVAr sizing. The proposed sizing results in the reduction of power losses 0%, 47.18%, and 42% along with enhancement of minimum voltage 0.9730, 0.9615, and 0.9296 p.u. Similarly, total power losses cost is reduced from 36,465$ to 20,977$ and total annual cost from 36,465$ to 26,817$ which turns to enhances the total net saving from 0$ to 9648$. So, it can be seen that significant enhancement is gathered through MPSO for the OPSC problem.
Figure 6. Convergence curve IEEE 15 bus system.
Figure 6. Convergence curve IEEE 15 bus system.
Energies 15 02452 g006
Figure 7. (a) IEEE 33 bus system (b) Voltage profile.
Figure 7. (a) IEEE 33 bus system (b) Voltage profile.
Energies 15 02452 g007

5.3. IEEE 33 Bus RDG

IEEE 33 bus system is taken as second test system for the proposed unique technique. System data are taken from [14], this system has 33 buses, 32 branches (observe Figure 7a), and it operates at 12.66kV, 100MVA base value with 3715kW active load, and 2230 kVAr reactive load. While examining the system for case-1 and case-2 (without capacitor placement) active power loss is 210.97 kW, the minimum system voltage is 0.9038p.u. at bus 18, power loss cost, and the total annual cost is 35,443$ and 110,886$ with zero net savings (see Table 7 and Table 8). Candidate buses are nominated using the LSF method, and potential buses are ranked in descending order, as shown in Figure A2 (Appendix A). Comparative results are presented to show the effectiveness of the proposed technique with other reported techniques; IP, SA, TSM, MMS, FPA, and LS. Our proposed modernistic technique suggested 320, 340, 500, 660, 380kVAr rating at bus 8, 16, 24, 30, 32 (case-1) and bus 13, 30 with 425 and 1125 kVAr (case-2) for the OPSC problem. The suggested sizing results in the power losses reduction up to 34.89%, 33.06% with 33.09%, 27.06% net saving (see Figure 8) with an enhanced minimum voltage of 0.9370, 0.9298 p.u. (observe Figure 7b). It is observed that a remarkable enhancement in annual net saving is achieved after OPSC using MPSO.
Figure 8. Convergence curve IEEE 33 bus system.
Figure 8. Convergence curve IEEE 33 bus system.
Energies 15 02452 g008
Moreover, our proposed technique is tested for different loading conditions; off-peak, mid-peak, and peak load (case-3) for 33 bus system as well. Initially, (without capacitor placement) system faces 48.783, 210.97 and 603.374kW power losses with 0.9540, 0.9038 and 0.8360 p.u. minimum voltage at bus 18, power loss cost, and the total annual cost is 5854$ and 66,582$, and 54,304$ with zero net savings (see Table 9). Our proposed unusual technique suggested bus 13,30 for the optimal placement of capacitor with 0, 1400, and 800kVAr sizing. The proposed sizing results in the reduction of power losses 0%, 32.35%, and 33.36% along with enhancement of minimum voltage 0.9540, 0.9277, and 0.8737 p.u. Similarly, total power losses cost is reduced from 126,740$ to 87,087$ and total annual cost from 126,740$ to 96,127$ which turns to enhances the total net saving from 0$ to 30,613$. So, it can be seen that significant enhancement is gathered through MPSO for the OPSC problem.
Figure 9. (a) IEEE 69 bus system. (b) Voltage profile.
Figure 9. (a) IEEE 69 bus system. (b) Voltage profile.
Energies 15 02452 g009

5.4. IEEE 69 Bus RDG

IEEE 69 bus system is taken as third test system for the proposed unfamiliar technique. System data is taken from [14], This system has 69 buses, 68 branches (observe Figure 9a), with connected 3801.89kW, 2693.6kVAr active and reactive load. While examining the system for case-1 and case-2 (without capacitor placement) active power loss is 225kW, the minimum system voltage is 0.9092p.u. at bus 65, power loss cost, and the total annual cost is 37,800$ and 118,260$ with zero net savings (see Table 10 and Table 11). Candidate buses are nominated using the LSF method, and potential buses are ranked in descending order, as shown in Figure A3 (Appendix A). Comparative results are presented to show the effectiveness of the proposed technique with other reported techniques; Fuzzy-GA, DE, MMS, TSM, FPA, LS.
Figure 10. Convergence curve IEEE 69 bus system.
Figure 10. Convergence curve IEEE 69 bus system.
Energies 15 02452 g010
Our proposed innovative technique suggested 320, 1200, 230kVAr rating at bus 21, 61, 64 (case-1) and bus 18, 61 with 300 and 1400kVAr (case-2) for the OPSC problem. The suggested sizing results in the power losses reduction up to 35.63%, 35.44% with 34.51%, 29.43% net saving (see Figure 10) with an enhanced minimum voltage of 0.9311, 0.9300 p.u. (observe Figure 9b). It is observed that remarkable enhancement in annual net saving is achieved after OPSC using MPSO.
Moreover, our proposed technique is tested for different loading conditions; off-peak, mid-peak, and peak load (case-3) for 69 bus system as well. Initially, (without capacitor placement) system faces 51.60, 225 and 652.43kW power losses with 0.9567, 0.9092 and 0.8445 p.u. minimum voltage at bus 65, power loss cost, and the total annual cost is 6192$ and 70487$ 58,719$ with zero net savings (see Table 12). Our proposed unique technique suggested bus 61 for the optimal placement of capacitor with 0, 1400, and 800 kVAr sizing. The proposed sizing results in the reduction of power losses 0%, 32.93%, and 33.66% along with enhancement of minimum voltage 0.9567, 0.9291, and 0.8767 p.u. Similarly, total power losses cost is reduced from 135,921$ to 92,770$ and total annual cost from 135,921$ to 100,810 $ which turns to enhances the total net saving from 0$ to 35,111$. So, it can be stated that significant enhancement is achieved from MPSO for OPSC problem.

6. Conclusions

In this paper, a novel particle swarm optimization technique based on the modification of particle velocity is utilized to resolve the OPSC problem effectively while considering constant and time-varying load for the reduction of power losses and total annual cost. The proposed technique is tested on IEEE 15, 33, and 69 bus system. To highlight the performance in solving the OPSC problem results are compared and evaluated for the reduction of power losses and total annual cost along with enhancement of voltage profile and total annual net saving. To compel a fair comparison, MPSO is tested on IEEE 15, 33, 69 RDG and acquired results are contrasted with other techniques reported recently in the literature.
The compared results authenticate that the MPSO is well appropriate for taking care of OPSC problem in RDG. This ability to handle the non-linear and incoherent complex formulation of MPSO is because of avoiding the repetition of particle velocity in each iteration. This modernistic characteristic enhances the exploration and exploitation process of MPSO. Due to this, the presented technique achieves an optimal solution for the OPSC problem in RDG. Furthermore, this proposed technique is not restricted to OPSC problems, it can also be utilized for other engineering and global optimization problems as well.
More efforts will be focused on the assessment of game plan strategies of reactive power compensation for the real time practical power system. More efforts will be focused on the assessment of game plan strategies of reactive power compensation for the real time practical power system. Additionally, some multi objective techniques can be taken on to get the best compromise course of action for the capacitor allocation, with various objectives such as voltage regulation and harmonic distortion.

Author Contributions

Conceptualization, M.J.T., M.B.R. and M.K.R.; methodology, M.J.T.; software, M.J.T.; validation, M.J.T., M.B.R. and M.K.R.; formal analysis, M.J.T. and M.B.R.; investigation, M.J.T. and M.B.R.; resources, M.K.R.; data curation, M.J.T.; writing—original draft preparation, M.J.T.; writing—review and editing, M.J.T., M.B.R.; visualization, M.J.T., M.B.R. and M.K.R.; supervision, M.B.R. and M.K.R.; project administration, M.K.R.; funding acquisition, M.K.R. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Data used in this research are easily available online and are also given in the Appendix A.

Acknowledgments

I would like to acknowledge BMI, UniKL for supporting me.

Conflicts of Interest

Annual net saving enhancement in power distribution system was the area of interest. To achieve this aim an unfamiliar modified PSO algorithm was used and results showed the robustness and precision of the proposed algorithm.

Abbreviations

The following abbreviations are used in this manuscript:
RDGRadial distribution system
OPSCOptimal placement and sizing of capacitors
LSFLoss sensitivity factor
VSIVoltage stability index
PLIPower loss index
MAPSOMulti-agent particle swarm optimization
TSMTwo-stage method
dPSODiscrete particle swarm optimization
DEDifferential evolution algorithm
IHAImproved harmony algorithm
FPAFlower pollination algorithm
MPSOModified particle swarm optimization
IPInterior point
SASimulated annealing
MMSModified monkey search
LSLocust search algorithm
Fuzzy-GAFuzzy genetic algorithm

Appendix A

Table A1. Parameters of Objective Function (Case-1).
Table A1. Parameters of Objective Function (Case-1).
Capacitor
Index (qc)
Capacitor Size (kVAr)
Qc=Q(qc)
Reactive Power
Cost ($/KVAr)
Capacitor
Index (qc)
Capacitor Size (kVAr)
Qc=Q(qc)
Reactive Power
Cost ($/KVAr)
11500.5001116500.193
23000.3501218000.187
34500.2531319500.211
46000.2201421000.176
57500.2761522500.197
69000.1831624000.170
710500.2281725500.189
812000.1701827000.187
913500.2071928500.183
1015000.2012030000.180
Table A2. IEEE 15 bus RDG line data.
Table A2. IEEE 15 bus RDG line data.
Line No.From BusTo BusLine Resistance
R ( Ω )
Line Reactance
X ( Ω )
Active Load
Power (kW)
Reactive Load
Power (kVAr)
1121.3530901.32349044.1044.99
2231.1702401.14464070.0071.40
3340.8411100.822710140.00142.82
4451.5234801.02760044.1044.99
5292.0131701.357900140.00142.82
69101.6867101.137700140.00142.82
7262.5572701.72490070.0071.40
8671.0882000.73400070.0071.40
9681.2514300.84410044.1044.99
103111.7955301.211100140.00142.82
1111122.4484501.65150070.0071.40
1212132.0131701.35790044.1044.99
134142.2308101.50470070.0071.40
144151.1970200.807400140.00142.82
Table A3. IEEE 33 bus RDG line data.
Table A3. IEEE 33 bus RDG line data.
Line No.From BusTo BusLine Resistance
R ( Ω )
Line Reactance
X ( Ω )
Active Load
Power (kW)
Reactive Load
Power (kVAr)
1120.092200.04770100.0060.00
2230.493000.2511090.0040.00
3340.366000.18640120.0080.00
4450.381100.1941060.0030.00
5560.819000.7070060.0020.00
6670.187200.61880200.00100.00
7781.711401.23510200.00100.00
8891.030000.7400060.0020.00
99101.040000.7400060.0020.00
1010110.196600.0650045.0030.00
1111120.374400.1238060.0035.00
1212131.468001.1550060.0035.00
1313140.541600.71290120.0080.00
1414150.591000.5260060.0010.00
1515160.746300.5450060.0020.00
1616171.289001.7210060.0020.00
1717180.732000.5740090.0040.00
182190.164000.1565090.0040.00
1919201.504201.3554090.0040.00
2020210.409500.4784090.0040.00
2121220.708900.9373090.0040.00
223230.451200.3083090.0050.00
2323240.898000.70910420.00200.00
2424250.896000.70110420.00200.00
256260.203000.1034060.0025.00
2626270.284200.1447060.0025.00
2727281.059000.9337060.0020.00
2828290.804200.70060120.0070.00
2929300.507500.25850200.00600.00
3030310.974400.96300150.0070.00
3131320.310500.36190210.00100.00
3232330.341000.5302060.0040.00
Table A4. IEEE 69 bus RDG line data.
Table A4. IEEE 69 bus RDG line data.
Line No.From BusTo BusLine Resistance
R ( Ω )
Line Reactance
X ( Ω )
Active Load
Power (kW)
Reactive Load
Power (kVAr)
1120.00050.00120.000.00
2230.00050.00120.000.00
3340.00150.00360.000.00
4450.02510.02940.000.00
5560.36600.18642.602.20
6670.38100.194140.4030.00
7780.09220.047075.0054.00
8890.04930.025130.0022.00
99100.81900.270728.0019.00
1010110.18720.0619145.00104.00
1111120.71140.2351145.00104.00
1212131.03000.34008.005.00
1313141.04400.34008.005.00
1414151.05800.34960.000.00
1515160.19660.065045.0030.00
1616170.37440.123860.0035.00
1717180.00470.001660.0035.00
1818190.32760.10830.000.00
1919200.21060.06901.000.60
2020210.34160.1129114.0081.00
2121220.01400.00465.003.50
2222230.15910.05260.000.00
2323240.34630.114528.0020.00
2424250.74880.24750.000.00
2525260.30890.102114.0010.00
2626270.17320.057214.0010.00
273280.00440.010826.0018.60
2828290.06400.156526.0018.60
2929300.39780.13150.000.00
3030310.07020.02320.000.00
3131320.35100.11600.000.00
3232330.83900.281614.0010.00
3333341.70800.564619.5014.00
3434351.47400.48736.004.00
353360.00440.010826.0018.55
3636370.06400.156526.0018.55
3737380.10530.12300.000.00
3838390.03040.035524.0017.00
3939400.00180.002124.0017.00
4040410.72830.85091.201.00
4141420.31000.36230.000.00
4242430.04100.04786.004.30
4343440.00920.01160.000.00
4444450.10890.137339.2226.30
4545460.00090.001239.2226.30
464470.00340.00840.000.00
4747480.08510.208379.0056.40
4848490.28980.7091384.70274.50
4949500.08220.2011384.70274.50
508510.09280.047340.5028.30
5151520.33190.11403.602.70
529530.17400.08864.353.50
5353540.20300.103426.4019.00
5454550.28420.144724.0017.20
5555560.28130.14330.000.00
5656571.59000.53370.000.00
5757580.78370.26300.000.00
5858590.30420.1006100.0072.00
5959600.38610.11720.000.00
6060610.50750.25851244.00888.00
6161620.09740.049632.0023.00
6262630.14500.07380.000.00
6363640.71050.3619227.00162.00
6464651.04100.530259.0042.00
6511660.20120.061118.0013.00
6666670.00470.001418.0013.00
6712680.73940.244428.0020.00
6868690.00470.001628.0020.00
Figure A1. Candidate buses for IEEE 15 bus system.
Figure A1. Candidate buses for IEEE 15 bus system.
Energies 15 02452 g0a1
Figure A2. Candidate buses for IEEE 33 bus system.
Figure A2. Candidate buses for IEEE 33 bus system.
Energies 15 02452 g0a2
Figure A3. Candidate buses for IEEE 69 bus system.
Figure A3. Candidate buses for IEEE 69 bus system.
Energies 15 02452 g0a3

References

  1. Soma, G.G. Optimal Sizing and Placement of Capacitor Banks in Distribution Networks Using a Genetic Algorithm. Electricity 2021, 2, 187–204. [Google Scholar] [CrossRef]
  2. Stanelyte, D. Review of voltage and reactive power control algorithms in electrical distribution networks. Energies 2020, 13, 58. [Google Scholar] [CrossRef] [Green Version]
  3. Gampa, S.R. Optimum placement of shunt capacitors in a radial distribution system for substation power factor improvement using fuzzy GA method. Int. J. Electr. Power Energy Syst. 2016, 77, 314–326. [Google Scholar] [CrossRef]
  4. Kola Sampangi, S. Optimal capacitor allocation in distribution networks for minimization of power loss and overall cost using water cycle algorithm and grey wolf optimizer. Int. Trans. Electr. Energy Syst. 2020, 30, e12320. [Google Scholar] [CrossRef]
  5. Elsayed, A.M. Distribution system performance enhancement (Egyptian distribution system real case study. Int. Trans. Electr. Energy Syst. 2018, 28, e2545. [Google Scholar] [CrossRef]
  6. Abul’Wafa, A.R. Ant-lion optimizer-based multi-objective optimal simultaneous allocation of distributed generations and synchronous condensers in distribution networks. Int. Trans. Electr. Energy Syst. 2019, 29, e2755. [Google Scholar] [CrossRef]
  7. Al-Jubori, W.K.S.; Hussain, A.N. Optimum reactive power compensation for distribution system using dolphin algorithm considering different load models. Int. J. Electr. Comput. Eng. 2020, 10, 5032. [Google Scholar]
  8. Sambaiah, K.S. Optimal allocation of renewable distributed generation and capacitor banks in distribution systems using Salp Swarm algorithm. Int. J. Renew. Energy Res. 2019, 9, 96–107. [Google Scholar]
  9. Tamilselvan, V. Optimal capacitor placement in radial distribution systems using flower pollination algorithm. Alex. Eng. J. 2018, 57, 2775–2786. [Google Scholar] [CrossRef]
  10. Duong, T.L. Determining optimal location and size of capacitors in radial distribution networks using moth swarm algorithm. Int. J. Electr. Comput. Eng. 2020, 10, 5032. [Google Scholar] [CrossRef]
  11. Da Silva, J. FPAES: A Hybrid Approach for the Optimal Placement and Sizing of Reactive Compensation in Distribution Grids. Energies 2020, 13, 6409. [Google Scholar] [CrossRef]
  12. Askarzadeh, A. Capacitor placement in distribution systems for power loss reduction and voltage improvement: A new methodology. IET Gener. Transm. Distrib. 2016, 10, 3631–3638. [Google Scholar] [CrossRef]
  13. Prakash, D.B. Optimal siting of capacitors in radial distribution network using whale optimization algorithm. Alex. Eng. J. 2017, 56, 499–509. [Google Scholar] [CrossRef] [Green Version]
  14. Díaz, P. A swarm approach for improving voltage profiles and reduce power loss on electrical distribution networks. IEEE Access 2018, 6, 49498–49512. [Google Scholar] [CrossRef]
  15. Gil-González, Optimal selection and location of fixed-step capacitor banks in distribution networks using a discrete version of the vortex search algorithm. Energies 2020, 13, 4914. [CrossRef]
  16. Dixit, M. Optimal integration of shunt capacitor banks in distribution networks for assessment of techno-economic asset. Comput. Electr. Eng. 2018, 71, 331–345. [Google Scholar] [CrossRef]
  17. Elazim, A. Optimal locations and sizing of capacitors in radial distribution systems using mine blast algorithm. Electr. Eng. 2018, 100, 1–9. [Google Scholar] [CrossRef]
  18. Youssef, A.R. Optimal capacitor allocation in radial distribution networks using a combined optimization approach. Electr. Power Components Syst. 2018, 46, 2084–2102. [Google Scholar] [CrossRef]
  19. Abdelaziz, A.Y. Flower pollination algorithm and loss sensitivity factors for optimal sizing and placement of capacitors in radial distribution systems. Electr. Power Components Syst. 2016, 78, 207–214. [Google Scholar] [CrossRef]
  20. Mosbah, M.; Mohammedi, R.D.; Arif, S.; Hellal, A. Optimal of shunt capacitor placement and size in algerian distribution network using particle swarm optimization. In Proceedings of the International Conference on Modelling, Identification and Control (ICMIC), Algiers, Algeria, 15–17 November 2016. [Google Scholar]
  21. Danish, S.M.S.; Ahmadi, M.; Yona, A.; Senjyu, T.; Krishna, N.; Takahashi, H. Multi-objective optimization of optimal capacitor allocation in radial distribution systems. Int. J. Emerg. Electr. Power Syst. 2020, 21, 1–11. [Google Scholar]
  22. Gnanasekaran, N. Optimal placement of capacitors in radial distribution system using shark smell optimization algorithm. Ain Shams Eng. J. 2016, 7, 907–916. [Google Scholar] [CrossRef] [Green Version]
  23. Yuvaraj, T. Optimal allocation of DG and DSTATCOM in radial distribution system using cuckoo search optimization algorithm. Model. Simul. Eng. 2017, 2017, 1–11. [Google Scholar] [CrossRef] [Green Version]
  24. Kishore, C. Symmetric fuzzy logic and IBFOA solutions for optimal position and rating of capacitors allocated to radial distribution networks. Energies 2018, 11, 766. [Google Scholar] [CrossRef] [Green Version]
  25. Muthukumar, K. Optimal placement and sizing of distributed generators and shunt capacitors for power loss minimization in radial distribution networks using hybrid heuristic search optimization technique. Int. J. Electr. Power Energy Syst. 2016, 78, 299–319. [Google Scholar] [CrossRef]
  26. Montazeri, M. Capacitor placement in radial distribution networks based on identification of high potential busses. Int. Trans. Electr. Energy Syst. 2019, 29, e2754. [Google Scholar] [CrossRef]
  27. Ali, E.S. Improved harmony algorithm and power loss index for optimal locations and sizing of capacitors in radial distribution systems. Int. J. Electr. Power Energy Syst. 2016, 80, 252–263. [Google Scholar] [CrossRef]
  28. El-Ela, A.A.A. Optimal capacitor placement in distribution systems for power loss reduction and voltage profile improvement. IET Gener. Transm. Distrib. 2016, 10, 1209–1221. [Google Scholar] [CrossRef]
  29. Moradian, S. Optimal placement of switched capacitors equipped with stand-alone voltage control systems in radial distribution networks. Int. Trans. Electr. Energy Syst. 2019, 29, e2753. [Google Scholar] [CrossRef]
  30. Olabode, O.E. A two-stage approach to shunt capacitor-based optimal reactive power compensation using loss sensitivity factor and cuckoo search algorithm. Energy Storage 2020, 2, e122. [Google Scholar] [CrossRef]
  31. Eberhart, R.; Kennedy, J. A new optimizer using particle swarm theory. MHS’95. In Proceedings of the Sixth International Symposium on Micro Machine and Human Science, Nagoya, Japan, 4–6 October 1995. [Google Scholar]
  32. Duque, F.G. Allocation of capacitor banks in distribution systems through a modified monkey search optimization technique. Int. J. Electr. Power Energy Syst. 2015, 73, 420–432. [Google Scholar] [CrossRef]
  33. Abdelaziz, A.Y. Optimal sizing and locations of capacitors in radial distribution systems via flower pollination optimization algorithm and power loss index. Eng. Sci. Technol. Int. J. 2016, 19, 610–618. [Google Scholar] [CrossRef] [Green Version]
  34. Shuaib, Y.M. Optimal capacitor placement in radial distribution system using gravitational search algorithm. Int. J. Electr. Power Energy Syst. 2015, 64, 384–397. [Google Scholar] [CrossRef]
Figure 1. Power flow between two buses in a distribution system.
Figure 1. Power flow between two buses in a distribution system.
Energies 15 02452 g001
Figure 2. Modified PSO vector diagram.
Figure 2. Modified PSO vector diagram.
Energies 15 02452 g002
Table 1. Parameters of objective functions.
Table 1. Parameters of objective functions.
ParametersStudy Case-1Study Case-2Study Case-3
K p 168$0.06$0.06$
K i c - - -1000$1000$
T- - -8760 h8760 h
K c f i x e d Refer to Appendix A Table A13$/kVAr3$/kVAr
K c s w i t c h e d - - -- - -3.2$/kVAr
Table 2. Annual load levels with respect to time duration.
Table 2. Annual load levels with respect to time duration.
Load LevelOff-Peak LoadMid-Peak LoadPeak Load
Time Duration200052601500
Table 3. MPSO based statistical results for optimal capacitor placement.
Table 3. MPSO based statistical results for optimal capacitor placement.
Annual Net Savings in $ (Case-1)
BestWorstAverageStandard DeviationIEEE
4.95 × 10 + 3 4.87 × 10 + 3 4.92 × 10 + 3 5.62 × 10 2 15
1.17 × 10 + 4 1.10 × 10 + 4 1.15 × 10 + 4 1.21 × 10 1 33
1.30 × 10 + 4 1.28 × 10 + 4 1.29 × 10 + 4 1.02 × 10 1 69
Annual Net Savings in $ (Case-2)
BestWorstAverageStandard DeviationIEEE
1.06 × 10 + 4 1.01 × 10 + 4 1.05 × 10 + 4 1.44 × 10 1 15
3.00 × 10 + 4 2.95 × 10 + 4 2.99 × 10 + 4 1.44 × 10 1 33
3.48 × 10 + 4 3.40 × 10 + 4 3.46 × 10 + 4 2.23 × 10 1 69
Annual Net Savings in $ (Case-3)
BestWorstAverageStandard DeviationIEEE
9.70 × 10 + 3 9.56 × 10 + 3 9.65 × 10 + 3 4.54 × 10 2 15
4.70 × 10 + 4 4.66 × 10 + 4 4.68 × 10 + 4 1.29 × 10 1 33
1.90 × 10 + 4 1.88 × 10 + 4 1.89 × 10 + 4 5.81 × 10 2 69
Table 4. Comparative results for IEEE 15 bus RDG (case-1).
Table 4. Comparative results for IEEE 15 bus RDG (case-1).
Base CaseMAPSO [10]TSM [9]dPSO [21]DE [33]IHA [27]FPA [33]MPSO
Total Power Losses (kW)61.792630.953432.426230.446332.331.125530.711230.1814
Loss Reduction(%)- - -50.0447.5150.7247.8649.7650.3051.16
Minimum Bus Voltage (p.u)0.94450.9780.96950.9712- - -0.96580.96760.9690
Candidate Buses- - -4, 6, 7, 11, 153, 6, 44, 6, 13, 153, 6, 116, 11, 156, 11, 154, 7, 11
OPSC (kVAr)- - -345, 264, 143, 300, 143175, 375, 750450, 450, 150, 150454, 500, 178350, 300, 300350, 350, 300510, 345, 325
Total kVar- - -119513001200113295010001180
Annual power loss Cost ($)103815200544851155426522951605071
Saving Due to Power Losses Reduction ($)- - -5209493352654982517952215311
Cap kVar cost ($)- - -501426378317333350364
Total Annual Cost ($)103815701587354935743556255105434
Annual Net Saving ($)- - -4708450648874665484748724947
Net Saving (%)- - -45.2343.4147.0844.8246.5746.9347.66
Table 5. Comparative results for IEEE 15 bus RDG (case-2).
Table 5. Comparative results for IEEE 15 bus RDG (case-2).
Base CaseMAPSO [10]TSM [9]dPSO [21]DE [33]IHA [27]FPA [33]MPSO
Total Power Losses (kW)61.792630.953432.426230.446332.331.125530.711231.634
Loss Reduction(%)- - -50.0447.5150.7247.8649.7650.3048.81
Minimum Bus Voltage (p.u)0.94450.9780.96950.9712- - -0.96580.96760.9630
Candidate Buses- - -4, 6, 7, 11, 153, 6, 44, 6, 13, 153, 6, 116, 11, 156, 11, 154, 6
OPSC (kVAr)- - -345, 264, 143, 300, 143175, 375, 750450, 450, 150, 150454, 500, 178350, 300, 300350, 350, 300670, 400
Total kVar- - -119513001200113295010001070
Annual power loss Cost ($)32,47816,26917,04316,00216,97716,3591614216627
Saving Due to Power Losses Reduction ($)- - -16,20015,42816,47215,58616,20316,33715,851
Cap kVar cost ($)- - -8585690076006396585060005210
Total Annual Cost ($)32,47824,85423,94323,60223,37322,20922,14221,837
Annual Net Saving ($)- - -761585288872919010,35310,33710,641
Net Saving (%)- - -23.4526.2627.3228.2231.7931.8332.76
Table 6. Results for IEEE 15 Bus RDG in different loading conditions (case-3).
Table 6. Results for IEEE 15 Bus RDG in different loading conditions (case-3).
Load LevelTotal Power
Losses (kW)
Minimum Bus
Voltage (p.u)
Candidate
Buses
Number of Switched
Capacitors/200kVAr
Capacitor
(kVAr)
Cap kVAr
Cost ($)
Annual Power
Loss Cost($)
Total Annual
Cost ($)
Annual Net
Saving ($)
Base CaseOff-Peak Load14.6980.9730- - -- - -- - -- - -17641764- - -
Mid-Peak Load61.79260.9445- - -- - -- - -- - -19,50219,502- - -
Peak Load168.8770.9081- - -- - -- - -- - -15,19915,199- - -
Total Without OPSC- - -- - -- - -- - -- - -- - -36,46536,465- - -
ProposedOff-Peak Load14.6980.9730- - -- - -- - -- - -176417640
MPSOMid-Peak Load32.64040.96154,63,2600, 400320010,30113,5016000
Peak Load97.9220.929641200640891295525647
Total With OPSC Including
2000$ Cap Installation Cost
- - -- - -4,661200584020,97726,8179648
Table 7. Comparative results for IEEE 33 bus RDG (case-1).
Table 7. Comparative results for IEEE 33 bus RDG (case-1).
Base CaseIP [34]SA [34]TSM [9]MMS [32]FPA [19]LS [14]MPSO
Total Power Losses (kW)210.97171.78151.75144.04135.77134.47138.61137.37
Loss Reduction(%)- - -18.5828.0731.7333.0133.6534.3034.89
Minimum Bus Voltage (p.u)0.90380.95010.95910.92510.94160.93650.93250.9370
Candidate Buses- - -9, 29, 3010, 30,147, 29, 309, 13, 296, 9, 305, 8, 11, 16, 24, 26, 30, 328, 16, 24, 30, 32
OPSC (kVAr)- - -450, 800, 900450, 350, 900850, 25, 900300, 300, 900250, 400, 950150, 150, 150, 150, 450, 150, 750, 150320, 340, 500, 660, 380
Total kVar- - -2150170017751500160021002200
Annual power loss Cost ($)35,44328,85925,49424,19922,80922,59123,28723,079
Saving Due to Power Losses Reduction ($)- - -6584994911,24411,29011,45812,15712,364
Cap kVar cost ($)- - -499401507375439771636
Total Annual Cost ($)- - -29,35825,89524,61123,18423,03024,05723,714
Annual Net Saving ($)35,4436085954810,83210,91511,01911,80711,729
Net Saving (%)- - -17.1726.9330.5632.0132.3632.1233.09
Table 8. Comparative results for IEEE 33 bus RDG (case-2).
Table 8. Comparative results for IEEE 33 bus RDG (case-2).
Base CaseIP [34]SA [34]TSM [9]MMS [32]FPA [19]LS [14]MPSO
Total Power Losses (kW)210.97171.78151.75144.04135.77134.47139.23141.23
Loss Reduction(%)- - -18.5828.0731.7333.0133.6534.0033.06
Minimum Bus Voltage (p.u)0.90380.95010.95910.92510.94160.93650.92910.9298
Candidate Buses- - -9, 29, 3010, 30, 147, 29, 309, 13, 296, 9, 3012, 25, 3013, 30
OPSC (kVAr)- - -450, 800, 900450, 350, 900850, 25, 900300, 300, 900250, 400, 950450, 350, 900425, 1125
Total kVar- - -2150170017751500160017001550
Annual power loss Cost ($)110,88690,28879,76075,70771,36170,67773,17974,231
Saving Due to Power Losses Reduction ($)- - -20,59831,12635,17835,16835,84137,70736,654
Cap kVar cost ($)- - -9450810083257500780081006650
Total Annual Cost ($)- - -99,73887,86084,03278,86178,47781,27980,881
Annual Net Saving ($)110,88611,14823,02626,85327,66828,04129,60730,004
Net Saving (%)- - -10.0520.7624.2125.9726.3326.7027.06
Table 9. Results for IEEE 33 Bus RDG in different loading conditions (case-3).
Table 9. Results for IEEE 33 Bus RDG in different loading conditions (case-3).
Load LevelTotal Power
Losses (kW)
Minimum Bus
Voltage (p.u)
Candidate
Buses
Number of Switched
Capacitors/200kVAr
Capacitor
(kVAr)
Cap kVAr
Cost ($)
Annual Power
Loss Cost($)
Total Annual
Cost ($)
Annual Net
Saving ($)
Base CaseOff-Peak Load48.7830.9540- - -- - -- - -- - -58545854- - -
Mid-Peak Load210.970.9038- - -- - -- - -- - -66,58266,582- - -
Peak Load603.3740.8360- - -- - -- - -- - -54,30454,304- - -
Total Without OPSC- - -- - -- - -- - -- - -- - -126,740126,740- - -
ProposedOff-Peak Load48.7830.9540- - -- - -- - -- - -585458540
MPSOMid-Peak Load142.7260.927713, 307400, 1000448045,04449,52417,058
Peak Load402.0950.873713, 304200, 600256036,18938,74915,555
Total With OPSC Including
2000$ Cap Installation Cost
- - -- - -13, 30112200904087,08796,12730,613
Table 10. Comparative results for IEEE 69 bus RDG (case-1).
Table 10. Comparative results for IEEE 69 bus RDG (case-1).
Base CaseFuzzy-GA [3]DE [33]MMS [32]TSM [9]FPA [19]LS [14]MPSO
Total Power Losses (kW)225156.62151.3763146.29148.91150.28144.25144.79
Loss Reduction(%)- - -30.4032.7034.9833.7333.235.8935.63
Minimum Bus Voltage (p.u)0.90920.93690.93110.93410.92890.93330.93150.9311
Candidate Buses- - -59, 61, 6457, 58, 59, 60, 6112, 21, 61, 62, 6419, 62, 636112, 21, 50, 54, 6121, 61, 64
OPSC (kVAr)- - -100, 700, 800150, 50, 100, 150, 1000200, 200, 600, 600, 200225, 900, 2251350350, 150, 40, 150, 1200320, 1200, 230
Total kVar- - -1600145018001350135023001750
Annual power loss Cost ($)37,80026,31225,43124,57725,01725,24724,23524,325
Saving Due to Power Losses Reduction ($)- - -11,47912,35913,21412,77412,54413,55713,475
Cap kVar cost ($)- - -425408564390280590431
Total Annual Cost ($)37,80026,73725,83925,14125,40725,52724,82524,756
Annual Net Saving ($)- - -11,05411,95112,65012,38412,26412,97513,044
Net Saving (%)- - -29.2531.6333.4732.7732.4534.3234.51
Table 11. Comparative results for IEEE 69 bus RDG (case-2).
Table 11. Comparative results for IEEE 69 bus RDG (case-2).
Base CaseFuzzy-GA [3]DE [33]MMS [32]TSM [9]FPA [19]LS [14]MPSO
Total Power Losses (kW)225156.62151.3763146.29148.91150.28146.61145.27
Loss Reduction (%)- - -30.432.734.9833.7333.234.8435.44
Minimum Bus Voltage (p.u)0.90920.93690.93110.93410.92890.93330.93000.9300
Candidate Buses- - -59, 61, 6457, 58, 59, 60, 6112, 21,61, 62, 6419, 62, 636117, 6118, 61
OPSC (kVAr)- - -100, 700, 800150, 50, 100, 150, 1000200, 200, 600, 600, 200225, 900, 2251350350, 1200300, 1400
Total kVar- - -1600145018001350135015501700
Annual power loss Cost ($)118,26082,31979,56376,89078,26778,98777,05876,354
Saving Due to Power Losses Reduction ($)- - -35,83038,64141,37039,83039,21841,20241,906
Cap kVar cost ($)- - -78009350104007050505066507100
Total Annual Cost ($)118,26090,11988,91387,29085,31784,03783,70883,454
Annual Net Saving ($)- - -28,03029,29130,97032,78034,16834,55234,806
Net Saving (%)- - -23.7224.7826.1927.7628.9129.2129.43
Table 12. Results for IEEE 69 Bus RDG in different loading conditions (case-3).
Table 12. Results for IEEE 69 Bus RDG in different loading conditions (case-3).
Load LevelTotal Power
Losses (kW)
Minimum Bus
Voltage (p.u)
Candidate
Buses
Number of Switched
Capacitors/200kVAr
Capacitor
(kVAr)
Cap kVAr
Cost ($)
Annual Power
Loss Cost($)
Total Annual
Cost ($)
Annual Net
Saving ($)
Base CaseOff-Peak Load51.600.9567- - -- - -- - -- - -61926192- - -
Mid-Peak Load2250.9092- - -- - -- - -- - -70,48770,487- - -
Peak Load652.430.8445- - -- - -- - -- - -58,71958,719- - -
Total Without OPSC- - -- - -- - -- - -- - -- - -135,921135,921- - -
ProposedOff-Peak Load51.600.9567- - -- - -- - -- - -619261920
MPSOMid-Peak Load150.900.92916171400448047,62552,10518,905
Peak Load432.810.8767614800256038,95341,51317,206
Total With OPSC Including
1000$ Cap Installation Cost
- - -- - -61112200804092,770100,81035,111
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Tahir, M.J.; Rasheed, M.B.; Rahmat, M.K. Optimal Placement of Capacitors in Radial Distribution Grids via Enhanced Modified Particle Swarm Optimization. Energies 2022, 15, 2452. https://doi.org/10.3390/en15072452

AMA Style

Tahir MJ, Rasheed MB, Rahmat MK. Optimal Placement of Capacitors in Radial Distribution Grids via Enhanced Modified Particle Swarm Optimization. Energies. 2022; 15(7):2452. https://doi.org/10.3390/en15072452

Chicago/Turabian Style

Tahir, Muhammad Junaid, Muhammad Babar Rasheed, and Mohd Khairil Rahmat. 2022. "Optimal Placement of Capacitors in Radial Distribution Grids via Enhanced Modified Particle Swarm Optimization" Energies 15, no. 7: 2452. https://doi.org/10.3390/en15072452

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop